Silent Knight SK-2224, SK-4224 User Manual

Cut Along the Dotted Line
SK-2224 Basic Operating Instructions P/N 151064
These instructions must be framed and displayed next to the SK-2224 panel in accordance with NFPA 72 fire code for Local Fire Alarm System.
LED (Color) Function
AC (green) ON = Good AC
OFF = Low AC trouble condition and it was acknowledged FLASHING = Unacknowledged AC Low trouble condition
GENERAL TROUBLE (yellow)
WALK TEST (yell ow) ON = Walk test is in progress
GND FAULT (yellow) ON = Ground fault condition exists and was acknowledged
LOW BATTERY (yellow) ON = Battery low condition that has been acknowledged
ZONE 1 and
ZONE 2
NAC 1 and
NAC 2
SYSTEM SILENCED (yellow)
ALARM (red) ON = Zone in alarm which has been ac knowledged
SUPERVISORY (yellow)
TROUBLE (yellow)
ACTIVE (yellow) ON = NAC is active during an alarm
TROUBLE (yellow)
Operation Keystrokes
Disable notification appliance circ uit . To re-enable the circuit, press [NAC
DISABLE] again. Disable a zone To re-enable the circuit, press [ZONE
DISABLE] again. Begin Walk Test Press [WALK TEST]. Walk Test LED turns on.
End Walk Test Press [WALK TEST].
Acknowledge condition (alarm, supervisory, trouble)
Silence Panel Press [SILENCE]. This will silence the on-board PZT and all active NAC circuits that have been configured as
Perform system reset Press [RESET]. Resets alarm s , supe rvi sori es, troubles and all LEDs. Manual Dialer Test. Press the [ACK] and [ SILENCE] butt ons at the same time. Dialer Reset. Press the [RESET] and [WALK TEST] buttons at the same time.
For Service Contact:
ON = System trouble OFF = System OK FLASHING = At least one serial device is in trouble DOUBLE FLASHING = Two types of serial devices are in trouble.
OFF = Walk test is off. FLASHING = Walk test is on and at least one zone is not ready
OFF = No fault FLASHING = A ground fault condition detected
OFF = Good battery condition FLASHING = Battery low condition
OFF = No Alarm FLASHING = Zone in alarm has not yet been acknowledged. ON = Zone has a supervisory condi ti on (self-restoring conditio n) OFF = No supervisory condition exists. FLASHING = supervisory trouble detected on that zone. ON = Zone has a trouble conditi on which has been acknowledg ed OFF = No zone trouble FLASHING = Zone has a trouble condition DOUBLE FLASHING = Zone was disabled CLEAN ME FLASHING =
Indicates that the smoke detector needs cleaning (LED is on long and
Off for a short time period)
OFF = NAC is not active during alarm ON = NAC has a trouble condition and was ackn owl ed ge d
OFF = No trouble condition FLASHING = NAC is in trouble DOUBLE FLASHING = Circuit was disabled ON = System audible output ha s bee n silenced OFF = Nothing silenced FLASHING = Partially silenced
Press the appropriate [NAC DISABL E ] key. The NAC circuit will be di sabled and the corresponding TROUBLE LED will Double Flash. This function is not available during an alarm condition.
Press the appropriate [ZONE DISABLE] key. The zone will be disabled and the corresponding TROUBLE LED will Double Flash. This function is not available during an alarm or supervisory condition.
Note: Walk test will not ac tivate if the control panel has a trouble, alarm , o r su pervisory condition.
NOTE: The Walk Test feature is not operational dur ing an alarm, supervisory or an y sy stem trouble condition.The test ends automatically after 10 minutes of no system activity.
Press [ACK]. The corresponding L ED will change from blinki ng to steady for the duratio n of the condition.
"silenceable".