Rockwell Automation 2705-DN42 User Manual

2705-DN42 DeviceNet Interface Communication Board
Installation Instructions
This document describes how to install a DeviceNet communications board.
Overview
LED Indicator
DeviceNet Connections
DeviceNet Components
Installation and Mounting
Setting the DIP Switches
DeviceNet Termination
Operations
Modes of Operation
DeviceNet Operations
Troubleshooting
Using the LED Indicator
User-Defined Configuration
For more information on the RediSTATION Operator Terminal and its DeviceNet Configuration refer to Publication 2705-804 on–line at htpp://www.ab.com.
For more information on the DeviceNet specifications, refer to the Open DeviceNet Vendor Association at http://www.odva.ors.
2

Overview

LED Indicator

DIP Switches

The RediSTATION has one bicolor LED (red/green) to show its operating status. The LED shows the following indications.
Color State Indication
None Off No power.
Solid Unrecoverable fault.
Red
Green
Flashing
Solid Normal runtime operation.
Flashing Device is idle or not allocated to a master.
Output error or configuration error.
The RediSTATION device is operating as a slave to the master controller.
The LED is visible when the cover of the enclosure is removed.
The RediSTATION has one 10-position DIP switch for setting:
DeviceNet Node Address
DeviceNet Data Rate
Output Fault State (Off or Last State)
Output Flash Rate
The DIP switch is located on the circuit board inside the enclosure. The switch settings and functions are shown below. The default setting for each switch or group of switches is underlined.
Default Configuration
OFF = 0
10 123456789
ON = 1
DeviceNet Address 000000 – 111111 DeviceNet Data Rate 00
Output Fault State 0 = Outputs Turn Off on Fault
Output Flash Rate 0 = 1 Hz (0.5 sec On, 0.5 sec Off)
= 125K BPS 01 = 250K BPS 10 = 500K BPS 11 = Invalid
1 = Outputs Hold Last State on Fault
1 = 2 Hz (0.25 sec On, 0.25 sec Off)
(0 to 63)
3

DeviceNet Connection

DeviceNet Components

The RediSTATION receives all power and communications through the DeviceNet cable. A separate power supply is not required. This is the only external connection to the RediSTATION.
The RediSTATION connects to the DeviceNet using the DeviceNet terminal block on the communication board.
DeviceNet
Terminal Block
Terminal Signal Function Color
1 COM Common Black 2 CAN_L Signal Low Blue
1
6
3 SHIELD Shield Uninsulated 4 CAN_H Signal High White 5 VDC+ Power Supply Red 6 E. GND Chassis Ground Green
DeviceNet cables and components are available from Allen-Bradley as separate catalog numbers.
It is your responsibility to install and implement the DeviceNet network and supported devices according to the DeviceNet guidelines.
4

Installation and Mounting

Setting the DIP Switches

The setting of the DIP switch on the circuit board determines:
DeviceNet node address
DeviceNet data rate
Output flash rate
Output fault state
The location of the DIP switch and the factory defaults are shown below.
DIP Switches
OFF = 0
10 123456789
ON = 1
Setting the DeviceNet Node Address
DIP switches 1 to 6 set the node address (0 to 63) of the RediSTATION on the DeviceNet network. The address is set using binary addressing.
OFF = 0
10 123456789
ON = 1
DeviceNet Address 000000 – 111111 (0 to 63)
The table below shows the switch settings for each address (0 to 63).
To set the DeviceNet node address:
1. Refer to the table below for switch settings of a specific address.
2. Using your finger or a pointed object, slide switches 1 through 6 to the appropriate ON/OFF positions.
ATTENTION: Do not use a pencil. Graphite from the pencil is conductive and may damage the DIP switch.
!
5
DeviceNet
Address
0 000000 16 010000 32 100000 48 110000 1 000001 17 010001 33 100001 49 110001 2 000010 18 010010 34 100010 50 110010 3 000011 19 010011 35 100011 51 110011 4 000100 20 010100 36 100100 52 110100 5 000101 21 010101 37 100101 53 110101 6 000110 22 010110 38 100110 54 110110 7 000111 23 010111 39 100111 55 110111 8 001000 24 011000 40 101000 56 111000
9 001001 25 011001 41 101001 57 111001 10 001010 26 011010 42 101010 58 111010 11 001011 27 011011 43 101011 59 111011 12 001100 28 011100 44 101100 60 111100 13 001101 29 011101 45 101101 61 111101 14 001110 30 011110 46 101110 62 111110 15 001111 31 011111 47 101111 63 111111
Switch Settings
6  1
DeviceNet
Address
Switch Settings
6  1
DeviceNet
Address
Switch Settings
6  1
DeviceNet
Address
Switch Settings
Setting the Data Rate
6  1
DIP switches 7 and 8 set the data rate at which the RediSTATION communicates on the DeviceNet network. The factory default setting is 125K BPS.
Default Configuration
OFF = 0
10 123456789
ON = 1
DeviceNet Data Rate 00 = 125K BPS
01 = 250K BPS 10 = 500K BPS 11 = Unused
The data rate determines the maximum length of the DeviceNet cable.
Data Rate Cable Length (Maximum)
125K BPS 500 meters (1600 feet) 250K BPS 200 meters (600 feet) 500K BPS 100 meters (300 feet)
To set the DeviceNet data rate:
1. Refer to the table above to select the correct data rate.
2. Slide switches 7 and 8 to the appropriate ON/OFF positions.
6
Setting the Output Fault State
DIP switch 9 sets the state of the outputs (pilot lights) when the device detects an error. The factory default setting is to turn the outputs off when an error is detected.
Default Configuration
OFF = 0
10 123456789
Output Fault State 0 = Outputs Turn Off on Fault
Output Fault States Description
Outputs Retain Last State
Outputs Turn Off on Error
ON = 1
1 = Outputs Hold Last State on Fault
When communications is lost, the station stops sending sig­nals. The station ignores push button presses in the error state. The outputs remain in their last state.
When communications is lost, the station turns off outputs. The station ignores push button presses in the error state. When communications is regained, the station updates itself and resumes operations.

DeviceNet Termination

To change the fault state, slide switch 9 to the appropriate ON/OFF setting.
Setting the Output Flash Rate
DIP switch 10 sets the flash rate of the outputs (pilot lights). The factory default setting is 1 Hz.
Default Configuration
OFF = 0
10 123456789
Output Flash Rate 0 = 1 Hz (0.5 sec On, 0.5 sec Off)
To change the flash rate, slide switch 10 to the appropriate ON/OFF position.
Devices on end nodes of the DeviceNet network require termination. If the RediSTATION is an end node, you must provide network termination.
To terminate the RediSTATION, install a 121 ohm 1% metal film resistor between the CAN_High and CAN_Low terminals on the DeviceNet terminal block.
ON = 1
1 = 2 Hz (0.25 sec On, 0.25 sec Off)
CAN_Low
DeviceNet Removable Terminal Block
CAN_High

Operations

7

Modes of Operation

The RediStation has 3 modes of operations:
Powerup / Reset mode
Run mode
Error mode
Powerup/Reset Mode
During a powerup or reset, the RediSTATION:
1. Clears outputs (turns outputs off) and sets the LED indicator to
solid red.
2. Performs powerup diagnostic tests including:
EPROM checksum testRAM read/write testWatchdog timer testSerial number verification
If any test fails, the outputs remain off and the LED remains solid red. You must cycle power to recover from a power-up diagnostic test failure. Repeated failures indicate a faulty unit.
3. Reads and stores the DIP switch settings.
Important: DIP switches are only read in powerup or reset mode. Changes to DIP switch settings under power cause an error.
4. Performs a duplicate node address check to verify that another node is not assigned the same DeviceNet address as the RediSTATION device.
If a duplicate node error occurs, the outputs turn off and the status led is set to blinking red. You must cycle power to clear the error.
During a powerup or reset, the LED is red. If the powerup or reset is successful, the RediSTATION enters run mode and the LED flashes green.
Run Mode
After a successful powerup or reset, the RediSTATION enters run mode and operates as a slave device to a master device. In run mode, the:
controller scans switch inputs and writes lamp outputs.
station accepts output messages and poll messages from other
nodes on the DeviceNet network.
station monitors outputs for underloads/overloads.
8
Critical
le)
Solid Red
Non-Critical
le)
Flashing Red
If an output error is detected, the RediSTATION sets the appropriate message bits and remains in run mode.
In run mode, you can configure the outputs to:
turn on
turn off
flash
DIP switch 10 controls the rate of flashing for outputs. The RediSTATION also supports DeviceNet configuration messages
that are received over the network.
Error Mode
In error mode (LED turns red), the RediSTATION monitors the error state for correct operation. Errors are critical or noncritical.
Error Type Description LED State
Failure of diagnostic tests during powerup/reset mode Over-temperature condition of outputs during runtime
(Not recoverab
(Recoverab
Changes to DIP switches during runtime Duplicate node address detected Incorrect data rate Pilot lamp burned out – open circuit on output Pilot lamp wired incorrectly – short circuit/overload I/O connection timeout
Solid Red
Flashing Red
See the troubleshooting chart for details on how to recover from an error.
9

DeviceNet Operations

The Allen-Bradley 1747-SDN and 1771-SDN DeviceNet Scanner Modules are master devices on the DeviceNet network. The RediSTATION supports the Master/Slave Connection Set for master/slave communications on the DeviceNet network.
To communicate with a RediSTATION, the DeviceNet Scanner Module must be configured with the RediSTATION:
node address
input bytes (1)
output bytes (1)
The DeviceNet Scanner Module:
connects to the RediSTATION slave device
performs the appropriate connection configuration
polls the RediSTATION for inputs and outputs
Response Times
The RediSTATION responds to a DeviceNet Scanner poll within 1 millisecond.
The switch inputs are debounced for 50 milliseconds. When a change of state is detected, the inputs are not read for another 50 milliseconds.
10
Wh
Wh

Troubleshooting

Using the LED Indicator

The LED provides status information on RediSTATION operations. The LED is visible when the enclosure cover is removed.
The troubleshooting chart shows LED indications. It also shows how to use the LED to detect and correct common operating problems.
LED
Color State
None 1. RediST ATION is not receiving input power. 1. Check DeviceNet power and cable
Red Solid 1. Diagnostics failed on powerup/reset.
at it Means:
2. DIP switch settings changed after powerup. DIP Switch settings are only read during a powerup/reset.
3. Over–temperature error detected during runtime. Outputs turn off.
4. Invalid data rate.
1. Duplicate DeviceNet node address. Two nodes cannot have the same address.
at to do:
connections and the power connection on the DeviceNet terminal block. Page 3 references this connection.
1. Internal fault. Reset device. If fault still exists, return RediSTATION for repair.
2. Power down RediSTATION. Set DIP switch settings. Reconnect power.
3. Check ambient temperature rating. Reset device.
4. Reset DIP switches 7 and 8 to a valid DeviceNet data rate. See page 5 for valid data rates and cable lengths. Reset device.
1. Reset DIP switches 1 through 6 using a valid address. Page 4 provides a table of possible address settings. Reset device.
2. Pilot light lamp is burnt out – open circuit on
Red Flashing
Green Solid 1. Normal operating state and device is
Green Flashing 1. Device is online but not allocated to master.
output.
3. Pilot light is not wired correctly to the I/O connector or the screw terminals of the device – short circuit/overload.
4. I/O connection timeout.
allocated to a master device.
2. Device is in idle state.
The LED does not indicate the following malfunctions.
Problem What it Means: What to do:
Switch or button operators do not function
1. Loose wiring
2. Incorrect address
3. Faulty contacts, switch or button
2. Replace pilot lamp bulb.
3. Check I/O cable connections for the pilot light device.
4. Reset device.
1. No action required.
1. Check DeviceNet master for correct RediST ATION configuration information (node address, input bytes, output bytes).
2. Check DeviceNet master for proper operation.
1. Check wiring and cable connections.
2. Check address setting of the DIP switch.
3. Use an ohmmeter to verify opening/closing of contacts.

User-Defined Configuration

An unpopulated configuration is available for customer configuration and installation of operator devices. This section provides information on:
Kit Contents
DeviceNet Interface Board Specifications
Mounting Dimensions of Board
Connecting Devices to Board
11

Kit Contents

The unpopulated configuration consists of:
DeviceNet Interface Board
Six I/O Connector Cables (supporting 4 inputs and 2 outputs)
DeviceNet PCB Terminal Block
Mounting Hardware
2 Circuit Board Mounting Screws
Interface Board
I/O Connector
DeviceNet Terminal Block
4 Circuit Board Spacers (2 sizes provided)
Six I/O Connector Cables
12

Specifications of DeviceNet Interface Board

Electrical
Supply Voltage 11 to 25 VDC Power Consumption 7 Watts Maximum Inputs
Maximum Number 4 Type Hard Contact Sourcing
Voltage/Current 24 VDC/24mA Maximum Isolation None
Outputs
Maximum Number 2 Voltage/Current 24 VDC/100mA Maximum Isolation None
Communications
DeviceNet Baud Rates 125K, 250K, 500K
Distance Max. 500 meters (1600 feet) @125K 200 meters (600 feet) @250K 100 meters (300 feet) @500K
Environment
Ambient Temperature
Operating 0 to 55° C (32 to 131° F) Storage -40 to 85° C (-40 to 185° F)
Relative Humidity (non-condensing) 5 to 95%
50% max at 40° C (104° F)
13

Connecting Devices

This section shows how to connect devices to the DeviceNet Interface Board and connect the DeviceNet cable to the DeviceNet terminal block connector.
To install devices:
1. Connect the device terminals to the I/O connector using the I/O cables. An I/O cable consists of a twisted (red/black) wire pair. Each set of contacts or pilot light connects to an I/O cable.
I/O Connector
I/O Cable
to Device Terminals
Every 2 consecutive pins on the I/O connector connects to an I/O cable connector. The I/O connector supports 2 outputs and 4 inputs.
I/O Connector
I/O Cable (Up to 6)
Circuit Board
ATTENTION: Do not connect I/O pins to standard control voltages. See Page 12 for maximum voltages. I/O pins are
!
not electrically isolated from the DeviceNet circuitry.
To Output To Output To Input To Input To Input To Input
14
Connects O
e
Connects O
e
Connects In
e
Connects In
e
Connects In
e
Connects In
e
To simplify wiring, input devices and output devices attach to opposite ends of the I/O connector. The following table defines pin functions on the I/O connector. Output devices connect to pins 1–2 and 3–4. Input devices connect to pins 5–6, 7–8, 9–10 and 11–12. Unused pins are left open.
I/O Connector Pin # Pin Label Function
1 OUT1+ 2 OUT1– 3 OUT2+ 4 OUT2– 5 IN4+ 6 IN4– 7 IN3+ 8 IN3–
9 IN2+ 10 IN2– 11 IN1+ 12 IN1–
utput Devic
utput Devic
put Devic
put Devic
put Devic
put Devic
2. Mount the circuit board using the spacers and mounting screws provided. Tighten circuit board mounting screws to 14 in-lbs.
3. Attach the 6 DeviceNet cable leads to the DeviceNet removable terminal block connector.
Page 3 provides a description of the DeviceNet connections.
Pin 1
Common
CAN Low
Shield
CAN High
VDC+
E GND
Pin 6
Removable Terminal Block Connector
Copyright 1999 Allen-Bradley Company, Inc. Printed in USA
41061-116-01(A)
Loading...