SilentKnight SD500-SDM User Manual

I56-3546-000
SD500-SDM Installation Instructions
The SD500-SDM two-wire smoke module allows you to connect a loop of conventional detectors to a Silent Knight addressable fire alarm control panel (FACP). Each loop can then be assigned an address on the FACP.

Specifications

Specification Parameter Rating
2-Wire Smoke Detector Loop Current:
Operating Voltage: SLC 32 VDC
SLC Current for battery calculation:
Operating Temperature: 32° - 120° F
Humidity: 10-85% RH Max. SLC Loop Resistance: 50 Ω Max. 2-wire Conventional Smoke Loop
Resistance Dimensions: Length: 4-7/8”
For indoor use only

Compatibility

Standby: 2 mA max. Alarm: 100 mA max.
Aux Power 24 VDC Alarm: .55 mA Standby: .55 mA
(0° - 49° C)
50 Ω
Width: 4-7/8” Depth: 7/8”

Wiring

Note: Installation and wiring of this device must be done in
accordance with NFPA 72 and local ordinances.
Important! All wiring is supervised and power limited.

Connecting the SD500-SDM to the SLC Loop

The SD500-SDM connections to the 5815XL internal and external are the same. Wire as shown in Figure 1.
Figure 1: SLC Wiring

Smoke Detector Connections

This section contain instructions on how to connect a 2-wire conventional smoke detector loop to the SD500-SDM for either Class B (Style B), or Class A (Style D).

Class B (Style B) Wiring

Wire Class B (Style B) conventional smoke detector loop to the SD500-SDM as shown in Figure 2. Place the jumper block in the Class B
The SD500-SDM is compatible with all Silent Knight addressable FACPs.
P/N 151193
SD500-SDM Installation Instructions
(Style B) supervision position (see Figure 4).
Figure 2: Class B (Style B) 2-Wire Detector Loop
Note: Auxiliary power is supplied by a Regulated UL listed
power supply for Fire Protective Signalling Systems.

Class A (Style D) Wiring

Wire Class A (Style D) conventional smoke detector loop to the SD500-SDM as shown in Figure 3. Place the jumper block in the Class A (Style D) supervision position (see Figure 4).
Flexput™ Circuits
The SD500-SDM can use aux power from any 24 VDC source. The following describes how to use the Flexput circuits as the auxiliary power source:
1. Connect the aux power wires to the Flexput terminals using “X” terminals as positive and “O” terminals as negative power. See Figure 5.
Figure 3: Class A (Style D) 2-Wire Detector Loop
Figure 4: Supervision Selection Jumper
Auxiliary Power Using
Figure 5: Flexput Auxiliary Power Output
2. Configure the auxiliary power output for constant output through programming. Refer to the FACP installation manual form more information.

For More Information

This document is for quick reference. For more information, refer to the FACP installation manual.

Two-Wire Smoke Detectors

Table 1 lists two-wire smoke detectors that are compatible with the fire control panel. The table
is organized by manufacturer. The columns show the number of detectors per loop that can be used.
SD500-SDM Identifier Operating Voltage Range
24H
18.5–27.4 VDC
2 P/N 151193
SD500-SDM Installation Instructions
Note: The maximum number of smoke detectors per zone is determined by both the current draw and the impedance of the smoke
detector. If too many smoke detectors are used on any zone, false alarms could occur.
Do not mix different models of detectors on any zone; false alarms could occur.
Do not mix detectors of different models unless the system is specifically intended to be installed in that configuration.
Control unit Smoke Reset T ime mu st be programmed for a number greater than or equal to the maximum r eset time of the smoke detector.
T able 1: Compatible Two-Wire Smoke Detectors
Model Name or Number
Manufacturer
Apollo 55000-350 (45681-200) 55000-350 45681-200 24 / loop
ESL 429C (S10A) N/A S10A 30 / loop
(Base model name or
number in parentheses.)
55000-250 (45681-200) 55000-250 45681-200 24 / loop 55000-225 55000-225 45681-255, 256, 55000-226 55000-226 15/ loop 55000-227 55000-227 15 / loop 55000-325 55000-325 15 / loop 55000-328 5500-328 15 / loop 55000-326 55000-326 15 / loop 55000-327 55000-327 15 / loop
429CRT (S11A) N/A S11A 30 / loop 429CST (S11A) N/A S11A 30 / loop 429CT (S10A) N/A S10A 30 / loop 609U01-11 S10 S00 40 / loop 609U02-11 S10 S00/S03 40 / loop 611U (601U or 602U) S10 S00/S03 40 / loop 611UD (601U or 602U) S10 S00/S03 40 / loop
Compatibility ID
# per Loop
Head Base
15 / loop
45681-200, 220 230, 232, 251, 252
611UT (601U or 602U) S10 S00/S03 40 / loop 612U (601U or 602U) S10 S00/S03 40 / loop 612UD (601U or 602U) S10 S00/S03 40 / loop 71 1U (701E or 701U) N/A S10A 25 / loop 712U (701E or 701U) N/A S10A 25 / loop 713-5U (702E or 701U) N/A S10A 25 / loop 713-6U (702E or 701U) N/A S10A 25 / loop 721-U (S10A) N/A S10A 30 / loop 721-UT (S10A) N/A S10A 30 / loop
Falcon 525 FDT1 N/A 17 / loop
525T FDT1 N/A 17 / loop
P/N 151193 3
SD500-SDM Installation Instructions
Table 1: Compatible Two-Wire Smoke Detect or s
Model Name or Number
Manufacturer
Hochiki SIH-24F (HS-224D OR
System Sensor 1400 A N/A 20 / loop
(Base model name or
number in parentheses.)
HD-3 HB-5 25 / loop
HSD-224) SLK-24F (HS-224D) HD-3 HB-5 25 / loop SLK-24FH (HS-224D) HD-3 HB-5 25 / loop
1451 (B401B) A A 20 / loop 2100 A N/A 20 / loop 2100T A N/A 20 / loop 2151 A N/A 16 / loop 2151T A N/A 16 / loop 2300T A N/A 20 / loop 2300 A N/A 20 / loop 2300TB A N/A 20 / loop 2400 A N/A 20 / loop 2400 (DH400) A N/A 20 / loop 2400AIT A N/A 20 / loop
Compatibility ID
# per Loop
Head Base
2400AT A N/A 20 / loop 2400TH A N/A 20 / loop 2451 (B401B) A N/A 20 / loop 2451DH (DH 400) A N/A 20 / loop 2451TH (B401B) A N/A 20 / loop 2W-B A N/A 20 / loop 2WT-B A N/A 20 / loop 2WTR-B A N/A 20 / loop
4 151193 Rev E
I56-3546-000
Loading...