PRODUCT DESCRIPTION
The APC
TM
by Schneider Electric Smart-UPSTM RT is a high performance, uninterruptible power
supply (UPS) that provides protection for electronic equipment from utility power blackouts,
brownouts, sags, and surges. The UPS filters small utility line fluctuations and isolates electronic
equipment from large disturbances by internally disconnecting from utility line power. The UPS
provides continuous power from the internal battery until utility power returns to safe levels or the
battery is fully discharged.
SAFETY AND GENERAL INFORMATION
INSPECT THE PACKAGE CONTENTS UPON RECEIPT. NOTIFY THE CARRIER AND DEALER IF THERE IS
ANY DAMAGE
EAD THE SAFETY INFORMATION IN THIS MANUAL BE F O RE INSTAL L ING T HE UPS.
R
.
• Adhere to all national and local electrical codes.
• All wiring must be performed by a qualified electrician.
• Changes and modifications to this unit not expressly approved by APC could void the
warranty.
• This unit is intended for indoor use only.
• Do not operate this unit in direct sunlight, in contact with fluids, or where there is
excessive dust or humidity.
• Be sure the air vents on the unit are not blocked. Allow adequate space for proper
ventilation.
• Connect the UPS power cable directly to a wall outlet. Do not use surge protectors or
extension cords.
• 230 V models only: In order to maintain compliance with the EMC directive for
products sold in Europe, output cords attached to the UPS must not exceed 10 meters
in length.
• Leakage current for a pluggable Type A UPS may exceed 3.5 mA when a separate
ground ter mi nal is used.
• The protective earth conductor for the UPS carries the leakage current from the load
devices (computer equipment). An insulated ground conductor is to be installed as part
of the branch circuit that supplies the UPS. The conductor must have the same size and
insulation material as the grounded and ungrounded branch circuit supply conductors.
The conductor will be green and with or without a yellow stripe.
• The UPS input ground conductor must be properly bonded to protective earth at the
service panel.
• If the UPS input power is supplied by a separately derived system, the ground
conductor must be properly bonded at the supply transformer or motor generator set.
1
• The attachment plug receptacles near the unit or subsystem must all be of a grounding
type, and the grounding conductors serving these receptacles must be connected to
earth ground at the service equipment.
• The battery typically lasts for two to five years. Environmental factors impact battery
life. Elevated ambient temperatures, poor quality utility power, and frequent short
duration discharges will shorten battery life.
• The equipment is heavy. Always practice safe lifting techniques adequate for the
weight of the equipment.
• The batteries are heavy. Remove the batteries before installing the UPS and XLBP in a
rack.
• Always install XLBPs at the bottom in rack-mount or stack configurations. The UPS
must be installed above the XLBPs.
• Always install peripheral equipment above the UPS in rack-mount or stack
configurations.
• The UPS will recognize as many as 10 external battery packs connected to the UPS.
However there is no limit to the number of XLBPs that can be used with the UPS.
• The model and serial numbers are located on a small, rear panel label. For some
models, an additional label is located on the chassis under the front bezel.
• Always recycle used batteries.
• Recycle the package materials or save them for reuse.
2
PACKAGE CONTENTS
Inspect the UPS upon receipt. Notify the carrier and dealer if there is damage.
The packaging is recyclable; save it for reuse or dispose of it properly.
Check the package contents:
UPS (with battery modules disconnected)
Front bezel
Stabilizer brackets and screws
Top cover and screws
SURTRK2 rail kit
Serial cable
SPECIFICATIONS
TEMPERATURE
PERATING
O
TORAGE
S
MAXIMUM
ELEVATION
OPERATING
TORAGE
S
HUMIDITY
WEIGHT
UPS
WITH
UPS
PACKAGING
0° to 40° C (32° to 104° F)
-15° to 45° C (5° to 113° F)
charge the UPS battery(s) every six mont hs
3,000 m (10,000 ft)
15,240 m (50,000 ft)
0 to 95% relative humidity, non-condensing
58 kg (128 lbs)
72 kg (159 lbs)
Literature kit containing:
Product documentation
Documentation CD
Warranty Information
Software CD
NMC card documentation
This unit is intended for indoor use only.
Select a location sturdy enough to handle the
weight.
Do not opera te the UPS where there is
excessive dust or the temperature and
humidity are outside the specified limits.
Ensure that the air vents are not blocked.
Environmental factors impact battery life.
High temperatures, poor utility power , and
frequent, short duration discharges will
shorten batte r y life.
3
I
NSTALL THE MOUNTING RAILS
For detailed rail installation instructions, refer to the rail installation guide included in the rail kit.
I
NSTALL IN A RACK
For detailed rack installation instructions, refer to the Installation Guide – Tower to SURTRK2 Rack
Conversion document.
R
EMOVE THE BATTERIES
The unit is heavy. To lighten the unit, remove the batteries.