Model 5204 Fire Control/Communicator Panel
Built-in Touchpad Operating Instructions
These instructions must be framed and displayed next to the Model 5204 panel
in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems.
Function Enter (On Built-in Touchpad):
System test
Reset alarms (or smoke det.)
Clear alarm memory
Reset dialer
Start download
Alarm memory display
Display troubles
Silence troubles or alarms
Disable/Enable
Begin fire drill
End fire drill
The system sounds an alarm and reports a fire test when you exit fire drill mode.
0 ENTER
1 ENTER + Code 0 or 1
2 ENTER
3 ENTER + Code 0
4 ENTER + Code 0
5 ENTER
6 ENTER
SILENCE
Zone #1-4 + DISABLE
+ Code 0 or 1
2 0 ENTER + Code 0
SILENCE
On 5230, also enter:
+ Code 0 or 1
Same
+ Code 0 or 1
Same
Same
+ Code 0 or 1
+ Code 0 or 1
+ Code 0 or 1
Same
+ Code 0 or 1
+ Code 0 or 1
Function Enter (On Built-in Touchpad or 5230):
Walk test
Zone Troubleshooting mode
Step Programming mode
Clear (start over if you make a
mistake)
Set time
For example, to set the time of
Wed., 4:30 p.m., enter:
1 0 4 3 0
3
2 2 ENTER + Code 0 *
2 5 ENTER + Code 0 *
2 7 ENTER + Code 0 *
CLEAR
9 ENTER + 6-digit date
Use wdhhmm format for time, where:
w = Day of week (0=Sun., 1=Mon., 2=Tue.,
3=Wed., 4=Thu., 5=Fri., 6=Sat.)
d = Time of day (0=AM, 1=PM)
hh = Hour (enter leading 0 for 1-digit hrs.)
mm = Minutes (enter leading 0 for 1-digit min.)
* To exit these modes with the 5230, press STEP STEP CLEAR CLEAR .
With the built-in touchpad, press
SILENCE SILENCE CLEAR CLEAR .
For service call:
Form # 150643 6/95