Rockwell Automation 1757-SWKIT400 User Manual

Quick Start
Getting Started with ProcessLogix R400.0
This Quick Start describes the tasks you need to become familiar with the
ProcessLogix™ system, including:
starting the software
creating a controller
creating digital and analog I/O modules
creating a PID Loop
creating a Control Modulebuilding the PID loopdownloading the Control Module to the 1757-PLX52 Control Processor
Module
– verifying proper operation
viewing pre-built screens
shutting down the system
The tasks described in this Quick Start represent a sample program. This program is not intended for actual process control applications. After you have completed the tasks in this sample program, you can use the sample to guide you as you program your own process control application.
As you complete the tasks in this Quick Start, always use the ProcessLogix parameter naming conventions so that the pre-built screens provided with the ProcessLogix system work correctly.
IMPORTANT
Refer to the ProcessLogix R400.0 Installation and Upgrade Guide, publication 1757-IN040 and the ProcessLogix Overview and Selection Guide, publication 1757-SO002 for information on the components that make up your ProcessLogix system.
The ProcessLogix R400.0 server runs on Microsoft Windows
2000® Server.
Publication 1757-QS040A-EN-P - October 2001
2 Getting Started with ProcessLogix R400.0
ATTENTION
!
IMPORTANT

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of these products must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. In no event will Allen-Bradley be responsible or liable for indirect or consequential damage resulting from the use or application of these products.
Any illustrations, charts, sample programs, and layout examples shown in this publication are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this publication, notes may be used to make you aware of safety considerations. The following annotations and their accompanying statements help you to identify a potential hazard, avoid a potential hazard, and recognize the consequences of a potential hazard:
Publication 1757-QS040A-EN-P - October 2001
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Getting Started with ProcessLogix R400.0 3
TIP
Rockwell Automation Technical Support
If you need any assistance with the information found in this document, first call your local Rockwell Automation representative, then:
Phone Support: (440) 646-5800
Web Support:
http://www.ab.com, under Support, click Product Support
Your Questions or Comments about this Manual
If you find a problem with this manual, please use the How are We Doing? form located in the Documentation section of Knowledge Builder to notify us.

Before You Begin

Before you begin, read through and follow this checklist to organize and implement your ProcessLogix R400.0 Software and Hardware installation.
Before you start the tasks in this Quick Start, ensure that you have already:
installed the chassis and power supply
installed the 1757-PLX52 Control Processor Module
installed the CNB module
installed the analog and digital I/O modules you want to use in your system
set up and configured the ProcessLogix Server
set up and configured the 1784-PCIC card
We explain how to do all of these tasks in the related manuals.
For details on installing ProcessLogix R400.0 software on a ProcessLogix Server, refer to the ProcessLogix Installation and Upgrade Guide, publication number 1757-IN040.
Publication 1757-QS040A-EN-P - October 2001
4 Getting Started with ProcessLogix R400.0
TIP
TIP

Starting the Software

In this section, we explain how to start:
The ProcessLogix R400.0 Server software
Control Builder software
The System Repository is the database that contains information about your control environment. The CDA program controls communications between ProcessLogix
server applications and RSLinx communication software. The
System Repository and the CDA program are both Windows 2000 Services that start automatically.
Verifying ControlNet nodes and I/O modules
The CDA program starts up RSLinx and all configured drivers for ControlNet
communications from the server to the controller backplane.
You should verify the ControlNet nodes and the I/O modules you will use in your system. For purposes of illustration, we use two ControlNet nodes:
ControlNet module with address 1 at slot 0 in the chassis
To set the node address, adjust the rotary switches on top of the module. See the schematic on the right side of the module for a guide to selecting the address
ProcessLogix Server at ControlNet address 24 (set in RSLinx Software)
If the LED on the front of the ControlNet module reads NET ERR, no other ControlNet devices are present on the network.
Publication 1757-QS040A-EN-P - October 2001
Getting Started with ProcessLogix R400.0 5
Verify the ControlNet Nodes Using NTools (Network Tools):
1. To view chassis configuration, click StartProgramsProcessLogix Engineering ToolsNTools.
2. Click OK to acknowledge the warning.
3. Click NetworkToolsSettings.
4. Select the Ping option and click OK.
5. Click NetworkToolsPing.
6. Click the CNB with Network Address 1. This can be found under the
Desktop tree icon in the upper left window.
7. Under the Local Chassis tab, adjust the number of slots in the scroll box to match the number of slots in your local chassis and click OK.
8. Verify that all I/O modules appear as configured in the chassis.
9. If the I/O modules do not all appear, try the following:
Check the power supply
Reseat the module(s) in the chassis
Adjust the number of Slots in Local Chassis
10. Select NetworkToolsExit.
Publication 1757-QS040A-EN-P - October 2001
6 Getting Started with ProcessLogix R400.0
TIP
Starting the ProcessLogix Server
The ProcessLogix Server program is the operating system for the ProcessLogix Server. To start the Server:
1. Click Start⇒ProgramsProcessLogix ServerStart-Stop ProcessLogix Server
to call up the ProcessLogix Server dialog box. Check that the Server is running.
OR
To display the “Full Mode” version of the ProcessLogix Server dialog box, click the icon to the left of ProcessLogix in the
title bar and click Advanced now appear in front of the Full Mode selection to show that it is active.
2. If the Server is running, close the dialog box. If the Server is not running: a. With the Full Mode version of the dialog box active, click the System
Running option. b. Click Yes to confirm the action and wait for the Server to change its state. c. Close the ProcessLogix Server dialog box.
Publication 1757-QS040A-EN-P - October 2001
Full Mode. A checkmark will
Getting Started with ProcessLogix R400.0 7
Turning Off Areas
Areas are portions of a process you wish to control. This Quick Start assumes that Areas are turned off. To turn off areas:
1. Click StartProgramsProcessLogix ServerStation.
2. Select ConfigureAreasAreas.
3. Access manager mode.
a. Click Oper in the bottom right of the screen. b. In the Station Logon dialog box, type mngr. c. Click OK.
Oper changes to Mngr.
4. To disable areas, uncheck the Areas Enabled check box.
5. Exit Station.
Starting Control Builder
Control Builder software is an application you use to develop CMs (Control Modules) and SCMs (Sequential Control Modules). The CMs and SCMs are downloaded to the 1757-PLX52 Control Processor Module. CMs contain Function Blocks, and together with SCMs you can tell the 1757-PLX52 how to control your process.
To start Control Builder:
1. Click StartProgramsProcessLogix Engineering ToolsControl Builder.
A Login Information window appears.
Publication 1757-QS040A-EN-P - October 2001
8 Getting Started with ProcessLogix R400.0
2. Enter mngr (lowercase) for your User Name and mngr1 (lowercase) for your
Password, and click OK.
3. Control Builder starts up displaying the Project tab:
The available tabs are described in the following table:
this tab: shows you:
Project the offline copy of your project
Monitoring the loaded or currently running copy of the application executing on the
Library
1757-PLX52 Control Processor Module
available I/O modules (IOM)
available function blocks for use in Control Modules
available function blocks for use in Sequential Control Modules
available control component libraries (CCLs)
Once you have opened Control Builder, you can begin configuring your hardware.

Creating a Controller

The first step in configuring your hardware is to create a controller.
1. In Control Builder, select FileNewControllersCPM-Control Processor
Module. You see the CPM Parameters dialog box (CPM = PLX52):
Publication 1757-QS040A-EN-P - October 2001
Loading...
+ 16 hidden pages