Schneider Electric MNB-300 Specifications

TAC I/A Series
MNB-300 BACnet Unitary Controller
I/A Series Micronet MNB-300
The TAC I/A Series™ MicroNet™ MNB-300 BACnet™ Unitary Controller is an interoperable controller with native BACnet MS/TP communications support. The controller features Sensor Link (S-Link) support, LED status and output indication, screw terminal blocks, as well as a panel mount sub-base with removable electronics module.
When programmed using WorkPlace Tech Tool, the Unitary controller provides a wide range of control strategies for packaged rooftop, heat pump, fan coil, unit ventilator, and similar applications.
Stand Alone or Connected
The TAC I/A Series BACnet Unitary Controller can
SPECIFICATIONS
HARDWARE
function either in a standalone mode or as part of a BACnet building automation system (BAS) network.
1
Dimensions
7.0 in. W x 3.94 in. H x 2.19 in. D
(178 mm x 100 mm x 56 mm)
Enclosure
Cover meets UL94V-0 flammability ratings.
Mounting
Panel mount.
Wiring Terminals
I/O Points
Fixed screw terminals; up to two AWG #14 (2.08 mm
Power and MS/TP
Removable screw terminals; single AWG #14 (2.08 mm or smaller wires.
ELECTRICAL
Power Supply Input
20.4 to 30 Vac, 50/60 Hz.
Maximum Power Consumption
16 VA at 24 Vac.
ENVIRONMENT
Operating Temperature
-40 to 140 °F (-40 to 60 °C)
Shipping and Storage Temperature
-40 to 160 °F (-40 to 71 °C)
Humidity
5 to 95% RH, non-condensing
2
) or smaller wire.
2
) wire or up to two AWG #18 (0.823 mm2)
AGENCY LISTINGS
US
FCC Part 15, Class A UL 916, File #E71385 Category PAZX UL 864, Category UUKL, File #S5381 Smoke-Control
Equipment
Canadian
UL Listed to Canadian Safety Standards (CAN/CSA 22.2)
CUL Listed to Standards ULC/ORD-C100-92 (Smoke Control System Equipment) and CAN-ULC-S527 (Control Units for Fire Alarm Systems)
Australian
Meets requirements to bear the C-Tick Mark
European Community
EMC Directive 89/336/EEC, EN61326
INPUTS AND OUTPUTS
Universal Inputs (6)
Universal Input characteristics are software­configured to respond to one of the following input types:
10k ohm Thermistor w/ 11k ohm Shunt Resistor
Sensor operating range -40 to 250 °F (-40 to 121 °C) range. TSMN-57011-850, TS-5700-850 Series or equivalent.
Specifications continued on next page.
TAC I/A Series
MNB-300 BACnet Unitary Controller
2
Specifications continued from first page.
1k ohm Balco Input
-40 to 250 °F (-40 to 121 °C) range. TSMN-81011, TS-8000 Series or equivalent.
1k ohm Platinum Input
-40 to 240 °F (-40 to 116 °C) range. TSMN-58011, TS-5800 Series or equivalent.
1k ohm Resistive
0 to 1.5k ohms.
10k ohm Resistive
0 to 10.5k ohms.
Analog Voltage
0 to 5 Vdc.
Analog Current
Range 0 to 20 mA, requires an external 250 ohm shunt resistor (AD-8969-202).
Digital Input
Dry switched contact. Detection of closed switch requires less than 300 ohms. Detection of open switch requires more than 2.5k ohms.
Standard Pulse Input (UI1-UI6)
Minimum Rate
1 pulse per 4 minutes.
Maximum Rate
1 pulse per second.
Fast Pulse Input (UI1)
Minimum Rate
1 pulse per 4 minutes.
Maximum Rate
10 pulses per second.
Digital Outputs - Triac (6)
12 VA at 24 Vac, 50/60 Hz, each output individually isolated.
Universal Outputs (3)
Current
0 to 20 mA (output load from 80 to 550 ohms).
Voltage
0 to 10 V (with external 500 ohms, 1/2 W, 1% resistor).
Capability to Drive Functional Devices
RIBUI1C Relay (UO configured for 0 to 20 mAdc, no external resistor).
BACnet is a registered trademark of ASHRAE. ASHRAE does not endorse, approve, or test products for compliance with ASHRAE standards. Compliance of listed products to the requirements of ASHRAE Standard 135 is the responsibility of BACnet International (BI). BTL is a regstered trademark of BI.
Schneider Electric
F-27339-4
COMMUNICATIONS
BACnet Networks
The TAC I/A Series MicroNet BACnet Unitary Controller incorporates an isolated EIA-485 (formerly RS-485) transceiver for BACnet MS/TP communications at 9.6 up to 76.8 kbaud using standard MS/TP wiring methods. Up to 128 TAC I/A Series MicroNet BACnet controllers can be connected to an MS/TP sub-net without repeaters.
S-Link
The Sensor Link (S-Link) communications wiring provides power and a communication interface for one MN-Sx MicroNet sensor. The various MN-Sx sensors can provide room temperature, room humidity, setpoint adjustment, and occupancy override. This connection uses two-wire, unshielded cable and is not polarity sensitive. Maximum S-Link bus length is 200 ft (61 m).
BACnet COMPLIANCE
BACnet Application Specific Controller (B-ASC).
FEATURES
The TAC I/A Series MicroNet BACnet Unitary Controller’s sequence of operation and BACnet image are fully programmable, using WorkPlace Tech Tool. The controllers can be applied to all common unitary HVAC applications.
Capability to function in standalone mode or as part of a TAC I/A Series building automation network.
Integral MS/TP jack for direct connection of PC with WorkPlace Tech Tool.
Removable electronics module mates with panel- mounted subbase.
Removable terminals for power and communications to facilitate commissioning.
Optional rugged, NEMA 1 plenum-rated sheet metal enclosure.
MS/TP DIP switch addressable.
Service pin button for BACnet “I am” message broadcast.
Isolated EIA-485 (formerly RS-485) transceiver for MS/TP communications.
MS/TP baud rate selection from 9.6 up to
76.8 kbaud.
LED indication of MS/TP communication activity, controller status, and UO and DO state.
Firmware upgradeable over the network.
Support for S-Link Sensor.
© 2009 Schneider Electric. All rights reserved.