Schneider Electric TAC Xenta OP Users Manual

TAC Vista
TAC Pangaea
WorkStation
TAC Xenta OP
Operating Manual
TAC Vista
TAC Xenta OP
Operating Manual
Copyright © 2007-2010 Schneider Electric Buildings AB. All rights reserved. This document, as well as the product it refers to, is only intended for licensed users. Schneider Electric Buildings AB owns the copyright of
Do not use the product for other purposes than those indicated in this document. Only licensed users of the product and the document are permitted to use the document or any information therein. Distribution, disclosure,
copying, storing or use of the product, the information or the illustrations in the document on the part of non-licensed users, in electronic or mechanical form, as a recording or by other means, including photo copying or information storage and retrieval systems, without the express written permission of Schneider Electric Buildings AB, will be regarded as a violation of copyright laws and is strictly prohibited.
Trademarks and registered trademarks are the property of their respective owners.
TAC Xenta, TAC Xenta OP Contents

Contents

INTRODUCTION
1 About this Manual 9
1.1 Structure..................................................................................................................... 9
1.2 Typographic Conventions.......................................................................................... 9
REFERENCE
2 Introduction 13
2.1 TAC Xenta OP........................................................................................................... 13
2.2 This Manual ............................................................................................................... 13
2.3 More information ....................................................................................................... 14
3 Connection and Basic Functions 15
3.1 Description................................................................................................................. 15
3.2 Connecting to TAC Xenta 100................................................................................... 16
3.3 Connecting to TAC Xenta 280/300/401 .................................................................... 16
3.4 Keys............................................................................................................................ 18
3.5 Local Functions of the OP Service Menu.................................................................. 19
3.5.1 Two Hardware Tests .................................................................................................. 19
3.5.2 System Information.................................................................................................... 20
3.5.3 Selecting the Language of the OP Messages ............................................................. 20
3.5.4 Controlling the Display Light .................................................................................... 20
3.5.5 Leaving the OP Service Menu ................................................................................... 21
3.5.6 Selecting the OP Mode............................................................................................... 21
3.6 Selecting the OP Communication Mode.................................................................... 21
3.6.1 Summary ....................................................................................................................22
3.6.2 Bindable ..................................................................................................................... 23
3.7 Remove the OP .......................................................................................................... 24
3.7.1 Tool: MetraVision...................................................................................................... 24
3.7.2 Tool: LonMaker ............................................................................. ..... .... ................... 25
4 Dialogs with TAC Xenta 100 27
4.1 General....................................................................................................................... 27
4.2 Connecting to TAC Xenta 100................................................................................... 27
4.3 Setting the Node State in TAC Xenta 100................................................................. 28
4.4 Reading/Checking NVs in TAC Xenta 100............................................................... 29
4.5 Initiate Service Pin Message............................................................... ....................... 30
5 Dialogs with TAC Xenta 280/300/401 31
5.1 The Menus...................................................................................... ............................ 31
5.2 Find and Change a Setpoint ....................................................................................... 32
Schneider Electric Buildings AB, Mar 2010 5 (46) 04-00065-01-en
Contents TAC Xenta, TAC Xenta OP
5.3 View/Acknowledge Alarms ....................................................................................... 33
5.4 Change the Time Channels......................................................................................... 35
5.5 Access Code ............................................................................................................... 37
5.6 Edit Access Code........................................................................................................ 37
5.7 Overriding Inputs/Outputs.......................................................................................... 38
5.8 Daylight Saving.......................................................................................................... 38
5.9 Log Off....................................................................................................................... 39
6 Technical Data 41
Index 43
6 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en

INTRODUCTION

1 About this Manual

TAC Xenta, TAC Xenta OP 1 About this Manual

1 About this Manual
This manual describes a particular process. For information on certain products, we refer you to the manual or the Help for the product in ques­tion.
For information on how to install software, we refer you to the instruc­tions delivered with the software.
For information on third party products, we refer you to the instructions delivered with the third party product.
If you discover errors and/or unclear descriptions in this manual, please contact your Schneider Electric representative.
Note
We are continuously improving and correcting our documenta­tion. This manual may have been updated.
Please check our Docnet site at
for the latest version.

1.1 Structure

The manual is divided into the following parts:
Introduction The Introduction section contains information on how this manual is structured and how it should be used to find information in the most efficient way.
Reference The Reference section contains more comprehensive information about various parts of the Getting Started section. It also provides you with information on alternative solutions not covered by the Getting Started section.

1.2 Typographic Conventions

Throughout the manual the following specially marked texts may occur.
Schneider Electric Buildings AB, Mar 2010 9 (46) 04-00065-01-en
1 About this Manual TAC Xenta, TAC Xenta OP
!
Warning
Alerts you that failure to take, or avoid, a specific action might result in physical harm to you or to the hardware.
Caution
Alerts you to possible data loss, breaches of security, or other more serious problems.
Important
Alerts you to supplementary information that is essential to the completion of a task.
Note
Alerts you to supplementary information.
Tip
Alerts you to supplementary information that is not essential to the completion of the task at hand.
Advanced
Alerts you that the following information applies to complex tasks or tasks restricted by access.
10 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en

REFERENCE

2 Introduction
3 Connection and Basic Functions
4 Dialogs with TAC Xenta 100
5 Dialogs with TAC Xenta 280/300/
401
6 Technical Data

TAC Xenta, TAC Xenta OP 2 Introduction

2 Introduction

2.1 TAC Xenta OP

TAC Xenta OP is a small operator panel designed to be used together with TAC Xenta 100, 280, 300, 401 and 901 units.
The operator panel gives the user access to parameters and alarms with­out communicating with a central system. Additionally, it is used to monitor status, adjust setpoints and time channels. All values are dis­played with an explanatory text in the alphanumeric display window.
Caution
The TAC Xenta OP and the other products of the Xenta family
Installation and repair may only be performed by authorized per-

2.2 This Manual

This handbook has the following contents:
Chapter 2
In this chapter the connection of the operator panel, TAC Xenta OP, to the TAC Xenta 100/280/300/401 controllers is shown.
Chapter 3
The use of the OP together with TAC Xenta 100 and the principles for handling display of Network Variables are explained in this chapter.
Chapter 4
The use of the OP together with TAC Xenta 300/401 controllers and the most common menus are discussed here.
must not be used for any other purpose than that for which it was designed.
sonnel.
Chapter 5
This chapter contains technical data on the TAC Xenta OP.
Schneider Electric Buildings AB, Mar 2010 13 (46) 04-00065-01-en
2 Introduction TAC Xenta, TAC Xenta OP

2.3 More information

TAC Xenta OP is also described or mentioned in the following docu­ments:
The TAC Xenta OP Operator panel data sheet
The handbooks for the different TAC Xenta controller units
The TAC Menta User’s manual
Stand-alone TAC Xenta 300/3000 controllers and I/O modules can be commissioned by using the Service menu of TAC Xenta OP (which is not the same as the local OP service menu). This procedure is described in the TAC Xenta 300 and 401 Handbook.
14 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en

TAC Xenta, TAC Xenta OP 3 Connection and Basic Functions

LCD display
Push buttons
Connectors (rear)
3 Connection and Basic Functions

3.1 Description

The TAC Xenta OP Operator panel has an LCD display with 4*20 characters and six push buttons. A modular socket or four screw termi­nals are used for communication and for connecting the power supply. These connectors are placed on the rear. There is also a potentiometer to adjust the contrast of the display, on the rear.
The OP has an LCD display that can be lighted from beneath. The light is controlled from the OP Service menu (section 2.5).
Schneider Electric Buildings AB, Mar 2010 15 (46) 04-00065-01-en
Fig. 3.1: The TAC Xenta OP operator panel.
The operator panel is used to monitor status and to adjust setpoints and time channels. It also makes it possible to list the alarms without com­municating with a central system.
The operator panel is controlled from a master, a TAC Xenta 100, 280, 300 or 401 controller. When you start using the operator panel, it will send a message to the master telling it what button was pushed. The master contains the dialog messages and will direct the operator panel what to show on the display. Thus the operator panel will act as a dumb terminal.
3 Connection and Basic Functions TAC Xenta, TAC Xenta OP
COMFORT ECONOMY OFF
TAC Xenta 100
Wall module

3.2 Connecting to TAC Xenta 100

Normally the TAC Xenta OP is connected to the modular jack on the lower side of the Wall Module. In this way the Xenta OP will get power supply from the TAC Xenta 100 unit.
Cable between controller and Operator panel: max. 10 m
Fig. 3.2: Connecting the TAC Xenta OP to TAC Xenta 100 via the Wall Module.
The contrast of the display can be adjusted with the potentiometer on the rear of the operator panel; please refer to the figure in the next section.

3.3 Connecting to TAC Xenta 280/300/401

Cable between controller and Operator panel: max. 10 m. When connecting the operator panel there are two alternatives (please
refer to the adjacent figures):
Use the modular socket on the front of the TAC Xenta 280/300/ 401 controller and the corresponding socket on the back of the operator panel. This requires a special cable.
Use the screw terminals on the back of the operator panel, labelled 1–4. Terminals 1 and 2 are used for communication and terminals 3 and 4 for 24 V AC (or DC).
16 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en
TAC Xenta, TAC Xenta OP 3 Connection and Basic Functions
TAC Xenta 280/300/401 controller
Socket for the connection to
the operator panel
Socket and screw terminal for the TAC Xenta controller connection
Service pin
Modular socket on the OP
Contrast adjustable
(on the rear)
l
At the controller you use the terminals C1, C2 and G, G0.
3
4
21
C1 C2 G G0
Fig. 3.3: TAC Xenta OP connectors and contrast potentiometer.
The contrast of the display can be adjusted with the potentiometer on the rear of the operator panel.
(The Service pin is available from the rear if, in special cases, the net­work configuration procedure requires this. When the pin is pressed, a unique hardware identity code is sent on the network.)
Schneider Electric Buildings AB, Mar 2010 17 (46) 04-00065-01-en
3 Connection and Basic Functions TAC Xenta, TAC Xenta OP
+

3.4 Keys

Fig. 3.4: The TAC Xenta OP keys.
+
Keys and their functions
is used to step up one level in the directory hierarchy (“Home”). There may be several levels in the hierarchy. The cursor will return to the line selected the last time this level was active. This button does not by itself make changes effective.
is used to decrease values. If this button is kept depressed, the stepping speed increases.
is used to increase values. If this button is kept depressed, the stepping speed increases.
is used to move the cursor upwards in a menu list or to move to previous alarm or logged record.
is used to move the cursor downwards in a menu list or to move to previous alarm or logged record.
is used to select a line, indicated by the cursor (“Enter”) or to move between the different adjustable values.
This button also makes changes effective.
18 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en
TAC Xenta, TAC Xenta OP 3 Connection and Basic Functions

3.5 Local Functions of the OP Service Menu

For simple hardware check of the OP and for certain system parameters there is a local Service menu in the operator panel. The OP functions are quite independent of the other TAC Xenta units and only require that the operator panel is connected to the network and that the panel has not been set in the TAC Xenta 100 communication mode (see below).
The Service menu appears if both the keys and are pressed for about three seconds simultaneously.
OP Service menu
1. Exit service mode
2. Keyboard test
3. Display test
4. LON address
5. National text
6. SW version
7. LonTalk status
8. Display backlight
9. Service pin
10. OP mode
Select the required function and press .
3.5.1 Two Hardware Tests
2. Keyboard test
This tests the keyboard functions.
* * * Press keys! * * Double-press * for QUIT
Each asterisk corresponds to a key. Double pressing on any key means leaving the test.
3. Display test
Keyboard test
This tests all display positions in a number of steps. Each step is initi­ated by pressing any key.
Schneider Electric Buildings AB, Mar 2010 19 (46) 04-00065-01-en
3 Connection and Basic Functions TAC Xenta, TAC Xenta OP
3.5.2 System Information
4. LON address
Shows the current Domain/Subnet/Node address for the operator panel.
6. SW version
Lists the current version of the operator panel version and
7. LonTalk status
Shows statistics from the network communication.
9. Service pin
Is a way to send the unique Neuron ID on the network. Mainly used for testing purposes.
3.5.3 Selecting the Language of the OP Messages
5. National text
Means that the operator can switch between different languages for those messages that are generated in the OP.
Select language No reply ... Wait ... Press Enter to save!
If you press or the language will change, for example into German:
Select language Keine Antwort ... Bitte warten ... Press Enter to save!
When you have selected a suitable language you press (“Enter”) and then leave the menu.
3.5.4 Controlling the Display Light
8. Display backlight
Controls the background light of the OP display. There are three modes: OFF, ON and AUTO.
•OFF Means that the backlight is always turned off,
20 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en
TAC Xenta, TAC Xenta OP 3 Connection and Basic Functions
+
+
•ON Means that the light is turned on permanently and
•AUTO Means that the light is turned on as soon as a button is pressed, but
goes off about 30 minutes after the last key has been pressed.
Use and to select the required mode. As the display light may cause loss of contrast if turned on permanently,
we recommend the AUTO or OFF mode.
3.5.5 Leaving the OP Service Menu
1. Exit service mode
Means leaving the local OP service menu. This will also happen if no key has been used during about 40 seconds.
3.5.6 Selecting the OP Mode
10. OP mode
In TAC Xenta networks the OP may working in one of two communi­cation modes:
For communication with TAC Xenta 280/300/400
For communication with TAC Xenta 100
Furthermore, the OP can be more or less mobile, depending on the way the OP is connected to the network.
Please refer to the next section!

3.6 Selecting the OP Communication Mode

Xenta 100: ON/OFF
When delivered, the OP is set for Base unit (TAC Xenta 280/300/400) communication. To change the communication mode, you have to call up the OP Service menu and go to the 10.OP mode menu, where the TAC Xenta 100 mode can be turned on/off.
Change OP mode Xenta 100 : OFF Bindable : TAC
Use or to change the Xenta 100 mode and press.
Schneider Electric Buildings AB, Mar 2010 21 (46) 04-00065-01-en
3 Connection and Basic Functions TAC Xenta, TAC Xenta OP
When the OP is set to allow the Xenta 100 mode, the operator is given a choice to access TAC Xenta 100 (in stead of TAC Xenta 280/300/400) by pressing “Enter”, each time an OP is connected.
The OP Service menu cannot be reached when the OP is in the Xenta 100 mode.
If you want to turn OFF the Xenta 100 mode, once you are in this mode, you must temporarily disconnect the OP and let the OP revert to the Base unit communication mode in order to be able to reach the Service menu and from there select the 10. Change OP mode menu.
The TAC Xenta 100 OP communication is described in the next chap­ter.
“Bindable” is explained after the Summary below.
3.6.1 Summary
To turn ON the Xenta 100 mode
Connecting to Xenta Base unit
OP Service menu
1. Exit service
1. Connect the OP and wait for message on display.
2. Press both keys and for about three seconds simultaneously.
mode
2. Keyboard test
3. Display test 10 OP mode 3. Select 10. OP mode menu. Change OP mode
Xenta 100 : ON
4. Press or to set the Xenta
+
100 mode ON and press .
Bindable : TAC Press enter to
access Xenta 100 Connecting to
5. Temporarily disconnect the OP and wait for message on display.
6. Press to access Xenta 100.
Xenta 100 ...
7. Wait for message on display.
22 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en
TAC Xenta, TAC Xenta OP 3 Connection and Basic Functions
+
+
To turn OFF the Xenta 100 mode
Press enter to access Xenta 100(wait)
Connecting to Xenta Base unit
1. Disconnect and then) connect the OP; wait for a couple of seconds for the Base unit message to appear.
2. Press both keys and for about three seconds simultaneously.
OP Service menu
1. Exit service mode
2. Keyboard test
3. Display test 10 OP mode 3. Select 10. OP mode menu. Change OP mode
Xenta 100 : OFF
4. Press or to set the Xenta 100 mode ON and press .
Bindable : TAC
1. Exit service mode
5. Select the 1. Exit service mode menu and press .
3.6.2 Bindable
“Bindable” is a LonWorks term, describing how the OP is connected and addressed in the network. This, in turn, affects the mobility of the OP.
Use or to select Bindable mode from the following:
TAC OP movable. Two available addresses following each TAC Xenta Base unit.
INST OP permanently electrically connected to the network; installed
with a binding tool.
MAN OP movable, the domain ID of the network has to be programmed
via OP Service menu – 4.LON address (communication is here lim­ited to Base units on the same channel).
For OP version 3.11 and earlier the following modes can be chosen:
•OFF OP movable. Two available addresses following each TAC Xenta
Base unit.
Schneider Electric Buildings AB, Mar 2010 23 (46) 04-00065-01-en
3 Connection and Basic Functions TAC Xenta, TAC Xenta OP
•ON OP permanently electrically connected to the network; installed
with a binding tool.
Confirm your choice by pressing .

3.7 Remove the OP

If the OP is to be removed from the network, it should be restored to the original factory setting to avoid problems, if used in another network.
Depending on which binding tool has been used, the removal is made according to one of the methods shown below.
3.7.1 Tool: MetraVision
1 Select OP Service menu 10. OP mode and set Bindable to
TAC or, in OP version < 3.11, OFF.
2 Disconnect the OP electrically from the network. 3 Remove” the OP node from the data base.
Factory setting
If the OP has been labelled ”Unconfig”, which may happen if step 3 above was executed before step 2, or for any other reason; the OP may be restored to the factory setting in one of two ways:
Reconnect the OP to the network, reinstall it and perform the steps above in the correct order, or
Use the Nodutil program and do the following.
Select OP Service menu in OP version < 3.11, OFF.
1 Start Nodutil. 2 Press the Service pin of the OP. 3 Type “G”. 4 Type “1”, press Enter. 5 Type “M”. 6 Type “S”. 7 Type “C”.
10. OP mode and set Bindable to TAC or,
24 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en
TAC Xenta, TAC Xenta OP 3 Connection and Basic Functions
3.7.2 Tool: LonMaker
1 Check in the OP Service menu 10. OP mode that Bindable is
set to TAC or, in OP version < 3.11, OFF.
2 Start the LonMaker Browser. 3 Right-click, and then click Properties.
Note
Restore SNVT_config_src from cfg_external (1) to cfg_local (0). SNVT_config_src is called var_2 in the Browser.
4 Disconnect the OP electrically from the network. 5 Remove the OP from the data base of LonMaker.
Factory setting
If the OP has been de-installed in an incorrect way, it may be restored to the factory setting in one of two ways:
Reconnect the OP to the network, reinstall it and perform the steps above in the correct order, or
Use the Nodutil program and perform the following.
1 Select OP Service menu
TAC or, in OP version < 3.11, OFF.
2 Start Nodutil. 3 Press the Service pin of the OP. 4 Type “G”. 5 Type “1”, and then press Enter. 6 Type “M”. 7 Type “S”. 8 Type “C”. 9 Type “U”. 10 Type “2”, and then press Enter. 11 Type “00”, and then press Enter.
10. OP mode and set Bindable to
Schneider Electric Buildings AB, Mar 2010 25 (46) 04-00065-01-en
3 Connection and Basic Functions TAC Xenta, TAC Xenta OP
26 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en

TAC Xenta, TAC Xenta OP 4 Dialogs with TAC Xenta 100

4 Dialogs with TAC Xenta 100

4.1 General

TAC Xenta OP can be used as a service and limited commissioning tool for the TAC Xenta 100 Zone Controllers. These controllers use Net­work Variables of the LonWorks standard type (“SNVT”, Standard Network Variable Type) for all data communication on the network. All Network Variables, including the configuration parameters can be accessed via the keypad and the LCD display.
In order to separate this general kind of communication from the dedi­cated communication used with TAC Xenta 280/300/401 controllers, the TAC Xenta OP has two different communication modes.

4.2 Connecting to TAC Xenta 100

Notes
The very first time a TAC Xenta OP is connected to a Xenta net­work, the TAC Xenta 100 communication mode is, by default, in the Off state.
Please refer to the end of chapter 2 for the necessary procedures to change the communication mode.
When this has been done, the operator is given a choice to access TAC Xenta 100 (instead of the TAC Xenta 280/300/401).
Press enter to access Xenta 100
Press the key to get the display
Connecting to Xenta 100 ...
Schneider Electric Buildings AB, Mar 2010 27 (46) 04-00065-01-en
4 Dialogs with TAC Xenta 100 TAC Xenta, TAC Xenta OP
Check that the LED on the Wall Module will flash for some 10 seconds or that the red Service LED turns on and then off after a couple of sec­onds, on the connected controller.
If contact is established without the LED flashing, Xenta OP has con­nected to another node in the network. In this case disconnect Xenta OP and then reconnect.
Wait for the display.
Xenta 100 is: Configured Press <DOWN> to continue
Press the key and wait for a display looking like:
Xenta 103v1.00-10 103/A/v10003 units as SI [^] NV index? 000
The first two lines, showing software versions, are displayed the first time only.
The third line shows which unit system is used, when SNVT values are presented in the OP menus.
The key toggles between SI (metric) and US Imperial (Inch-Pound) units.
From this display (normally only lines 3-4 appear) the different Net­work Variables can be selected.

4.3 Setting the Node State in TAC Xenta 100

When the display
Xenta 100 is: Configured Press <DOWN> to continue
28 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en
TAC Xenta, TAC Xenta OP 4 Dialogs with TAC Xenta 100
+
+
is shown, the second line can be switched between Configured and Unconfigured, using the and keys.
When Configured the TAC Xenta 100 can send and receive Network Variables.
When Unconfigured the TAC Xenta 100 cannot communicate on the network.
In normal operation on a network, the TAC Xenta 100 should always be set to Configured.
Configured/Unconfigured are normally set by a binding tool, in a net­work configuration and by TAC Xenta OP in a stand-alone configura­tion. See also the TAC Xenta Network guide.

4.4 Reading/Checking NVs in TAC Xenta 100

When a connection has been established (see, Section 4.2, “Connecting to TAC Xenta 100”, on page 27) a NV (Network Variable) index can be selected by the use of the and keys.
Keep the key pressed to increase the toggling speed. Press the key to display the selected variable.
Example: Select NV 004 to get the Effective Setpoint:
4 nvoEffectSetpt
21.00 °C
nvo indicates that this is an output value and cannot be changed from the OP.
Use the key to return to NV index selection. Input variables appear further down in the list: Example: Select NV 013 to get the Application Mode:
13 nviApplicMode Auto _
nvi indicates that this is an input value. The cursor is visible and allows the value to be changed from the OP.
Use and to change the value. Keep the key pressed to
+
increase the toggling speed. Press to enter the new value.
Schneider Electric Buildings AB, Mar 2010 29 (46) 04-00065-01-en
4 Dialogs with TAC Xenta 100 TAC Xenta, TAC Xenta OP
If or or is pressed before , no change will take place. The keys and will take you to the adjoining NVs in the list.

4.5 Initiate Service Pin Message

When the NV index selection is displayed
uunits as SI [^]
NV index? 000
a service pin message is sent from the Xenta 100, initiated from the OP, each time the key is pressed.
30 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en

TAC Xenta, TAC Xenta OP 5 Dialogs with TAC Xenta 280/300/401

5 Dialogs with TAC Xenta 280/300/
401

5.1 The Menus

The menus of the operator panel and the order in which they are pre­sented are designed by an application programmer, using the TAC Menta design tool.
Thus, the menus shown below are onl y examples. The principles show­ing how to select among the menus and how to change the values are, however, general.
Cyrillic characters
The TAC Xenta OP/RU model has the capability of displaying Cyrillic characters.
The TAC Menta User’s manual describes how you switch the character files of the OP.
24 hour clock vs. AM/PM clock
In those menus that allow time (clock) entries, like the Time Schedule, the Holiday chart (Time channels) and the Daylight saving menus, you may choose to present time with a 24 hour clock or with a 12 hour clock, also called an AM/PM clock. The choice is made already during the menu design phase in TAC Menta.
To translate between the two modes of display the following table can be used.
24 hour clock AM/PM clock
01.00 01.00 AM
06.00 06.00 AM
11.59 11.59 AM
12.00 12.00 PM
12.59 12.59 PM
13.00 01.00 PM
Schneider Electric Buildings AB, Mar 2010 31 (46) 04-00065-01-en
5 Dialogs with TAC Xenta 280/300/401 TAC Xenta, TAC Xenta OP
24 hour clock AM/PM clock
18.00 06.00 PM
23.59 11.59 PM
00.00 12.00 AM
00.59 12.59 AM
When the AM/PM clock is used, the time in the OP menus are com­pressed to hhAmm and hhPmm for hh.mm AM and hh.mm PM respec­tively.

5.2 Find and Change a Setpoint

This example starts with the first screen showing all TAC Xenta 300/ 401 controllers in the network and shows how to find and change the supply air setpoint in “AH02 West”:
AH01 East AH02 West HEAT-1 North HEAT-2 South
Press once and then .
AH02: West _STATUS TEMPERATURES ALARMS
Press once and then .
AH02: Temperatures Outdoor temp: Now: 16.5 C Max:22.5 Min:11.3
Press until the required screen is found.
32 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en
TAC Xenta, TAC Xenta OP 5 Dialogs with TAC Xenta 280/300/401
+
AH02: Temperatures Supply air Measured: 17.1 C Set value: 27.5 C
As there is only one value that could be changed in this screen the cursor is already in the right position and the setpoint could be set with
and . Changes will be effective as soon as is pressed.

5.3 View/Acknowledge Alarms

To make the operator aware of unacknowledged alarms in the alarm list the abbreviated application/base unit name (“AH02” in our examples) will flash. When the item “Alarms” has been found and selected with Enter, a screen like the following will appear:
AH02 ALARMS: 6/6 P1 PUMP STOPPED 99-JAN-15 14:05 ON
On the top row there is an indication that this is alarm number six of six in the list. To see the other alarms in the list use or .
The text ON in the above alarm example indicates that the alarm has tripped but not been acknowledged.
A selected alarm is acknowledged when the operator presses (Enter). The text ON will change to, for example, “ACK”.
Alarms which have tripped and then returned to normal state are indi­cated with OFF.
On the Operator panel, for each point at any given moment, at most one of the three alternatives below can appear:
Schneider Electric Buildings AB, Mar 2010 33 (46) 04-00065-01-en
5 Dialogs with TAC Xenta 280/300/401 TAC Xenta, TAC Xenta OP
t1 Alarm ON t2b Alarm OFF
t2a Alarm ACK
t3 Alarm ON
t3 Alarm ON
- - - -
- - - -
t1 Alarm ON
Acknowledge
Alarm goes off
New alarm
New alarm
Alarm goes off
Acknowledge
New Alarm
Transitions between these three states at moments in time t1, t2 etc., and the disappearance from the list, may occur in the way shown in the dia­gram below.
Fig. 5.1: Possible events at alarms and the way they are presented in the alarm list: time, Alarm text, status
The alarm list is sorted in chronological order with the oldest event dis­played at the top. The alarm list is dimensioned to allow all points of alarm to appear at the same time.
If a TAC Xenta controller is connected to a supervisory system like TAC Vista, another indication may appear in the alarm list. An asterisk (*) in front of the signal name means that the alarm is blocked, that is, information about changes between alarm on and alarm off will not be sent to TAC Vista.
The alarms will, however, be listed on the OP as usual. The blocking request is set/removed from TAC Vista. Example:
AH02 ALARMS: 2/6 *SF1 SUPPLY FAN STOPPED 99-JAN-15 13:50 OFF
34 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en
TAC Xenta, TAC Xenta OP 5 Dialogs with TAC Xenta 280/300/401
+
Notes
Starting with TAC Xenta System program v 3.4 this blocking function has been changed. The alarm information will be sent to TAC Vista, as any normal alarm, but it will not be displayed on the OP.
TAC Vista stores the alarm event in the historical log, even if alarms of priority 0 are not displayed in the alarm list.

5.4 Change the Time Channels

The operating hours for a selected object can be adjusted by altering one or more time channels. This can be done from the operator panel. The number of week schedules available for a specific time schedule is defined in the application program.
The following is an example of an object (AH02) controlled by three different schedules. The object is active 08:00–12:00 and 13:00–17:00 on weekdays and 08:00–12:00 on Saturdays. The example shows how to change operating hours on Saturdays to be 08:00–13:30.
Example:
Week schedule
Go to the week schedule for AH02.
AH02: Time schedule
1234567
08:00–12:00 MTWTF 13:00–17:00 MTWTF
To get to the next schedule controlling AH02 press once.
AH02: Time schedule
1234567
08:00–12:00 S
As the cursor is positioned under “08”, must be pressed twice to move the cursor to “12”. Use and to change the off hour to “13”. Press once and adjust the minutes.
Schneider Electric Buildings AB, Mar 2010 35 (46) 04-00065-01-en
5 Dialogs with TAC Xenta 280/300/401 TAC Xenta, TAC Xenta OP
+
When finished, press after the last entry and then use to return to the previous menu level.
Holiday chart
The week schedule can be modified by a Holiday chart which defines conditions for certain dates, for example when Christmas Eve occurs on a workday:
AH02: Holiday chart
1234567 14:00–17:00 MTWTF **-12-24 : **-12-24
The asterisks (**) act as “wild card”, that is, the date will in this case be valid each year.
Use and to change the time and date values. Use to
move the cursor between the fields. To obtain asterisks in the date fields, toggle the month value past 12. To obtain asterisks for the year value, you must toggle backward from the value 94.
When finished, press after the last entry and then use to return to the previous menu level.
The Holiday chart is valid throughout the 24 hours. Note, for example, the following case:
Week schedule says active 08:00-18:00 Holiday chart says active 00:00-00:01
The object will be active for the one minute only.
Special cases
If you want the time channel to be turned off for the whole day and night and use the 24 hour clock, you indicate this by
00:00-00:00
and with the AM/PM clock (please refer to section 4.1)
12A00-12A00
If, instead, you want the time channel to be turned on for the whole day and night and use the 24 hour clock, you indicate this by
00:00-24:00
and with the AM/PM clock
12A00-00P00
36 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en
TAC Xenta, TAC Xenta OP 5 Dialogs with TAC Xenta 280/300/401
+
In the latter case the end time (24:00 respective 00P00) is a normally ’nonexistent’ time value.

5.5 Access Code

Every item that is displayed in a menu on the operator panel has an access level, which can be low, medium or high. An item with low access level will always be visible on the display of the operator panel.
To show items, with access level medium or high, a correct access code has to be given. There is one code giving access to low and medium level items and one to give access to all levels.
The default codes are
Medium level: 1111 High level: 2222
To change access level go to the following menu:
AH02: ACCESS CODE CODE: 0000 Change code to extend menu
Use to move the cursor between the digits and use and
to change their value. When finished, leave the menu with .
If the correct code has been entered, some more items will now be vis­ible in the list, for example, “Edit Access code”.

5.6 Edit Access Code

To change the code that gives the operator access to the medium or high level items, the access level code for the level to be changed must first be entered as described above. Then go to the Edit Access Code screen:
A2: EDIT ACCESS CODE EDIT CODE: 0000 Change code for the active level (no.)
Use to move the cursor between the digits and use and
to change their value. When finished, press and leave the
Schneider Electric Buildings AB, Mar 2010 37 (46) 04-00065-01-en
+
5 Dialogs with TAC Xenta 280/300/401 TAC Xenta, TAC Xenta OP
+
menu with . As the access code is changed only the standard (low level) items will be shown. To show the medium or high level menu items the new access code has to be entered as described in the previous example.
After the download of an application from TAC Menta, the access code will revert to the default value.

5.7 Overriding Inputs/Outputs

For access code high, it is possible to override the input and output val­ues in the Status displays of the OP.
For example, to override a digital output you must indicate “manual override” in the field just in front of the displayed value:
A2: Fan status
SF_out _0
With the cursor in the position just to the left of the 0 value, use or twice to toggle up the manual override indicator (
Press to confirm and to move the cursor to the value itself. It is now possible to change the value, a value that will override the value set by the controller.
The override indicator will remain visible (for all access levels) until it is reset to normal, automatic mode.
Network Variables (please refer to the TAC Menta User’s manual) can also be overridden in this way.

5.8 Daylight Saving

TAC Xenta 280/300 has built-in support for the European standard day­light saving. However, the OP can be used to set other conditions.
To change the Daylight saving period, the following menu is used.
L2: DAYLIGHT SAVING MODE: 1 HOURS: 1
→).
FROM: MM:DD HH:MM TO : MM:DD HH:MM
38 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en
TAC Xenta, TAC Xenta OP 5 Dialogs with TAC Xenta 280/300/401
+
As long as MODE: is 1, the European standard changeover prevails (one hour on the night before the last Sunday of March at 02:00 and October at 03:00).
If MODE: is toggled to 2 the displayed (entered) values will govern the changeover from/to the Daylight saving time.
MODE: equal to 0 means that there will be no change. Press to move the cursor between the figures and use and
to change the values. When you are finished, press a last
time and leave the menu with . If an AM/PM clock is used, the time is entered according to the instruc-
tions given in section 4.1
Note
During the first hour after the automatic changeover from day­light saving time (MODE:1, 03:00 to 02:00) you must not set the time manually. Should this happen, the clock will once again move back to 02:00 when the time reaches 03:00.

5.9 Log Off

If no changes have been made within 30 minutes, the operator will be logged off and the access level returned to the default access level low.
Values that have been modified in the menu, but not “Entered”, will not be saved at Log off.
Schneider Electric Buildings AB, Mar 2010 39 (46) 04-00065-01-en
5 Dialogs with TAC Xenta 280/300/401 TAC Xenta, TAC Xenta OP
40 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en

TAC Xenta, TAC Xenta OP 6 Technical Data

6 Technical Data
Supply voltage (from TAC Xenta or external source)
..................................................... ............24 V AC ±20%, 50/60 Hz
..................................................... ......... ......... ...or 24 (20–30) V DC
Power consumption
........................................................................................max 0,5 W
With the display backlight on, in total............................. max 1,2 W
Ambient temperature
Storage................................................................. –20 °C to +50 °C
Operating...................................................... ............ ±0 °C to 50 °C
Humidity.................................................max. 90% RH non-condensing
Display....................................................4×20 characters, alphanumeric
Mechanical:
Enclosure............................................................................ABS/PC
Dimensions (mm)..................................................... ......144×96×32
Weight....................................................................................0,4 kg
Panel cutout (mm)...........................................136 ± 0,5 x 91,5 ± 0,5
Enclosure rating
Hand-held panel.......................................................................IP 20
Network communication
Protocol............................................................FTT-10, LonTalk™
Communication speed..................................................... ....78 kbit/s
Unit connection
TAC Xenta 100............................via modular jack on Wall Module
TAC Xenta 280................................modular jack or screw terminal
TAC Xenta 300................................modular jack or screw terminal
TAC Xenta 401................................modular jack or screw terminal
Standards
Emission.......................................................................EN 50081-1
Schneider Electric Buildings AB, Mar 2010 41 (46) 04-00065-01-en
6 Technical Data TAC Xenta, TAC Xenta OP
Immunity..................................................... ..................EN 50082-1
Part number
Operator terminal TAC Xenta OP..................................007309072
Operator terminal TAC Xenta OP/RU...........................007309231
Mounting kit panel TAC Xenta OP................................007309040
42 (46) Schneider Electric Buildings AB, Mar 2010
04-00065-01-en
TAC Xenta, TAC Xenta OP Index

Index

Numerics
24 hour clock 31
A
Access code 37 adjust contrast adjust setpoints adjust time channels AM/PM clock Ambient temperature
B
Bindable 23
C
Cable 16 Change a setpoint change communication mode communication communication modes Communication speed configuration parameters Configured connecting connecting the operator panel connection of OP contrast Cyrillic characters
D
data communication 27 Daylight saving Dimensions Display display display - network variables Display backlight Display Light Display test Docnet
15
15
15
31
41
32
15
27
41
27
29
15
13
17
31
38
41
41
15
13
20
20
19
9
21
16
Exit service mode
21
F
Factory setting 2425
H
handling display 13 hardware check Hardware Tests Holiday chart Humidity
19 19
36
41
I
I/O modules 14 Initiate Service Pin Message
K
Keyboard test 19
L
Language 20 lighted
15
limited commissioning tool list alarms Local Functions Log off LON address LonMaker LonTalk status
15
19
39
20
25
20
M
Mechanical 41 menus of the operator panel MetraVision modular jack modular socket monitor status
24
16
1516
15
N
National text 20 Network communication Network Variables Node State
28
41
13, 27
30
27
31
E
Enclosure rating 41
Schneider Electric Buildings AB, Mar 2010 43 (46) 04-00065-01-en
Index TAC Xenta, TAC Xenta OP
O
OP Communication Mode 21 OP Mode OP Service Menu OP Service Menu - exiting Operator panel Overriding inputs/outputs
21
19
21
15
38
P
Part number 42 potentiometer Power consumption power supply Protocol push buttons
15
41
1516
41
15
R
Reading/Checking NVs 29
S
screw terminals 1516 service
27
Service menu Service pin service pin Service Pin Message Special cases Standards Supply voltage SW version System Information system parameters
14
20
17
30
36
41
41
20
20
19
T
TAC Menta 31 TAC Xenta 100 TAC Xenta 280/300/400 TAC Xenta 300/3000 TAC Xenta OP Time channels
2728
21
14
13, 15
35
U
Unconfigured 29 Unit connection
41
W
Weight 41
X
Xenta 100 21 Xenta 100 mode
44 (46) Schneider Electric Buildings AB, Mar 2010
22
04-00065-01-en
opyright © 2007-2010, Schneider Electric Buildings AB
C All brand names, trademarks and registered trademarks are the property of their respective owners. Information con­tained within this document is subject to changewithout no­tice. All rights reserved.
04-00065-01-en
Last Manual Page
Loading...