SILENT KNIGHT SD505-DUCT, SD505-DTS-K, SD505-DUCTR Installation Instructions Manual

II. MOUNTING THE DETECTOR
The sampling tubes may be ordered to a desired length or ordered in one of 3 standard lengths and cut per requirements. The intake sampling tube consists of a piece of steel piping with a series of holes drilled the entire length of the tube and should extend the entire width of the duct. The holes must be facing into the air flow (see Figure 2). The exhaust tube consists of a piece of steel piping approximately 7-1/2" long.
1. Remove paper backing from mounting template AP 121 (packaged in installation kit) and affix to duct at desired location.
2. Using template as a guide, drill 4 mounting holes (3/32" diameter) for duct mounting screws (4 #12 x 1/2" sheet metal screws packaged in installation kit). Drill or punch holes for sampling tubes in air ducts (1-3/8" diameter), using template as a guide. Clean all holes.
Duct Smoke Detector Location Requirements: To prevent false alarms the detectors should
not be mounted in areas of extreme high or low temperatures, in areas where high humidity exist, or in areas where duct air may contain gases or excess dust. The duct detector should, when possible, be located a minimum of six duct widths downstream from a source of turbulence (bends, inlets, or deflection plates). At these locations, air flow is less turbulent and the air/smoke mixture should be more homogenous. Refer to NFPA 90A, 72, and 101 for more information. See Figure 1A and 1B.
Exception: Where it is physically impossible to locate the duct detector accordingly, the duct detector can be positioned closer than six duct widths, but as far as possible from inlets, bends, or deflection plates.
These are Installation Instructions (DWG.# HA-06-094) for the Duct Housing customized as follows:
SD505-DUCT Duct Housing with the SD505-APS Analog Photoelectric Smoke Sensor*
SD505-DUCTR Duct Housing with the SD505-APS Analog Photoelectric Smoke Sensor & Relays*
SD505-DTS-K Remote Test Switch
INSTALLATION INSTRUCTIONS FOR THE
DUCT SMOKE DETECTOR
A. DUCT PREPARATION
C. SAMPLING TUBE ASSEMBLY (See Figure 2)
The Duct Detectors are designed for use in ducts where the air velocities are from 300 to 4000 feet per minute. Verify this by checking specifications of installation and if necessary, use an Alnor Model 6000P velocity meter (or equivalent) to check the air velocity. See Figure 2 for sampling tube orientation to air flow direction.
B. VERIFY AIR FLOW AND DIRECTION
FIGURE 1 B: DUC T HOUSING MOUNTING
TOP OF DUCT HOUSING
To verify proper sampling of air, use a Dwyer Model 4000 differential pressure gauge (or equivalent). See Figure 3 for gauge connections. The pressure differential between input sampling tube and exhaust tube should be greater than
0.01" of water and less than 1.2" of water.
E. MOUNT THE DUCT HOUSING (See Figure 1B & 2)
Move duct housing/sampling tube assembly to desired location. Use 4 mounting screws (4 #12 x 1/2" sheet metal screws, packaged in installation kit) to secure the housing to the air duct.
1. Sampling tube connectors are equipped with set screws, which allow the tubes to be mounted only in directions shown in Figure 2. Establish proper orientation considering airflow direction.
2. Insert intake and exhaust tubes into connectors, align set screw to set screw hole in tubes and tighten firmly.
1. Cut the intake sampling tube to the desired length.
2. Firmly insert the stopper (packaged in installation kit) in the end of the INTAKE sampling tube.
INTAKE SAMPLING TUBES STANDARD LENGTHS:
Installation Instructions (P/N 1700-09882 HA-06-094) Page 1 of 3
F. VERIFY AIR SAMPLING (See Figure 3)
D. MOUNT SAMPLING TUBES (See Figure 2)
Specifications subject to change without notice. * September 2014
For duct widths of 1.0' to 2.5' For duct widths of 2.5' to 5.0' For duct widths of 5.0' to 10.0'
SD505-T2 SD505-T5 SD505-T10
I. LOCATION REQUIREMENTS
R
by Honeywell
1. With power source de-energized and the smoke detector not installed, wire all connections per engineering drawings. Refer to the applicable figures below depending on your duct housing model number.
2. With all wiring in place, install the detector head.
3. Energize the duct detector.
Wiring must conform to applicable local codes, ordinances and regulations covering these types of devices. Wire the detectors according to the engineering drawings for the particular job requirements. These detectors
are not intended for open area protection, nor should they be used for open air protection. Refer to NFPA 90A and NFPA 72 for general and
additional information on Duct Smoke Detectors concerning operation
and installation. Terminals are suitable for up to #14 gauge wire.
B. DETECTOR WIRING
A. GENERAL INFORMATION
III. ELECTRICAL INSTALLATION
FIG. 3 AIR SAMPLING
VERIFICATION
EXHAUST TUBE
HOLE &
CONNECTOR
LOW PRESSURE
SIDE
DWYER #4000 DIFFERENTIAL PRESSURE GAUGE (OR EQUIVALENT) WITH TUBING AND SIZE 0 RUBBER STOPPERS (HA PART# 0700-01118).
HIGH PRESSURE
SIDE
INTAKE TUBE
HOLE &
CONNECTOR
Specific ations subj ect to change without notice. * September 2014
Installation I nstructions (P/N 1 700-09882 HA-06-094) Page 2 of 3
NOT USED
The SD505-DUCT is not a self-contained sensor.
This product is compatible only with fire alarm
control panels that utilize Silent Knight's Digital
Communications Protocol.
C. WIRING DIAGRAMS
UL LISTED
CONTROL PANEL
LOOP INTERFACE
S (+)
SC (-)
STANDBY and ALARM current should be 0.55mA
TO NEXT
SENSOR
-R +RL2L1
1 2 3 4
ANALOG SENSOR
Terminate Remote Accessories as indicated above (if required).
This is not a self-contained stand alone detector.
A U.L. Listed Analog Addressable Fire System is required.
ANALOG ADDRESSABLE
FIELD LOOP WIRING
OBSERVE POLARITY
INPUT VOLTAGE
24 V.D.C.
S (+)
SC (-)
UL LISTED
CONTROL PANEL
A.A.
CONTROL
PANEL
ADDRESSABLE
LOOP
13 14
20 mA Standby
62mA Alarm
1 2
+
-
SD505-DUCTR WIRING DIAGRAM
SUPPLY VOLTAGE
TO NEXT SENSOR
OR RETURN
TO CONTROL PANEL
TROUBLE
10.0A @ 250VAC
6
10
ALARM CONTACTS
10.0A @ 250VAC
NONC
C
3 4 5
NO
C
NC
8
7
FAN
REMOTE TEST
SWITCH
(Test function only. Does not reset.)
FAN SHUTDOWN EXAMPLE
Test SW
GND
PILOT
LED
ALARM
LED
9
11 12
SD505-DTS
SD505-DUCT WIRING DIAGRAM
Maximum SLC Resistance
SLC Input Current
Aux. Power Input Current
Trouble Relay Contact Rating Operating Voltage
Alarm Relay Contact Rating
Air Velocity Rating
Humidity
Operating Temperature
0.5mA
10% ~ 85% RH Non-Condensing
50 Ohms 32F ~ 100F
2.5A @ 30VDC 24VDC
10A @ 24VDC
SPECIFICATIONS
20mA Standby 62mA Alarm
RATING
SD505-DUCT
300 ~ 4000 ft./min.
0.5mA
10% ~ 85% RH Non-Condensing
50 Ohms 32F ~ 100F
300 ~ 4000 ft./min.
SD505-DUCTR
SPECIFICATIONS
10A @ 115VAC 10A @ 240VAC
12 Clintonville Road
Northford, CT 06472
Phone: 203-484-7161 * Fax: 203-484-7118
Specifications subject to change without notice. * September 2014
Installa tion Instructi ons (P/N 170 0-09882 HA -06-094) Page 3 of 3
R
by Honeywell
SD505-DUCTR AND SD505-DTS-K WIRING CONNECTIONS
REFER TO INSTALLATION INSTRUCTIONS (HA-06-094)
* SILENT KNIGHT DETECT ORS ARE INTENDED FO R USE WITH AIR DUCT VELOCITIES FROM 300 TO 4000 FEET PER MINUTE. VERIFY THIS B Y CHECKING THE SPECI FICATIONS O F HVAC INSTALLATION AND IF NECESSARY, USE AN ALNOR MODEL 6000P VELOCI TY METER OR EQUIVALENT TO CHECK AIR VELOCITY. * PRESSURE DIFFER ENTIAL MEASUREMENTS S HOULD BE MADE USING A DWYER PRESSURE GAGE (CATALOG #2003 - 3" WATER FULL SCALE) TO I NSURE AIR FLO W IN THIS CHAMBER. THE PRESSURE DIFFERENTIAL BETWEEN INPUT AND EXHAUST TUBE SHO ULD BE BETWEEN 0.01 AND 1.2 INCHES OF WATER. * DO NOT INSTALL WHER E AMBIENT TEMPERATURE EXCEEDS 100 °F (38 °C).
FOR TERMINALS 3,4,5,6,7,8 DO NOT USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE RUN TO PROV IDE SUPERVISION OF CONNECTION.
CAUTION:
24 VDC
(+)
(-)
NC
COMNONC
COM
NO
ALARM
TROUBLE
TEST
GND
PILOT
ALARM
SLC-
SLC+
SW
LED
LED
+ BASE -
BJ
5
910
105 50K 730
473
702
N4
MM 76A
N4
2447W9
A
VDE
EBYEBYEBYEBYEBY
EBY
2127H1
A
Bottom View
MADE IN I NDONESIA
105
335
200
4
105
2004
1
P
9
1V H
BJ
5
673
10
16E
C2K
G43
673 10 16E
104
105
50K
730
105
50K
730
471
473
910
1V H
105
105
V104
103
D217
725S
D217
725S
D217
725S
102
153
104
153
473
A
7
5
473
A
752
T
105 50K 730
473
473
105
474
473
LM393
75M
CR7RG4
V104
153
472
153
105
50K
730
473
474
2004
2004
152
152
A7
5
1V H
1P
9
472
2
T
1P
9
702
152
473
152
473
473
2T
A7
5
A7
5
TEST GND
PILOT
ALARM
LED
LED
Class A (Style 6) Wiring
SC­SLC
OUT
IN
TEST
GND
PILOT
ALARM
SLC-
SLC+
SW
LED
LED
EBYEBY
EBY
TEST
GND
PILOT
ALARM
SLC-
SLC+
SW
LED
LED
EBYEBY
EBY
TEST
GND
PILOT
ALARM
SLC-
SLC+
SW
LED
LED
Silent Knight Control Panel
S+
SC­SLC
S+
SC­SLC
OUT
IN
S+
SC­SLC
S+
EBYEBY
EBY
Class B (Style 4) Wiring
Silent Knight Control Panel
Loading...