Rockwell Automation 2706 User Manual

Packing Data
Installation Instructions
PK
   
This document describes how to install a Dataliner DL40 display in a panel or enclosure and connect power.
European Union Directive Compliance
wiring and safety guidelines
enclosures
mounting dimensions
clearances
installing the DL40 display in a panel
connecting AC power
For more information on the Dataliner DL40 display, refer to the Dataliner DL40 User Manual (Publication 2706-807).
Dataliner DL40 Message Display2

European Union Directive Compliance

If a Dataliner Message Display is installed within the European Union or EFTA regions and has a CE mark, the following regulations apply.

EMC Directive

This apparatus is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) using a technical construction file and the following standards in whole or in part.
EN 50081-2 EMC – Generic Emission Standard, Part 2 -
Industrial Environment
EN 50082-2 EMC – Generic Immunity Standard, Part 2 -
Industrial Environment
Dataliner products are intended for use in an industrial environment.

Low Voltage Directive

This apparatus is tested to meet Council Directive 73/23/EEC with amendments, including 93/68/EEC Low Voltage (LVD) using the pertinent sections of the following standards.
EN 61131-2:1992 Programmable Controllers - Equipment
Requirements and T ests
EN 60950-1:1992 Safety of Information T echnology Equipment

Intended Use of Product

According to these Standards, the factor which determines, for EMC purposes, whether an apparatus is deemed to be “Industrial” or “Residential, commercial and light industrial”, is given in Clause 1 of EN50081-2 as follows:
Dataliner DL40 Message Display 3
Apparatus covered by this standard is not intended for connection to a public mains network but is intended to be connected to a power network supplied from a high- or medium-voltage transformer dedicated for the supply of an installation feeding a manufacturing or similar plant.
This product is intended for use solely in an industrial environment as defined above. When installed in Europe, any other application is in contravention of European Union Directives, and a breach of these laws.

Wiring and Safety Guidelines

Install the Dataliner DL40 display using publication 70E, Electrical Safety Requirements for Employee Workplaces. In addition to the NFPA general guidelines, follow these recommendations:
Connect the Dataliner display to its own branch circuit. The input power
source should be protected by a fuse or circuit breaker rated at no more than 15 amps.
Route incoming power to the DL40 display by a separate path
from the communications cable.
Where power and communication lines must cross, they should cross at right
angles. Communications lines can be installed in the same conduit as low level DC I/O lines (less than 10 Volts).
Grounding minimizes noise from Electromagnetic Interference (EMI) and is
a safety measure in electrical installations. T o avoid EMI, shield and ground cables appropriately.
A source for grounding recommendations is the National Electrical Code
published by the National Fire Protection Association of Boston.

Enclosures

Mount the DL40 display in a panel or enclosure to protect the internal circuitry. The display meets NEMA T ype 12/13, 4 (indoor use), and 4X (for stainless steel faceplate versions) ratings only when properly mounted in a panel or enclosure with the equivalent rating.
Dataliner DL40 Message Display4
Allow enough space within the enclosure for adequate ventilation. Consider heat produced by other devices in the enclosure. The ambient temperature around the display must be between 0 and 60C (32 and 140F).
Make provisions for accessing the back panel of the display for wiring, maintenance, installing a memory module, and troubleshooting.

Required Tools

Other than the tools required to make the panel cutout, the tools required for installation are:
3/8 inch deep well socket wrench
small slotted screwdriver
torque wrench (in. / lbs).
Dataliner DL40 Message Display 5

Installing Display in Panel

To install the Dataliner display:
ATTENTION: Disconnect all electrical power from the panel before
!
making cutout. Make sure the area around the panel cutout is clear. Take precautions so that metal cuttings do not enter any components
that may already be installed in panel. Failure to follow this warning may result in personal injury or damage
to the panel components.

Mounting the DL40

The following figures provide panel cutout dimensions and overall dimensions for the DL40.
You can mount the DL40 in a custom panel or enclosure. Dataliner enclosures Catalog Numbers 2706-NE1 (two-line display) and 2706-NE2 (four-line display) are available When the DL40 is properly installed, the faceplate of the DL40 provides a NEMA T ype 12/13, 4 (indoor), and 4X (for stainless steel faceplate versions) enclosure integrity.
T o install the DL40, perform the following steps:
1. Cut and drill the appropriate mounting holes in the enclosure or panel.
2. Remove the six mounting nuts from the hardware kit included with the DL40.
3. Position the DL40 in the panel or enclosure mounting hole.
4. Install and tighten the six nuts on the mounting studs to a torque of 14 in•lbs
(1.6Nm) each.
ATTENTION: Mounting nuts must be tightened to a torque of 14
!
inch-pounds to provide a proper seal and to prevent potential damage to the display. Allen-Bradley assumes no responsibility for water or chemical damage to the display or other equipment within the enclosure because of improper installation.
Dataliner DL40 Message Display6

Mounting Dimensions

Figure 1 Two-Line DL40 Mounting Dimensions
Top V iew
337.6 mm (13.29 in.)
352.3 mm (13.87 in.)
Front View
365.0 mm (14.37 in.)
SELECT ENTER MSG ACK
COMM
111.3 mm (4.38 in.)
FAULT
Dataliner DL40 Message Display 7
Two-Line DL40 Mounting Dimensions (Continued)
Side View
3.05 mm (0.12 in.)
111.3 mm (4.38 in.)
Figure 2 Four-Line DL40 Mounting Dimensions
88.9 mm (3.50 in.)
Front Panel
Panel Thickness
3.05 mm (0.12 in.)
115.1 mm (4.53 in.)
3.05 mm (0.12 in.) Gasket Before Compression
98.6 mm (3.88 in.)
#10-32 Mt’g Stud (6 Places)
Top V iew
337.6 mm (13.29 in.)
3.05 mm (0.12 in.)
RS-232 Connector
Terminal Block
5.59 mm (0.22 in.)
352.3 mm (13.87 in.)
Dataliner DL40 Message Display8
Four-Line DL
Mou
ued
40
nting Dimensions (Contin
)
Front View
157.0 mm (6.18 in.)
SELECT ENTER MSG ACK
3.05 mm (0.12 in.)
134.6 mm (5.30 in.)
365.0 mm (14.37 in.)
Side View
115.1 mm (4.53 in.)
3.05 mm (0.12 in.) Gasket Before­Compression
144.3 mm (5.68 in.)
157.0 mm (6.18 in.)
COMM FAULT
3.05 mm (0.12 in.)
RS-232 Connector
Terminal Block
Front Panel
5.59 mm (0.22 in.)
#10-32 Mt’g Stud (6 Places)
Panel Thickness
3.05 mm (0.12 in.)
Dataliner DL40 Message Display 9
de, Top

Clearances

Allow adequate clearances for mounting, air flow , maintenance, and wiring. See Figure 3.
Figure 3 Minimum Mounting Clearances
Si
and Bottom Clearances
Display Cutout
Front View
Leave 25 mm (1 in.)
for Mounting and Air Flow
Leave 25 mm (1 in.)
for Mounting and Air Flow
Leave 38 mm (1.5 in.)
for Mounting and Air Flow
Leave 25 mm (1 in.)
for Mounting and Air Flow
Dataliner DL40 Message Display10

Cutout Dimensions

Figures 4 and 5 show a reduced size cutout.
Figure 4 Panel Cutout Dimensions for Two-Line DL40
Cutout 345.9 mm
(13.62 in.)
4.8 mm (0.19 in.)
173.0 mm (6.81 in.)
Cutout
88.9 mm (3.50 in.)
4.8 mm (0.19 in.)
Figure 5 Panel Cutout Dimensions for Four-Line DL40
4.8 mm (0.19 in.)
Cutout
134.6 mm (5.30 in.)
176.1 mm (6.94 in.)
Cutout 345.9 mm
173.0 mm (6.81 in.)
352.3 mm (13.87 in.)
(13.62 in.)
98.4 mm (3.88 in.)
6.4 mm (0.25 in.) Dia. Hole (6 Places)
144.3 mm (5.68 in.)
4.8 mm (0.19 in.)
176.1 mm (6.94 in.)
352.3 mm (13.87 in.)
6.4 mm (0.25 in.) Dia. Hole (6 Places)
Dataliner DL40 Message Display 11

EMI Power-Line Filters (EU Installations Only)

DL40 displays intended for use in the European Union require a power-line filter. One line filter is required for each installed display. Two filter models are available. These filters are functionally identical, they differ only in termination style.
Schaffner Part No. Termination Style
FN 660-3/06 Fast-On (Spade) connectors FN 660-3/07 Wire leads
Line filters are available from an authorized Schaffner distributor.
Part Number
(FN 660-3/07)
Part Number
(FN 660-3/06)
(1.18 in.)
85 mm
(3.35 in.)
30mm
65 mm
(2.56 in.)
27mm
(1.06 in.)
54 mm
(2.13 in.)
5.3 mm
(0.21 in.)
12 mm
(0.47 in.)
75 mm
(2.95 in.)
When properly installed, power-line filters prevent interference currents in the power lines. Interference currents can affect other devices on the same power line and other nearby equipment. Connect the Dataliner message display to the power-line filter as shown on the following page.
Dataliner DL40 Message Display12

Connecting AC Power

The table below shows the electrical ratings for the Dataliner DL40 display.
Supply Voltage Power Consumption
100-240V ac, 50/60 Hz 45 VA maximum
ATTENTION: The Dataliner DL40 display is designed for safe use
!
!
when installed in a suitably rated NEMA Type 12, 13, 4X (indoor use only), IP54 or IP65 enclosure.
ATTENTION: Do not apply power to the display until all wiring
connections have been made. Failure to do so may result in electrical shock.
Wiring Guidelines (EU Installations Only)
10 cm (4 in.)
Maximum
L1
To
Dataliner
AC Input
For installations within the European Union use the following guidelines to minimize Radio Frequency Interference (RFI) and achieve maximum Electromagnetic Compatibility (EMC).
L2N
L1
L2N
To
AC Mains
Supply
Follow all local safety regulations regarding proper grounding.
Dataliner DL40 Message Display 13
Output leads from the power-line filter to the Dataliner must be 10 cm (4 in.) or
less.
Both Dataliner and power-line filter must be connected to a low impedance earth
ground
All parts of the grounding system must be connected together with low
impedance connections. Keep all ground connections as short as possible
Power-line filter must be connected to earth ground before connecting the power
source.
Do not run signal wiring and power wiring in the same conduit.
When control or communication wires must cross, they should cross at an angle
as close to 90 degrees as possible.
Follow Dataliner display shielded cable requirements as specified in the user
manual.
Make sure cable shielding connections and terminations are connected as
specified in the appropriate Dataliner User Manual.
Keep the filter line side leads well separated from the load side leads.
Dataliner DL40 Message Display14

Wiring Diagram

The following diagram shows how to connect the power-line filter for installations within the European Union. For non-European Union installations, the power-line filter can be omitted. For all other wiring connections refer to the DL40 User Manual (Publication 2706-807).
Parallel Port Version Shown
Other DL40 Displays Are Similar
PARALLEL PORT 5-24VDC INPUT
D15
D14
D13
D12
D11
D10D9D8D7D6D5D4D3D2D1D0
RESET
MS3
MS2
MS1
SW1 SW2
MS0
ISO +12V
KEYBOARD
1 - 2 - 3 - 4 - 5 - 6
RS-485
1 – E GND 2 – SHLD 3 – COMM 4 – CH A 5 – CH B 6 – TERM
REM RES
ISO
GND
N.O.
10 cm (4 in.)
L1
L2N
RELAY
N.C.COM
Maximum
PWRRS-232
AC PWR
L1 L2N
LOAD
FN 660 FILTER
LINE LINE
CHA GND
Dataliner DL40 Message Display 15

Fuse Information

The DL40 display utilizes two fuses, one on L1 and the other on L2N. Both fuses use the following replacement types:

Fuse Type

USA 1.25 amperes, 250V ac, Type MDL
European 1.5 amperes, 250V ac, Type GMC
ATTENTION: Neutral fusing. Disconnect all electrical
!
power from the DL40 before replacing either fuse.

AC Power Connections

Connection
L1 Black (Line) Brown (Line)
L2N White (Neutral) Blue (Neutral)
P.E. Green (Earth Ground) Green/Yellow (Protective Earth)
120/240V ac, 3 Wire
U.S. Color Code
120/240V ac, 3 Wire
European Harmonized Color Code

Additional Information

For additional information on communication port wiring and display configuration, refer to the Dataliner DL40 User Manual (Publication 2706-807).
Copyright 1999 Allen-Bradley Company, Inc. Printed in USA
41061-015-01(B)