SilentKnight SD505-6SB User Manual

SD505-6SB 6” Sounder Base Installation Instructions

This sheet is intended to be used to install the SD505-6SB to a Silent Knight Addressable control panel. Refer to the control panel installation manual for programming instructions (P/N 151139 or 151209).
The SD505-6SB adds an audible output function to a Silent Knight addressable detector.

Specifications

Parameter Rating
Operating Voltage:
Aux. Input Power Current:
SLC Current Draw for Battery Calculation:
Operating Temperature:
Humidity: 10-85% RH Max. SLC Loop Resistance: 50 Ω
SLC Loop 32 VDC Aux. Input 24 VDC Standby: 1 mA Alarm: 34.3 mA Standby: .082 mA Alarm: .082 mA
32° - 120° F (0° - 49° C)

Wiring

This section contains instructions to wire the SD505-6SB to the FACP, and auxiliary power. For system supervision of terminals, do not use looped wire under the terminals. Break the wire run to provide supervision of connections. See Figure 3.

Figure 1: Class B (Style 4) Wiring

Figure 2: Class A (Style 6) Wiring

SLC Wiring

The SD505-6SB can be connected to the FACP for either Class B (Style 4) or Class A (Style 6) supervision. Connect the SD505-6SB to the FACP as shown in Figure 1 or Figure 2.

Figure 3: Correct wiring methods

P/N 151191

Auxiliary Power Wiring

(P/Ns 151209 & 151139).
The SD505-6SB can use aux power from a UL listed, power-limited 24 VDC source. Figure 4 shows how to connect the SD505-6SB to an auxiliary power supply.

Figure 4: Auxiliary Power Connections

Note: Auxiliary power is supplied by a regulated UL
listed power supply for Fire Protective Signalling Systems.

Auxiliary Power Using Flexput™ Circuits

The following describes how to use the Flexput circuits as the auxiliary power source:

Mounting

This section contains instruction on how to mount the SD505-6SB. Refer to Figure 6.

Figure 6: Mounting the SD505-6SB

1. Mount the extension base using the #8 1-1/2 screws through any of the extension base mounting holes. (See Figure 6.)

2. Connect Aux power and the SLC loop as shown in Figure 1, Figure 2 and Figure 4.

1. Connect the aux power wires to the Flexput terminals using “X” terminals as positive, and “O” terminals as negative power. See Figure 5.

Figure 5: Flexput Auxiliary Power Output
2. Configure the auxiliary power output for constant output through programming (refer to Section 7.4 of the IntelliKnight 5820XL or
IFP-1000 Analog/Addressable Fire System
2

3. Connect wiring harness (P/N 140675) to the smoke base and SD505-6SB as shown in Figure 6.

4. Attach the smoke base to extension base (P/ N 120505) using the #8 1/2” screws, through the smoke base mounting standoffs. (See Figure 6.)

7550 Meridian Circle, Ste 100
Maple Grove, MN 55369-4927
763-493-6455 or 800-328-0103
© 2008 Honeywell International Inc. PN 151191 Rev C
Fax: 763-493-6475
www.silentknight.com