SilentKnight SD505-6IB User Manual

SILENT KNIGHT
®
SD505-6IB (6” Isolator Base) Installation Instructions
The SD505-6IB is a 6 inch isolator base that fits underneath the 6 inch detector base.
An isolator base is used to isolate a short circuit wiring fault on a Class A (Style 7) SLC loop. Normally if the control panel detects a short on the SLC loop the entire loop is disabled. When isolator modules are used (as shown in Figure 1) and a short, open or ground fault occurs on the SLC loop, it will be detected as a trouble but all the SLC devices will continue to operate.
Class B (Style 4) Configuration
0-50 devices, up to 10 per branch
Figure 2: Class B (Style 4) Example
1. If a short occurs at point A (Figure 2), isolator base 1 will activate, isolating SLC devices 2 and 3 from the rest of the loop.
2. If a short occurs at point B (Figure 2), isolator base 2 will activate, isolating SLC devices 5 and 6 from the rest of the loop.
3. If a short occurs at point C (Figure 2), isolator base 3 will activate, isolating SLC devices 8 and 9 from the rest of the loop.
Figure 1: Class A (Style 7) Example
SD505-6IB Specifications
Specification Parameter Rating
Operating Temperature: 32° - 120° F
(0° - 49° C)
Length: 4-7/8”
Dimensions:
Operating Voltage: 32 VDC Battery Current Draw dur-
ing AC loss: SLC Current: 50 uA Max. SLC Loop Resistance: 50
Width 4-7/8” Depth: 7/8”
Alarm/Standby: 92 uA
For indoor use only
P/N 151175
Model SD505-6IB Installation Instructions
Wiring the SD505-6IB
Note: Installation and wiring of this device must be done
in accordance with NFPA 72 and local ordinances.
Important!: All wiring is supervised and power limited. Important!: No more than 256 is olator devices (SD505-
LIM or SD505-6IB) can be used on a SLC loop.
Wiring the SD505-6IB to the SLC Terminals
The SD505-6IB connections for the SLC loop internal and external are the same. Wire as shown in Figure 3 or Figure 4. Notice that “Out Terminals” wire to “In Terminals”.
1. Mount the extension base using the #8 1-1/2 screws through the extension base mounting holes. (See Figure 5.)
2. Wire the SLC loop as shown in Figure 3 or Figure 4.
3. Connect wiring harness to the smoke base as shown in Figure 5.
4. Plug wiring harness into harness connector. Refer to Figure 3 and Figure 5.
5. Attach the smoke base (P/N SD505-6AB) to extension base (P/N 120505) using the #8 1/2”. (See Figure 5.)
Note: Do Not over tighten screws.
Figure 3: Class A (Style 7) Wiring for SLC loop
Figure 4: Class B (Style 4) Wiring for SLC Loop
Figure 5: SD505-6IB Mounting
7550 Meridian Circle
Mounting the SD505-6IB
Maple Grove, MN 55369-4927 612-493-6455
The SD505-6IB mounts on a standard single or double gang electrical switch box.
800-328-0103 Fax: 612-493-6475 © 2000 Silent Knight
Follow these steps to mount the SD505-6IB:
2 P/N 151175
P/N 151175B, 12/00