Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://www.rockwellautomation.com/literature) describes some important
differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this
equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for
indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to
use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of
safety considerations.
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information about practices or circumstances
that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property
damage, or economic loss.
Identifies information that is critical for successful
application and understanding of the product.
Identifies information about practices or circumstances
that can lead to personal injury or death, property
damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that dangerous voltage may
be present.
Labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that surfaces may be
dangerous temperatures.
Table of Contents
Preface
Pico DeviceNet Interface
Installation
Who Should Use this Manual. . . . . . . . . . . . . . . . . . . . . . . P-1
Read this preface to familiarize yourself with the rest of the manual. It
provides information concerning:
• who should use this manual
• the purpose of this manual
• related documentation
• conventions used in this manual
• Rockwell Automation support
Who Should Use this
Manual
Purpose of this Manual
Use this manual if you are responsible for designing, installing,
programming, or troubleshooting control systems that use Pico
controllers.
You should have a basic understanding of electrical circuitry and
familiarity with relay logic. If you do not, obtain the proper training
before using this product.
This manual is a reference guide for Pico controllers and the Pico
DeviceNet Interface. It describes the procedures you use to install,
wire, and troubleshoot the Pico DeviceNet Interface.
Refer to publication 1760-GR001, Pico Controller Getting Results
Manual for a basic overview of Pico and an introduction to Pico
programming.
1Publication 1760-UM003A-EN-P - September 2005
Preface 2
Related Documentation
The following documents contain additional information concerning
Rockwell Automation products. To obtain a copy, contact your local
Rockwell Automation office or distributor.
ForRead this DocumentDocument Number
A basic overview of Pico and an introduction to Pico programming.Pico Controller Getting Results
Manual
In-depth information on grounding and wiring Allen-Bradley
programmable controllers
A description of important differences between solid-state
programmable controller products and hard-wired electromechanical
devices
An article on wire sizes and types for grounding electrical equipmentNational Electrical Code - Published by the National Fire
A complete listing of current documentation, including ordering
instructions. Also indicates whether the documents are available on
CD-ROM or in multi-languages.
A glossary of industrial automation terms and abbreviationsAllen-Bradley Industrial Automation
Common Techniques Used
in this Manual
The following conventions are used throughout this manual:
• Bulleted lists such as this one provide information, not
Allen-Bradley Programmable
Controller Grounding and Wiring
Guidelines
Application Considerations for
Solid-State Controls
Protection Association of Boston, MA.
Allen-Bradley Publication IndexSD499
Glossary
1760-GR001
1770-4.1
SGI-1.1
AG-7.1
procedural steps.
• Numbered lists provide sequential steps or hierarchical
information.
Publication 1760-UM003A-EN-P - September 2005
Preface 3
Rockwell Automation
Support
Rockwell Automation offers support services worldwide, with over 75
Sales/Support Offices, 512 authorized Distributors and 260 authorized
Systems Integrators located throughout the United States alone, plus
Rockwell Automation representatives in every major country in the
world.
Local Product Support
Contact your local Rockwell Automation representative for:
• sales and order support
• product technical training
• warranty support
• support service agreements
Technical Product Assistance
If you need to contact Rockwell Automation for technical assistance,
please review the Troubleshooting section on page 8-1 in this manual
first. Then call your local Rockwell Automation representative.
You can also find a local Rockwell Automation Technical Support
contact at:
If you find a problem with this manual, or you have any suggestions
for how this manual could be made more useful to you, please
contact us at the address below:
Rockwell Automation
Control and Information Group
Technical Communication, Dept. A602V
P.O. Box 2086
Milwaukee, WI 53201-2086
or visit our internet page at:
http://www.ab.com/pico or http://www.rockwellautomation.com
Publication 1760-UM003A-EN-P - September 2005
Preface 4
Publication 1760-UM003A-EN-P - September 2005
Chapter
1
Pico DeviceNet Interface
The 1760-DNET communication module has been developed for
automation tasks with the DeviceNet field bus. The 1760-DNET acts as
a ’gateway’ and can only be operated in conjunction with Pico and
Pico GFX-70 controllers.
The system unit consists of the Pico control device and the
1760-DNET DeviceNet gateway and operates exclusively as a slave
station on the DeviceNet fieldbus system.
System Overview
The DeviceNet slaves are integrated into a DeviceNet fieldbus system.
Figure 1.1 Implementation of 1760-DNET in DeviceNet
a
b
a Master area, SLC 500 programmable controller or PC with CAN card
b Slave area, e.g.: Pico or Pico GFX-70 with DeviceNet interface
1Publication 1760-UM003A-EN-P - September 2005
1-2 Pico DeviceNet Interface
Structure of the Unit
Communication Profile
Figure 1.2
1Pico-Link Socket
25-pin DeviceNet Connector
a
f
e
d
MS
NS
c
324V dc Power Supply
4Equipment Rating Plate
5Network Status LED
b
6Module Status LED
• Predefined master/slave communication settings
– The I/O polling connection is used for the transfer of 3 bytes
of input data (R1 to R16) and 3 bytes of output data (S1 to S8)
between the base unit with gateway interconnection and the
DeviceNet programmable controller.
– The I/O Change of State/Cyclic connection (acknowledged,
unacknowledged) is used to transfer 2 bytes of diagnostic
data from the control relay to the DeviceNet programmable
controller.
– The explicit connection set-up is used for read/write access
to function relay parameters in the control relay. This type of
connection set-up also supports the configuration, diagnostics
and management services of the control relay.
• DeviceNet Communication adapter profile (device type 12),
which has been expanded by requests
• Group 2 server
• UCMM-capable device
• Dynamic set-up of explicit and I/O connections are possible
• Device Heartbeat Message
• Device Shutdown Message
• Offline communication settings
Hardware and Operating
System Requirements
Publication 1760-UM003A-EN-P - September 2005
The 1760-DNET expansion unit operates together with Pico Series B
and Pico GFX-70 controllers.
Pico DeviceNet Interface 1-3
Use Other Than Intended
Pico and Pico GFX-70 controllers may not be used to replace
safety-relevant control circuits, e.g.:
• Furnace,
• emergency-stop,
• crane or
• Two-hand safety controls.
Publication 1760-UM003A-EN-P - September 2005
1-4 Pico DeviceNet Interface
Publication 1760-UM003A-EN-P - September 2005
Connect to the Basic Unit
Installation
Mounting is the same as for Pico Expansion I/O modules.
1
2
Chapter
2
Pico
Pico GFX-70
4
3
connector
1760-DNET
1Publication 1760-UM003A-EN-P - September 2005
2-2 Installation
Connect the Power Supply
The module operates with a 24V dc supply voltage (see Power Supply
specifications on page A-3).
WARNING
+24 V
0 V
Always ensure safe electrical isolation between the
extra low voltage (SELV) and the 24V power supply.
> 1 A
+24 V 0 V
Connect DeviceNet
A 5-pin DeviceNet plug connects the DeviceNet interface of the
device to the DeviceNet field bus.
Use a special DeviceNet plug and DeviceNet cable for this connection.
Both are specified in the ODVA specification. The type of cable
determines the maximum available cable length and the data transfer
rate.
DeviceNet Pin Assignment
1
1
2
2
3
3
4
4
5
5
V– GND (Black)
CAN_L (Blue)
Shield (Clear)
CAN_H (White)
V+ (24 V) (Red)
Publication 1760-UM003A-EN-P - September 2005
Installation 2-3
All pins of the plug must be connected to ensure safe communication
of the
1760-DNET on the fieldbus DeviceNet. This also applies to the
24V bus voltage.
EMC Compatible Wiring
IMPORTANT
The gateway does not participate in communication
on the bus if the bus voltage is not available. The
Network status LED is OFF in this situation.
Terminating Resistors
The first and last node of a DeviceNet network must be terminated by
means of a 120 O
interconnected between the CAN_H and CAN_L terminals.
0
R
T
Electromagnetic interference may lead to unwanted effects on the
communications fieldbus, which can be significantly reduced by using
the cable described above, a shielded RJ45 connector and by
terminating the screen.
bus termination resistor. This device is
. . .
1
n
R
T
The two figures below show the correct termination of the shielding.
Figure 1.3 Shield Connection to the Mounting Rail
Publication 1760-UM003A-EN-P - September 2005
2-4 Installation
Figure 1.4 Shield Connection to the Mounting Plate
Potential Isolation
Data Transfer Rates –
Automatic Baud Rate
Recognition
The following potential isolation specifications apply to 1760-DNET
interfaces:
a
+ –
c
1Safe electrical isolation between PicoLink and the 240 VAC mains
2Simple electrical isolation to the DeviceNet communication bus
3Power supply 24 V DC
After it is switched on, the 1760-DNET module automatically detects
the data transfer rate of the communication network. However, this is
possible only if at least one network node transmits valid message
frames. The device supports the following data transfer rates
according to ODVA:
b
Publication 1760-UM003A-EN-P - September 2005
• 125 kbps,
• 250 kbps,
• 500 kbps,
Maximum Distances and Bus Cable Lengths
The max. bus length is not determined by the data transfer rate, but
rather by the cable used. The following cables are permitted:
• Thin Cable,
• Thick Cable
• or Flat Cable.
The data cable requirements are specified by the ODVA.
Baud Rate (kbps)Maximum Cable Length (m)
Thick CableThin CableFlat Cable
125500100420
250250100200
500100100100
Installation 2-5
Publication 1760-UM003A-EN-P - September 2005
2-6 Installation
Publication 1760-UM003A-EN-P - September 2005
Operate the DeviceNet Interface
Chapter
3
Initial Power On
DeviceNet Setting the
Slave Address
Before you apply power to the DeviceNet Interface, verify that it is
properly connected to the power supply, to the bus connectors and to
the basic unit. Then, switch on the power supply for the basic unit
and the DeviceNet Interface.
The LEDs of the 1760-DNET flicker.The device automatically detects
the correct baud rate (see Data Transfer Rates – Automatic Baud Rate
Recognition on page 2-4). The GW information (intelligent station
connected) is displayed on the basic unit.
When the device in the network management is switched to the
‘Operational’ status, the state of the GW changes to static even on the
devices with a flashing GW,(see Network Status LED (NS) on
page 3-5).
If the unit has default configuration (node ID = 127), you need to
define the DeviceNet slave address.
Each DeviceNet slave requires a unique address (MAC ID) in the
DeviceNet structure. Within a DeviceNet structure, you can assign a
maximum of 64 addresses (0 to 63). Each MAC ID must be unique
within the entire bus structure.
There are three ways to set the DeviceNet address of an 1760-DNET:
• Using the integrated display and keyboard on the basic unit
• Using Pico-Soft V3.01 or higher on the PC
• Using Pico-Soft Pro on the PC
• Using the configuration software of the installed master
programmable controller (possibly by means of an explicit
message).
Set the Address on the Controller Unit with Display:
Make sure that:
• The respective basic units and DeviceNet Interface are supplied
with voltage.
1Publication 1760-UM003A-EN-P - September 2005
3-2 Operate the DeviceNet Interface
• The basic unit is accessible (password protection not activated).
• The basic unit has a valid operating system version.
• The basic unit is in STOP mode.
+
PASSWORD...
SYSTEM...
GB D F E I
CONFIGURATOR
PASSWORD...
SYSTEM...
GB D F E I
CONFIGURATOR
NET...
LINK...
1. Press the DEL + ALT keys to change to the special menu.
2. Use the cursor keys
Í or Ú to change to the Configurator.
3. Press OK.
4. Select the LINK.... menu with the Pico-GFX units.
5. Press OK.
DEVICENET
MAC ID 0026
222-01.20- D
Publication 1760-UM003A-EN-P - September 2005
The DEVICENET menu appears.
6. Set the address using the cursor keys:
– Set the current numeric value using the
– You can change the current numeric value using
2 . . . 9 0
1 . . .
o
0001PP000
o
1 0 9 . . .
2 . . .
Í or Ú keys.
ú or í.
1
7. Press OK to accept the address.
8. Press ESC to cancel address input.
Information about the 4th display line:
xxx -x x . x x - xx
222 - 02 . 10 - B
Set the Address with Pico-SOFT
With Pico-SOFT, version 3.1
Operate the DeviceNet Interface 3-3
Hardware version, Index: b
Software version, OS version: 2.1
Device identity: 1760-DNET
‹Menu l Online l Configuration of expansion units›
With Pico-SOFT, version 4.01 and later
‹Menu l Communication l Configuration l Expansion units l
1760-DNET›.
IMPORTANT
IMPORTANT
The menu is only available in the communication
view; therefore please activate the ‘Communication’
tab.
After you have modified the MAC ID via the basic
unit, restart the DeviceNet Interface by switching
power off and on.
Set the Address with the DeviceNet Master
The configuration software supplied with your master programmable
controller offers the option of setting or modifying the MAC ID of the
gateway.
Publication 1760-UM003A-EN-P - September 2005
3-4 Operate the DeviceNet Interface
For more information, refer to the programmable controller’s
documentation.
You can also use various other software packages to modify the MAC
ID by sending an explicit message. Do so by using the corresponding
service of the DeviceNet object (see DeviceNet Object on page 4-6).
LED Status Displays
The DeviceNet Interface expansion module is equipped with two
indicator LEDs for quick diagnostics. The module monitors itself as
well as the DeviceNet communication bus.
Module Status LED (MS)
The dual-color LED (GREEN/RED) indicates the status of the module.
It monitors whether the device is fully functional and operates without
fault.
Table 3.1 Module Status LED Description
LED StatusDescription
OffNo power supply at the module.
GreenThe module is in normal operational
state.
Green flashingThe module is in standby mode. The
configuration is faulty or incomplete,
or a configuration does not exist.
t
t
Publication 1760-UM003A-EN-P - September 2005
Red flashingAn error has occurred. There is no
need to replace the module.
RedA fatal error has occurred. The
module must be replaced.
Green-Red flashingThe module is performing a self-test.
t
t
t
t
Operate the DeviceNet Interface 3-5
Network Status LED (NS)
The dual-color LED (GREEN/RED) indicates the status of the
DeviceNet communication bus. This function monitors operability and
correct operation of the module.
Table 3.2 Network Status LED Description
LED Status Description
OFFThe module is offline. Either it is performing
a DUP_MAC_ID test or power is missing at
the device or bus.
GREEN
flashing
GREENThe module is online and the connection is
RED
flashing
REDA fatal network error has occurred. The
GREEN-RED
flashing
The module is online. Communication has
not yet been established.
active.
Time-out of at least one I/O connection
(time-out state).
module has shut down communication.
The module has detected a network access
error and is now in communication error
state.
t
t
t
t
t
Cycle Time of the Pico
Basic Unit
EDS File
Network traffic between the Pico basic unit and the DeviceNet
Interface via Pico-LINK extends the cycle scan time of the basic unit
In the worst case, this time can be extended by 25 ms.
Please take this factor into account when you calculate the response
times of the basic unit.
You can implement the module into the DeviceNet structure by means
of a standardised EDS file (Electronic Data Sheet).
This EDS file primarily defines the polled I/O connection, the COS I/O
connection and the cyclic I/O connection of the gateway. It does not
contain data or parameters (Pico object) for functions of the controller.
These functions are accessed by means of explicit messages.
You can download updates of the EDS file from:
http://www.ab.com/networks/eds/
Publication 1760-UM003A-EN-P - September 2005
3-6 Operate the DeviceNet Interface
Search for the catalog number 1760.
IMPORTANT
The Identity Object entry - Major Revision defines
the current operating system state of the 1760-DNET
communication module. As the device with a newer
operating system version can deviate from the EDS
description in this point, this entry must be modified
accordingly, Identity Object on 4-4.
Publication 1760-UM003A-EN-P - September 2005
DeviceNet Functions
Chapter
4
Object Model
The Pico DeviceNet Interface is based on the Communications
Adapter Profile according to the ODVA specifications (Release V2.0).
The DeviceNet object model can be used to describe all 1760-DNET
functions. The object model reflects the principle of communication at
the application layer. This manual deals in the following only with
objects relevant for your application. Primary topic is the
manufacturer-specific class Pico object.
Figure 3.5 DeviceNet Objects
Pico-LINK
Protocol Handler
Identity
Object
Message Router
Object
DeviceNet
Object
Assembly
Object
Object
Polled I/O
Connection
COS/Cyclic I/O
Bit Strobed I/O
Connection
Pico
Object
Acknowledge Handler
Object
Connection
Explicit Message
Connection
Dynamic
Connection
Connection Object
DeviceNet
The DeviceNet objects in the illustration can be compiled again as
‘Management objects’, ‘Connection objects’ and ‘Manufacturer-specific
objects’.
1Publication 1760-UM003A-EN-P - September 2005
4-2 DeviceNet Functions
Table 3.3
ObjectsObject AddressService AddressFunction
Class ID (Hex)Instance ID (Hex)(Hex)Attribute ID (Hex)
Management Objects
Identity Object0101
Message Router0201
Connection Objects
DeviceNet Object0301
Connection
Object
Manufacturer-Specific
Objects
Pico Object6401
Direct Access:
inputs/outputs,
mode
Read0E
Write10
Extended access:
time, image data,
function blocks
Pico Series B
Pico GFX-70
Assembly Object0464 ... 66
0501 ... 04,
04 ... 0F
Management Objects
32
Publication 1760-UM003A-EN-P - September 2005
These objects define DeviceNet-specific data and functions and must
be supported by all DeviceNet devices:
• Identity Object
The Identity Object (Class ID 01
) contains all data for unique
hex
identification of a network node, e.g. the Vendor ID, Device
Type and Product Code. It also comprises the actual status of a
device, the serial number and the product name.
Detailed information can be found on page 4-4.
• Message Router Object
DeviceNet Functions 4-3
The Message Router Object (Class ID 02
) provides access to
hex
all classes and instances in the device by means of explicit
messages.
Connection Objects
These objects define messages exchanged via DeviceNet:
• DeviceNet Object
All devices must support the DeviceNet object (Class ID: 03
It defines the physical interconnection of a device to the
DeviceNet network, meaning it also contains the device address
(MAC ID) and the currently set transmission speed, for example.
Detailed information page 4-6.
• Connection Object
The Connection Object (Class ID: 05
DeviceNet devices in at least one instance. It defines the access
to data via I/O messages or explicit messages, the path and
length of producer/consumer data, the CAN connection
identifier, the watchdog and the error response.
) is supported by all
hex
hex
).
Publication 1760-UM003A-EN-P - September 2005
4-4 DeviceNet Functions
Manufacturer-Specific Objects
These objects define device-specific data and functions (Application
Objects, Parameter Object, Assembly Object).
• Application Objects – Pico Object
Application objects (Class ID: 64
) describe simple
hex
applications for automation engineering. They are either
predefined in the DeviceNet object library or by the user.
Refer to Pico Object on page 4-6.
• Assembly Objects
The Assembly Object (Class ID: 04
) provides the user with
hex
mapping options, that is attribute data of different instances in
different classes can be grouped together to form a single
attribute of an instance in an assembly object.
Identity Object
Object AddressFunctionAccess
Class IDInstance IDAttribute IDService Code
01
hex
01
hex
Table 4.4Table 4.5
Publication 1760-UM003A-EN-P - September 2005
Table 4.4 Attribute IDs of the Identity Object Instance
Attribute IDAccess NameDescriptionSize
(byte)
1ReadVendor IDAllen-Bradley Vendor ID = 12
2ReadDevice typeThe 1760-DNET belongs to the
Table 4.4 Attribute IDs of the Identity Object Instance
Attribute IDAccess NameDescriptionSize
(byte)
4ReadDevice
version
Two bytes are returned when reading the
device version.
Hardware
version,
Operating
The low byte defines the hardware
version, the high byte the operating
system version.
1
1
system
version
5ReadStatusThis attribute describes the global status
2
of the device.
6ReadSerial
number
7ReadProduct name The product name 1760-DNET is stored as
The serial number of the device can be
read with this attribute.
4
12
hex value in ASCII format.
9ReadConfiguration
consistency
value
10Read/
Write
Heartbeat
Interval
This attribute returns a counter value that
monitors the number of modifications in
non-volatile memory (E2PROM).
Defines an interval between heartbeat
messages in [s].
2
2
Service Code
The Identity Object Instance and also the following instances support
the services listed in the table below.
Table 4.5 Service Code
Service Code ValueService NameDescription
05
hex
ResetCalls the reset function of
the communication module.
0E
hex
Get_Attribute_SingleThis service can be used to
fetch the value of a selected
attribute from the
communication module.
10
hex
Set_Attribute_SingleThis service can be used to
set a selected attribute in
the device.
Publication 1760-UM003A-EN-P - September 2005
4-6 DeviceNet Functions
DeviceNet Object
Object AddressFunctionAccess
Class IDInstance IDAttribute IDService Code
03
hex
The DeviceNet object instance is used to configure the
communication module and to define the physical environment. The
Service Codes used for the Identity Object also apply in this case.
Table 4.6 DeviceNet Object Instance Attribute IDs
Attribute IDAccess NameDescriptionSize
01
hex
Table 4.6Table 4.5
(byte)
1Read/
Write
2Read/
Write
3Read/
Write
4Read/
Write
Pico Object
MAC IDThe MAC ID represents the network
address of a network node. It can be read
and set for the module via the DeviceNet
fieldbus by means of this attribute. Range
of values: 0 to 63
Setting the Slave Address on page 3-1)
Baud rateThis attribute can be used to read/set the
data transfer rate for communication
functions. Range of values: 0 to 2, 125 to
500 kbps (see Data Transfer Rates –
Automatic Baud Rate Recognition on page
2-4).
BOI (Bus-Off
interrupt)
Bus-Off
counter
This attribute can be used to define the
reaction to a Bus-Off event (CAN-specific).
This values shows how often a Bus-Off
event has occurred. Range of values: 0 to
255.
. (see DeviceNet
dec
1
1
1
1
Publication 1760-UM003A-EN-P - September 2005
Object AddressFunctionAccess
Class IDInstance IDAttribute IDService Code
64
hex
01
hex
Table 4.7Table 4.8
The Pico object can be used to access Pico/GFX functions via the
DeviceNet communication bus . The table below shows the attributes
Loading...
+ 138 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.