SilentKnight SD505-TCHB100 User Manual

TCH-B100-NS PROGRAMMER OPERATING INSTRUCTIONS
Remote Programming Cable (All Modules except DCP-FRCME-S)
Remote Programming
Jack
To Remote Programming Jack
Programming Buttons
Display
Remote Programming Cable (DCP-FRCME-S)
GENERAL DESCRIPTION:
TCH-B100-NS is designed for use with the following products: ALG-V/ALG-EA
AIE-EA
ATG-EA FRCME-S FRCME-4 SOM R2M CZM DIMM
PROGRAMMING BUTTONS
LEFT GRAY BUTTON
Analog Photoelectric Smoke Sensor Analog Ionization Smoke Sensor Analog Heat Sensor DCP Fast Response Contact Module DCP Fast Response Contact Monitor DCP Signal Output Module DCP Dual Relay Module
DCP Conventional Zone Module DCP Dual Input Monitor Module
Power on. Automatically reads the address of a sensor. Subsequent
operations will advance the device address by ten.
RIGHT GRAY BUTTON RED BUTTON
Power off. Advances the device address by one. Stores the displayed addresss to the device and is used to read sensor
analog levels.
NOTE: PRIOR TO PROGRAMMING ENSURE BATTERY IS CONNECTED.
1.
Install sensor onto programmer, ensuring that sensor protrusions align with programmer grooves.
2.
Press the left gray button to switch programmed on. A battery check message will appear followed by the devices address ( un-programmed sensors will read address 127).
3.
Set the required address by incrementing the left and right gray buttons (the display will show three red flashing dots if the address being programmed is different from the device's current address).
When the desired address is present press the red button to store that address. The three red dots on
4.
the display will no longer be present.
HOCHIKI AMERICA CORPORATION
7051 Village Drive, Suite 100
Buena Park, CA 90621-2268.
DWG # HA-06-082 Page 1 of 2, 05-03
PART # 1700-09906
TESTING A SENSOR
NOTE: Ionization sensors require a 30 seconds stabilization period before analog value reading should be taken.
1.
Install the sensor and power up programmer as previously described on page 1. Press the "Red" button. An "A" will appear on the display followed by the analog value.
2. The value will be continuously updated for three minutes.
3.
The "ALG" photoelectric sensor should have a value displayed of between 56-63. The "AIE" ionization sensor should have a value displayed of bewteen 52-73.
Values out of these ranges indicate that the sensor chamber has become contaminated. Refer to technical bulletin "HA-96" for proper servicing instructions or return sensor to factory for
servicing.
DISPLAY MESSAGES: bAt - On upon power up (battery check). Also on when battery is low. Low battery good for up to
3,000 address setting operation. E0 - Attempting to set an address beyond 127.
E1 - Attempting to program an address with no device connected. E2 - Can not find device after power up. E3 - Invalid sensor response. E4 - Can not find the device program. E5 - Device read error. E6 - Fail during Analog value reading.
DWG # HA-06-082 Page 2 of 2, 05-03 PART # 1700-09906