Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1
your local Rockwell Automation® sales office or online at http://www.rockwellautomation.com/literature/
important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference,
and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from
) describes some
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Identifies information that is critical for successful application and understanding of the product.
Allen-Bradley, Rockwell Automation, Rockwell Software, PowerFlex, Studio 5000, and Connected Components Workbench are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
(2) The online help is installed with the software.
(2)
(2)
(1)
(1)
ODVA Pub. 148
ODVA Pub. 35
IASIMP-QR023
520COM-IN001
LINX-GR001
–
Manual Conventions
The following conventions are used throughout this manual:
• Parameter names are shown in the format Device parameter xx [*] or Host
parameter axxx [*]. The xx/xxx represents the parameter number and the a
represents the parameter group. The * represents the parameter name— for
example Device parameter 01 [MultiDrv Sel].
• Menu commands are shown in bold type face and follow the format Menu
> Command. For example, if you read “Select File > Open,” yo u s ho ul d
click the File menu and then click the Open command.
Rockwell Automation Publication 520COM-UM003A-EN-E - June 20137
Preface Overview
• The Studio 5000™ Engineering and Design Environment combines
engineering and design elements into a common environment. The first
element in the Studio 5000 environment is the Logix Designer
application. The Logix Designer application is the rebranding of
RSLogix 5000 software and will continue to be the product to program
Logix 5000 controllers for discrete, process, batch, motion, safety, and
drive-based solutions. The Studio 5000 environment is the foundation for
the future of Rockwell Automation engineering design tools and
capabilities. It is the one place for design engineers to develop all the
elements of their control system.
• RSLogix 5000 software (version 20) was used for the screen captures in
this manual. Different versions of the software may differ in appearance
and procedures.
• The PowerFlex 520-series Adjustable Frequency AC Drive consists of
PowerFlex 525 (used in the examples throughout this manual) and
PowerFlex 523.
8Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Chapter 1
Item PartDescription
➊Communication
card-Drive header
A 40-pin, double-row shrouded female
header. An interface connector is used to
connect this header to a header on the
drive.
➋Node Address switches Sets the network node address of the
adapter when not using:
• A BOOTP or DHCP server
• Adapter parameters
See Setting the Node Address
on page 16.
➌CS1/CS2 terminalsProvides a clean ground for the
communication bus cable shields.
CS1 or CS2 should be connected to a clean
ground or PE ground on the drive.
➍ENET1 Network por tAn RJ-45 connector for the Ethernet
cable. It is CAT-5 compliant to ensure
reliable data transfer on 100Base-Tx
Ethernet connections.
➎ENET2 Network port
➏Status indicatorsFour LEDs that indicate the status of the
connected drive, adapter and network.
See Troubleshooting
on page 115.
25-COMM-E2P
➊
➋
➌
➍
➎➏
Getting Started
The Dual-port EtherNet/IP adapter is a communication option intended for
installation into a PowerFlex 520-series drive. The Multi-Drive feature (see Usi ng
Multi-Drive Mode on page 87) also provides a means for other supported
PowerFlex drives and DSI Hosts to connect to an EtherNet/IP network.
Rockwell Automation Publication 520COM-UM003A-EN-E - June 20139
Chapter 1Getting Started
Features
The features of the Dual-port EtherNet/IP adapter include:
• Industrial Ethernet switch, and ENET1 and ENET2 network ports that
provide connections for EtherNet/IP star, linear, or device-level ring
(DLR) network topologies.
• Switches to set a network node address before applying power to the
drive—or you can disable the switches and use a BOOTP server, a
Dynamic Host Configuration Protocol (DHCP) server, or adapter
parameters to configure the IP address.
• Compatibility with various configuration tools to configure the adapter
and host drive. The tools include the PowerFlex 4/40-class HIM (Human
Interface Module 22-HIM-A3 or 22-HIM-C2S), and drive-configuration
software such as RSLogix 5000 (version 17 or greater), Logix Designer
(version 21 or greater), and Connected Components Workbench (version
3 or greater).
• Status indicators that report the status of the adapter and network
communications.
• Parameter-configured 16-bit Datalinks in the I/O to meet application
requirements (four Datalinks to write data from the network to the drive,
and four Datalinks to read data to the network from the drive).
• Explicit Messaging support.
• Master-Slave hierarchy that can be configured to transmit data to and from
a controller on the network.
• Multi-drive mode which allows up to five drives to share a single
EtherNet/IP node.
• User-defined fault actions to determine how the adapter and its host
PowerFlex 520-series drive respond to:
– I/O messaging communication disruptions (Comm Flt Action)
– Controllers in idle mode (Idle Flt Action)
• Automatic Device Configuration (ADC) is an RSLogix 5000 (version 20
or greater) and Logix Designer (version 21 or greater) software feature that
supports the automatic download of configuration data upon the Logix
controller establishing an EtherNet/IP network connection to a
PowerFlex 520-series drive and its associated peripherals.
Understanding Parameter
Types
10Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
This manual references two types of parameters:
• Device parameters are used to configure the adapter to operate on the
network. These parameters reside on the adapter.
• Host parameters are used to configure the drive, including the datalink
configuration for the datalinks used by the adapter. These parameters
reside on the drive.
Getting StartedChapter 1
Yo u c an vi ew ad ap te r Device parameters and Host parameters with any of the
following drive configuration tools:
• PowerFlex 4-class HIM (22-HIM-A3 or 22-HIM-C2S)
• Connected Components Workbench software – click the tab for the
adapter at the bottom of the window, and click the Parameters icon in the
tool bar.
Compatible Products
Required Equipment
At the time of publication, the adapter is compatible with Allen-Bradley
PowerFlex 525 and PowerFlex 523 drives.
Equipment Shipped with the Drive
When you unpack the adapter, verify that the package includes:
❑ One PowerFlex 520-series Dual-port EtherNet/IP communications adapter (25-COMM-E2P)
(installed in a PowerFlex 520-series drive control module back cover)
❑ Two interface connectors (for connecting the Communication card-Drive header to the header on the drive)
❑ One PowerFlex 520-series Communication Adapters Installation Instructions, publication 520COM-IN001
User-Supplied Equipment
The adapter parameters can be configured using the drive keypad interface (see
Using the Drive Keypad Interface to Access Parameters
you must supply:
❑ Ethernet cable (see the EtherNet/IP Media Planning and Installation Manual, ODVA publication 148 available on the
ODVA web site at http://odva.org/Home/ODVATECHNOLOGIES/EtherNetIP/EtherNetIPLibrary/tabid/76/Default.aspx
for details)
❑ Ethernet switch (see the Ethernet Design Considerations Reference Manual, Rockwell Automation publication
ENET-RM002
❑ Optional configuration tool, such as:
– PowerFlex 22-HIM-A3/-C2S HIM
– DHCP/BOOTP Utilities
❑ Controller configuration software, such as:
– RSLinx Classic (version 2.50 or later)
– RSLogix 5000 (version 17 or greater) or Logix Designer (version 21 or greater) when using drive-specific Add-On
– Connected Components Workbench (version 3 or greater)
❑ A PC connection to the EtherNet/IP network
for details)
Profile (AOP)
on page 25). In addition,
Rockwell Automation Publication 520COM-UM003A-EN-E - June 201311
Chapter 1Getting Started
Safety Precautions
Please read the following safety precautions carefully.
ATT EN TI ON : Risk of injury or death exists. The PowerFlex drive may contain
high voltages that can cause injury or death. Remove all power from the
PowerFlex drive, and then verify power has been removed before installing or
removing an adapter.
ATT EN TI ON : Risk of injury or equipment damage exists. Only personnel
familiar with drive and power products and the associated machinery should
plan or implement the installation, start up, configuration, and subsequent
maintenance of the drive using this Dual-port EtherNet/IP adapter. Failure to
comply may result in injury and/or equipment damage.
ATT EN TI ON : Risk of equipment damage exists. The adapter contains ESD
(Electrostatic Discharge) sensitive parts that can be damaged if you do not
follow ESD control procedures. Static control precautions are required when
handling the adapter. If you are unfamiliar with static control procedures, see
Guarding Against Electrostatic Damage, publication 8000-4.5.2
ATT EN TI ON : Risk of injury or equipment damage exists. If the adapter is
transmitting control I/O to the drive, the drive may fault when you reset the
adapter. Determine how your drive will respond before resetting the adapter.
ATT EN TI ON : Risk of injury or equipment damage exists. Device parameters 23
[Comm Flt Action] and 24 [Idle Flt Action] let you determine the action of
the adapter and drive if I/O communication is disrupted, the controller is idle, or
explicit messaging for drive control is disrupted. By default, these parameters
fault the drive. You may configure these parameters so that the drive continues
to run, however, precautions should be taken to ensure that the settings of
these parameters do not create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds correctly to various
situations (for example, a disconnected cable or a controller in idle state).
ATT EN TI ON : Risk of injury or equipment damage exists. When a system is
configured for the first time, there may be unintended or incorrect machine
motion. Disconnect the motor from the machine or process during initial system
testing.
ATT EN TI ON : Risk of injury or equipment damage exists. The examples in this
publication are intended solely for purposes of example. There are many
variables and requirements with any application. Rockwell Automation, Inc.
does not assume responsibility or liability (to include intellectual property
liability) for actual use of the examples shown in this publication.
.
12Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Getting StartedChapter 1
Quick Start
This section is provided to help experienced users quickly start using the adapter.
If you are unsure how to complete a step, refer to the referenced chapter.
Step ActionSee...
1Review the safety precautions for the adapter.Throughout this manual
2Verify that the PowerFlex drive is properly installed.PowerFlex 525
3Commission the adapter.
Set the adapter IP address. When using the adapter node address switches, set the IP
address now and proceed with step 4. When using a DHCP or BOOTP server, or adapter
parameters instead to set the IP address, proceed with step 4.
4Install the adapter.
Verify that the PowerFlex drive is not powered. Then, connect the adapter to the drive
using the interface connector (included with adapter).
5Connect the adapter to the EtherNet/IP network.
Verify that the PowerFlex drive is not powered. Then, connect the adapter to the
network using an Ethernet cable.
6Apply power to the drive.
a. Replace the control module cover.
b. The adapter receives power from the drive. Apply power to the drive. The status
indicators should be green. If they flash red, there is a problem. See
Troubleshooting on page 115.
c. Configure and verify key drive parameters.
7Configure the adapter for your application.
Set adapter parameters for the following functions as required by your application:
– IP address, subnet mask, and gateway address (only when not using adapter
8Configure the controller to communicate with the adapter.
Use a control ler configuration too l such as RSLogix 500 0 or Logix Designer to configure
the master on the EtherNet/IP network to recognize the adapter and drive.
9Create a ladder logic program.
Use a controller configuration tool such as RSLogix 5000 or Logix Designer to create a
ladder logic program that enables you to:
– Control the adapter and connected drive using I/O.
– Monitor or configure the drive using Explicit messages.
Adjustable Freq uency AC
Drive User Manual,
publication 520-UM001
Chapter 2,
Installing the Adapter
PowerFlex 520-Series
Communication Adap ters
Installation Instructions,
publication 520COM-
IN001 and
Chapter 2,
Installing the Adapter
Chapter 2,
Installing the Adapter
,
Chapter 3
Configuring the Adapter
Chapter 4,
Configuring the I/O
Chapter 5,
Using the I/O
Chapter 6,
Using Explicit Messaging
Rockwell Automation Publication 520COM-UM003A-EN-E - June 201313
Chapter 1Getting Started
Notes:
14Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Chapter 2
Installing the Adapter
Chapter 2 provides instructions for installing the Dual-port EtherNet/IP adapter
in a PowerFlex 520-series drive.
Top icPa ge
Preparing for Set-Up
Setting the Node Address16
Connecting the Ad apter to the Drive18
Connecting the Adapter to the Network20
Applying Power22
Commissioning the Adapter24
15
Preparing for Set-Up
Before installing the adapter, do the following:
• Make sure the Ethernet switch is the correct type. A “managed” switch that
supports IGMP snooping is usually recommended. An “unmanaged”
switch can be used instead if RSLogix 5000 software (version 18 or
greater) is used and all devices on the network are configured for “unicast”
I/O. For more details, see the following documents:
– EtherNet/IP Media Planning and Installation Manual,
The adapter is a multicast device. In most situations, an IGMP snooping
(managed) switch is required. If more than one or two adapters are
connected to the switch, a managed switch is required—otherwise the
drive may fault on a Net I/O Timeout network loss. The adapter,
RSLogix 5000 (version 18 or greater), Logix Designer (version 21 or
greater), and a ControlLogix or CompactLogix controller will support
unicast. Unicast setup is required when adding the drive to the I/O. When
all adapters are set up as unicast devices, then an IGMP snooping
(managed) switch is not needed.
Much of EtherNet/IP implicit (I/O) messaging uses IP multicast to
distribute I/O control data, which is consistent with the CIP producer/
consumer model. Historically, most switches have treated multicast
packets the same as broadcast packets. That is, all multicast packets are retransmitted to all ports.
Rockwell Automation Publication 520COM-UM003A-EN-E - June 201315
Chapter 2Installing the Adapter
IMPORTANT
IGMP snooping constrains the flooding of multicast traffic by dynamically
configuring switch ports so that multicast traffic is forwarded only to ports
associated with a particular IP multicast group.
Switches that support IGMP snooping (managed switches) “learn” which
ports have devices that are part of a particular multicast group and only
forward the multicast packets to the ports that are part of the multicast
group.
Be careful as to what level of support a switch has of IGMP snooping.
Some layer 2 switches that support IGMP snooping require a router
(which could be a layer 3 switch) to send out IGMP polls to learn what
devices are part of the multicast group. Some layer 2 switches can use
IGMP snooping without a router sending polls. If your control system is a
stand-alone network or is required to continue performing if the router is
out of service, make sure the switch you are using supports IGMP
snooping without a router being present.
• See Specifications
on page 123 for the number of CIP connections
supported by the adapter.
• Verify that you have all required equipment. See Required Equipment
page 11.
on
Setting the Node Address
ATT EN TI ON : Risk of equipment damage exists. The adapter contains ESD
(Electrostatic Discharge) sensitive parts that can be damaged if you do not
follow ESD control procedures. Static control precautions are required when
handling the adapter. If you are unfamiliar with static control procedures, see
Guarding Against Electrostatic Damage, publication 8000-4.5.2
.
The adapter has EtherNet/IP embedded switch technology, and ENET1 and
ENET2 network ports to connect to a linear or device-level ring (DLR) network
in a single subnet.
You cannot use ENET1 and ENET 2 network ports as two network interface
cards connected to two different subnets.
There are four methods for configuring the adapter’s node address:
• Node Address Switches — Use these switches when working on a simple
isolated network (for example, 192.168.1.xxx) that has other products
with switches to set their IP addresses, does not need to be accessed from
outside the network, and you prefer a simplified node addressing method.
The three rotary switches are read when the drive powers up, and represent
three decimal digits from top to bottom (see Setting the Node Address
Switches on page 18). When set to a valid address (001...254), the adapter
will use that value as the lower octet of its IP address (192.168.1.xxx, where
xxx = rotary switch settings), along with a subnet mask of 255.255.255.0,
and a gateway address of 0.0.0.0 when switches are set to 001, or a gateway
address of 192.168.1.1 when switches are set from 002...254. Also, the
setting for Device parameter 04 [Net Addr Sel] is automatically ignored.
16Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Installing the AdapterChapter 2
IMPORTANT
IMPORTANT
IMPORTANT
See Setting the Node Address Switches on page 18 and its accompanying
table for all possible switch settings and their related descriptions.
When using the Node Address switches, set the network node address
before power is applied because the adapter uses the node address it
detects when it first receives power.
•Adapter Parameters — Use adapter parameters when you want more
flexibility in setting up the IP address, or need to communicate outside the
control network using a gateway. To use parameters as the source for the IP
address, the Node Address switches must be set to a value other than
001...254 or 888, and Device parameter 04 [Net Addr Sel] must be set to
1“Parameters”. The IP address, subnet mask, and gateway addresses will
then come from the parameters you set. See Using Adapter Parameters
page 31for more information.
If parameter values are invalid or the adapter was not reset for the
values to take effect, the node address is established by using DHCP.
on
•BOOTP Server — Use BOOTP when you want to configure a temporary
IP address, subnet mask, and gateway address for the adapter using a
BOOTP server. To use BOOTP as the source for the IP address, the Node
Address switches must be set to a value other than 001...254 or 888, and
Device parameter 04 [Net Addr Sel] must be set to 2 “BOOTP”.
Note the adapter’s hardware Ethernet Address (MAC) on the adapter’s
data nameplate label located on the provided control module back cover,
which will be used in Step 7 when configuring the BOOTP server (see
Using a BOOTP or DHCP Ser ver
on page 28 for details).
• DHCP (Dynamic Host Configuration Protocol) — Use DHCP, the
default, when you want additional flexibility and ease-of-use compared to
BOOTP in configuring the IP address, subnet mask, and gateway address
for the adapter using a DHCP server. To use DHCP as the source for the
IP address, the Node Address switches must be set to a value other than
001…254 or 888, and Device parameter 04 [Net Addr Sel] must be set to 3
“DHCP”.
Note the adapter’s hardware Ethernet Address (MAC) on the adapter’s
data nameplate label located on the provided control module back cover,
which will be used in Step 7 when configuring the DHCP server (see
Using a BOOTP or DHCP Ser ver
on page 28 for details).
Regardless of the method used to set the adapter’s node address, each node on
the EtherNet/IP network must have a unique IP address. To change a node
address, you must set the new value and then remove and reapply power to (or
reset) the drive.
Rockwell Automation Publication 520COM-UM003A-EN-E - June 201317
Chapter 2Installing the Adapter
Hundreds
position
Ten s
position
Ones
position
SettingDescription
001...254The adapter will use the Node Address switch settings for the network node address (192.168.1.xxx,
where xxx = rotary switch settings). The value stored in Device parameter 04 [Net Addr Sel] is
automatically ignored.
888Resets the adapter network node address to factory defaults. Thereafter, the drive must be powered
down, the Node Address switches must be set to a correct value (001…254), and then the drive must be
powered up again to accept the new address.
Any other
setting
Disables the Node Address switches, and requires using Device parameter 04 [Net Addr Sel] to select
the source for the adapter’s network node address:
• 1 = Parameters of the adapter
• 2 = BOOTP server
• 3 = DHCP server (Default)
Setting the Node Address Switches
Connecting the Adapter to
the Drive
The Node Address switch settings can be verified by viewing Diagnostic Item
number 58 (see page 118
and page 120) with a PowerFlex 22-HIM-A3 or 22HIM-C2S HIM, or Connected Components Workbench (version 3 or greater)
software. Also, you can use Device parameter 05 [Net Addr Src], a read-only
parameter, to verify the selected setting for Device parameter 04 [Net Addr Sel].
ATT EN TI ON : Risk of injury or death exists. The PowerFlex drive may contain
high voltages that can cause injury or death. Remove all power from the
PowerFlex drive, and then verify power has been removed before installing or
removing an adapter.
1. Remove power from the drive.
2. Use static control precautions.
3. Separate the drive’s control module from the power module.
18Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Installing the AdapterChapter 2
a. Press and hold down the catch on both sides of the frame cover, then
pullout and swing upwards to remove (Frames B...E only).
b. Press down and slide out the top cover of the control module to unlock
it from the power module.
c. Hold the sides and top of the control module firmly, then pull out to
separate it from the power module.
Rockwell Automation Publication 520COM-UM003A-EN-E - June 201319
Chapter 2Installing the Adapter
IMPORTANT
4. Insert the interface connector for the adapter into the header located at the
back of the control module.
5. Align the Communication card-Drive header on the adapter with the
interface connector. Then, press down firmly around the adapter. The
adapter snaps into the back of the control module.
The CS1/CS2 terminals on the adapter provide a clean ground for the
communication bus cable shields. You should connect the CS1 or CS2
terminal to a clean ground or PE ground on the drive.
6. Attach the control module to the power module.
Connecting the Adapter to
the Network
20Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
ATT EN TI ON : Risk of injury or death exists. The PowerFlex drive may contain
high voltages that can cause injur y or death. Remove power from the drive, and
then verify power has been discharged before connecting the adapter to the
network.
Installing the AdapterChapter 2
IMPORTANT
1 (Front)1 (Front)1 (Front)
2 (Rear)
00:00:BC:2E:69:F6
Esc
Sel
Esc
Sel
External
Ethernet
switch
1769-L36ERM CompactLogix controller
with embedded EtherNet/IP bridge
PowerFlex 520-series drives with
25-COMM-E2P adapter
(1)
(Frame A shown)
Computer with
Ethernet Connection
To o ther
EtherNet/IP
networks
(1) The Ethernet cable may be connected to the adapter’s ENET1 or ENET 2 network port.
1 (Front)1 (Front)1 (Front)
2 (Rear)
00:00:BC:2E:69:F6
Esc
Sel
Esc
Sel
External
Ethernet
switch
1769-L36ERM CompactLogix controller
with embedded EtherNet/IP bridge
PowerFlex 520-series drives with
25-COMM-E2P adapter
(1)
(Frame A shown)
Computer with
Ethernet Connection
To o ther
EtherNet/IP
networks
(1) The adapter’s ENET1 and ENET2 network ports are used.
1. Remove power from the drive.
2. Use static control precautions.
3. Connect one end of an Ethernet cable to the network.
Examples of different EtherNet/IP network topologies are shown in
Connecting the Ethernet Cable in a Star Topology Network
Connecting the Ethernet Cable in a Linear Topology Network
on page 21,
on page 21,
and Connecting the Ethernet Cable in a DLR Topology Network
page 22. For information about linear and device-level ring (DLR)
topologies, see EtherNet/IP Embedded Switch Technology, publication
ENET-AP005.
The adapter has EtherNet/IP embedded switch technology, and ENET1 and
ENET2 network ports to connect to a linear or device-level ring (DLR) network
in a single subnet.
You cannot use ENET1 and ENET 2 network ports as two network interface
cards connected to two different subnets.
on
Connecting the Ethernet Cable in a Star Topology Network
Connecting the Ethernet Cable in a Linear Topology Network
Rockwell Automation Publication 520COM-UM003A-EN-E - June 201321
Chapter 2Installing the Adapter
1 (Front)1 (Front)1 (Front)
2 (Rear)
00:00:BC:2E:69:F6
Esc
Sel
Esc
Sel
1783-ETAP
1769-L36ERM CompactLogix controller
with embedded EtherNet/IP bridge
PowerFlex 520-series drives with
25-COMM-E2P adapter
(1)
(Frame A shown)
Computer with
Ethernet Connection
To o ther
EtherNet/IP
networks
(1) The adapter’s ENET1 and ENET2 network ports are used.
1783-ETAP
Connecting the Ethernet Cable in a DLR Topology Network
4. Depending on the network topology, do one of the following:
• Star Network Topology—Route the other end of the Ethernet cable
from the network through the bottom of the drive, and insert its cable
plug into the option module’s ENET1 or ENET2 network port.
• Linear or DLR Network Topology—Route the other end of the
Ethernet cable from the network through the bottom of the first drive,
and insert its cable plug into the option module ENET1 network port.
Applying Power
To connect to the second drive, attach another Ethernet cable between
the first drive’s option module ENET2 network port and the second
drive’s option module ENET1 network port.
To connect additional drives, repeat these daisy-chain connections in
the same way.
ATT EN TI ON : Risk of equipment damage, injury, or death exists. Unpredictable
operation may occur if you fail to verify that parameter settings are compatible
with your application. Verify that settings are compatible with your application
before applying power to the drive.
Apply power to the drive. The adapter receives its power from the drive.
Startup Status Indication
After power has been applied, the status indicators can be viewed on the front of
the drive. When you apply power to the adapter for the first time, the status
indicators should be green after an initialization. If the status indicators go red,
there is a problem. See Troubleshooting
on page 115.
22Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Drive and Adapter Status Indicators
Esc
Sel
➊
➋
➌
25-COMM-E2PPowerFlex 525 Frame A shown
➍
➊
➋
➌
➍
Item Status IndicatorStatus
(1)
(1) If all status indicators are off, the adapter is not receiving power. If any other conditions occur, see Troubleshooting on page 85.
Description
➊PORTFlashing greenNormal operation. The adapter is establishing an I/O
connection to the drive. This status indicator will turn
steady green or red.
Steady greenNormal operation. The adapter is properly connected and is
communicating with the drive.
➋MODFlashing greenNormal operation. The adapter is operating but is not
transferring I/O data to a controller.
Steady greenNormal operation. The adapter is operating and transferring
I/O data to a controller.
➌NET AFlashing greenNormal operation. The adapter is properly connected but is
not communicating with any devices on the network.
Steady greenNormal operation. The adapter is properly connected and
communicating on the network to a controller.
➍NET BOffNormal operation. The adapter is properly connected, but is
idle.
Flashing greenNormal operation. The adapter is properly connected and
transmitting on the network.
Installing the AdapterChapter 2
FWD
ENET LINK
EtherNet/IP
For more details on status indicator operation see Understanding the Status
Indicators on page 115.
Configuring/Verifying Key Drive Parameters
The PowerFlex 525 drive can be separately configured for the control and
Reference functions in various combinations. For example, you could set the
drive to have its control come from a peripheral or terminal block with the
Reference coming from the network. Or you could set the drive to have its
control come from the network with the Reference coming from another
peripheral or terminal block. Or you could set the drive to have both its control
and Reference come from the network.
Configuring the Host parameters can be done using the drive’s keypad, a HIM,
and software such as RSLogix 5000 or Logix Designer, or Connected
Components Workbench. In the following example, the drive will receive the
Logic Command and Reference from the network.
1. Set the value of Host parameter P046 [Start Source 1]
to 4 “Network Opt”.
Rockwell Automation Publication 520COM-UM003A-EN-E - June 201323
Chapter 2Installing the Adapter
TIP
IMPORTANT
2. Set the value of Host parameter P047 [Speed Reference1]
to 4 “Network Opt”.
The PowerFlex 525 drive supports up to three control functions and
three Reference functions.
For more information on how to set different combinations of the control and
Reference functions, see the PowerFlex 525 drive user manual,
publication 520-UM001
.
Commissioning the Adapter
To commission the adapter, you must set a unique network node address. See the
Glossary
Address switches, see Setting the Node Address
using these switches, a BOOTP or DHCP server, or adapter parameters can be
used to set the node address after connecting the adapter to the network and
applying power to the drive.
By default, the adapter is configured so that you must set the node address using a
DHCP server. For details, see Using a BOOTP or DHCP Server
set the node address using adapter parameters, see Using Adapter Parameters
page 31.
on page 161 for details about IP addresses. When using the Node
on page 15 for details. When not
on page 28. To
on
New settings for some adapter parameters (for example, Device parameters 06
[IP Addr Cfg 1] through 09 [IP Addr Cfg 4]) are recognized only when power
is applied to the adapter or it is reset. After you change parameter settings,
cycle drive power or reset the adapter.
24Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Chapter 3
IMPORTANT
Configuring the Adapter
This chapter provides instructions and information for setting the parameters to
configure the Dual-port EtherNet/IP adapter.
Top icPa ge
Configurat ion Tools
Using the Drive Keypad Interface to Access Parameters25
Using the PowerFlex 4-Class HIM to Access Parameters27
Using a BOOTP or DHCP Server28
Using Adapter Parameters31
Setting the Data Rate32
Using Master-Slave Hierarchy33
Setting a Fault Action34
Resetting the Ad apter36
Viewing the Adapter Status Using Parameters37
25
Configuration Tools
Using the Drive Keypad
Interface to Access
Parameters
For a list of parameters, seeAdapter Parameters
terms in this chapter, see the Glossary
The parameters can be configured using the drive keypad interface (see page 25)
or a PowerFlex 4-class HIM (Human Interface Module, see page 27
Software such as RSLogix 5000 (version 17 or greater), Logix Designer (version
21 or greater), and Connected Components Workbench (version 3 or greater)
can also be used to access the parameters.
The following is an example of basic integral keypad and display functions. This
example provides basic navigation instructions and illustrates how to program a
parameter.
The Dual-port EtherNet/IP adapter Device parameters can be accessed on the
drive keypad via the “N” (Network) group. Note that the parameters in the “N”
group will appear offset from the Device parameter numbers referenced in this
manual by 1000 (decimal) on the LCD display.
on page 161.
on page 125. For definitions of
).
Rockwell Automation Publication 520COM-UM003A-EN-E - June 201325
Chapter 3Configuring the Adapter
HERT
Z
FWD
Esc
FWD
Esc
FWD
or
FWD
Sel
or
FWD
or
FWD
FWD
Sel
or
PROGRAM
FWD
or
PROGRAM
FWD
Sel
PROGRAM
FWD
Esc
or
FWD
FWD
or
Esc
FWD
StepKey(s)Example Display
1. When power is applied, the last user-selected
Basic Display Group parameter number is briefly
displayed with flashing characters. The display
then defaults to that parameter’s current value
(Example shows the value of b001 [Output
Freq] with the drive stopped).
2. Press Esc to display the Basic Display Group
parameter number shown on power-up. The
parameter number will flash.
3. Press Esc to enter the parameter group list. The
parameter group letter will flash.
4. Press the Up Ar row or Down Arrow to scroll
through the group list (b, P, t, C, L, d, A, f, N, M,
and Gx).
5. Press Enter or Sel to enter a group. The right
digit of the last viewed parameter in that group
will flash.
6. Press the Up Ar row or Down Arrow to scroll
through the parameter list.
7. Press Enter to view the value of the parameter.
Or
Press Esc to return to the parameter list.
8. Press Enter or Sel to enter Program Mode and
edit the value. The right digit will flash and the
word Program on the LCD display will light up.
9. Press the Up Arrow or Down Arrow to change
the parameter value.
10. If desired, press Sel to move from digit to digit
or bit to bit. The digit or bit that you can change
will flash.
11. Press Esc to cancel a change and exit Program
Mode.
Or
Press Enter to save a change and exit Program
Mode.
The digit will stop flashing and the word
Program on the LCD display will turn off.
12. Press Esc to return to the parameter list.
Continue to press Esc to back out of the
programming menu.
If pressing Esc does not change the display, then
b001 [Output Freq] is displayed. Press Enter or
Sel to enter the group list again.
26Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Configuring the AdapterChapter 3
Para meters
Groups
Linear List
Changed Params
DIAG
PAR A M DSELMEMSEL
Sel
Device Select
DSI Devices
DIAG PARAM
DSELMEMSEL
and
DSI Devices
PowerFlex 525
25-COMM-E2P
and
DSI Devices
PowerFlex 525
25-COMM-E2P
Using the PowerFlex 4-Class
HIM to Access Parameters
The PowerFlex 4-class HIM can be used to access parameters in the drive (see
basic steps shown below). It is recommended that you read through the steps for
your HIM before performing the sequence. For additional HIM information,
refer to the HIM Quick Reference card, publication 22HIM-QR001
StepKey(s)Example Display
1. Power up the drive. Then connect the HIM
to the DSI port of the drive. The Parameters
tab for the drive will be displayed.
2. Press Sel until the DSEL tab is selected.
3. Select DSI Device in the DSEL tab if it is not
already selected using the Up Arrow or
Down Arrow.
Press Enter to selec t DSI Device.
.
Setting the Adapter Node
Address
4. Press the Up Arrow or Down Arrow to scroll
to 25-COMM-E2P.
Press Enter to reload the HIM to browse
only the Communication Adapter (25COMM-E2P) parameters.
To display the Host parameters, repeat steps 1 through 3 and select “PowerFlex
525” at step 3.
When the Node Address switches (see Setting the Node Address Switches on
page 18) are set to a value other than 001...254 or 888, Device parameter 04 [Net
Addr Sel] determines the source for the adapter node address. By default, the
Node Address switches are set to 999 and Device parameter 04 [Net Addr Sel] is
set to 3 “DHCP”. This combination selects a DHCP server as the source for the
node address. To use a BOOTP or DHCP server to set the node address, see
Using a BOOTP or DHCP Ser ver
Using Adapter Parameters
Rockwell Automation Publication 520COM-UM003A-EN-E - June 201327
on page 31.
on page 28. To use adapter parameters, see
Chapter 3Configuring the Adapter
TIP
Ethernet Address label example
Using a BOOTP or DHCP
Server
By default, the adapter is configured to accept an IP address, subnet mask, and
gateway address from a DHCP server. You can select from a variety of DHCP/
BOOTP utilities.
The instructions below use the DHCP/BOOTP Utility (version 2.3 or greater),
a free stand-alone program from Rockwell Automation that incorporates the
functionality of standard DHCP/BOOTP utilities with a graphical interface. It
is available from http://www.ab.com/networks/ethernet/bootp.html
Readme file and online Help for directions and more information.
If desired, you can disable BOOTP and configure the IP address, subnet mask,
and gateway address using parameters. For details, see Using Adapter
Parameters on page 31.
. See the
Configuring the Adapter Using a DHCP/BOOTP Utility
1. Depending on the type of server (BOOTP or DHCP) being used, set
Device parameter 04 [Net Addr Sel] to either 2 “BOOTP” or 3 “DHCP”
respectively.
Options1“Parameters”
2“BOOTP”
3 “DHCP” (Default)
2. Verify and note the adapter’s hardware Ethernet Address (MAC), which
will be used in Step 7. There are two ways to do this:
• Use the PowerFlex 525 drive’s keypad or a HIM to access the diagnostic
items of the drive. Scroll to items 34 [HW Addr 1] through 39 [HW Addr 6] to view the adapter’s hardware Ethernet Address (MAC).
Finally, convert these decimal values to a hex value.
• Locate the adapter’s hardware Ethernet Address (MAC) label on the
ENET1/ENET2 ports (provided with the adapter).
28Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Configuring the AdapterChapter 3
3. On a computer connected to the EtherNet/IP network, start the
BOOTP/DHCP software. The BOOTP/DHCP Server window
appears.
4. To properly configure devices on your EtherNet/IP network, you must
configure settings in the BOOTP/DHCP software to match the network.
Select To o l s > Net work Settings to display the Network Settings window.
5. Edit the following:
BoxType
Subnet Mask
Gateway
Primary DNSThe address of the primary DNS server to be used on the local end of the link for
Secondary DNSOptional – the address of the secondary DNS server to be used on the local end of the
Domain NameThe text name corresponding to the numeric IP address that was assigned to the server
(1) For definitions of these terms, see the Glossary on page 161.
(1)
(1)
The subnet mask for the adapter’s network.
The IP address of the gateway device on the adapter’s network.
negotiating with remote devices.
link for negotiating with remote devices when the primary DNS server is unavailable.
that controls the network.
6. Click OK to apply the settings. Devices on the network issuing BOOTP/
DHCP requests appear in the BOOTP/DHCP Request History list.
Rockwell Automation Publication 520COM-UM003A-EN-E - June 201329
Chapter 3Configuring the Adapter
TIP
7. In the BOOTP/DHCP Request History list, either double-click the
adapter’s Ethernet Address (MAC) noted in Step 2, or click New in the
Relation List. The New Entry window appears. In the first case, the
Ethernet Address (MAC) is automatically entered. In the latter case, you
must manually enter it.
8. Edit the following:
BoxType
(1)
IP Address
Host NameOptional
DescriptionOptional
(1) For definitions of these terms, see the Glossary on page 161.
A unique IP address for the adapter
9. Click OK to apply the settings. The adapter appears in the Relation List
with the new settings.
10. To assign this configuration to the adapter, select the device in the Relation
List and click Disable BOOTP/DHCP. When power is cycled on the
drive, the adapter will use the configuration you assigned it and not issue
new BOOTP/DHCP requests.
To enable BOOTP for an embedded adapter that has had BOOTP
disabled, first select the adapter in the Relation List. Then, depending
on the type of server, click Enable BOOTP or Enable DHCP and,
lastly, reset the adapter or power cycle the drive.
11. To save the Relation List, select File > Save.
30Rockwell Automation Publication 520COM-UM003A-EN-E - June 2013
Loading...
+ 142 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.