Rockwell Automation 2364P User Manual

Parallel DC Bus Supply
User
Configurations
(Using Bulletin 2364E NRUs and Bulletin 2364F RGUs)
Bulletin 2364P
Manual

Important User Information Solid-State equipment has operational characteristics differing from

those of electro m echan i ca l equ ip me nt. “Saf ety G u ide lines for the Application, Installation and Maintenance of Solid-State Controls”
(Publication SGI-1.1) describes some important differences between solid-state equi pment and hard-wired electromechanic al devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy th emse lves that e ach inte nded appl ication of this equipment is acceptable .
In no event will Rockwell Automation be responsible or liable for indirect or consequential damages resulting from the use of application of this equipment.
The examples and diagrams in this manual are included solely for illustrati ve purpose s. Bec ause of th e many var iable s and requi rements associated with any partic ular installation, the Rockwe ll Automation cannot assume responsibility or liability for actua l use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation with respect use of information, circuits, equipment, or software des cribed in this manual.
Reproduction of the conten ts of this manual, in whole or in part, without written permission of Rockwell Automation is prohibit ed.
Throughout this manual we use notes to make you aware of safety considerations:
ATTENTION: Identifies infor mation about practi ces or circums tan ce s tha t can lead to p erso n al inj ury or
!
Attention statements help you to:
identify a hazard
avoid a hazard
recognize the consequenc es
Datab is a trademark of W . H. Brady Company
NRU, RGU, HIM, Remote I/O, DeviceNet, and ControlNet are trademarks of Rockwell International or its subsidiaries.
death, property damage or economic loss.
Table of Contents

Preface Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1

Purpose of This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Contents of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-3
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-4
Receiving Your Drive System . . . . . . . . . . . . . . . . . . . . . . . . . . . P-5
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . P-5
Local Product Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-5
Technical Product Assistance . . . . . . . . . . . . . . . . . . . . . . . . . P-5

Chapter 1 Theory of Operation

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
RGU//RGU Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Output of RGU//RGU Configurations . . . . . . . . . . . . . . . . . . . 1-4
NRU//RGU Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Output of NRU//RGU Configurations . . . . . . . . . . . . . . . . . . 1-7
Precharge Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-11

Chapter 2 R1 and S1-Code Parallel Configurations

R1-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
S1-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4

Chapter 3 R2 and S2-Code Parallel Configurations

R2-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
S2-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4

Chapter 4 R3 and S3-Code Parallel Configurations

R3-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
S3-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
toc–ii Table of Contents

Chapter 5 R4 and S4-Code Parallel Configurations

R4-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
S4-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4

Chapter 6 T1 and V1-Code Parallel Configurations

T1-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
V1-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4

Chapter 7 T2 and V2-Code Parallel Configurations

T2-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
V2-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4

Chapter 8 T3 and V3-Code Parallel Configurations

T3-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
V3-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4

Chapter 9 T4 and V4-Code Parallel Configurations

T4-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
V4-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4

Chapter 10 T5 and V5-Code Parallel Configurations

T5-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
V5-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-4

Chapter 11 T6 and V6-Code Parallel Configurations

T6-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
V6-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-4

Chapter 12 W1-Code Parallel Configuration

W1-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . 12-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-4

Chapter 13 W2-Code Parallel Configurations

W2-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . 13-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-4

Chapter 14 W3-Code Parallel Configurations

W2-Code Parallel Configuration . . . . . . . . . . . . . . . . . . . . . . . . 14-1
Component Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-2
Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-4

Chapter 15 Installation

Receiving, Handling, and Installing the Parallel Configuration . . 15-1
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
Overhead Bus Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-3
Internal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-3
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-3
Ground-Fault Detection Option . . . . . . . . . . . . . . . . . . . . . . . 15-5
Phase-Loss Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-7
RGU-to-RGU (R2R) Communications . . . . . . . . . . . . . . . . . . . 15-9
Customer Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-11
Analog Input/Output (RGU Main Control Board) . . . . . . . . . . 15-11
SCANport (RGU Main Control Board) . . . . . . . . . . . . . . . . . . 15-12
Terminal Blocks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-13
Configuring the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-15
Connecting the AC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16
Isolation Transformer . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16
MOV Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16
Feeder Bay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16
Input Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-17
Testing the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-18
Prepower Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-18
Testing The System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-18
Table of Contents toc–iii
toc–iv Table of Contents

Chapter 16 Setting Up the Parallel Configuration

Introduction to the
Human Interface Module (HIM) . . . . . . . . . . . . . . . . . . . . . . . . . 16-1
Basic Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-3
Starting the RGU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-3
Programming the RGU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-4
Enabling the RGU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-6
Advanced Startup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . 16-7

Appendix A Specifications

Watts Dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
Physical Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9

Appendix B Catalog Numbers and Spare Parts Kits

Understanding Catalog Numbers . . . . . . . . . . . . . . . . . . . . . . . . B-1
Spare Parts Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4

Glossary

Index

Preface

Preface

Who Should Use This Manual This manual is intende d for those who are re sponsible for instal ling or

operating an Allen-Bradley parallel DC bus supply configuration.
If you do not have a basic understanding of this product, please read through this m anual. Contact your local Rockwell Automation Drive Systems represent ative if you have questions about th e conte nt of this manual or the product.

Purpose of This Manual This manual contains specifications, installation instructions, and

operating instru ctions for the 2364P parallel configuration.

Safety Precautions The following general precautions apply when installing, servicing,

or operating paralle l configurations and drive system li neups:
ATTENTION: Only those familiar with the drive system, the products used in the system, and the
!
associated machinery should plan or implement the installation, startup, and future maintenance of the system. Failure to comply can result in personal injury and/or equipment damage.
ATTENTION: Verify tha t al l sources of AC and DC power are deenergized and locked out or tagged out in accordance with the requirements of ANSI/NFPA 70E, Part II.
ATTENTION: The system may contain stored ener gy devices. To avoid the hazard of elec tric al shock, ve rify that all voltage on capacitors has b een discharge d before attempting to service, repair, or remove a drive system or its components. You should only attempt the procedures in this manual if you are qualified to do so and are familiar with solid-state control equipment and the safety procedures in ANSI/NFPA 70E.
P-2
ATTENTION: An incorrectly applied or incorrectly installed drive system can res ult in component damage
!
and/or a reduction in product life. Wiring or application
errors–such as undersizing the motor, incorre ct or inadequate AC supply, and excessive ambient temperatures–can result in the malfunction of the drive equipment.
ATTENTION: This drive system contains parts and assemblies that are sensitive to ESD (elec trostatic discharge). Static control precautions a re required when installing, testing, or repairing this assembly. Component damage can result if ESD control procedures are not followed. I f you are not familiar with static control procedur es, refer to Rockwell Automation publication 8000-4. 5.2, Guardi ng Against Electr ostatic Damage, or another adequate handbook on ESD protection.
Publication 2364P- 5.01 December 1999

Contents of this Manual

Chapter Title Contents
Preface Safety precautions, reference tables, and support information.
1 Theory of Operation Overview of the parallel configurations. Includes basic theory and operational
information.
2 R1 and S1-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the R1 and
S1-code parallel configurations.
3 R2 and S2-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the R2 and
S2-code parallel configurations.
4 R3 and S3-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the R3 and
S3-code parallel configurations.
5 R4 and S4-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the R4 and
S4-code parallel configurations.
6 T1 and V1-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the T1 and
V1-code parallel configurations.
7 T2 and V2-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the T2 and
V2-code parallel configurations.
8 T3 and V3-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the T3 and
V3-code parallel configurations.
9 T4 and V4-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the T4 and
V4-code parallel configurations.
10 T5 and V5-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the T5 and
V5-code parallel configurations.
11 T6 and V6-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the T6 and
V6-code parallel configurations.
12 W1-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the W1-code
parallel configurations.
13 W2-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the W2-code
parallel configurations.
14 W3-Code Parallel Configurations Schematics, component layout, and overhead bus configuration for the W3-code
parallel configurations.
15 Installation Instructions for installing, wiring, and testing the parallel configuration.
P-3
16 Setting Up the Parallel Configuration Instructions for setting the RGU parameters in the parallel configuration.
A Specifications Operational, environmental, and electrical specifications for the parallel
configuration.
B Catalog Numbers and Spare Parts Kits Information concerning the parallel configuration catalog numbers and spare parts
kits.
C Physical Details Enclosure dimensions and sound levels.
Index
Publication 2364P-5.01 December 1999
P-4

Related Documentation The following documents include information that may be helpful

when installing or servic es components in your drive system. To obtain a copy of any of the Rockwell Automation publ ications, contact your local Rockwell Autom ation office or distibutor.
For Read This Document Document Number
NRU layout diagrams, schematics, component information, and installation/ setup instructions.
RGU layout diagrams, schematics, component information, installation/setup instructions, and parameter listings.
Troubleshooting information, testing procedures, and fault descriptions for the RGU.
Instructions for installing an overhead bus assembly. Overhead Bus Installation Instructions for Bulletin
Information for operating and understanding the Graphic Programming Terminal (GPT).
Information for installing and configuring the Remote I/O (RIO) Communications Module.
Information for installing and configuring the DeviceNet Communications Module.
Information for installing and configuring the Series Communications Module. Bulletin 1203 Series Communications Module–
Information for installing, configuring, programming, and troubleshooting the 1336 FORCE adjustable frequency AC drive.
Information for installing, configuring, programming, and troubleshooting the 1336 PLUS adjustable frequency AC drive.
Instructions for properly handling and moving motor control centers. Receiving, Handling, and Storing Motor Control
Instructions for enclosure and busbar assembly. Bulletin 2300 Family of Drive Systems–Installation
Information for installing, configuring, and programming the SA3000 AC drive.
Information for installing, configuring, and programming the SA3100 AC drive.
Instructions for working with FD86N enclosures. FD86N Drive Systems Enclosure Hardware–
Electrical specifications established by the National Fire Protection Association (NFPA), Boston, MA.
List of documentation available through Allen-Bradley. Allen-Bradley Publication Index SD499
Non-Regenerative DC Bus Supply Unit (NRU)–User Manual
Regenerative DC Bus Supply Unit (RGU)–User Manual
Regenerative DC Bus Supply Unit (RGU)– Troubleshooting Guide
2300 MCCs Bulletin 1201 Graphic Programming Terminal–
User Manual Bulletin 1203 Remote I/O Communications
Module–Getting Started Manual Bulletin 1203 DeviceNet Communications
Module–User Manual
User Manual 1336 FORCE Adjustable Frequency AC Drive–User
Manual 1336 PLUS Adjustable Frequency AC Drive–User
Manual
Centers–Instructions
Manual SA3000 Binder S-3001
SA3100 Binder S-3053
Installation Manual National Electrical Code ANSI/NFPA70
2364E-5.01
2364F-5.01
2364F-5.05
2364P-5.10
1201-5.0
1203-5.1
1203-5.3
1203-5.5
1336 FORCE-5.12
1336 PLUS-5.0
2100-5.5
2300-5.1
S-3062
Dictionary of terms that are common to industrial automation. Industrial Automation Glossary AG-7.1
Publication 2364P- 5.01 December 1999
P-5

Receiving Your Drive System The Customer is responsibl e for thoroughly inspe cting the equipment

before accepting the shipment from the freight company. Check the item(s) that you r eceive against your purchase order. If any items are obviously damaged, do not accept the delivery until the freight agent has noted the damage on the freight bill. Should you discover any concealed damage during unpac king, you are responsible for notifying the freight agent. In such a case, leave the shipping container intact and request that the freight agent make a visua l inspection of the equipment.

Rockwell Automation Support Rockwell Automation offers support services worldwide, with Sales/

Support Office s, a uthorized distributors, and authorized Systems Integrators loc ated throughout the United States, plus Rockwell Automation representa tives in every major country in the world.

Local Product Support

Please contact your local Rockwell Automation representative for:
sales and order support
product technical training
warranty support
support service agreements

Technical Product Assistance

If you need to cont act us fo r tech n ical assis ta nce, pleas e rev iew th e product and troubleshooting information in this manual first.
When you do contact us, please have the catalog numbers of your products ready when you call so we c an provi de the qui ckest response for your situation.
Publication 2364P-5.01 December 1999
P-6
Publication 2364P-5.01 December 1999

Chapter 1

Theory of Operation

Introduction The parallel configuration, a DC bus supply front-end with

regenerative c apability, is used to supply DC power for AC digital drive inverter unit s in a common bus drive syste m. Twenty-three different parallel configurations provide a spectrum of different supply and regenerative capabilities.
Figure 1.1 Parallel Configuration
3-Phase
AC Line
NRU
RGU RGU
DC Supply for
Drive Lineup
DC
AC
Inverters
DC
AC
DC
AC
Publication 2364P-5.01 December 1999
1-2 Theory of Operation
Parallel configur ations use the following front-end units:
Regenerative DC Bus Supply Unit ( RGU)
Non-Regenerative DC Bus Supply Unit (NRU)
Each parallel config uration will include one, two, or three Regenerative DC Bus Supply Units (RGUs). The se units are used to supply motoring current to the DC bus, and are used to regenerate current back onto the AC line.
Most of the parallel configur ations will also include a Non-Regenerative DC Bus Supply Unit (NRU) to supply the motoring current to the DC bus.
Note: When there is an NRU in the configuration, the NRU supplies motoring curr ent while the RGUs regenerate most of the excess capacity (the RGU also cont ributes 10% of its rated motoring current to the DC bus).
Figure 1.2 NRU and RGU Operation
NRU//RGU Configuration
3-Phase
AC Line
RGU//RGU Configuration
3-Phase
AC Line
Motoring
Current
Motoring
Current
NRU RGU
RGU
Regenerating
Current
10%
Motoring
Current
Motoring
Current
RGU
Regenerating
Current
DC Supply for Drive Lineup
Regenerating
Current
DC Supply for Drive Lineup
Publication 2364P-5.01 December 1999

Parallel Configuration RGU//RGU Configurations

In an RGU//RGU configuration, each RGU supplies 100% motoring current and 100% regenerative curr ent. When operating, the master RGU evaluates the bus voltage and sends cur rent c ommands to the slave RGUs through an RGU-to-RGU (R2R) communicati on network. This allows the RGUs to operate together to supply the appropriate current while maintaining a constant voltage on the DC bus.
Figure 1.3 RGU//RGU Configuration
3-Phase
AC Line
RGU
RGU-to-RGU
Communications
Each RGU//RGU configuration has one master RGU in parallel with either one or two slave RGUs. Each slave RGU includes a common mode choke accommodate for minor switchi ng differences between the RGUs and to reduce c irculat ing cur rents bet ween the master RGU and the slave RGUs.
RGU RGU
Theory of Operation 1-3
DC Supply for
Drive Lineup
Master
3-Phase
AC Line
Figure 1.4 RGU//RGU Configuration–Master/Slave
Common Mode Choke
RGU RGU
R2R
Communication
Slave
DC Supply
for Drive
Lineup
Publication 2364P-5.01 December 1999
1-4 Theory of Operation
Output of RGU//RGU Configurations
In an RGU//RGU configuration, each RGU (when enabled) switches its IGBTs to maintain a constant voltage on the DC bus (which is typically 1.52 times the input voltage).
In this pr ocess, t he maste r R GU evaluat es the bu s vol tage and se nds a current com ma n d (whi ch is used t o corr ect the bu s voltag e ) to the slave RGUs. Each RGU switches its IGBTs to regulate the current (motoring or regenerative) needed to mainta in the bus voltage.
Figure 1.5 RGU//RGU Bus Voltage–Motoring or Regenerating
~1.52 x V AC
DC Bus Voltage
0 V DC
0%
% Load
100%
When the RGUs are not enabled, power is supplied through the free­wheeling diodes. The diode bridge produces a voltage of 1.35 tim es the input voltage with no load, and decre ases to 1.22 times the input voltage at full load. During this operation, the RGUs do not regulate the voltage or regenerat e any curr ent.
Figure 1.6 RGU//RGU Bus Voltage–Diode Bridge Operation (RGU Not Enabled)
1.35 x V AC
1.22 x V AC
DC Bus Voltage
0 V DC
0%
% Load
100%
Publication 2364P-5.01 December 1999
3-Phase
AC Line
Theory of Operation 1-5
NRU//RGU Configurations
In the NRU//RGU configura tion, the NRU is used to supply m otoring current to the DC bus, while the RGUs are used to regenerate current to the AC line.
When motoring, the NRU operates to supply its maximum motoring current to the DC bus, and the RGUs ope rate to supply 10% of their maximum motoring current to the DC bus. When regenerating, the NRUs diode bridge stops operating, and the RGUs regener ate the current back onto the AC line.
Figure 1.7 NRU//RGU Configuration
NRU
RGU RGU
RGU-to-RGU
Communications
DC Supply for
Drive Lineup
The NRU supplies motoring c urrent through its diode bridge, and the RGU supplies motoring and regenerative current through its power structure.
Figure 1.8 Line Waveform–NRU//RGU Configuration
Line Voltage
Line Current
Publication 2364P-5.01 December 1999
1-6 Theory of Operation
In the NRU//RGU configuration, the NRU has chokes on the DC bus. These chokes reduce cir culating c urrent between the RGU and NRU. If a slave RGU is in the configuration, the slave RGU will have a common mode choke installed on its AC line.
Figure 1.9 NRU//RGU Configuration–Basic Components
Pow er Structure
(w ith IG BTs)
3-Phase
AC Line
NRU RGU
Diode Bridge
DC Supply
for Drive
Lineup
Chokes
The RGU evaluates the bus vo ltage and adjusts it s cu rrent to mai ntain the nominal bus voltage. If there are two RGUs in the configuration, the master RGU eva luates the vol tage and sends cur rent commands to the slave RGU, and both RGUs will switch their IGBTs to regulate the necessary current on the DC bus.
Publication 2364P-5.01 December 1999
Theory of Operation 1-7
Output of NRU//RGU Configurations
The RGUs supply up to 10% of their rated amperes as motoring current. In this first 10%, the RGUs will regula te the voltage to 1.52 times the line voltage, the voltage on the DC bus will be greater than the AC line, and the diodes in the NRU will not conduct.
Figure 1.10 RGU Motoring–Load Up To 10% of RGU Rating
3-Phase
AC Line
smaller voltage
No
Current
v
RGUNRU
Current
(Up to 1 0% of the
RGU rating)
greater voltage
V
1.52 x AC Line Voltage
When the load increases beyond the fir st 10%, the RGU is no longe r able to regu late the voltage (since the current limit is set to 10%), a nd the bus voltage drops to a level where the diode s in the NRU can conduct. The NRU then supplies the motoring current for the remainder of the load, resulting in a bus voltage of 1.35 times the line voltage.
Figure 1.11 RGU and NRU Motoring–Load Over 10% of RGU Rating
3-Phase
AC Line
Current
V
RGUNRU
v
Current (10% of th e RGU rating)
1.35 x AC Line Voltage
When the load drops under the 10% capabilit y of the RGUs, the RGUs will begin to regulate the bus voltage again to 1.52 times the line voltage, and the diodes in the NRU will stop c onducting.
Publication 2364P-5.01 December 1999
1-8 Theory of Operation
The diagram below shows the NRU//RGU motoring bus voltage. The RGUs regulate the bus voltage for the first 10% of the rated current for the RGUs, then the NR Us su ppl y cu rren t fo r the rem ai nd er o f the load (while the RGU current is limited to 10% of the RGU rating).
Figure 1.12 NRU//RGU Bus Voltage–Motoring
1.52 x V AC
1.35 x V AC
DC Bus Voltage
0 V DC
0%
10%
(of RGU rating)
% Load
100% (Total NRU rating + 10% of RGU rating)
When the load is under 10% of the maximum motoring current, the RGUs can regulate (or maintain) the bus voltage. The RGU (master RGU) will evaluate the voltage on the bus, and will calculate the current needed to maintai n the bus voltage. If a regenerative current is needed to m aintain the voltage, the RGUs will begin switching their IGBTs to regenerate current onto the AC line. The diodes in the NRU will still not conduct current.
Figure 1.13 RGU Regenerating
3-Phase
AC Line
No
Current
v
RGUNRU
V
Current
(Up to 100% of the
RGU rating)
1.52 x AC Line Voltage
Publication 2364P-5.01 December 1999
Theory of Operation 1-9
The diagram below shows the NRU//RGU regenerative bus volta ge. The RGUs regenerate up to 100% of their rated curre nt to the AC line while the NRU diode bridge stops conduct ing.
Figure 1.14 NRU//RGU Bus Voltage–Regenerating
1.52 x V AC
DC Bus Voltage
0 V DC
0%
% Load
100%
When the RGUs are not enabled, only the NRU supplies current to the DC bus. The bus voltage is 1. 35 times the line voltage at no load, and decreases to 1.22 times the line voltage at full load. During this operation, the RGUs do not regulate the voltage or regenerate any current.
Figure 1.15 NRU//RGU Bus Voltage–RGUs Not Enabled
1.35 x V AC
1.22 x V AC
DC Bus Voltage
0 V DC
0%
% Load
100%
Publication 2364P-5.01 December 1999
1-10 Theory of Operation
Motoring - Up to 10% of RGU Rated Amperes
3-Phase
AC Line
If there are two RGUs in the configuration, each RGU will supply up to 10% of its rated motoring current . If the load is in this 10%, the RGUs will regula te the bus voltage. The master RGU will evaluate the bus voltage, and will determine the current required to maintai n the nominal bus voltage (1.52 times the line voltage). The master RGU will send a current command to the slave RGU, and both R GUs will begin switching their IGBTs to provide the proper motoring or regenerative current.
Figure 1.16 NRU With Two RGUs–Motoring
v
No
Current
NRU
V
Current
(Up to 10% of
RGU rated
amperes)
RGU RGU
RGU-to-RGU
Communications
Current (Up to 10% of the RGU rated
amperes)
1.52 x AC Line Voltage
Motoring - Over 10% of RGU Rated Amperes
3-Phase
AC Line
Current
(Up to 100% of
the NRU rated
amperes)
V
NRU
v
Figure 1.17 NRU With Two RGUs–Regenerating
3-Phase
AC Line
No
Current
v
NRU
V
Current
(10% of RGU rated amperes )
Current
(Up to 100% of RGU rated
amperes)
RGU RGU
RGU-to-RGU
Communications
RGU RGU
RGU-to-RGU
Communications
Current
(10% of the
RGU rated
amperes)
1.35 x AC Line
Current
(Up to 100% of
the RGU rated
amperes)
1.52 x AC Line
Voltage
Voltage
Publication 2364P-5.01 December 1999
Theory of Operation 1-11
Precharge Operation
When the disconnects are closed and the start switch is turned on, each RGU in the parallel configuration will begin its precharge routine. This routine charges the capacitors on the DC bus (the RGU capacitor bank and inverter capacitors) in a controlled fashion.
T wo contactors (M1 and M2) are used to perform the precharge operation in the K, L, a nd M-code RGUs (the N-code RGU precharge circuit is slightly different).
When the disconnect ( MCP1 or CB1) is closed and the start switch is turned on, the main contactor (M1) remains open, the precharge contactor (M2) closes, and c urrent begins to flow through the precharge circuit (bypassing the main 3-phase circuit). This precharge circuit (which has a resistive load) charges up the capacitor bank. As the bank approaches capacity, the main contactor (M1) closes, the precharge contactor (M2) opens, the NRU circuit breaker closes, and normal operation begins.
Circuit Breaker or
MCP
(CB1 or MCP1)
Precharge
Contactor
(M2)
Main
Contactor
(M1)
Figure 1.18 Precharge Circuit
Precharge Circuit
R
Note:
The precharge circuitry is slightly different in the N-code RGU. See the product schematics for further details.
Publication 2364P-5.01 December 1999
1-12 Theory of Operation
The RGUs will precharge the capa citors on the bus until the bus voltage rises to be equal to the lin e volt age. Then, the precharge circuit will open, the main circuit will close, the NRU circuit breake r will close, and the DC bus voltage will rise to 1.35 times the line voltage.
ATTENTION: If there is too much capacitance on the DC bus, the RGUs may not be able to raise the bus
!
voltage to the threshold f or normal operation, resul ting in damage to equipment.
Figure 1.19 Precharge Voltage
1.35 x V AC
DC Bus Voltage
1 x V AC
0 V DC
0 sec
Precharging
Time
Normal Diode-Bridge
Operation
Unable to Precharge
(Too many inv erters)
t
Publication 2364P-5.01 December 1999

Chapter 2

R1 and S1-Code Parallel Configurations

R1-Code Parallel Configuration The R1-code parallel configur ation is a common DC bus front-end
unit consisting of an D-code NRU in parall el with a K-code RGU.
Figure 2.1 R1-Code Parallel Configuration–Information

R1-code Parallel ConfigurationR1-code Ratings

Input Voltage
(V AC)
380 1520 460 575
DC Bus Current
(A DC)
1520 1520
Rated DC Bus
kW
780 944
1180
D-code
NRU
K-code RGU
S1-Code Parallel Configuration The S1-code parallel configuration is a common DC bus front-end
unit consisting of an E-code NRU in parallel with a K-code RGU.
Figure 2.2 S1-Code Parallel Configuration–Information

S1-code Parallel ConfigurationS1-code Ratings

Input Voltage
(V AC)
380 2020 460 575
DC Bus Current
(A DC)
2020 2020
Rated DC Bus
kW
1036 1254 1568
E-code
NRU
K-code RGU
Note: Information for the D-code NRU and E-code NRU can be found in publication 2364E-5.01. Information for the K-code RGU can be found in publication 2364F-5.01.
Publication 2364P-5.01 December 1999
2-2 R1 and S1-Code Parallel Configurations

Component Layout Figure 2.3

Enclosure Layout
Front View
Shipping Split
101.25"
91.5"
Cutaway View
30" 30" 25" 25" 20"
Customer Supplied
AC Input Lines
Publication 2364P-5.01 December 1999
Feeder D-code NRU (1500A) K-code RGU
Figure 2.4 Overhead Bus Assembly
Feeder
Splice Kit
R1 and S1-Code Parallel Configurations 2-3
30" Overhead Bus Assembly
End Cap
4" Bus Tabs
To Feeder Buswork
To NRU circuit breaker
Flex Bus
Drop Tabs
New and Revised NRU and RGU Components in the R1 and S1 Configurations
NRU
RGU
CB1 2000A, RD-frame with motor operator, aux contact (2NO/2NC) EA10 F4, F6
Control power filter, 4kHz Primary fuse for 5kVA control transformer
Primary fuse for 10kVA control transformer (Opt 6P)
25A, KLDR (for 380V AC input)
30A, KLDR (for 460V AC input)
25A, KLDR (for 575V AC input)
PT1 TB10
CR4 F4, F6
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input) Control power transformer, 5kVA Control terminal block, 30A, 600V
Precharge Lockout Relay (2NO/2NC) Primary fuse for 2kVA transformer
Control power transformer, 10kVA (Opt 6P)
10A, KLDR (for 380V AC input) 9A, KLDR (for 460V AC input) 8A, KLDR (for 575V AC input)
F21, F22 DC bus fuses, 250A, 700V, 170M F25 PT1 TR1
TB4
Fuse, NRU CB1 motor operator, 10A, KLDR Control power transformer, 2kVA Timer relay (3NO/1NC)
Control Terminal block, 30A, 600V
35A, KLDR (for 380V AC input)
The RGU AC line is connected to the bus stubs on the NRU circuit breaker
Overhead bus assembly
Publication 2364P-5.01 December 1999
2-4 R1 and S1-Code Parallel Configurations
Schematics Figure 2.5

Schematics

NRU
TB1-1
Optional Remote Interlock
(JMPR)
TB1-2
Airflow Loss
Bridge Bay
1
EA5-CR
CB Bay
Overtemp
SP4
EA3
Line RC Suppressor
Com
L1
L2
L3
SP1
F14 F15 F16
SP2
PE
SP3
4KHZ Control Power Filter
EA10
F4
F8
F7
(X1)
460VAC
115VAC
PT1
(X2)
MTR1
Rect. Bridge
MTR2
Choke Comp.
MTR3
CB Bay
CR2
Right
Choke
Overtemp
CH11-TG
CR1
Airflow Loss
3
CB Bay
13
EA6-CR
Heatsink
Overtemp
Left
Heatsink
Overtemp
F6
PE
TB1-9
TB1-10
Publication 2364P-5.01 December 1999
S3
Phase Loss
TB1-3
S1
To Ground Fault Detector
B
and Airflow Sensors
CR1
TB1-4 TB1-5 TB1-6
S2
Fault
CR2
Fault
PL2
A
Not
Faulted
1
L
­C A V
0
2
1
115VAC
Control Bus To
Inverter Units
N
­C A V
0
2
1
R1 and S1-Code Parallel Configurations 2-5
Customer Supplied
3-phase Input
-Bus
Heat Sink
D1
D3
CT1
F1 F2 F3
M
CB1- NRU
Note:
Control power for this motorized breaker originates in the RGU. Do not operate this breaker manually.
AC Line Current
AM1
F11
F12
F13
Heat Sink
D2
D4
A
B
CR
C
+Bus
A
To RGU
AC Input
CR1
Phase
Loss
Relay
B
From NRU
Control Power
B
From NRU
Control Power
7
115VAC
ACN-ACL +
ACG
To Grounding
9
PS1
Resistor
Input
624
TB1-8
TB1-7
1012
Ground Fault
Detector
VM2
J2
3
To Cust omer
Monitoring Device
EA5
J2
In15
Sig 1
In26
+5 2
Com 3
J11
S5
Y R B
Flow
Sensor
D5
EA4
Bridge Suppressor
EA2
Bus Indicator PCB
+Bus
-Bus
(X4)
CH11 CH11
(X3)
DC Horizontal Bus To
LED1 LED2
VM1
DC Bus Voltage
Inverter Units
D6HS1 HS2
DC Bus Energized
R
PL1
(X1)
(X2)
Publication 2364P-5.01 December 1999
2-6 R1 and S1-Code Parallel Configurations
Figure 2.6 Schematics (cont.)
RGU
D
To
CB1-NRU
circuitry
TB1-1
Optional
Remote
Interlock
(JMPR)
RGU/DC Bus
Supply
Off On
S12
TB1-2
TR1
CR4
TR1
From
A
3-phase AC Input
CB1-RGU
4KHZ Control Power Filter
EA10
SP4
SP1
SP2
PE
SP3
F4
460VAC
F7
(X1)
115VAC
(X2)
F25
RGU Uni t Not
Faulted
14
TB6 TB6
Isolat i on Boa rd
F6
PT1
MTR1
RGU Door Fan
MTR2
RGU Door Fan
CR2
Fault
PL2
A
Not
Faulted
PE
TB1-9
TB1-10
Fault
C
To RGU Input
Fuses
CR2
TB1
TR1
Precharge
11
CR4
12
TB1
CR3
CR4
Timer
M2
Precharge
(20 sec)
TB1-5 TB1-6
Avail able f o r
Customer Use
6
TB6
CR3
Publication 2364P-5.01 December 1999
Bus Control
Isolation Board
CR3
CR4
M1
TB6
TB4-4
9
TB10-7
E
CB1-NRU-A
To RGU
Control
Circuitry
TB10-8
TB4-5
CR3
Pilot
CR4
Precharge
Lockout
M1
Main
External M ain
Enable
F
Isolation Board
To RGU
D
Control Power
From RGU
R1 and S1-Code Parallel Configurations 2-7
TB4-8
CB1-NRU
PE
TR1
CR3
TR1
Spring Windup
Wht/Red
TB4-6
TB10-1
Blu
TB4-9
TB10-3
TB4-7 TB10-4
TB4-3
TB10-5
TB10-7
TB4--4 TB4-5
Blk
Red
Blk
LS
X
Y
Y
Y X
X
LS
M
Y
X
CB1-NRU-A
CB1-NRU-B
Blk
TB10-10
CB1-NRU-A
CB1-NRU-B
TB4-1
Not
Used
TB4-2
Open
Motor
Close
UVR
TB10-2
Wht
TB10-6
Red
TB10-8
Blu
TB10-9
Red
TB10-11
Blu
TB10-12
Publication 2364P-5.01 December 1999
2-8 R1 and S1-Code Parallel Configurations
Figure 2.7 Schematics (cont.)
B
From RGU
AC Line
From RGU
Control
Circuitry
AC Rtn
R10
F2
R11
F3
F4
R12
CT1
F17 F18 F19
Bridge
Fan
Rs Ss Ts
0
6
2
2
1
1
-
-
-
1
1
1
J
J
J
CT3
To
PE
Gnd
J7
P1
1
6
-
-
1
1
J
J
M2
CH11
F1
M1
F2
F3
From RGU
E
Control Power
CH1 CH2 CH3
Isolation Board
TB5
1
Fault
F
Reset
S11
Enable
2
Fault Reset
3
External Main
4
Common
SW1 Settings
115VAC
OffX
24VDCOn
For TB5-1, -2, -3
Burden Resistors
1
TB1
Publication 2364P-5.01 December 1999
To RGU
Control
Circuitry
To RGU
Control
Circuitry
TB6
1
3
4
6
8
9
Aux Control Fault
Bus Control
TB2
TB3
3
1
TB2 Resistor Not Required
3
1
3
J2
R1 and S1-Code Parallel Configurations 2-9
d
r
a
o B r
e
b
b
u
n S
To System Network
UP
C1
G
E1
UN
C1
G
E1
J7
Main Bus
DC-DC
Converter
TP3
-t
J6
Bridge Thermal
Sensor (NTC)
J12
Gate Drivers
TP5
-15V+24V +15V
Shd
(+)
Horizontal
DC Bus
(-)
F1
G
G
24V
DC-DC
Aux 24V
J10
WP
C1
E1
Cap
Bank
WN
C1
E1
J10
+15V
-15V +5V +12V
-12V
J1
J3
J7
d
r
a
o B
G
r
e
b
E1
b
u
n S
VN
C1
G
E1
J8
F1
d
r
a
o
B
r
e
b
b
u
n
S
Gate Driver Board
+24V
VP
C1
Converter
TP8TP4TP6
TP9
+12V+5V -12V
Main Control Bo a rd
J2
RIO Adapter Option
1
1203-GM1
2 3
Y
R
YY
SW1
SW2
J4
Blu
1
SW3
Shd
Clr
2
Off On
Off On
Off On
J1 J8 J9
2
Power
B T
Supply
Filter
1
Board
B T
J11
TB7
P13
TB4
TB1
+
-
PE
TE
2 1
1 2
1 2 3 4 5 6 7 8 9
10
+Bus
-Bus
+
-
- Analog In 1 + Analog In 1 Analog In 1 Common
- Analog In 2 + Analog In 2 Analog In 2 Common Analog Out 1 Analog Out 1 Common Analog Out 2 Analog Out 2 Common
Horizontal DC Bus
To Inve rter Units
EA2
Bus Indicator Board
EA4
Bus Suppressor
LED1 LED2
PL1
R
DC Bus Energized
RIO Ext SCANport 1 SCANport 2 R2R Comm
Publication 2364P-5.01 December 1999
2-10 R1 and S1-Code Parallel Configurations
Publication 2364P-5.01 December 1999

Chapter 3

R2 and S2-Code Parallel Configurations

R2-Code Parallel Configuration The R2-code parallel configur ation is a common DC bus front-end
unit consisting of an D-code NRU in parall el with a L-code RGU.
Figure 3.1 R2-Code Parallel Configuration–Information

R2-code Parallel ConfigurationR2-code Ratings

Input Voltage
(V AC)
380 1536 460 575
DC Bus Current
(A DC)
1536 1533
Rated DC Bus
kW
788 954
1190
D-code
NRU
L-code RGU
S2-Code Parallel Configuration The S2-code parallel configuration is a common DC bus front-end
unit consisting of an E-code NRU in parallel with a L-code RGU.
Figure 3.2 S2-Code Parallel Configuration–Information

S2-code Parallel ConfigurationS2-code Ratings

Input Voltage
(V AC)
380 2036 460 575
DC Bus Current
(A DC)
2036 2033
Rated DC Bus
kW
1045 1265 1578
E-code
NRU
L-code RGU
Note: Information for the D-code NRU and E-code NRU can be found in publication 2364E-5.01. Information for the L-code RGU can be found in publication 2364F-5.01.
Publication 2364P-5.01 December 1999
3-2 R2 and S2-Code Parallel Configurations

Component Layout Figure 3.3

Enclosure Layout
Front View
Shipping Split
101.25"
91.5"
30" 30" 25" 30" 25"
Cutaway View
Note: The D-code NRU has only
one AC line fuse per phase.
Customer Supplied
AC Input Lines
Feeder D-code NRU (1500A) or E-code NRU (2000A) L-code RGU
Publication 2364P-5.01 December 1999
Figure 3.4 Overhead Bus Assembly
Feeder
Splice Kit
R2 and S2-Code Parallel Configurations 3-3
30" Overhead Bus Assembly
End Cap
4" Bus Tabs
To Feeder Buswork
To NRU circuit breaker
Flex Bus
Drop Tabs
New and Revised NRU and RGU Components in the R2 and S2 Configurations
NRU CB1 2000A, RD-frame with motor operator, aux contact (2NO/2NC)
RGU
EA10 F4, F6
PT1 TB10
CR4 F4, F6
F21, F22 DC bus fuses, 500A, 700V, 170M F25 PT1 TR1
TB4
Control power filter, 2kHz Primary fuse for 5kVA control transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input) Control power transformer, 5kVA Control terminal block, 30A, 600V
Precharge Lockout Relay (2NO/2NC) Primary fuse for 5kVA transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input)
Fuse, NRU CB1 motor operator, 10A, KLDR Control power transformer, 5kVA Timer relay (3NO/1NC)
Control Terminal block, 30A, 600V
Primary fuse for 10kVA control transformer (Opt 6P)
35A, KLDR (for 380V AC input)
30A, KLDR (for 460V AC input)
25A, KLDR (for 575V AC input)
Control power transformer, 10kVA (Opt 6P)
The RGU AC line is connected to the bus stubs on the NRU circuit breaker
Overhead bus assembly
Publication 2364P-5.01 December 1999
3-4 R2 and S2-Code Parallel Configurations
Schematics Figure 3.5

Schematics

NRU
TB1-1
Optional Remote Interlock
(JMPR)
TB1-2
Airflow Loss
Bridge Bay
1
EA5-CR
CB Bay
Overtemp
SP4
EA3
Line RC Suppressor
Com
L1
L2
L3
SP1
F14 F15 F16
SP2
PE
SP3
2KHZ Control Power Filter
EA10
F4
F8
F7
(X1)
460VAC
115VAC
PT1
(X2)
MTR1
Rect. Bridge
MTR2
Choke Comp.
MTR3
CB Bay
CR2
Right
Choke
Overtemp
CH11-TG
CR1
Airflow Loss
3
CB Bay
13
EA6-CR
Heatsink
Overtemp
Left
Heatsink
Overtemp
F6
PE
TB1-9
TB1-10
Publication 2364P-5.01 December 1999
S3
Phase Loss
TB1-3
S1
To Ground Fault Detector
B
and Airflow Sensors
CR1
TB1-4 TB1-5 TB1-6
S2
Fault
CR2
Fault
PL2
A
Not
Faulted
1
L
­C A V
0
2
1
115VAC
Control Bus To
Inverter Units
N
­C A V
0
2
1
R2 and S2-Code Parallel Configurations 3-5
Customer Supplied
3-phase Input
-Bus
Heat Sink
D1
D3
CT1
F1 F2 F3
M
CB1- NRU
Note:
Control power for this motorized breaker originates in the RGU. Do not operate this breaker manually.
AC Line Current
AM1
F11
F12
F13
Heat Sink
D2
D4
A
B
CR
C
+Bus
A
To RGU
AC Input
CR1
Phase
Loss
Relay
B
From NRU
Control Power
B
From NRU
Control Power
7
115VAC
ACN-ACL +
ACG
To Grounding
9
PS1
Resistor
Input
624
TB1-8
TB1-7
1012
Ground Fault
Detector
VM2
J2
3
To Cust omer
Monitoring Device
EA5
J2
In15
Sig 1
In26
+5 2
Com 3
J11
S5
Y R B
Flow
Sensor
D5
EA4
Bridge Suppressor
EA2
Bus Indicator PCB
+Bus
-Bus
(X4)
CH11 CH11
(X3)
DC Horizontal Bus To
LED1 LED2
VM1
DC Bus Voltage
Inverter Units
D6HS1 HS2
DC Bus Energized
R
PL1
(X1)
(X2)
Publication 2364P-5.01 December 1999
3-6 R2 and S2-Code Parallel Configurations
Figure 3.6 Schematics (cont.)
RGU
D
To
CB1-NRU
circuitry
TB1-1
Optional
Remote
Interlock
(JMPR)
RGU/DC Bus
Supply
Off On
S12
TB1-2
TR1
CR4
TR1
From
A
3-phase AC Input
CB1-RGU
2KHZ Control Power Filter
EA10
SP4
SP1
SP2
PE
SP3
F4
460VAC
F7
(X1)
115VAC
(X2)
F25
RGU Uni t Not
Faulted
14
TB6 TB6
Isolat i on Boa rd
F6
PT1
MTR1,2
Bay Door Fans
MTR3,4
Bay 1 Door Fans
CR2
Fault
PL2
A
Not
Faulted
PE
TB1-9
TB1-10
Fault
C
To RGU Input
Fuses
CR2
TB1
TR1
Precharge
11
CR4
12
TB1
CR3
CR4
Timer
M2
Precharge
(20 sec)
TB1-5 TB1-6
Avail able f o r
Customer Use
6
TB6
CR3
Publication 2364P-5.01 December 1999
Bus Control
Isolation Board
CR3
CR4
M1
TB6
TB4-4
9
E
CB1-NRU-A
TB10-7 TB10-8
To RGU
Control
Circuitry
TB4-5
CR3
Pilot
CR4
Precharge
Lockout
M1
Main
External M ain
Enable
F
Isolation Board
To RGU
D
Control Power
From RGU
R2 and S2-Code Parallel Configurations 3-7
TB4-8
CB1-NRU
PE
TR1
CR3
TR1
Spring Windup
Wht/Red
TB4-6
TB10-1
Blu
TB4-9
TB10-3
TB4-7 TB10-4
TB4-3
TB10-5
TB4-4 TB4-5
TB10-7
Blk
Red
Blk
LS
X
Y
Y
Y X
X
LS
M
Y
X
CB1-NRU-A
CB1-NRU-B
Blk
TB10-10
CB1-NRU-A
CB1-NRU-B
TB4-1
Not
Used
TB4-2
Open
Motor
Close
UVR
TB10-2
Wht
TB10-6
Red
TB10-8
Blu
TB10-9
Red
TB10-11
Blu
TB10-12
Publication 2364P-5.01 December 1999
3-8 R2 and S2-Code Parallel Configurations
Figure 3.7 Schematics (cont.)
B
From RGU
AC Line
From RGU
Control
Circuitry
AC Rtn
R10
F2
R11
F3
F4
R12
CT1
F17 F18 F19
Bridge
Fan
Rs Ss Ts
0
6
2
2
1
1
-
-
-
1
1
1
J
J
J
CT3
To
PE
Gnd
J7
P1
1
6
-
-
1
1
J
J
M2
F1
M1
F2
F3
From RGU
E
Control Power
CH1 CH2 CH3
CH11
Isolation Board
TB5
1
Fault
F
Reset
S11
Enable
2
Fault Reset
3
External Main
4
Common
SW1 Settings
115VAC
OffX
24VDCOn
For TB5-1, -2, -3
Burden Resistors
1
TB1
Publication 2364P-5.01 December 1999
To RGU
Control
Circuitry
To RGU
Control
Circuitry
TB6
1
3
4
6
8
9
Aux Control Fault
Bus Control
TB2
TB3
3
1
TB2 Resisto r Not Required
3
1
3
J2
R2 and S2-Code Parallel Configurations 3-9
e
c
e
a
t
f
a
r
e
G
t
n
I
e
c
e
a
t
f
r
a
e
G
t
n
I
To System Network
C1
G
E1
C1
G
E1
J7
Main Bus
DC-DC
Converter
TP3
-t
J6
Bridge Thermal
Sensor (NTC)
J12
UP
DETAIL
UN
Gate Drivers
TP5
-15V+24V +15V
Shd
(+)
Horizontal
DC Bus
(-)
F1
See U
r
Phase
e
b
b
Detail
u
n S
VP
See U Phase Detail
VN
J8
F1
J2
J4
Blu
1
Shd
Clr
2
TP8TP4TP6
TP9
+12V+5V -12V
RIO Adapter Option
1 2 3
SW1
SW2
SW3
+24V
1203-GM1
R
J1 J8 J9
See U
r
Phase
e
b
b
Detail
u
n S
WP
See U Phase
Detail
WN
Gate Driver Board
24V
DC-DC
Converter
Aux 24V
Main Control Bo a rd
Y
YY
Off On
Off On
Off On
J10
r
e
b
b
u
n S
Cap
Bank
J10
+15V
-15V +5V +12V
-12V
J1
J3
J7
2
Power
B T
Supply
Filter
1
Board
B T
J11
TB7
P13
TB4
TB1
+
-
PE
TE
2 1
1 2
1 2 3 4 5 6 7 8 9
10
+Bus
-Bus
+
-
- Analog In 1 + Analog In 1 Analog In 1 Common
- Analog In 2 + Analog In 2 Analog In 2 Common Analog Out 1 Analog Out 1 Common Analog Out 2 Analog Out 2 Common
Horizontal DC Bus
To Inve rter Units
EA2
Bus Indicator Board
EA4
Bus Suppressor
LED1 LED2
PL1
R
DC Bus Energized
RIO Ext SCANport 1 SCANport 2 R2R Comm
Publication 2364P-5.01 December 1999
3-10 R2 and S2-Code Parallel Configurations
Publication 2364P-5.01 December 1999

Chapter 4

R3 and S3-Code Parallel Configurations

R3-Code Parallel Configuration The R3-code parallel configur ation is a common DC bus front-end
unit consisting of an D-code NRU in parall el with an M-code RGU.
Figure 4.1 R3-Code Parallel Configuration–Information

R3-code Parallel ConfigurationR3-code Ratings

Input Voltage
(V AC)
380 1575 460 575
DC Bus Current
(A DC)
1575 1569
Rated DC Bus
kW
808 978
1218
D-code
NRU
M-code RGU
S3-Code Parallel Configuration The S3-code parallel configuration is a common DC bus front-end
unit consisting of an E-code NRU in parallel with an M-code RGU.
Figure 4.2 S3-Code Parallel Configuration–Information

S3-code Parallel ConfigurationS3-code Ratings

Input Voltage
(V AC)
380 2075 460 575
DC Bus Current
(A DC)
2075 2069
Rated DC Bus
kW
1064 1289 1606
E-code
NRU
M-code RGU
Note: Information for the D-code NRU and E-code NRU can be found in publication 2364E-5.01. Information for the M-code RGU can be found in publication 2364F-5.01.
Publication 2364P-5.01 December 1999
4-2 R3 and S3-Code Parallel Configurations

Component Layout Figure 4.3

Enclosure Layout
Front View
Shipping Split
101.25"
91.5"
30" 30" 25" 35" 35"
Cutaway View
Note:
The D-code NRU has only one AC line fuse per phase.
Customer Supplied
AC Input Lines
Feeder D-code NRU (1500A) or E-code NRU (2000A) M-code RGU
Publication 2364P-5.01 December 1999
R3 and S3-Code Parallel Configurations 4-3
Figure 4.4 Overhead Bus Assembly
Feeder
Splice Kit
To Feeder Buswork
30" Overhead Bus Assembly
4" Bus Tabs
Flex Bus
Drop Tabs
To NRU circuit breaker
25" Overhead
Bus Assembly
Joiner-Splice Kits
New and Revised NRU and RGU Components in the R3 and S3 Configurations
NRU CB1 2000A, RD-frame with motor operator, aux contact (2NO/2NC)
EA10 F4, F6
PT1 TB10
Control power filter, 2kHz Primary fuse for 5kVA control transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input) Control power transformer, 5kVA Control terminal block, 30A, 600V
35" Overhead Bus Assembly
End
Cap
2" Bus Tabs
Flex Bus
Drop Tabs
To RGU circuit breaker
Primary fuse for 10kVA control transformer (Opt 6P)
35A, KLDR (for 380V AC input)
30A, KLDR (for 460V AC input)
25A, KLDR (for 575V AC input)
Control power transformer, 10kVA (Opt 6P)
RGU
CR4 F4, F6
Precharge Lockout Relay (2NO/2NC) Primary fuse for 5kVA transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input)
F21, F22 DC bus fuses, 500A, 700V, 170M 21A, 22A
F25 PT1 TR1
TB4
Fuse, NRU CB1 motor operator, 10A, KLDR Control power transformer, 5kVA Timer relay (3NO/1NC)
Control Terminal block, 30A, 600V
Overhead bus assembly
Publication 2364P-5.01 December 1999
4-4 R3 and S3-Code Parallel Configurations
Schematics Figure 4.5

Schematics

NRU
TB1-1
Optional Remote Interlock
(JMPR)
TB1-2
Airflow Loss
Bridge Bay
1
EA5-CR
CB Bay
Overtemp
SP4
EA3
Line RC Suppressor
Com
L1
L2
L3
SP1
F14 F15 F16
SP2
PE
SP3
2KHZ Control Power Filter
EA10
F4
F8
F7
(X1)
460VAC
115VAC
PT1
(X2)
MTR1
Rect. Bridge
MTR2
Choke Comp.
MTR3
CB Bay
CR2
Right
Choke
Overtemp
CH11-TG
CR1
Airflow Loss
3
CB Bay
13
EA6-CR
Heatsink
Overtemp
Left
Heatsink
Overtemp
F6
PE
TB1-9
TB1-10
Publication 2364P-5.01 December 1999
S3
Phase Loss
TB1-3
S1
To Ground Fault Detector
B
and Airflow Sensors
CR1
TB1-4 TB1-5 TB1-6
S2
Fault
CR2
Fault
PL2
A
Not
Faulted
1
L
­C A V
0
2
1
115VAC
Control Bus To
Inverter Units
N
­C A V
0
2
1
R3 and S3-Code Parallel Configurations 4-5
Customer Supplied
3-phase Input
-Bus
Heat Sink
D1
D3
CT1
F1 F2 F3
M
CB1- NRU
Note:
Control power for this motorized breaker originates in the RGU. Do not operate this breaker manually.
AC Line Current
AM1
F11
F12
F13
Heat Sink
D2
D4
A
B
CR
C
+Bus
A
To RGU
AC Input
CR1
Phase
Loss
Relay
B
From NRU
Control Power
B
From NRU
Control Power
7
115VAC
ACN-ACL +
ACG
To Grounding
9
PS1
Resistor
Input
624
TB1-8
TB1-7
1012
Ground Fault
Detector
VM2
J2
3
To Cust omer
Monitoring Device
EA5
J2
In15
Sig 1
In26
+5 2
Com 3
J11
S5
Y R B
Flow
Sensor
D5
EA4
Bridge Suppressor
EA2
Bus Indicator PCB
+Bus
-Bus
(X4)
CH11 CH11
(X3)
DC Horizontal Bus To
LED1 LED2
VM1
DC Bus Voltage
Inverter Units
D6HS1 HS2
DC Bus Energized
R
PL1
(X1)
(X2)
Publication 2364P-5.01 December 1999
4-6 R3 and S3-Code Parallel Configurations
Figure 4.6 Schematics (cont.)
RGU
D
To
CB1-NRU
circuitry
TB1-1
Optional
Remote
Interlock
(JMPR)
RGU/DC Bus
Supply
Off On
S12
TB1-2
TR1
F7
Choke
Thermoguards
S1 - 3
CR4
TR1
EA10
F25
11
TB1
CR4
CR4
2KHZ Control Power Filter
460VAC
(X1)
115VAC
RGU Uni t Not
Faulted
14
TB6 TB6
Isolat i on Boa rd
12
TB1
CR3
SP4
PE
PT1
(X2)
Bay 1 Door Fan
Bay 1 Internal Fan
RGU Door Fans
Precharge
Precharge
F4
F6
MTR2
MTR3
MTR1
CR2
Fault
PL2
A
Not
Faulted
TR1
Timer
M2
SP1
SP2
SP3
PE
TB1-9
TB1-10
(20 sec)
From 3-phase AC Input
A
Fault
CR2
TB1-5 TB1-6
Avail able f o r
Customer Use
CB1-RGU
C
To RGU Input
Fuses
6
TB6
CR3
Publication 2364P-5.01 December 1999
Bus Control
Isolation Board
CR3
CR4
M1
TB6
TB4-4
9
E
CB1-NRU-A
TB10-7 TB10-8
To RGU
Control
Circuitry
TB4-5
CR3
Pilot
CR4
Precharge
Lockout
M1
Main
External Main
Enable
F
Isolation Board
To RGU
D
From RGU
Control Power
R3 and S3-Code Parallel Configurations 4-7
TB4-8
CB1-NRU
PE
TR1
CR3
TR1
Spring Windup
Wht/Red
TB4-6
TB10-1
Blu
TB4-9
TB10-3
TB4-7 TB10-4
TB4-3
TB10-5
TB10-7
TB4-4 TB4-5
Blk
Red
Blk
LS
X
Y
Y
Y
X
X
LS
M
Y
X
CB1-NRU-A
CB1-NRU-B
Blk
TB10-10
CB1-NRU-A
CB1-NRU-B
TB4-1
Not
Used
TB4-2
Open
Motor
Close
UVR
TB10-2
Wht
TB10-6
Red
TB10-8
Blu
TB10-9
Red
TB10-11
Blu
TB10-12
Publication 2364P-5.01 December 1999
4-8 R3 and S3-Code Parallel Configurations
Figure 4.7 Schematics (cont.)
B
From RGU
AC Line
From RGU
Control
Circuitry
M2
F1
M1
F2
F3
From RGU
E
Control Power
Fault
F
Reset
CH1 CH2 CH3
S11
F2
F3
F4
AC Rtn
Isolation Board
TB5
1
Enable
2
Fault Reset
3
External Main
4
Common
R10, R10A
R11, R11A
R12, R12A
CH
F17 F18 F19
Bridge
Fan
CT1
CT2
Rs Ss Ts
0
6
2
2
1
1
-
-
-
1
1
1
J
J
J
SW1 Settings
For TB5-1, -2, -3
CT3
CT Power
Supply
CR
To
PE
Gnd
J7
P1
115VAC
OffX
24VDCOn
Burden Resistors
1
TB1
1
6
-
-
1
1
J
J
Publication 2364P-5.01 December 1999
To RGU
Control
Circuitry
To RGU
Control
Circuitry
TB6
1
3
4
6
8
9
Aux Control Fault
Bus Control
TB2
TB3
3
1
3
1
3
J2
R3 and S3-Code Parallel Configurations 4-9
e
c
e
a
t
f
a
r
e
G
t
n
I
e
c
e
a
t
f
r
a
e
G
t
n
I
To System Networ k
C1 G
E1
C1 G
E1
J7
Main Bus
DC-DC
Converter
TP3
-t
J6
Bridge Thermal
Sensor (NTC)
J12
UP1
DETAIL
UP2
C1
G
E1
UN1
UN2
C1
G
E1
Gate Drivers
TP5
(+)
Horizontal
DC Bus
(-)
+
See U
r
Phase
e
b
b
Detail
u
n S
VP1 VP2
See U Phase Detail
VN1 VN2
J8
F1
-15V+24V +15V
J2
J4
Blu
1
Shd
Shd
Clr
2
TP8TP4TP6
TP9
+12V+5V -12V
RIO Adapter Option
1 2 3
SW1
SW2
SW3
+24V
1203-GM1
R
J1 J8 J9
See U
r
Phase
e
b
b
Detail
u
n S
WP1 WP2
See U Phase
Detail
WN1 WN2
Gate Driver Board
24V
DC-DC
Converter
Aux 24V
Main Control Bo a rd
Y
YY
Off On
Off On
Off On
J10
r
e
b
b
u
n S
Cap
+15V
-15V +5V +12V
-12V
Bank
J10
J1
J3
J7
2
Power
B T
Supply
Filter
1
Board
B T
J11
TB7
P13
TB4
TB1
-
PE
TE
2 1
1 2
1 2 3 4 5 6 7 8 9
10
+Bus
-Bus
+
-
- Analog In 1 + Analog In 1 Analog In 1 Common
- Analog In 2 + Analog In 2 Analog In 2 Common Analog Out 1 Analog Out 1 Common Analog Out 2 Analog Out 2 Common
Horizontal DC Bus
To Inve rter Units
EA2
Bus Indicator Board
EA4
Bus Suppressor
LED1 LED2
PL1
R
DC Bus Energized
RIO Ext SCANport 1 SCANport 2 R2R Comm
Publication 2364P-5.01 December 1999
4-10 R3 and S3-Code Parallel Configurations
Publication 2364P-5.01 December 1999

Chapter 5

R4 and S4-Code Parallel Configurations

R4-Code Parallel Configuration The R4-code parallel configur ation is a common DC bus front-end
unit consisting of an D-code NRU in parall el with an N-code RGU.
Figure 5.1 R4-Code Parallel Configuration–Information

R4-code Parallel ConfigurationR4-code Ratings

Input Voltage
(V AC)
380 1600 460 575
DC Bus Current
(A DC)
1600 1591
Rated DC Bus
kW
821 994
1235
D-code
NRU
N-code RGU
S4-Code Parallel Configuration The S4-code parallel configuration is a common DC bus front-end
unit consisting of an E-code NRU in parallel with an N-code RGU.
Figure 5.2 S4-Code Parallel Configuration–Information

S4-code Parallel ConfigurationS4-code Ratings

Input Voltage
(V AC)
380 2100 460 575
DC Bus Current
(A DC)
2100 2091
Rated DC Bus
kW
1077 1304 1623
E-code
NRU
N-code RGU
Note: Information for the D-code NRU and E-code NRU can be found in publication 2364E-5.01. Information for the N-code RGU can be found in publication 2364F-5.01.
Publication 2364P-5.01 December 1999
5-2 R4 and S4-Code Parallel Configurations
9

Component Layout Figure 5.3

Enclosure Layout
Front View
101.25"
Shipping Split
Cutaway View
30" 30" 25" 35" 35"
Customer Supplied
AC Input Lines
20"
Feeder D-code NRU (1500A) or E-code NRU (2000A) N-code RGU
Publication 2364P-5.01 December 1999
R4 and S4-Code Parallel Configurations 5-3
20" Overhead
Figure 5.4 Overhead Bus Assembly
Feeder
Splice Kit
To Feeder Buswork
30" Overhead Bus Assembly
4" Bus Tabs
Flex Bus
Drop Tabs
To NRU circuit breaker
25" Overhead Bus Assembly
Bus Assembly
Joiner-Splice Kits
New and Revised NRU and RGU Components in the R4 and S4 Configurations
NRU CB1 2000A, RD-frame with motor operator, aux contact (2NO/2NC)
EA10 F4, F6
PT1 TB10
Control power filter, 2kHz Primary fuse for 5kVA control transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input) Control power transformer, 5kVA Control terminal block, 30A, 600V
Primary fuse for 10kVA control transformer (Opt 6P)
35A, KLDR (for 380V AC input)
30A, KLDR (for 460V AC input)
25A, KLDR (for 575V AC input)
Control power transformer, 10kVA (Opt 6P)
35" Overhead Bus Assembly
End Cap
2" Bus Tabs
Flex Bus
Drop Tabs
To RGU circuit breaker
RGU
CR3 Pilot Relay (2NO/2NC) with aux contact (1NO/1NC) CR4 F4, F6
Precharge Lockout Relay (2NO/2NC) Primary fuse for 5kVA transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input)
F21, F22
DC bus fuses, 500A, 700V, 170M
21A, 22A F25
PT1 TR1 TB4
Fuse, NRU CB1 motor operator, 10A, KLDR Control power transformer, 5kVA Timer relay (3NO/1NC)
Control Terminal block, 30A, 600V
Overhead bus assembly
Publication 2364P-5.01 December 1999
5-4 R4 and S4-Code Parallel Configurations
Schematics Figure 5.5

Schematics

NRU
TB1-1
Optional Remote Interlock
(JMPR)
TB1-2
Airflow Loss
Bridge Bay
1
EA5-CR
CB Bay
Overtemp
SP4
EA3
Line RC Suppressor
Com
L1
L2
L3
SP1
F14 F15 F16
SP2
PE
SP3
2KHZ Control Power Filter
EA10
F4
F8
F7
(X1)
460VAC
115VAC
PT1
(X2)
MTR1
Rect. Bridge
MTR2
Choke Comp.
MTR3
CB Bay
CR2
Right
Choke
Overtemp
CH11-TG
CR1
Airflow Loss
3
CB Bay
13
EA6-CR
Heatsink
Overtemp
Left
Heatsink
Overtemp
F6
PE
TB1-9
TB1-10
Publication 2364P-5.01 December 1999
S3
Phase Loss
TB1-3
S1
To Ground Fault Detector
B
and Airflow Sensors
CR1
TB1-4 TB1-5 TB1-6
S2
Fault
CR2
Fault
PL2
A
Not
Faulted
1
L
­C A V
0
2
1
115VAC
Control Bus To
Inverter Units
N
­C A V
0
2
1
R4 and S4-Code Parallel Configurations 5-5
Customer Supplied
3-phase Input
-Bus
Heat Sink
D1
D3
CT1
F1 F2 F3
M
CB1- NRU
Note:
Control power for this motorized breaker originates in the RGU. Do not operate this breaker manually.
AC Line Current
AM1
F11
F12
F13
Heat Sink
D2
D4
A
B
CR
C
+Bus
A
To RGU
AC Input
CR1
Phase
Loss
Relay
B
From NRU
Control Power
B
From NRU
Control Power
7
115VAC
ACN-ACL +
ACG
To Grounding
9
PS1
Resistor
Input
624
TB1-8
TB1-7
1012
Ground Fault
Detector
VM2
J2
3
To Cust omer
Monitoring Device
EA5
J2
In15
Sig 1
In26
+5 2
Com 3
J11
S5
Y R B
Flow
Sensor
D5
EA4
Bridge Suppressor
EA2
Bus Indicator PCB
+Bus
-Bus
(X4)
CH11 CH11
(X3)
DC Horizontal Bus To
LED1 LED2
VM1
DC Bus Voltage
Inverter Units
D6HS1 HS2
DC Bus Energized
R
PL1
(X1)
(X2)
Publication 2364P-5.01 December 1999
5-6 R4 and S4-Code Parallel Configurations
Figure 5.6 Schematics (cont.)
RGU
D
To
CB1-NRU
circuitry
TB1-1
Optional
Remote
Interlock
(JMPR)
RGU/DC Bus
Supply
Off On
S12
TB1-2
TR1
F7
Choke
Thermoguards
S1 - 3
CR4
TR1
EA10
F25
11
TB1
CR4
CR4
PE
2KHZ Control Power Filter
460VAC
(X1)
115VAC
F5
RGU Uni t Not
Faulted
14
TB6 TB6
Isolat i on Boa rd
12
TB1
CR3
SP4
(X2)
SP1
SP2
SP3
F4
F6
PT1
MTR6
Bay 1 Door Fan
MTR4,5
Bay 2 Fan
MTR1,2,3
RGU Door Fans
CR2
Fault
PL2
A
Not
Faulted
TR1
Precharge
Timer
M2
Precharge
TB1-9
TB1-10
(20 sec)
PE
From
3-phase
AC Input
A
G
To RGU
Precharge
Circuitry
TB1-5 TB1-6
CB1-RGU
CB2-RGU
Fault
CR2
Avail able for
Customer Use
C
To RGU Input
Fuses
6
TB6
CB1-RGU
TB3-7
CR3
CR3
Publication 2364P-5.01 December 1999
Bus Control
Isolation Board
CR3
CR4
TB3-8
TB3-7
TB3-10
9
TB6
TB4-4
CB1-RGU
E
CB1-NRU-A
TB10-7 TB10-8
UVR
To RGU
Control
Circuitry
TB4-5
TB3-8 TB3-9 TB3-11 TB3-12
CR3
Pilot
CR4
Precharge
Lockout
External Main
Enable
To RGU
F
Isolation Board
D
From RGU
Control Power
R4 and S4-Code Parallel Configurations 5-7
TB4-8
CB1-NRU
PE
TR1
CR3
TR1
Spring Windup
Wht/Red
TB4-6
TB10-1
Blu
TB4-9
TB10-3
TB4-7 TB10-4
TB4-3
TB10-5
TB10-7
TB4-4 TB4-5
Blk
Red
Blk
LS
X
Y
Y
Y
X
X
LS
M
Y
X
CB1-NRU-A
CB1-NRU-B
Blk
TB10-10
CB1-NRU-A
CB1-NRU-B
TB4-1
Not
Used
TB4-2
Open
Motor
Close
UVR
TB10-2
Wht
TB10-6
Red
TB10-8
Blu
TB10-9
Red
TB10-11
Blu
TB10-12
Publication 2364P-5.01 December 1999
5-8 R4 and S4-Code Parallel Configurations
Figure 5.7 Schematics (cont.)
G
From
RGU-CB1
B
From RGU
AC Line
From RGU
Control
Circuitry
M2
F1
M1
F2
F3
From RGU
E
Control Power
Fault
F
Reset
CH1 CH2 CH3
S11
F2
F3
F4
AC Rtn
Isolation Board
TB5
1
Enable
2
Fault Reset
3
External Main
4
Common
R10, R10A
R11, R11A
R12, R12A
CH
F17 F18 F19
Bridge
Fan
CT1
CT2
Rs Ss Ts
0
6
2
2
1
1
-
-
-
1
1
1
J
J
J
SW1 Settings
For TB5-1, -2, -3
CT3
CT Power
Supply
CR
To
PE
Gnd
J7
P1
115VAC
OffX
24VDCOn
Burden Resistors
1
TB1
1
6
-
-
1
1
J
J
Publication 2364P-5.01 December 1999
To RGU
Control
Circuitry
To RGU
Control
Circuitry
TB6
1
3
4
6
8
9
Aux Control Fault
Bus Control
TB2
TB3
3
1
3
1
3
J2
R4 and S4-Code Parallel Configurations 5-9
e
c
e
a
t
f
a
r
e
G
t
n
I
e
c
e
a
t
f
r
a
e
G
t
n
I
To System Networ k
C1
DETAIL
G
E1
C1 G
E1
J7
Main Bus
DC-DC
Converter
TP3
-t
J6
Bridge Thermal
Sensor (NTC)
J12
UP1
UP2
C1
G
E1
UN1
UN2
C1
G
E1
Gate Drivers
TP5
(+)
Horizontal
DC Bus
(-)
+
See U
r
Phase
e
b
b
Detail
u
n S
VP1 VP2
See U Phase Detail
VN1 VN2
J8
F1
-15V+24V +15V
J2
J4
Blu
1
Shd
Shd
Clr
2
TP8TP4TP6
TP9
+12V+5V -12V
RIO Adapter Option
1 2 3
SW1
SW2
SW3
+24V
1203-GM1
R
J1 J8 J9
See U
r
Phase
e
b
b
Detail
u
n S
WP1 WP2
See U Phase
Detail
WN1 WN2
Gate Driver Board
24V
DC-DC
Converter
Aux 24V
Main Control Bo a rd
Y
YY
Off On
Off On
Off On
J10
r
e
b
b
u
n S
Cap
+15V
-15V +5V +12V
-12V
Bank
J10
J1
J3
J7
2
Power
B T
Supply
Filter
1
Board
B T
J11
TB7
P13
TB4
TB1
-
PE
TE
2 1
1 2
1 2 3 4 5 6 7 8 9
10
+Bus
-Bus
+
-
- Analog In 1 + Analog In 1 Analog In 1 Common
- Analog In 2 + Analog In 2 Analog In 2 Common Analog Out 1 Analog Out 1 Common Analog Out 2 Analog Out 2 Common
Horizontal DC Bus
To Inve rter Units
EA2
Bus Indicator Board
EA4
Bus Suppressor
LED1 LED2
PL1
R
DC Bus Energized
RIO Ext SCANport 1 SCANport 2 R2R Comm
Publication 2364P-5.01 December 1999
5-10 R4 and S4-Code Parallel Configurations
Publication 2364P-5.01 December 1999

Chapter 6

T1 and V1-Code Parallel Configurations

T1-Code Parallel Configuration The T1-code paralle l configuration is a common DC bus front-end
unit consisting of an F-code NRU in paralle l with a K-code RGU.
Figure 6.1 T1-Code Parallel Configuration–Information

T1-code Parallel ConfigurationT1-code Ratings

Input Voltage
(V AC)
380 2520 460 575
DC Bus Current
(A DC)
2520 2520
Rated DC Bus
kW
1293 1565 1956
F-code
NRU
K-code RGU
V1-Code Parallel Configuration The V1-code parallel configuration is a common DC bus front-end
unit consisting of an G-code NRU in parall el with a K-code RGU.
Figure 6.2 V1-Code Parallel Configuration–Information

V1-code Parallel ConfigurationV1-code Ratings

Input Voltage
(V AC)
380 3000 460 575
DC Bus Current
(A DC)
3000 3000
Rated DC Bus
kW
1539 1863 2329
G-code
NRU
K-code RGU
Note: Information for the F-code NRU and G-code NRU can be found in publication 2364E-5.01. Information for the K-code RGU can be found in publication 2364F-5.01.
Publication 2364P-5.01 December 1999
6-2 T1 and V1-Code Parallel Configurations

Component Layout Figure 6.3

Enclosure Layout
Front View
Shipping Split
101.25"
91.5"
Cutaway View
30" 30" 35" 25" 20"
Customer Supplied
AC Input Lines
Feeder F-code (2500A) or G-code (3000A) NRU K-code RGU
Publication 2364P-5.01 December 1999
Figure 6.4 Overhead Bus Assembly
Feeder
Splice Kit
T1 and V1-Code Parallel Configurations 6-3
30" Overhead Bus Assembly
End Cap
4" Bus Tabs
To Feeder Buswork
To NRU circuit breaker
Flex Bus
Drop Tabs
New and Revised NRU and RGU Components in the T1 and V1 Configurations
NRU CB1 (T1 config) 2500A, SPB-frame with motor operator
(V1 config) 3000A, SPB-frame with motor operator
RGU
EA10 F4, F6
PT1 TB10
CR4 F4, F6
F21, F22 DC bus fuses, 250A, 700V, 170M F25 PT1
TR1 TB4
Control power filter, 4kHz Primary fuse for 5kVA control transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input)
Control power transformer, 5kVA Control terminal block, 30A, 600V
Precharge Lockout Relay (2NO/2NC) Primary fuse for 2kVA transformer
10A, KLDR (for 380V AC input) 9A, KLDR (for 460V AC input) 8A, KLDR (for 575V AC input)
Fuse, NRU CB1 motor operator, 10A, KLDR Control power transformer, 2kVA Timer relay (3NO/1NC)
Control Terminal block, 30A, 600V
Primary fuse for 10kVA control transformer (Opt 6P)
35A, KLDR (for 380V AC input)
30A, KLDR (for 460V AC input)
25A, KLDR (for 575V AC input)
Control power transformer, 10kVA (Opt 6P)
The RGU AC line is connected to the bus stubs on the NRU circuit breaker
Overhead bus assembly
Publication 2364P-5.01 December 1999
6-4 T1 and V1-Code Parallel Configurations
Schematics Figure 6.5

Schematics

NRU
TB1-1
Optional Remote Interlock
(JMPR)
TB1-2
Airflow Loss
Bridge Bay
1
EA5-CR
CB Bay
Overtemp
SP4
EA3
Line RC Suppressor
Com
L1
L2
L3
SP1
F14 F15 F16
SP2
PE
SP3
4KHZ Control Power Filter
EA10
F4
F8
F7
(X1)
460VAC
115VAC
PT1
(X2)
MTR1
Rect. Bridge
MTR2,3
Choke Comp.
MTR4,5,6
CB Bay
CR2
Right
Choke
Overtemp
CH11-TG
CR1
Airflow Loss
3
CB Bay
13
EA6-CR
Heatsink
Overtemp
Left
Heatsink
Overtemp
F6
PE
TB1-9
TB1-10
Publication 2364P-5.01 December 1999
S3
Phase Loss
TB1-3
S1
To Ground Fault Detector
B
and Airflow Sensors
CR1
TB1-4 TB1-5 TB1-6
S2
Fault
CR2
Fault
PL2
A
Not
Faulted
1
L
­C A V
0
2
1
115VAC
Control Bus To
Inverter Units
N
­C A V
0
2
1
T1 and V1-Code Parallel Configurations 6-5
Customer Supplied
3-phase Input
-Bus
Heat Sink
D1
D3
CT1
F1 F2 F3
M
CB1- NRU
Note:
Control power for this motorized breaker originates in the RGU. Do not operate this breaker manually.
AC Line Current
AM1
F11
F12
F13
Heat Sink
D2
D4
A
B
CR
C
+Bus
A
To RGU
AC Input
CR1
Phase
Loss
Relay
B
From NRU
Control Power
B
From NRU
Control Power
7
115VAC
ACN-ACL +
ACG
To Grounding
9
PS1
Resistor
Input
624
TB1-8
TB1-7
1012
Ground Fault
Detector
VM2
J2
3
J2
3
To Cust omer
Monitoring Device
EA5
J2
In15
Sig 1
In26
+5 2
Com 3
J11
EA6
J2
In15
Sig 1
+5 2
In26
Com 3
J11
S5
Y R B
Flow
Sensor
S6
Y R B
Flow
Sensor
CH11
(X4)
(X3)
+Bus
-Bus
D5
EA2
EA4
Bus Indicator PCB
VM1
DC Bus Voltage
DC Horizontal Bus To
Inverter Units
Bridge Suppressor
LED1 LED2
D6HS1 HS2
DC Bus Energized
R
PL1
(X1)
CH11
(X2)
Publication 2364P-5.01 December 1999
6-6 T1 and V1-Code Parallel Configurations
Figure 6.6 Schematics (cont.)
RGU
D
To
CB1-NRU
circuitry
TB1-1
Optional
Remote
Interlock
(JMPR)
RGU/DC Bus
Supply
Off On
S12
TB1-2
TR1
CR4
TR1
From
A
3-phase AC Input
CB1-RGU
4KHZ Control Power Filter
EA10
SP4
SP1
SP2
PE
SP3
F4
460VAC
F7
(X1)
115VAC
(X2)
F25
RGU Uni t Not
Faulted
14
TB6 TB6
Isolat i on Boa rd
F6
PT1
MTR1
RGU Door Fan
MTR2
RGU Door Fan
CR2
Fault
PL2
A
Not
Faulted
PE
TB1-9
TB1-10
Fault
C
To RGU Input
Fuses
CR2
TB1
TR1
Precharge
11
CR4
12
TB1
CR3
CR4
Timer
M2
Precharge
(20 sec)
TB1-5 TB1-6
Avail able f o r
Customer Use
6
TB6
CR3
Publication 2364P-5.01 December 1999
Bus Control
Isolation Board
CR3
CR4
M1
TB6
TB4-4
9
TB10-7
E
CB1-NRU-A
TB10-8
To RGU
Control
Circuitry
TB4-5
CR3
Pilot
CR4
Precharge
Lockout
M1
Main
External Main
Enable
F
Isolation Board
To RGU
D
From RGU
Control Power
T1 and V1-Code Parallel Configurations 6-7
TB4-8
CB1-NRU
PE
TR1
TR1
TB4-1
Spring
Windup
TB4-2
CR3
TB4-3
TB4-4 TB10-7 TB4-5TB10-8
TB10-1
TB10-3
A12
Wht/Red
D9
Wht
D10
A6
A3
A1
B2
Digitrip
Blk
Blu
Org
Brn
SR
Spring
Release
Resistor When Required (Not on 120 VAC)
Blk
Y
ARM
b
CB1-NRU-A
UVR
LC
Grn
SC
(Bot)
SC
CB1-NRU-B
CB1-NRU-A
TB10-10
B5
Blk
CB1-NRU-B
TB4-6
CB1-NRU-A
TB4-7
Not
Used
TB10-13
B8
Blk
CB1-NRU-B
TB4-9
CB1-NRU-A
TB10-16
B11
Blk
CB1-NRU-B
Red
Blu
Red
Blu
Red
Blu
Red
Blu
Red
A11
A2
B7
B9
B10
B12
TB10-2
TB10-5
B1
B3
TB10-9
B4
TB10-11
B6
TB10-12
TB10-14
Available For
Customer Use
TB10-15
TB10-17
TB10-18
Publication 2364P-5.01 December 1999
6-8 T1 and V1-Code Parallel Configurations
Figure 6.7 Schematics (cont.)
B
From RGU
AC Line
From RGU
Control
Circuitry
AC Rtn
R10
F2
R11
F3
F4
R12
CT1
F17 F18 F19
Bridge
Fan
Rs Ss Ts
0
6
2
2
1
1
-
-
-
1
1
1
J
J
J
CT3
To
PE
Gnd
J7
P1
1
6
-
-
1
1
J
J
M2
CH11
F1
M1
F2
F3
From RGU
E
Control Power
CH1 CH2 CH3
Isolation Board
TB5
1
Fault
F
Reset
S11
Enable
2
Fault Reset
3
External Main
4
Common
SW1 Settings
115VAC
OffX
24VDCOn
For TB5-1, -2, -3
Burden Resistors
1
TB1
Publication 2364P-5.01 December 1999
To RGU
Control
Circuitry
To RGU
Control
Circuitry
TB6
1
3
4
6
8
9
Aux Control Fault
Bus Control
TB2
TB3
3
1
TB2 Resistor Not Required
3
1
3
J2
T1 and V1-Code Parallel Configurations 6-9
d
r
a
o B r
e
b
b
u
n S
To System Network
UP
C1
G
E1
UN
C1
G
E1
J7
Main Bus
DC-DC
Converter
TP3
-t
J6
Bridge Thermal
Sensor (NTC)
J12
Gate Drivers
TP5
-15V+24V +15V
Shd
(+)
Horizontal
DC Bus
(-)
F1
G
G
24V
DC-DC
Aux 24V
J10
WP
C1
E1
Cap
Bank
WN
C1
E1
J10
+15V
-15V +5V +12V
-12V
J1
J3
J7
d
r
a
o B
G
r
e
b
E1
b
u
n S
VN
C1
G
E1
J8
F1
d
r
a
o
B
r
e
b
b
u
n
S
Gate Driver Board
+24V
VP
C1
Converter
TP8TP4TP6
TP9
+12V+5V -12V
Main Control Bo a rd
J2
RIO Adapter Option
1
1203-GM1
2 3
Y
R
YY
SW1
SW2
J4
Blu
1
SW3
Shd
Clr
2
OF
F
O
N
OF
F
O
N
OF
F
O
N
J1 J8 J9
2
Power
B T
Supply
Filter
1
Board
B T
J11
TB7
P13
TB4
TB1
+
-
PE
TE
2 1
1 2
1 2 3 4 5 6 7 8 9
10
+Bus
-Bus
+
-
- Analog In 1 + Analog In 1 Analog In 1 Common
- Analog In 2 + Analog In 2 Analog In 2 Common Analog Out 1 Analog Out 1 Common Analog Out 2 Analog Out 2 Common
Horizontal DC Bus
To Inve rter Units
EA2
Bus Indicator Board
EA4
Bus Suppressor
LED1 LED2
PL1
R
DC Bus Energized
RIO Ext SCANport 1 SCANport 2 R2R Comm
Publication 2364P-5.01 December 1999
6-10 T1 and V1-Code Parallel Configurations
Publication 2364P-5.01 December 1999

Chapter 7

T2 and V2-Code Parallel Configurations

T2-Code Parallel Configuration The T2-code paralle l configuration is a common DC bus front-end
unit consisting of an F-code NRU in paralle l with a L-code RGU.
Figure 7.1 T2-Code Parallel Configuration–Information

T2-code Parallel ConfigurationT2-code Ratings

Input Voltage
(V AC)
380 2536 460 575
DC Bus Current
(A DC)
2536 2536
Rated DC Bus
kW
1301 1575 1966
F-code
NRU
L-code RGU
V2-Code Parallel Configuration The V2-code parallel configuration is a common DC bus front-end
unit consisting of an G-code NRU in parall el with a L-code RGU.
Figure 7.2 V2-Code Parallel Configuration–Information

V2-code Parallel ConfigurationV2-code Ratings

Input Voltage
(V AC)
380 3000 460 575
DC Bus Current
(A DC)
3000 3000
Rated DC Bus
kW
1539 1863 2329
G-code
NRU
L-code RGU
Note: Information for the F-code NRU and G-code NRU can be found in publication 2364E-5.01. Information for the L-code RGU can be found in publication 2364F-5.01.
Publication 2364P-5.01 December 1999
7-2 T2 and V2-Code Parallel Configurations

Component Layout Figure 7.3

Enclosure Layout
Front View
Shipping Split
101.25"
91.5"
30" 25"30" 30" 35"
Cutaway View
Customer Supplied
AC Input Lines
Feeder F-code (2500A) or G-code (3000A) NRU
L-code RGU
Publication 2364P-5.01 December 1999
Figure 7.4 Overhead Bus Assembly
Feeder
Splice Kit
T2 and V2-Code Parallel Configurations 7-3
30" Overhead Bus Assembly
End Cap
4" Bus Tabs
To Feeder Buswork
To NRU circuit breaker
Flex Bus
Drop Tabs
New and Revised NRU and RGU Components in the T2 and V2 Configurations
NRU CB1 (T1 config) 2500A, SPB-frame with motor operator
(V1 config) 3000A, SPB-frame with motor operator
RGU
EA10 F4, F6
PT1 TB10
CR4 F4, F6
F21, F22 DC bus fuses, 500A, 700V, 170M F25 PT1
TR1 TB4
Control power filter, 2kHz Primary fuse for 5kVA control transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input)
Control power transformer, 5kVA Control terminal block, 30A, 600V
Precharge Lockout Relay (2NO/2NC) Primary fuse for 5kVA transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input)
Fuse, NRU CB1 motor operator, 10A, KLDR Control power transformer, 5kVA Timer relay (3NO/1NC)
Control Terminal block, 30A, 600V
Primary fuse for 10kVA control transformer (Opt 6P)
35A, KLDR (for 380V AC input)
30A, KLDR (for 460V AC input)
25A, KLDR (for 575V AC input)
Control power transformer, 10kVA (Opt 6P)
The RGU AC line is connected to the bus stubs on the NRU circuit breaker
Overhead bus assembly
Publication 2364P-5.01 December 1999
7-4 T2 and V2-Code Parallel Configurations
Schematics Figure 7.5

Schematics

NRU
TB1-1
Optional Remote Interlock
(JMPR)
TB1-2
Airflow Loss
Bridge Bay
1
EA5-CR
CB Bay
Overtemp
SP4
EA3
Line RC Suppressor
Com
L1
L2
L3
SP1
F14 F15 F16
SP2
PE
SP3
2KHZ Control Power Filter
EA10
F4
F8
F7
(X1)
460VAC
115VAC
PT1
(X2)
MTR1
Rect. Bridge
MTR2,3
Choke Comp.
MTR4,5,6
CB Bay
CR2
Right
Choke
Overtemp
CH11-TG
CR1
Airflow Loss
3
CB Bay
13
EA6-CR
Heatsink
Overtemp
Left
Heatsink
Overtemp
F6
PE
TB1-9
TB1-10
Publication 2364P-5.01 December 1999
S3
Phase Loss
TB1-3
S1
To Ground Fault Detector
B
and Airflow Sensors
CR1
TB1-4 TB1-5 TB1-6
S2
Fault
CR2
Fault
PL2
A
Not
Faulted
1
L
­C A V
0
2
1
115VAC
Control Bus To
Inverter Units
N
­C A V
0
2
1
T2 and V2-Code Parallel Configurations 7-5
Customer Supplied
3-phase Input
-Bus
Heat Sink
D1
D3
CT1
F1 F2 F3
M
CB1- NRU
Note:
Control power for this motorized breaker originates in the RGU. Do not operate this breaker manually.
AC Line Current
AM1
F11
F12
F13
Heat Sink
D2
D4
A
B
CR
C
+Bus
A
To RGU
AC Input
CR1
Phase
Loss
Relay
B
From NRU
Control Power
B
From NRU
Control Power
7
115VAC
ACN-ACL +
ACG
To Grounding
9
PS1
Resistor
Input
624
TB1-8
TB1-7
1012
Ground Fault
Detector
VM2
J2
3
J2
3
To Cust omer
Monitoring Device
EA5
J2
In15
Sig 1
In26
+5 2
Com 3
J11
EA6
J2
In15
Sig 1
+5 2
In26
Com 3
J11
S5
Y R B
Flow
Sensor
S6
Y R B
Flow
Sensor
D5
EA4
Bridge Suppressor
EA2
Bus Indicator PCB
+Bus
-Bus
(X4)
CH11 CH11
(X3)
DC Horizontal Bus To
LED1 LED2
VM1
DC Bus Voltage
Inverter Units
D6HS1 HS2
DC Bus Energized
R
PL1
(X1)
(X2)
Publication 2364P-5.01 December 1999
7-6 T2 and V2-Code Parallel Configurations
Figure 7.6 Schematics (cont.)
RGU
D
To
CB1-NRU
circuitry
TB1-1
Optional
Remote
Interlock
(JMPR)
RGU/DC Bus
Supply
Off On
S12
TB1-2
TR1
CR4
TR1
From
A
3-phase
AC Input
CB1-RGU
2KHZ Control Power Filter
EA10
SP4
SP1
SP2
PE
SP3
F4
460VAC
F7
(X1)
115VAC
(X2)
F25
RGU Uni t Not
Faulted
14
TB6 TB6
Isolat i on Boa rd
F6
PT1
MTR1,2
Bay Door Fans
MTR3,4
Bay 1 Door Fans
CR2
Fault
PL2
A
Not
Faulted
PE
TB1-9
TB1-10
Fault
C
To RGU Input
Fuses
CR2
TB1
TR1
Precharge
11
CR4
12
TB1
CR3
CR4
Timer
M2
Precharge
(20 sec)
TB1-5 TB1-6
Avail able f o r
Customer Use
6
TB6
CR3
Publication 2364P-5.01 December 1999
Bus Control
Isolation Board
CR3
CR4
M1
TB6
TB4-4
9
TB10-7
E
CB1-NRU-A
To RGU
Control
Circuitry
TB10-8
TB4-5
CR3
Pilot
CR4
Precharge
Lockout
M1
Main
External M ain
Enable
F
Isolation Board
To RGU
D
From RGU
Control Power
T2 and V2-Code Parallel Configurations 7-7
TB4-8
CB1-NRU
PE
TR1
TR1
TB4-1
Spring
Windup
TB4-2
CR3
TB4-3
TB4-4 TB10-7 TB4-5TB10-8
TB10-1
TB10-3
A12
Wht/Red
D9
Wht
D10
A6
A3
A1
B2
Digitrip
Blk
Blu
Org
Brn
SR
Spring
Release
Resistor When Required (Not on 120 VAC)
Blk
Y
ARM
b
CB1-NRU-A
UVR
LC
Grn
SC
(Bot)
SC
CB1-NRU-B
CB1-NRU-A
TB10-10
B5
Blk
CB1-NRU-B
TB4-6
CB1-NRU-A
TB4-7
Not
Used
TB10-13
B8
Blk
CB1-NRU-B
TB4-9
CB1-NRU-A
TB10-16
B11
Blk
CB1-NRU-B
Red
Blu
Red
Blu
Red
Blu
Red
Blu
Red
A11
B10
B12
TB10-2
A2
TB10-5
B1
B3
TB10-9
B4
TB10-11
B6
TB10-12
B7
TB10-14
Available For
B9
Customer Use
TB10-15
TB10-17
TB10-18
Publication 2364P-5.01 December 1999
7-8 T2 and V2-Code Parallel Configurations
Figure 7.7 Schematics (cont.)
B
From RGU
AC Line
From RGU
Control
Circuitry
AC Rtn
R10
F2
R11
F3
F4
R12
CT1
F17 F18 F19
Bridge
Fan
Rs Ss Ts
0
6
2
2
1
1
-
-
-
1
1
1
J
J
J
CT3
To
PE
Gnd
J7
P1
1
6
-
-
1
1
J
J
M2
F1
M1
F2
F3
From RGU
E
Control Power
CH1 CH2 CH3
CH11
Isolation Board
TB5
1
Fault
F
Reset
S11
Enable
2
Fault Reset
3
External Main
4
Common
SW1 Settings
115VAC
OffX
24VDCOn
For TB5-1, -2, -3
Burden Resistors
1
TB1
Publication 2364P-5.01 December 1999
To RGU
Control
Circuitry
To RGU
Control
Circuitry
TB6
1
3
4
6
8
9
Aux Control Fault
Bus Control
TB2
TB3
3
1
TB2 Resisto r Not Required
3
1
3
J2
T2 and V2-Code Parallel Configurations 7-9
e
c
e
a
t
f
a
r
e
G
t
n
I
e
c
e
a
t
f
r
a
e
G
t
n
I
To System Network
C1
G
E1
C1
G
E1
J7
Main Bus
DC-DC
Converter
TP3
-t
J6
Bridge Thermal
Sensor (NTC)
J12
UP
DETAIL
UN
Gate Drivers
TP5
-15V+24V +15V
Shd
(+)
Horizontal
DC Bus
(-)
F1
See U
r
Phase
e
b
b
Detail
u
n S
VP
See U Phase Detail
VN
J8
F1
J2
J4
Blu
1
Shd
Clr
2
TP8TP4TP6
TP9
+12V+5V -12V
RIO Adapter Option
1 2 3
SW1
SW2
SW3
+24V
1203-GM1
R
J1 J8 J9
See U
r
Phase
e
b
b
Detail
u
n S
WP
See U Phase
Detail
WN
Gate Driver Board
24V
DC-DC
Converter
Aux 24V
Main Control Bo a rd
Y
YY
Off On
Off On
Off On
J10
r
e
b
b
u
n S
Cap
Bank
J10
+15V
-15V +5V +12V
-12V
J1
J3
J7
2
Power
B T
Supply
Filter
1
Board
B T
J11
TB7
P13
TB4
TB1
+
-
PE
TE
2 1
1 2
1 2 3 4 5 6 7 8 9
10
+Bus
-Bus
+
-
- Analog In 1 + Analog In 1 Analog In 1 Common
- Analog In 2 + Analog In 2 Analog In 2 Common Analog Out 1 Analog Out 1 Common Analog Out 2 Analog Out 2 Common
Horizontal DC Bus
To Inve rter Units
EA2
Bus Indicator Board
EA4
Bus Suppressor
LED1 LED2
PL1
R
DC Bus Energized
RIO Ext SCANport 1 SCANport 2 R2R Comm
Publication 2364P-5.01 December 1999
7-10 T2 and V2-Code Parallel Configurations
Publication 2364P-5.01 December 1999

Chapter 8

T3 and V3-Code Parallel Configurations

T3-Code Parallel Configuration The T3-code paralle l configuration is a common DC bus front-end
unit consisting of an F-code NRU in paralle l with a M-code RGU.
Figure 8.1 T3-Code Parallel Configuration–Information

T3-code Parallel ConfigurationT3-code Ratings

Input Voltage
(V AC)
380 2575 460 575
DC Bus Current
(A DC)
2575 2575
Rated DC Bus
kW
1321 1599 1994
F-code
NRU
M-code RGU
V3-Code Parallel Configuration The V3-code parallel configuration is a common DC bus front-end
unit consisting of an G-code NRU in parall el with a M-code RGU.
Figure 8.2 V3-Code Parallel Configuration–Information

V3-code Parallel ConfigurationV3-code Ratings

Input Voltage
(V AC)
380 3000 460 575
DC Bus Current
(A DC)
3000 3000
Rated DC Bus
kW
1539 1863 2329
G-code
NRU
M-code RGU
Note: Information for the F-code NRU and G-code NRU can be found in publication 2364E-5.01. Information for the M-code RGU can be found in publication 2364F-5.01.
Publication 2364P-5.01 December 1999
8-2 T3 and V3-Code Parallel Configurations

Component Layout Figure 8.3

Enclosure Layout
Front View
101.25"
30" 30" 35"
Shipping Split
91.5"
35" 35"
Cutaway View
Customer Supplied
AC Input Lines
Feeder F-code (2500A) or G-code (3000A) NRU
M-code RGU
Publication 2364P-5.01 December 1999
T3 and V3-Code Parallel Configurations 8-3
Figure 8.4 Overhead Bus Assembly
Feeder
Splice Kit
To Feeder Buswork
30" Overhead Bus Assembly
4" Bus Tabs
Flex Bus
Drop Tabs
To NRU circuit breaker
35" Overhead Bus Assembly
Joiner-Splice Kits
New and Revised NRU and RGU Components in the T3 and V3 Configurations
NRU CB1 (T1 config) 2500A, SPB-frame with motor operator
(V1 config) 3000A, SPB-frame with motor operator EA10 F4, F6
PT1 TB10
Control power filter, 2kHz
Primary fuse for 5kVA control transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input)
Control power transformer, 5kVA
Control terminal block, 30A, 600V
35" Overhead Bus Assembly
End Cap
2" Bus Tabs
Flex Bus
Drop Tabs
To RGU circuit breaker
Primary fuse for 10kVA control transformer (Opt 6P)
35A, KLDR (for 380V AC input)
30A, KLDR (for 460V AC input)
25A, KLDR (for 575V AC input)
Control power transformer, 10kVA (Opt 6P)
RGU
CR4 F4, F6
Precharge Lockout Relay (2NO/2NC)
Primary fuse for 5kVA transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input)
F21, F22 DC bus fuses, 500A, 700V, 170M
21A, 22A
F25 PT1 TR1
Fuse, NRU CB1 motor operator, 10A, KLDR
Control power transformer, 5kVA
Timer relay (3NO/1NC) TB4 Control Terminal block, 30A, 600V
Overhead bus assembly
Publication 2364P-5.01 December 1999
8-4 T3 and V3-Code Parallel Configurations
Schematics Figure 8.5

Schematics

NRU
TB1-1
Optional Remote Interlock
(JMPR)
TB1-2
Airflow Loss
Bridge Bay
1
EA5-CR
CB Bay
Overtemp
SP4
EA3
Line RC Suppressor
Com
L1
L2
L3
SP1
F14 F15 F16
SP2
PE
SP3
2KHZ Control Power Filter
EA10
F4
F8
F7
(X1)
460VAC
115VAC
PT1
(X2)
MTR1
Rect. Bridge
MTR2,3
Choke Comp.
MTR4,5,6
CB Bay
CR2
Right
Choke
Overtemp
CH11-TG
CR1
Airflow Loss
3
CB Bay
13
EA6-CR
Heatsink
Overtemp
Left
Heatsink
Overtemp
F6
PE
TB1-9
TB1-10
Publication 2364P-5.01 December 1999
S3
Phase Loss
TB1-3
S1
To Ground Fault Detector
B
and Airflow Sensors
CR1
TB1-4 TB1-5 TB1-6
S2
Fault
CR2
Fault
PL2
A
Not
Faulted
1
L
­C A V
0
2
1
115VAC
Control Bus To
Inverter Units
N
­C A V
0
2
1
T3 and V3-Code Parallel Configurations 8-5
Customer Supplied
3-phase Input
-Bus
Heat Sink
D1
D3
CT1
F1 F2 F3
M
CB1- NRU
Note:
Control power for this motorized breaker originates in the RGU. Do not operate this breaker manually.
AC Line Current
AM1
F11
F12
F13
Heat Sink
D2
D4
A
B
CR
C
+Bus
A
To RGU
AC Input
CR1
Phase
Loss
Relay
B
From NRU
Control Power
B
From NRU
Control Power
7
115VAC
ACN-ACL +
ACG
To Grounding
9
PS1
Resistor
Input
624
TB1-8
TB1-7
1012
Ground Fault
Detector
VM2
J2
3
J2
3
To Cust omer
Monitoring Device
EA5
J2
In15
Sig 1
In26
+5 2
Com 3
J11
EA6
J2
In15
Sig 1
+5 2
In26
Com 3
J11
S5
Y R B
Flow
Sensor
S6
Y R B
Flow
Sensor
D5
EA4
Bridge Suppressor
EA2
Bus Indicator PCB
+Bus
-Bus
(X4)
CH11 CH11
(X3)
DC Horizontal Bus To
LED1 LED2
VM1
DC Bus Voltage
Inverter Units
D6HS1 HS2
DC Bus Energized
R
PL1
(X1)
(X2)
Publication 2364P-5.01 December 1999
8-6 T3 and V3-Code Parallel Configurations
Figure 8.6 Schematics (cont.)
RGU
D
To
CB1-NRU
circuitry
TB1-1
Optional
Remote
Interlock
(JMPR)
RGU/DC Bus
Supply
Off On
S12
TB1-2
TR1
F7
Choke
Thermoguards
S1 - 3
CR4
TR1
EA10
F25
11
TB1
CR4
CR4
2KHZ Control Power Filter
460VAC
(X1)
115VAC
RGU Uni t Not
Faulted
14
TB6 TB6
Isolat i on Boa rd
12
TB1
CR3
SP4
PE
PT1
(X2)
Bay 1 Door Fan
Bay 1 Internal Fan
RGU Door Fans
Precharge
Precharge
F4
F6
MTR2
MTR3
MTR1
CR2
Fault
PL2
A
Not
Faulted
TR1
Timer
M2
SP1
SP2
SP3
PE
TB1-9
TB1-10
(20 sec)
From
3-phase
AC Input
A
Fault
CR2
TB1-5 TB1-6
Avail able f o r
Customer Use
CB1-RGU
C
To RGU Input
Fuses
6
TB6
CR3
Publication 2364P-5.01 December 1999
Bus Control
Isolation Board
CR3
CR4
M1
TB6
TB4-4
9
TB10-7
E
CB1-NRU-A
To RGU
Control
Circuitry
TB10-8
TB4-5
CR3
Pilot
CR4
Precharge
Lockout
M1
Main
External M ain
Enable
F
Isolation Board
To RGU
D
Control Power
From RGU
T3 and V3-Code Parallel Configurations 8-7
TB4-8
CB1-NRU
PE
TR1
TR1
TB4-1
Spring
Windup
TB4-2
CR3
TB4-3
TB4-4 TB10-7 TB4-5TB10-8
TB10-1
TB10-3
A12
Wht/Red
D9
Wht
D10
A6
A3
A1
B2
Digitrip
Blk
Blu
Org
Brn
SR
Spring
Release
Resistor When Required (Not on 120 VAC)
Blk
Y
ARM
b
CB1-NRU-A
UVR
LC
Grn
SC
(Bot)
SC
CB1-NRU-B
CB1-NRU-A
TB10-10
B5
Blk
CB1-NRU-B
TB4-6
CB1-NRU-A
TB4-7
Not
Used
TB10-13
B8
Blk
CB1-NRU-B
TB4-9
CB1-NRU-A
TB10-16
B11
Blk
CB1-NRU-B
Red
Blu
Red
Blu
Red
Blu
Red
Blu
Red
A11
B10
B12
TB10-2
A2
TB10-5
B1
B3
TB10-9
B4
TB10-11
B6
TB10-12
B7
TB10-14
Available For
B9
Customer Use
TB10-15
TB10-17
TB10-18
Publication 2364P-5.01 December 1999
8-8 T3 and V3-Code Parallel Configurations
Figure 8.7 Schematics (cont.)
B
From RGU
AC Line
From RGU
Control
Circuitry
M2
F1
M1
F2
F3
From RGU
E
Control Power
Fault
F
Reset
CH1 CH2 CH3
S11
F2
F3
F4
AC Rtn
Isolation Board
TB5
1
Enable
2
Fault Reset
3
External Main
4
Common
R10, R10A
R11, R11A
R12, R12A
CH
F17 F18 F19
Bridge
Fan
CT1
CT2
Rs Ss Ts
0
6
2
2
1
1
-
-
-
1
1
1
J
J
J
SW1 Settings
For TB5-1, -2, -3
CT3
CT Power
Supply
CR
To
PE
Gnd
J7
P1
115VAC
OffX
24VDCOn
Burden Resistors
1
TB1
1
6
-
-
1
1
J
J
Publication 2364P-5.01 December 1999
To RGU
Control
Circuitry
To RGU
Control
Circuitry
TB6
1
3
4
6
8
9
Aux Control Fault
Bus Control
TB2
TB3
3
1
3
1
3
J2
T3 and V3-Code Parallel Configurations 8-9
e
c
e
a
t
f
a
r
e
G
t
n
I
e
c
e
a
t
f
r
a
e
G
t
n
I
To System Networ k
C1
DETAIL
G
E1
C1 G
E1
J7
Main Bus
DC-DC
Converter
TP3
-t
J6
Bridge Thermal
Sensor (NTC)
J12
UP1
UP2
C1
G
E1
UN1
UN2
C1
G
E1
Gate Drivers
TP5
(+)
Horizontal
DC Bus
(-)
+
See U
r
Phase
e
b
b
Detail
u
n S
VP1 VP2
See U Phase Detail
VN1 VN2
J8
F1
-15V+24V +15V
J2
J4
Blu
1
Shd
Shd
Clr
2
TP8TP4TP6
TP9
+12V+5V -12V
RIO Adapter Option
1 2 3
SW1
SW2
SW3
+24V
1203-GM1
R
J1 J8 J9
See U
r
Phase
e
b
b
Detail
u
n S
WP1 WP2
See U Phase
Detail
WN1 WN2
Gate Driver Board
24V
DC-DC
Converter
Aux 24V
Main Control Bo a rd
Y
YY
Off On
Off On
Off On
J10
r
e
b
b
u
n S
Cap
+15V
-15V +5V +12V
-12V
Bank
J10
J1
J3
J7
2
Power
B T
Supply
Filter
1
Board
B T
J11
TB7
P13
TB4
TB1
-
PE
TE
2 1
1 2
1 2 3 4 5 6 7 8 9
10
+Bus
-Bus
+
-
- Analog In 1 + Analog In 1 Analog In 1 Common
- Analog In 2 + Analog In 2 Analog In 2 Common Analog Out 1 Analog Out 1 Common Analog Out 2 Analog Out 2 Common
Horizontal DC Bus
To Inve rter Units
EA2
Bus Indicator Board
EA4
Bus Suppressor
LED1 LED2
PL1
R
DC Bus Energized
RIO Ext SCANport 1 SCANport 2 R2R Comm
Publication 2364P-5.01 December 1999
8-10 T3 and V3-Code Parallel Configurations
Publication 2364P-5.01 December 1999

Chapter 9

T4 and V4-Code Parallel Configurations

T4-Code Parallel Configuration The T4-code paralle l configuration is a common DC bus front-end
unit consisting of an F-code NRU in paralle l with a N-code RGU.
Figure 9.1 T4-Code Parallel Configuration–Information

T4-code Parallel ConfigurationT4-code Ratings

Input Voltage
(V AC)
380 2600 460 575
DC Bus Current
(A DC)
2600 2591
Rated DC Bus
kW
1334 1615 2012
F-code
NRU
N-code RGU
V4-Code Parallel Configuration The V4-code parallel configuration is a common DC bus front-end
unit consisting of an G-code NRU in parall el with a N-code RGU.
Figure 9.2 V4-Code Parallel Configuration–Information

V4-code Parallel ConfigurationV4-code Ratings

Input Voltage
(V AC)
380 3000 460 575
DC Bus Current
(A DC)
3000 3000
Rated DC Bus
kW
1539 1863 2329
G-code
NRU
N-code RGU
Note: Information for the F-code NRU and G-code NRU can be found in publication 2364E-5.01. Information for the N-code RGU can be found in publication 2364F-5.01.
Publication 2364P-5.01 December 1999
9-2 T4 and V4-Code Parallel Configurations

Component Layout Figure 9.3

Enclosure Layout
Front View
101.25"
30" 30" 35"
Shipping Split
20"
91.5"
35" 35"
Cutaway View
Customer Supplied
AC Input Lines
Feeder F-code (2500A) or G-code (3000A) NRU
N-code RGU
Publication 2364P-5.01 December 1999
T4 and V4-Code Parallel Configurations 9-3
20" Overhead
Figure 9.4 Overhead Bus Assembly
Feeder Splice
Assembly
To Feeder Buswork
30" Overhead Bus Assembly
4" Bus Tabs
Flex Bus
Drop Tabs
To NRU circuit breaker
35" Overhead Bus Assembly
Bus Assembly
Joiner-Splice
Assemblies
New and Revised NRU and RGU Components in the T4 and V4 Configurations
NRU CB1
EA10 F4, F6
PT1 TB10
(T1 config) 2500A, SPB-frame with motor operator (V1 config) 3000A, SPB-frame with motor operator
Control power filter, 2kHz Primary fuse for 5kVA control transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input)
Control power transformer, 5kVA Control terminal block, 30A, 600V
Primary fuse for 10kVA control transformer (Opt 6P)
35A, KLDR (for 380V AC input)
30A, KLDR (for 460V AC input)
25A, KLDR (for 575V AC input)
Control power transformer, 10kVA (Opt 6P)
35" Overhead Bus Assembly
End
Cap
2" Bus Tabs
Flex Bus
Drop Tabs
To RGU circuit breaker
RGU
CR3 Pilot relay (2NO/2NC) with aux contact (1NO/1NC) CR4 F4, F6
Precharge Lockout Relay (2NO/2NC) Primary fuse for 5kVA transformer
25A, KLDR (for 380V AC input)
20A, KLDR (for 460V AC input)
17.5A, KLDR (for 575V AC input)
F21, F22 DC bus fuses, 500A, 700V, 170M
21A, 22A
F25 PT1 TR1
Fuse, NRU CB1 motor operator, 10A, KLDR Control power transformer, 5kVA Timer relay (3NO/1NC)
TB4 Control Terminal block, 30A, 600V
Overhead bus assembly
Publication 2364P-5.01 December 1999
9-4 T4 and V4-Code Parallel Configurations
Schematics Figure 9.5

Schematics

NRU
TB1-1
Optional Remote Interlock
(JMPR)
TB1-2
Airflow Loss
Bridge Bay
1
EA5-CR
CB Bay
Overtemp
SP4
EA3
Line RC Suppressor
Com
L1
L2
L3
SP1
F14 F15 F16
SP2
PE
SP3
2KHZ Control Power Filter
EA10
F4
F8
F7
(X1)
460VAC
115VAC
PT1
(X2)
MTR1
Rect. Bridge
MTR2,3
Choke Comp.
MTR4,5,6
CB Bay
CR2
Right
Choke
Overtemp
CH11-TG
CR1
Airflow Loss
3
CB Bay
13
EA6-CR
Heatsink
Overtemp
Left
Heatsink
Overtemp
F6
PE
TB1-9
TB1-10
Publication 2364P-5.01 December 1999
S3
Phase Loss
TB1-3
S1
To Ground Fault Detector
B
and Airflow Sensors
CR1
TB1-4 TB1-5 TB1-6
S2
Fault
CR2
Fault
PL2
A
Not
Faulted
1
L
­C A V
0
2
1
115VAC
Control Bus To
Inverter Units
N
­C A V
0
2
1
T4 and V4-Code Parallel Configurations 9-5
Customer Supplied
3-phase Input
-Bus
Heat Sink
D1
D3
CT1
F1 F2 F3
M
CB1- NRU
Note:
Control power for this motorized breaker originates in the RGU. Do not operate this breaker manually.
AC Line Current
AM1
F11
F12
F13
Heat Sink
D2
D4
A
B
CR
C
+Bus
A
To RGU
AC Input
CR1
Phase
Loss
Relay
B
From NRU
Control Power
B
From NRU
Control Power
7
115VAC
ACN-ACL +
ACG
To Grounding
9
PS1
Resistor
Input
624
TB1-8
TB1-7
1012
Ground Fault
Detector
VM2
J2
3
J2
3
To Cust omer
Monitoring Device
EA5
J2
In15
Sig 1
In26
+5 2
Com 3
J11
EA6
J2
In15
Sig 1
+5 2
In26
Com 3
J11
S5
Y R B
Flow
Sensor
S6
Y R B
Flow
Sensor
D5
EA4
Bridge Suppressor
EA2
Bus Indicator PCB
+Bus
-Bus
(X4)
CH11 CH11
(X3)
DC Horizontal Bus To
LED1 LED2
VM1
DC Bus Voltage
Inverter Units
D6HS1 HS2
DC Bus Energized
R
PL1
(X1)
(X2)
Publication 2364P-5.01 December 1999
9-6 T4 and V4-Code Parallel Configurations
Figure 9.6 Schematics (cont.)
RGU
D
To
CB1-NRU
circuitry
TB1-1
Optional
Remote
Interlock
(JMPR)
RGU/DC Bus
Supply
Off On
S12
TB1-2
TR1
F7
Choke
Thermoguards
S1 - 3
CR4
TR1
EA10
F25
11
TB1
CR4
CR4
PE
2KHZ Control Power Filter
460VAC
(X1)
115VAC
F5
RGU Uni t Not
Faulted
14
TB6 TB6
Isolat i on Boa rd
12
TB1
CR3
SP4
(X2)
SP1
SP2
SP3
F4
F6
PT1
MTR6
Bay 1 Door Fan
MTR4,5
Bay 2 Fan
MTR1,2,3
RGU Door Fans
CR2
Fault
PL2
A
Not
Faulted
TR1
Precharge
Timer
M2
Precharge
TB1-9
TB1-10
(20 sec)
PE
From
3-phase
AC Input
A
G
To RGU
Precharge
Circuitry
TB1-5 TB1-6
CB1-RGU
CB2-RGU
Fault
CR2
Avail able for
Customer Use
C
To RGU Input
Fuses
6
TB6
CB1-RGU
TB3-7
CR3
CR3
Publication 2364P-5.01 December 1999
Bus Control
Isolation Board
CR3
CR4
TB3-8
TB3-7
TB3-10
9
TB6
TB4-4
CB1-RGU
TB10-7
E
CB1-NRU-A
UVR
To RGU
Control
Circuitry
TB10-8
TB4-5
TB3-8 TB3-9 TB3-11 TB3-12
CR3
Pilot
CR4
Precharge
Lockout
External Main
Enable
To RGU
F
Isolation Board
Loading...