SEW-Eurodrive MOVITRAC MC07B, MC07B0055-5A3-4-00, MC07B0030-5A3-4-S0, MC07B0040-5A3-4-S0, MC07B0015-5A3-4-S0 User Manual

...
Drive Technology \ Drive Automation \ System Integration \ Services
Manual
MOVITRAC
®
MC07B
Functional Safety
SEW-EURODRIVE—Driving the world
Manual – Functional Safety MOVITRAC® MC07B
3
Contents
Contents
1 General Information............................................................................................ 4
1.1 How to use this documentation................................................................... 4
1.2 Underlying standards.................................................................................. 4
1.3 Structure of the safety notes......................................... ... .... ... ... ... ... .... ....... 5
1.4 Rights to claim under warranty ................................................................... 6
1.5 Exclusion of liability..................................................................................... 6
1.6 Copyright notice.......................................................................................... 6
1.7 Document content....................................................................................... 6
1.8 Other applicable publications...................................................................... 6
2 Integrated Safety Technology............................................................................ 7
2.1 Safe condition ............... ... ... ... .......................................... .... ... ... ... .............. 7
2.2 Safety concept ............................................................................................ 7
2.3 Schematic representation – "safety concept for MOVITRAC
®
B"............... 8
2.4 Safety functions .......................................................................................... 9
2.5 Restrictions ............................................................................................... 11
3 Safety Conditions.............................................................................................. 12
3.1 Approved devices ..................................................................................... 13
3.2 Installation requirements........................................................................... 14
3.3 Requirements on the external safety controller ........................................ 16
3.4 Requirements on startup........................................................................... 17
3.5 Requirements on operation....................................................................... 17
4 Connection Variants ............. ... ... ... .... .......................................... ... ... ... ... .... ..... 18
4.1 General information ................................................................................ .. 18
4.2 Requirements............................................................................................ 19
4.3 Disconnection of a single drive ................................................................. 20
4.4 Disconnection of group drives................................................................... 26
5 Technical Data .................................................................................................. 30
5.1 Safety characteristics................................................................................ 30
5.2 Electronics data X17: Signal terminal block for STO safety contact......... 30
Index................................................................................................................... 31
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
4
Manual – Functional Safety MOVITRAC® MC07B
1
How to use this documentation
General Information
Functional Safety MOVITRAC® MC07B
1 General Information
1.1 How to use this documentation
The documentation is an integral part of the product and contains impo rtant information on operation and service. The documentation is written for all employees wh o assemble, install, start up, and service this product.
The documentation must be accessible and legib le. Make sure that persons responsible for the system and its operation, as well as persons who wor k independently on the unit, have read through the documentation carefully and understood it. If you are unclear about any of the information in this documentation, or if you require further information, contact SEW-EURODRIVE.
Make sure you always use the latest documentation and software version. Our documentation is available in various languages for download from the SEW
homepage
. Consult SEW-EURODRIVE if you are unclear
about any of the info
rmation in this docu
mentation, or if you require further information.
You can also order the printed documentatio n from SEW-EURODRIVE.
1.2 Underlying standards
The safety assessment of the unit is based on the following standards and safety classes:
Underlying standards
Safety class/underlying standard
Performance level (PL) according to EN ISO 13849­1:2008
Category 3 according to EN 954-1:1996
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
5
1
Structure of the safety notes
General Information
1.3 Structure of the safety notes
1.3.1 Meaning of signal words
The following table shows the grading and meaning of the signal words for safety notes, notes on potential risks of damage to property, an d ot he r no te s.
1.3.2 Structure of the section safety notes
Section safety notes do not apply to a specific action but to several actions pertaining to one subject. The symbols used either indicate a general hazard or a specific hazard.
This is the formal structure of a section safety note:
1.3.3 Structure of the embedded safety notes
Embedded safety notes are directly integrated in the instructions just before the descrip­tion of the dangerous action.
This is the formal structure of an embedded safety note:
SIGNAL WORD Type and source of danger. Possible consequence(s) if disregarded. – Measure(s) to prevent the danger.
Signal word Meaning Consequences if disregarded
DANGER Imminent danger Severe or fatal injuries WARNING Possible dangerous situation Severe or fatal injuries CAUTION Possible dangerous situ ation M inor injuries
NOTICE Possible damage to property Damage to the drive system or its
environment
INFORMATION Useful information or tip:
implifies the handling of the drive system.
SIGNAL WORD
Type and source of danger. Possible consequence(s) if disregarded.
Measure(s) to prevent the danger.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
6
Manual – Functional Safety MOVITRAC® MC07B
1
Rights to claim under warranty
General Information
1.4 Rights to claim under warranty
A requirement of fault-free operation and fulfillment of any rights to claim under limited warranty is that you adhere to the information in the MOVITRAC
®
documentation.
Therefore, read the operating instructions before you start working with the unit. Make sure that the documentation is available to persons responsible for the system and
its operation as well as to persons who work independently on the unit. You must also ensure that the documentation is legible.
1.5 Exclusion of liability
Adherence to the operating instructions is essential to ensure safe operation of MOVITRAC
®
MC07B units and to achieve the specified product characteristics and performance features. SEW-EURODRIVE assumes no liability for injury to persons or damage to equipment or property resulting from non-adherence to these operating instructions. In such cases, any liability for defects is excluded.
1.6 Copyright notice
© 2010 – SEW-EURODRIVE. All rights reserved. Copyright law prohibits the unauthorized duplication, modification, distribution, and use
of this document, in whole or in part.
1.7 Document content
This publication contains conditions and amendments related to MOVITRAC® MC07B units in safety-related applications.
The system comprises a drive inverter with AC motor and safety-tested external disconnecting device.
1.8 Other applicable publications
This document supplements the MOVITRAC® MC07B operating instructions and limits the application notes according to the following information. It may only be used together with the MOVITRAC
®
MC07B operating instructions.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
7
2
Safe condition
Integrated Safety Technology
2 Integrated Safety Technology
The safety technology of MOVITR AC®MC07B units described below has been devel­oped and tested in accordance with the following safety requirements:
Category 3 according to EN 954-1: 1996
PL d according to EN ISO 13849-1: 2008 This was certified by TÜV Nord. Copies of the TÜV certificate can be obtained from
SEW-EURODRIVE.
2.1 Safe condition
For safety-related operation of MOVITRAC®MC07B, safe torque off is defined as safe condition (see STO safety function). The safety concept is based on this definition.
2.2 Safety concept
In the event of danger, any potential risk related to a machine must be eliminated as
quickly as possible. Standstill with restart prevention is generally the safe condition for preventing dangerous movements.
The MOVITRAC
®
MC07B inverter is characterized by the option to connect an external safety relay. This safety re lay disconnects all active elem ents (disconnec­tion of the safety-related 24 V power supply of the output stag e control) that generate the pulse trains to the power output stage (IGBT) when a connected control device (E-STOP button with latching function) is activated.
Disconnecting the safety-related 24 V supply voltage ensures that the supply voltages required for operating the inverter and consequently for generating a rotat­ing field of pulse patterns (whic h allow the generation of a rotating field) are saf ely interrupted, preventing automatic restart.
Instead of galvanic separation of the drive from the power supply by means of relays or switches, the disconnection of the 24 V supply described here safely prevents the control of the power semiconductors in the drive inverter. This process disconnects the rotating field generation for the respective motor. The individual motor cannot develop any torque in this state even though the line voltage is still present.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
8
Manual – Functional Safety MOVITRAC® MC07B
2
Schematic representation – "safety concept for MOVITRAC® B"
Integrated Safety Technology
2.3 Schematic representation – "safety concept for MOVITRAC® B"
1797262603
[1] Safety-related DC 24 V voltage supply [2] Electrical isolation [3] Voltage supply for control of power transistors [4] Pulse width modulated signals for the output stage
S24V S0V24
M
Uz-
Uz+
24V
SNT
S0V24
SVI24
L1 L2 L3
GND
[1]
[2]
[3]
[4]
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
9
2
Safety functions
Integrated Safety Technology
2.4 Safety functions
The following drive-related safety functions can be used:
STO (safe torque off according to EN 61800-5-2) by disconnecting the STO input. If the STO function is activated, the frequency inverter no longer supplies power to
the motor for generating torque. This safety function corresponds to a non-co ntrolled stop according to EN 60204-1, stop category 0.
The STO input must be disabled by a suitable external safety controller/safety relay. The following figure shows the STO function:
2463228171
v Velocity tTime t
1
Time at which STO is triggered Disconnection range
v
t
t
1
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
10
Manual – Functional Safety MOVITRAC® MC07B
2
Safety functions
Integrated Safety Technology
SS1(c) (safe stop 1, function variant c according to EN 61800-5-2) by means of suitable external control (e.g. safety relay with delayed disconnection)
The following sequence is mandatory: – Decelerate the drive using an appropriate brake ramp specified via setpoints. – Disconnect the STO input (= triggering the STO function) after a specified safety-
related time delay.
This safety function corresponds to a controlled stop according to EN 602041, stop category 1.
The following figure illustrates the SS1(c) function:
2463226251
v Velocity tTime t
1
Point of time when the brake ramp is initiated
t
2
Point of time when STO is triggered
t Time between initiating the brake ramp and STO
Safe time delay range Disconnection range
v
t
t
1
tt
2
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
11
2
Restrictions
Integrated Safety Technology
2.5 Restrictions
Note that if the drive does not have a mechanical brake, or if the brake is defective, the drive may coast to a halt (depending on the friction and mass moment of inertia of the system). In case of regenerative loads, the drive can even accelerate. This must be taken into account in a risk assessment of the system/machine. Additional safety measures might have to be implemented (e.g. safety brake system).
MOVITRAC
®
MC07B cannot be used without an additional brake system for appli-
cation-specific safety functions that require active deceleration (braking).
When using the SS1(c) function as described in chapter "Safety functions", the brake ramp of the drive is not monitored with respect to safety. In case of a fault, the drive might not be decelerated after the delay time, or it might be accelerated in the worst case. In this case, th e STO function (see chapter "Safety functions") is only activated after the set time delay has elapsed. The re sulting danger must be taken into account in the risk assessment of the system/machine. Additional safety measures might have to be implemented.
WARNING
The safety concept is only suitable for performing mechanical work on the system/ machine components.
When the STO signal is disconnected, the line voltage is still present at the DC link of MOVITRAC
®
MC07B.
Severe or fatal injuries from electric shock.
Before working on the electric part of the drive system, disconnect it from the supply system using an appropriate external disconnecting device and secure it against unintentional reconnection to the power supply.
INFORMATION
In case of safety-related disconnection of the DC 24 V supply at X17 (STO activated), the brake is always applied. The brake control in MOVITR AC
®
MC07B is not safety-
related.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
12
Manual – Functional Safety MOVITRAC® MC07B
3
Safety Conditions
3 Safety Conditions
The requirement for safe operation is that the safety functions of MOVITRAC® MC07B are properly integrated into an application-specific higher-level safety function. A system/machine-specific risk assessment must be carried out by the system/machine manufacturer and taken into account for operating the drive system with MOVITRAC
®
MC07B. The system/machine manufacturer and the operator are responsible for compliance of
the system/machine with applicable safety regulations. The following requirements are mandatory when installing and operating MOVITRAC
®
MC07B units in safety-related applications.
The requirements are divided into:
Approved devices
Requirements on the installation
Requirements on external safety controllers and safety relays
Requirements on startup
Requirements on operation
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
13
3
Approved devices
Safety Conditions
3.1 Approved devices
The following unit variants of MOVITRAC® MC07B are permitted for safety-related applications:
3.1.1 MOVITRAC
®
MC07B for a supply voltage of 3 × AC 380 – 500 V
3.1.2 MOVITRAC
®
MC07B for a supply voltage of AC 200 – 240 V
Power kW
Size Type
0.55 0S MC07B0005-5A3-4-S0
0.75 0S MC07B0008-5A3-4-S0
1.1 0S MC07B0011-5A3-4-S0
1.5 0S MC07B0015-5A3-4-S0
2.2 0L MC07B0022-5A3-4-S0
3.0 0L MC07B0030-5A3-4-S0
4.0 0L MC07B0040-5A3-4-S0
5.5 2S MC07B0055-5A3-4-00
7.5 2S MC07B0075-5A3-4-00 11 2 MC07B0110-5A3-4-00 15 3 MC07B0150-503-4-00 22 3 MC07B0220-503-4-00 30 3 MC07B0300-503-4-00 37 4 MC07B0370-503-4-00 45 4 MC07B0450-503-4-00 55 5 MC07B0550-503-4-00 75 5 MC07B0750-503-4-00
Power kW
Size Type
0.55 0S MC07B0005-2A3-4-S0
0.75 0S MC07B0008-2A3-4-S0
1.1 0L MC07B0011-2A3-4-S0
1.5 0L MC07B0015-2A3-4-S0
2.2 0L MC07B0022-2A3-4-S0
3.7 1 MC07B0037-2A3-4-00
5.5 2 MC07B0055-2A3-4-00
7.5 2 MC07B0075-2A3-4-00 11 3 MC07B0110-203-4-00 15 3 MC07B0150-203-4-00 22 4 MC07B0220-203-4-00 30 4 MC07B0300-203-4-00
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
14
Manual – Functional Safety MOVITRAC® MC07B
3
Installation requirements
Safety Conditions
3.2 Installation requirements
For size 0 units of the type MC07B...-S0, an external 24V supply must always be connected because the control electronics can only be powered in this way.
The safety-related DC 24 V supply voltage must be routed according to EMC guide­lines as follows:
– Outside an electrical installation space, shielded cables must be routed perma-
nently (fixed) and protected against external damage, or other equivalent mea-
sures have to be taken. – Individual conductors can be routed inside an electrical installation space. – Adhere to the regulations in force for the application.
Power lines and safety-related control lines have to be installed in separate cables.
Make sure that no parasitic voltages can be generated in the safety-related control lines.
Wiring technology must comply with EN 60204-1.
Use only grounded voltage sources with safe isolation (PELV) according to VDE0100 and EN 60204-1. In case of a single fault, the voltage between the outputs or between any output and grounded parts must not exceed DC 60 V.
Observe the notes in the "MOVITRAC
®
MC07B" operating instructions for informa­tion on EMC-compliant cabling. It is essential that you connect the shield of the safety-related DC 24 V supply cable to the housing at both ends.
The lines of the safety-related 24 V voltage supply (terminal X17) must be clamped under the signaling electronics shield clamp.
When planning the installation, observe the technical data of MOVITRAC
®
MC07B.
Observe the values specified for safety components when designing the safety cir­cuits.
The cable length of the safety-related DC 24 V supply may not exceed 100 m.
The safety-related DC 24 V supply may not be used for feedback.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
15
3
Installation requirements
Safety Conditions
All connections (such as lines or data communication using bus systems) must already have been taken into account in the performance level of one of the sub­systems involved, or it must be possible that faults in the connections can be excluded or neglected.
The fault assumption "short circuit between any two conductors" can be excluded according to EN ISO 13849-2: 2008 under the following conditions:
The conductors are – permanently (fixed) installed and protected against external dam age (for example
using a cable duct or armored conduit)
– installed in different light plastic-sheathed cables in an electrical installation space
provided that both the lines and the installation space meet the relevant require-
ments, see EN 60204-1 – protected individually by a ground connection The fault assumption "short circuit between any conductor and an exposed conduc-
tive part or earth or a protective conductor" can be excluded under the following conditions:
– Short circuit between conductor and any exposed conductive part in an installa-
tion space.
For applications with safety-related disconnection of the drive, remove the jumpers on X17:1 to X17:4 ( following figure).
1797603595
Removing jumpers
SVI
SOV
24V
GND
X17
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
16
Manual – Functional Safety MOVITRAC® MC07B
3
Requirements on the external safety controller
Safety Conditions
3.3 Requirements on the external safety controller
A safety relay can be used as an alternative to a safety controller. The following require­ments apply analogously.
The safety controller and all other safety-related subsystems must be approved for at least that safety class which is required in the overall system for the respective, application-related safety function.
The following table shows an example of the required safety class of the safety controller:
1593958923
[1] Safety relay with approval [2] DC 24 V voltage supply [3] Fuses in accordance with the manufacturer's specifications of the safety relay [4] Safety-related DC 24 V voltage supply [5] Reset button for manual reset [6] Approved EMERGENCY STOP actuating device
Application Safety controller requirements
Performance level d according to EN ISO
13849-1
Performance level d according to EN ISO
13849-1
SIL 2 according to EN 61508
[4]
[3]
[1]
[5]
[6]
[2] U
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
17
3
Requirements on startup
Safety Conditions
The wiring of the safety controller must be suitable for the required safety class, (see manufacturer documentation).
– If the DC 24 V supply is safely disconnected at the positive pole only, no test
pulses must be applied to this pole in disconnected condition. If the DC 24 V supply is disconnected at both poles, the test pulses must not be
applied at the same time at the plus and minus outputs. In this case , the test pulse must be applied with a time delay.
– SEW-EURODRIVE recommends to switch off the 24 V supply at two poles.
The values specified for the safety controller must be strictly adhered to wh en de­signing the circuit.
The switching capacity of the safety relays or the relay outputs of the safety controller must correspond at least to t he maximally permitted, limited output current of the 24 V voltage supply.
Observe the manufacturer's instructions concerning the permitted contact loads and fusing that may be required for the safety contacts. If the manufacturer provides no specific information, the contacts must be protected with 0.6 times the nominal value of the maximum contact rating specified by the manuf ac tu re r.
To ensure protection against unintended restart in accordance with EN 1037, the safe control system must be designed and connecte d in such a way that resetting the control device alone does not lead to a restart. A restart may only b e carried out after a manual reset of the safety circuit.
3.4 Requirements on startup
To validate the implemented safety functions, they must be documented and checked after successful startup (validation).
Observe the limitations for safety functions in chapter "Limitations" for the validation of the safety functions. Non-safety-related parts and components that affect the result of the validation test (e.g. motor brake) must be deactivated, if necessary.
For using MOVITRAC
®
MC07B in safety-relevant applications, it is essential that you
perform and record startup checks for the disconnectin g device and for proper wiring.
3.5 Requirements on operation
Operation is only allowed within the limits specified in the data sheets. This pr inciple applies to the external safety control as well as toMOVITRAC
®
MC07B and approved
options.
You must check the safety functions on a regular basis to ensure proper functioning. The test intervals should be specified in accordance with the risk assessment.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
18
Manual – Functional Safety MOVITRAC® MC07B
4
General information
Connection Variants
4 Connection Variants
4.1 General information
Generally, all the connection variants listed in this documentation are permitted for safety-relevant applications as long as the basic safety concept is met. This means you have to make sure that the DC 24 V safety inputs are operated by an external safety relay or a safety controller, thus preventing an automatic restart.
All safety conditions mentioned in chapter 2, 3 and 4 of this docu mentation must be met for the basic selection, installation, and application of the safety components, such as safety relay, EMERGENCY STOP switch, etc., and the approved connection variants.
The wiring diagrams are block diagrams whose only purpose is to show the safety function(s) with the relevant components. Circuit-related measures, which usually always have to be implemented additionally, are not shown in the diagrams to enh ance clarity. Such measures are t aken , fo r exam ple, to ensure protection against contact, to handle overvoltage and undervoltage, to detect insulation faults, line-to-ground faults and short circuits, which can occur on externally installed lines, or to ensure the neces­sary immunity against electromagnetic interference.
4.1.1 X17 terminal on MOVITRAC
®
MC07B
The following figure shows the X17 terminal at the bottom of the control unit.
3210370059
* View of the underside of the unit
[1] X17: Signal terminal block for STO safety contacts
[1]
[1]
X17
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
19
4
Requirements
Connection Variants
4.2 Requirements
4.2.1 Use of safety relays
The requirements of the manufacturers of safety relays (such as protecting the output contacts against welding) or other safety components must be strictly observed. For cable routing, the basic requirements apply as described in this publication.
For connecting MOVITRAC
®
with the safety relays, observe the installation require-
ments in chapter "Installation requirements" (page 14). Other instructions by the manufacturer on the use of safety relays for specific applica-
tions must also be observed.
4.2.2 Use of safety relays
Observe the ZVEI specifications for safety sensors if you use a safety PLC. The starting and stopping pulses of the safe digital outputs (F-DO) used must be 1ms.
The ratio must not fall below 1:1000.
3211043979
<1ms >1000ms
High
Low
t
INFORMATION
If the DC 24 V supply at X17 is switched off safely (STO activated), you must observe chapter "Requirements on the exter nal safety co ntroller (pa ge 16)" with regard to the test pulses.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
20
Manual – Functional Safety MOVITRAC® MC07B
4
Disconnection of a single drive
Connection Variants
4.3 Disconnection of a single drive
4.3.1 STO according to PL d (EN ISO 13849-1)
The procedure is as follows:
Recommendation: X12:1 and X12:4 are disconne cted at the same time, e.g. in case of an emergency stop.
The 24 V safety input X17 is disabled.
The motor coasts to a halt, if no brake is installed.
STO – Safe Torque Off (EN 6180 0-5-2)
4949829771
t
n
X17
X12:4
X12:1
INFORMATION
The illustrated STO disconnections can be used up to PL d according to EN ISO 13849 -1 taking account of chapter "Requirements" (page 19).
•MOVITRAC
®
MC07B size 0 requires an external DC 24 V voltage supply.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
21
4
Disconnection of a single drive
Connection Variants
Binary control with safety relay (dual-channel)
Binary control with safety relay (single-channel)
4891650443
+24 V
Feedback emergency stop
Reset
Higher-level
controller
PLC
IN
OUT
Safety relay
Emerg. stop
Start
Stop
GND
Mains
MC07B
2
X12
1
4
X17
456
1 2 3 4
'0'=Controller inhibit '1'=Controller enable '0'=Stop '1'=START CW '0'=Rapid stop '1'=Enable
8
24VIO
9
GND
DGND VO24
SVI24
SOV24
X2
M
UVW
4891648523
+24 V
Feedback emergency stop
Reset
Higher-level
controller
PLC
IN
OUT
Safety relay
Emerg. stop
Start
Stop
Mains
MC07B
2
X12
1
4
X17
456
1 2 3 4
'0'=Controller inhibit '1'=Controller enable '0'=Stop '1'=START CW '0'=Rapid stop '1'=Enable
8
24VIO
9
GND
DGND VO24
SVI24
SOV24
X2
M
UVW
INFORMATION
With single-channel disconnection, certain fault assumptions have to be made and handled through fault exclusion. Observe the "Requirements" (page 19) chapter.
SEW-EURODRIVE recommends to switch off the 24 V supply of the STO input X17 at two poles.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
22
Manual – Functional Safety MOVITRAC® MC07B
4
Disconnection of a single drive
Connection Variants
Binary control with safety PLC
Fieldbus control with safety PLC
4891654283
+24 V
Higher-level
controller
Standard Safe
IN
OUT
Emerg. stop
Start
Stop
GND
Mains
IN
OUT
MC07B
2
X12
1
4
X17
456
1 2 3 4
'0'=Ctrl. inhibit '1'=Ctrl. enable '0'=Stop '1'=START CW '0'=Rapid stop '1'=Enable
8
9
24VIO GND
DGND VO24
SVI24
SOV24
X2
M
UVW
4891656203
+24 V
Higher-level
controller
Standard
Safe
IN
Emerg. stop
Start
Stop
GND
GND
Mains
IN
MC07B
X12
X30
DFS 21B
X17
456
1 2 3 4
DGND VO24
SVI24
SOV24
(GND) (24 V_LS)
GND
(F_DO_M) (F_DO_P)
24VIO
X2
M
UVW
1 2 3 4 8 9
PROFINET
PROFIsafe
INFORMATION
Controller inhibit/enable and rapid stop/enable are set via fieldbus.
Note the respective fieldbus manuals, e.g. – "DFS11B PROFIBUS DP-V1 Fieldbus Interface with PROFIsafe" manual – "DFS21B PROFINET IO Fieldbus Interface with PROFIsafe" manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
23
4
Disconnection of a single drive
Connection Variants
4.3.2 SS1(c) according to PL d (EN ISO 13849-1)
The procedure is as follows:
X12:1 must not be disconnected.
X12:4 is disconnected, e.g. in case of an emergency stop.
During the safety time interval t
1
, the motor decelerates to a complete stop along the
ramp.
After t
1
has elapsed, the safety input X17 is disconnected. The safety time interval t
1
must be sufficient for the motor to reach a complete stop.
SS1(c) – Safe Stop 1 (EN 61800-5-2)
4949929739
t
n
X17
X12:4
t
1
X12:1
INFORMATION
The illustrated SS1(c) disconnections can be used up to PL d according to EN ISO 13849 -1 taking account of chapter "Requirements" (page 19).
•MOVITRAC
®
MC07B size 0 requires an external DC 24 V voltage supply.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
24
Manual – Functional Safety MOVITRAC® MC07B
4
Disconnection of a single drive
Connection Variants
Binary control with safety relay (dual-channel)
Binary control with safety relay (single-channel)
4891646603
+24 V
Feedback emergency stop
Reset
Higher-level
controller
PLC
IN
OUT
Safety relay
Emerg. stop
Start
Stop
GND
Mains
MC07B
2
X12
1
4
X17
456
1 2 3 4
'0'=Controller inhibit '1'=Controller enable '0'=Stop '1'=START CW '0'=Rapid stop '1'=Enable
8 24VIO 9 GND
DGND VO24
SVI24
SOV24
X2
M
UVW
t
1
4891658123
+24 V
Feedback
emergency stop Reset
Higher-level
controller
PLC
IN
OUT
Safety relay
Emerg. stop
Start
Stop
Mains
MC07B
2
X12
1
4
X17
456
1 2 3 4
'0'=Controller inhibit '1'=Controller enable '0'=Stop '1'=START CW '0'=Rapid stop '1'=Enable
8
24VIO
9
GND
DGND VO24
SVI24
SOV24
X2
M
UVW
t
1
INFORMATION
With single-channel disconnection, certain fault assumptions have to be made and handled by fault exclusion. Observe the "Requirements" (page 19) chapter.
SEW-EURODRIVE recommends to switch off the 24 V supply of the STO input X17 at two poles.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
25
4
Disconnection of a single drive
Connection Variants
Binary control with safety PLC
Fieldbus control with safety PLC
4891654283
+24 V
Higher-level
controller
Standard Safe
IN
OUT
Emerg. stop
Start
Stop
GND
Mains
IN
OUT
MC07B
2
X12
1
4
X17
456
1 2 3 4
'0'=Ctrl. inhibit '1'=Ctrl. enable '0'=Stop '1'=START CW '0'=Rapid stop '1'=Enable
8
9
24VIO GND
DGND VO24
SVI24
SOV24
X2
M
UVW
4891656203
+24 V
Higher-level
controller
Standard
Safe
IN
Emerg. stop
Start
Stop
GND
GND
Mains
IN
MC07B
X12
X30
DFS 21B
X17
456
1 2 3 4
DGND VO24
SVI24
SOV24
(GND) (24 V_LS)
GND
(F_DO_M) (F_DO_P)
24VIO
X2
M
UVW
1 2 3 4 8 9
PROFINET
PROFIsafe
INFORMATION
Controller inhibit/enable and rapid stop/enable are set via fieldbus.
Note the respective fieldbus manuals, e.g. – "DFS11B PROFIBUS DP-V1 Fieldbus Interface with PROFIsafe" manual – "DFS21B PROFINET IO Fieldbus Interface with PROFIsafe" manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
26
Manual – Functional Safety MOVITRAC® MC07B
4
Disconnection of group drives
Connection Variants
4.4 Disconnection of group drives
This chapter describes how several MOVITRAC® MC07B units are controlled safely.
4.4.1 Requirements
For group drives, the 24 V safety inputs of several MOVITRAC
®
MC07B inverters can be made available by a single safety relay. The maximum number of axis modules results from the maximum permitted contact load of the sa fety relay or safety controller .
Other requirements of the manufacturers of safety relays (such as protecting the output contacts against welding) or other safety components must be strictly observed. For cable routing, observe the basic requirements in chapter "Installation requirements" (page 14).
For connecting MOVITRAC
®
inverters with safety relays, observe the installation
requirements in chapter "Installation requirements" (page 14). Other instructions by the manufacturer on the use of safety relays for specific applica-
tions must also be observed.
Determining the maximum number of MOVITRAC
®
units for group disconnection
The number (n units) of MOVITRAC
®
MC07B units that can be controlled with group
disconnection is limited by the following points:
1. Switching capacity of the safety relay.
A fuse must be connected in front of the safety contacts according to the specifica­tions of the emergency stop relay manufacturer to prevent contact welding.
The project planner is responsible for ensuring that the specifications for the switch­ing capacity to EN 60947-4-1, 02/1 and EN 60947-5-1, 11/97 as well as on contact fuse protection given in the operating instructions of the safety relay manufacturer are strictly observed.
2. Maximum permitted voltage drop in the 24 V power supply cable.
Values concerning cable lengths and permitted voltage drops must be observed during project planning for axis systems.
3. Maximum cable cross section of 1 × 1.5 mm
2
or 2 × 0.75 mm2.
4. Power consumption of STO input X17: Input voltage, see chapter "Technical Data"
(page 30).
5. When using self-testing semiconductor outputs, the increased capacitances of STO
input X17 caused by group disconnection (parallel connection) might result in diagnostics errors.
INFORMATION
SEW-EURODRIVE does not recommend group disconnection via safety PLC.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
27
4
Disconnection of group drives
Connection Variants
4.4.2 Implementing group disconnection with a safety relay
Group disconnection with one safety relay
The safety inputs of all MOVITRAC
®
MC07B can be controlled with one safety relay.
Group disconnection with two safety relays
The safety inputs of the assigned MOVITRAC
®
MC07B inverters can be controlled with
several safety relays. In the following example, MOVITRAC
®
MC07B size 3 inverters
and MOVITRAC
®
MC07B size 0 inverters each form one group, and each group is
controlled by a safety relay.
4892037259
MC07B
Safety relay (SG)
®
Control cabinet
X17
X17
X17
BG0BG0
BG3 BG3
X17 X17
BG3
SG1
MOVITRAC
MC07B
MC07B
MC07B
MC07B
4891918091
MC07
Safety relay (SG)
®
Control cabinet
X17
X17
X17
BG0BG0
BG3
MC07
BG3
X17 X17
BG3
MOVITRAC
SG1 SG1
MC07 MC07
MC07
P
i
f
kVA
Hz
n
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
28
Manual – Functional Safety MOVITRAC® MC07B
4
Disconnection of group drives
Connection Variants
4.4.3 STO according to PL d (EN ISO 13849-1)
The procedure is as follows:
Recommendation: X12:1 and X12:4 are disconne cted at the same time, e.g. in case
of an emergency stop.
The 24 V safety input X17 is disconnected.
The motor coasts to a halt, if no brake is installed.
STO – Safe Torque Off (EN 6180 0-5-2)
4949829771
t
n
X17
X12:4
X12:1
INFORMATION
The displayed STO disconnections can be used up to PL d according to EN ISO 13849-1.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
29
4
Disconnection of group drives
Connection Variants
Example: Group disconnection with three MOVITRAC® MC07B
+24 V
Feedback emergency stop
Reset
Higher-level
controller
PLC
IN
OUT
Safety relay
Emergency stop
Start
Stop
GND
Mains
MC07B
2
X12
1
4
X17
4 56
1 2 3 4
'0'=Controller inhibit '1'=Controller enable '0'=Stop '1'=START CW '0'=Rapid stop '1'=Enable
8
24VIO
9
GND
DGND VO24
SVI24
SOV24
X2
X1
M
UVW
MC07B
2
X12
1
4
X17
4 56
1 2 3 4
'0'=Controller inhibit '1'=Controller enable '0'=Stop '1'=START CW '0'=Rapid stop '1'=Enable
8
24VIO
9
GND
DGND VO24
SVI24
SOV24
X2
Power supply connection
L3L2L1
1
2
3
X1
M
UVW
Power supply connection
L3L2L1
1
2
3
MC07B
2
X12
1
4
X17
4 56
1 2 3 4
'0'=Controller inhibit '1'=Controller enable '0'=Stop '1'=START CW '0'=Rapid stop '1'=Enable
8
24VIO
9
GND
DGND VO24
SVI24
SOV24
X2
Power supply connection
L3L2L1
1
2
3
X1
M
UVW
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
30
Manual – Functional Safety MOVITRAC® MC07B
5
Safety characteristics
Technical Data
5 Technical Data
The table below shows the technical data of MOVITRAC® MC07B related to integrated safety technology. The technical data and approvals in the respective MOVITRAC
®
MC07B operating instructions must also be observed.
5.1 Safety characteristics
5.2 Electronics data X17: Signal terminal block for STO safety contact
Safety characteristics
Tested safety class / underlying standards Category 3 according to EN 954-1
Performance Level d according to EN ISO 13849-1
Probability of dangerous failure per hour (PFH value)
0 (fault exclusion)
Service life 20 years, after which the component must be replaced with a new one. Safe condition Safe torque off (STO) Safety function STO, SS1
1)
according to EN 61800-5-2
1) With suitable external control
MOVITRAC® MC07B General electronics data
Safety contact X17:1 X17:2
X17:3 X17:4
Permitted cable cross section
Power consumption X17:4
Input capacitance X17:4
DGND: Reference potential for X17:2 VO24: : V
OUT
= DC 24 V, only to supply X17:4 of the same unit; cannot be used to
supply other units. SOV24: Reference potential for DC +24 V "STO" input (safety contact) SVI24: DC+24 V "STO" input (safety contact)
One core per terminal: 0.08...1.5 mm
2
(AWG28...16)
Two cores per terminal: 0.25 ... 1.0 mm
2
(AWG23...17)
Size 0: 3 W Size 1: 5 W Size 2: 6 W Size 3: 7.5 W Size 4: 8 W Size 5: 10 W
Size 0: 27 µF Sizes 1 to 5: 270 µF
Technical data of the STO input Min. Typical Max.
Input voltage range DC 19.2 V DC 24 V DC 30 V Time to inhibit the output stage BG0 = 20 ms
BG1 – 5 = 100 ms
Time for restart 200 ms
P
i
f
kVA
Hz
n
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Manual – Functional Safety MOVITRAC® MC07B
31
Index
Index
A
Approved devices ..................................................13
C
Checking the disconnection device.... .... ... ... ... .... ...17
Connection variants ...............................................18
Copyright notice.......................................................6
D
Disconnection of a single drive ....... ... .... ... ... ... .... ...20
STO according to PL d (EN 13849-1)...... ....... ...20
Disconnection of group drives................................26
Requirements.....................................................26
Disconnection of single drive
Requirements.....................................................19
Document content........................ ... ... .... ... ...... .... ... ..6
E
Embedded safety notes ...........................................5
Exclusion of liability..................................................6
External safety controller........................................16
G
Group disconnection
STO according to PL d (EN 13849-1)...... ....... ...28
With safety relay ................................................27
H
How to use this documentation.......... .... ... ... ... .... ... ..4
I
Information, general.................................................4
Installation
Notes on routing the control leads.....................14
Requirements.....................................................14
O
Operation, requirements ........................................17
P
Publications, applicable ...........................................6
R
Requirements
External safety controller...................................16
Installation..........................................................14
Operation...........................................................17
Startup...............................................................17
Right to claim under warranty..................................6
S
Safe condition..........................................................7
Safe stop 1, function variant c (SS1(c)).................10
Safe torque off (STO) ..............................................9
Safety concept.........................................................7
Restrictions........................................................11
Schematic representation....................................8
Safety conditions ...................................................12
Safety controllers, requirements............................19
Safety controller, external......................................16
Requirements ....................................................16
Safety control, requirements................................ ..19
Safety notes
Designation in the documentation .......................5
Structure of the embedded safety notes..............5
Structure of the section safety notes ...................5
Safety notes, structure.............................................5
Safety technology
Safe condition......................................................7
Scope.......................................................................4
Section safety notes ................................................5
Signal words in safety notes...... ... .... ... ... ...... .... ... ... .5
Single disconnection
SS1 according to PL d (EN 13849-1) ................23
SS1 according to PL d (EN 13849-1) ....................23
SS1(c) (safe stop 1, function variant c)..................10
Standards ................................................................4
Startup, requirements ....................... ... ... ... ... .... ... ..17
STO according to PL d (EN 13849-1)..............20, 28
STO input................... ... ... .... ... ... ... .........................30
STO (safe torque off)...............................................9
Structure of the safety notes....................................5
Switching capacity of the safety relay....................17
V
Validation...............................................................17
Verification of safety functions...............................17
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Loading...