Rockwell Automation 1746-NT8 User Manual

SLC 500 Thermocouple/mV Analog Input Module
1746-NT8
User Manual

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety considerations.
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
identify a hazard
avoid a hazard
recognize the consequence
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present.
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be dangerous temperatures.

Table of Contents

Preface
Module Overview
Installing And Wiring Your Module
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . P-1
What This Manual Covers . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Common Techniques Used in this Manual . . . . . . . . . . . . . P-2
Chapter 1
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Input Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Hardware Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Diagnostic LEDs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
System Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Module Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Module Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Block Diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Linear Millivolt Device Compatibility. . . . . . . . . . . . . . . 1-7
Chapter 2
Electrostatic Damage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Considerations for a Modular System . . . . . . . . . . . . . . 2-2
Fixed I/O Chassis - I/O Module Compatibility . . . . . . . . 2-3
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Module Installation and Removal . . . . . . . . . . . . . . . . . . . . 2-5
Terminal Block Removal . . . . . . . . . . . . . . . . . . . . . . . 2-6
Wiring Your Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Preparing and Wiring the Cables . . . . . . . . . . . . . . . . . 2-9
Cold-Junction Compensation (CJC) . . . . . . . . . . . . . . . . 2-11
Chapter 3
Considerations Before Using Your Module
i Publication 1746-UM022B-EN-P - January 2005
Module ID Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Module Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Output Image - Configuration Words . . . . . . . . . . . . . . 3-2
Input Image - Data Words and Status Words. . . . . . . . . 3-3
Channel Filter Frequency Selection . . . . . . . . . . . . . . . . . . 3-3
Channel Cut-Off Frequencyc . . . . . . . . . . . . . . . . . . . . 3-4
Channel Step Response . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Update Time. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Update Time Calculation Example . . . . . . . . . . . . . . . . 3-8
Channel Turn-On, Turn-Off, and Reconfiguration Times . . . 3-8
Auto-calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Response to Slot Disabling . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Input Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Output Response . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Table of Contents ii
Channel Configuration, Data, and Status
Chapter 4
Channel Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Channel Configuration Procedure . . . . . . . . . . . . . . . . . . . 4-2
Select Channel Enable (Bit 0) . . . . . . . . . . . . . . . . . . . . 4-5
Select Input Types (Bits 1 through 4) . . . . . . . . . . . . . . 4-5
Select Data Format (Bits 5 and 6) . . . . . . . . . . . . . . . . . 4-5
Using Scaled-for-PID and Proportional Counts . . . . . . . 4-6
Effective Resolutions . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Scaling Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Select Open-Circuit State (Bits 7 and 8). . . . . . . . . . . . . 4-9
Select Temperature Units (Bit 9) . . . . . . . . . . . . . . . . . . 4-10
Select Channel Filter Frequency (Bits 10 and 11) . . . . . . 4-10
Unused Bits (Bits 12 through 14) . . . . . . . . . . . . . . . . . 4-11
Select Input Image Type (Bit 15) . . . . . . . . . . . . . . . . . 4-11
Channel Data/Status Word. . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Channel Status Checking . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Channel Status (Bit 0) . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Input Type Status (Bits 1 through 4) . . . . . . . . . . . . . . . 4-14
Data Format Type Status (Bits 5 and 6) . . . . . . . . . . . . . 4-14
Open-Circuit Type Status (Bits 7 and 8) . . . . . . . . . . . . 4-14
Temperature Units Type Status (Bit 9). . . . . . . . . . . . . . 4-14
Channel Filter Frequency (Bits 10 and 11). . . . . . . . . . . 4-15
Open-Circuit E. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
Under-Range Error (Bit 13). . . . . . . . . . . . . . . . . . . . . . 4-15
Over-Range Error (Bit 14). . . . . . . . . . . . . . . . . . . . . . . 4-15
Channel Error (Bit 15) . . . . . . . . . . . . . . . . . . . . . . . . . 4-15
Programming Examples
Troubleshooting Your Module
Publication 1746-UM022B-EN-P - January 2005
Chapter 5
Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Automatic Monitoring Thermocouples and CJC Sensors . . . 5-3
Verifying Configuration Changes . . . . . . . . . . . . . . . . . . . . 5-3
Interfacing to the PID Instruction. . . . . . . . . . . . . . . . . . . . 5-7
Monitoring Channel Status Bits . . . . . . . . . . . . . . . . . . . . . 5-8
Monitoring Channel Status Bits Example . . . . . . . . . . . . 5-9
PLC 5 Example with NT8 in Remote I/O Rack . . . . . . . . . . 5-13
SLC 500 Example with NT8 in Remote I/O Rack. . . . . . . . . 5-15
Chapter 6
Module and Channel Diagnostics. . . . . . . . . . . . . . . . . . . . 6-1
Module Diagnostics at Powerup . . . . . . . . . . . . . . . . . . 6-1
Channel Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
LED Troubleshooting Tables. . . . . . . . . . . . . . . . . . . . . 6-3
Channel-status LEDs (Green) . . . . . . . . . . . . . . . . . . . . 6-4
Open-circuit Detection (Bit 12). . . . . . . . . . . . . . . . . . . 6-4
Maintaining Your Module And Safety Considerations
Module Specifications
Table of Contents iii
Out-of-Range Detection (Bit 13 for Under Range, Bit 14 for
Over Range) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-4
Channel Error (Bit 15) . . . . . . . . . . . . . . . . . . . . . . . . . 6-5
Module Status LED (Green) . . . . . . . . . . . . . . . . . . . . . 6-5
Interpreting I/O Error Codes . . . . . . . . . . . . . . . . . . . . . . . 6-5
Chapter 7
Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Appendix A
Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Physical Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . A-2
Input Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Overall Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
Millivolt. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
Using Grounded Junction, Ungrounded Junction, and Exposed Junction Thermocouples
Configuring the 1746-NT8 Module with RSLogix 500
Appendix B
Thermocouple Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Grounded Junction . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Ungrounded (Insulated) Junction . . . . . . . . . . . . . . . . . B-2
Exposed Junction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Isolation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Grounded Junction . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Exposed Junction Thermocouples. . . . . . . . . . . . . . . . . B-4
Appendix C
Glossary
Index
Publication 1746-UM022B-EN-P - January 2005
Table of Contents iv
Publication 1746-UM022B-EN-P - January 2005

Summary of Changes

The information below summarizes the changes to this manual since the last printing. Updates to the manual include using RSLogix 500 instead of APS software.
To help you find new and updated information in this release of the manual, we have included change bars as shown to the right of this paragraph.
The table below lists the sections that document new features and additional or updated information on existing features.
For this information: See
updated data table for initial programming page 5-2
added SLC 500 example with NT8 in Remote I/O Rack
updated thermocouple graphs page A-8
configuring NT8 with RSLogix 500 page C-1
page 5-15
1 Publication 1746-UM022B-EN-P - January 2005
Summary of Changes 2
Publication 1746-UM022B-EN-P - January 2005

Preface

Read this preface to familiarize yourself with this user manual. This preface covers:
who should use this manual
what this manual provides
related documents
common techniques used in this manual

Who Should Use This Manual

What This Manual Covers

Use this manual if you design, install, program, or maintain a control
system that uses SLC 500 controllers.
You should have a basic understanding of SLC 500 products. You should also understand electronic process control and the ladder program instructions required to generate the electronic signals that control your application. If you do not, contact your local Rockwell Automation representative for the proper training before using these products.
This manual covers the 1746-NT8 thermocouple/millivolt analog input module. It contains the information you need to install, wire, use, and maintain these modules. It also provides diagnostic and troubleshooting help should the need arise.
1 Publication 1746-UM022B-EN-P - January 2005
Preface 2

Related Documentation

The following table lists several Rockwell Automation documents that may help you as you use these products.
Publication Number
1746-SG001 SLC 500™ Systems Selection Guide
SGI-1.1 Safety Guidlines for the Application, Installation and
1770-4.1 Industrial Automation Wiringing and Grounding Guidelines
1747-UM011 SLC 500 Modular Modular Hardware Style User Manual
1747-6.21 Installation & Operation Manual for Fixed Hardware Style
1747-RM001 SLC 500 Instruction Set Reference Manual
AG-7.1 Allen-Bradley Industrial Automation Glossary
Title
Maintenance of Solid State Controllers
Programmable Controllers
If you would like to:
view and download the publication, go to Literature Library at
http://www.rockwellautomation.com/literature
order printed copies, contact your Allen-Bradley Distributor or
Rockwell Automation Sales Office.

Common Techniques Used in this Manual

The following conventions are used throughout this manual:
Bulleted lists such as this one provide information, not
procedural steps.
Numbered lists provide sequential steps or hierarchical
information.
Text in this font indicates words or phrases you should type.
Key names appear in bold, capital letters within brackets (for
example, [ENTER]).
Publication 1746-UM022B-EN-P - January 2005
Chapter
1

Module Overview

This chapter describes the thermocouple/mV input module and explains how the SLC 500 processor reads thermocouple or millivolt analog input data from the module.
Read this chapter to familiarize yourself further with your thermocouple/mV analog input module. This chapter covers:
general description and hardware features
an overview of system and module operation
block diagram of channel input circuits

General Description

This module mounts into 1746 I/O chassis for use with SLC 500 fixed and modular systems. The module stores digitally converted thermocouple/mV analog data in its image table for retrieval by all fixed and modular SLC 500 processors. The module supports connections from any combination of up to eight thermocouple/mV analog sensors.
Input Ranges
The following tables define thermocouple types and associated temperature ranges and the millivolt analog input signal ranges that each of the module’s input channels support. To determine the practical temperature range of your thermocouple, refer to the specifications in Appendix A.
Thermocouple Temperature Ranges
Type °C Temperature Range °F Temperature Range
J -210°C to +760°C -346°F to +1400°F
K -270°C to +1370°C -454°F to +2498°F
T -270°C to +400°C -454°F to +752°F
B +300°C to +1820°C +572°C to +3308°F
E -270°C to +1000°C -454°F to +1832°F
R 0°C to +1768°C +32 F to +3214°F
1 Publication 1746-UM022B-EN-P - January 2005
1-2 Module Overview
Type °C Temperature Range °F Temperature Range
S 0°C to +1768°C +32°F to +3214°F
N 0°C to +1300°C +32°F to +2372°F
CJC Sensor -25°C to +105°C -13°F to +221 °F
Millivolt Input Ranges
-50 to +50 mV
-100 to +100 mV
(1)
Each input channel is individually configured for a specific input device, and provides open-circuit, over-range, and under-range detection and indication.
Hardware Features
The module fits into any single slot for I/O modules in either an SLC 500 modular system or an SLC 500 fixed system expansion chassis (1746-A2), except the zero slot which is reserved for the processor. It
is a Class 1 module using 8 input words and 8 output words.
The module contains a removable terminal block providing connections for eight thermocouple and/or analog input devices. On the terminal block are two cold-junction compensation (CJC) sensors that compensate for the cold junction at ambient temperature. It should also be noted there are no output channels on the module. Configure the module with software rather than with jumpers or switches.
(2)
Publication 1746-UM022B-EN-P - January 2005
IMPORTANT
There is a jumper (JP1) on the circuit board. The module is shipped with the jumper in the up position as illustrated below. Do not change the position of JP1. The jumper is used for test purposes only.
(1) Output impedance of input device must be less than 100 ohm to meet accuracy specifications.
(2) Requires use of a Block Transfer when used in a remote rack with a 1747-ASB.
Module Overview 1-3
Channel Status LEDs (green)
Module Status LEDs (green)
Removable Terminal Block
CJC Sensors
Cable Tie Slots
INPUT
CHANNEL
014
5 2 123
Door Label
1746-NT8
CJC A+ CJC A­CHL 0+ CHL 0­SHIELD CHL 1+ CHL 1­CHL 2+ CHL 2­SHIELD CHL 3+ CHL 3­CHL 4+ CHL 4­SHIELD CHL 5+ CHL 5­CHL 6+ CHL 6­SHIELD CHL 7+ CHL 7­CJC B+ CJC B-
Jumper - Do not move
JP1
Self-Locking Tabs
STATUS
MODULE
THERMOCOUPLE/mV
Side Label
CAT
SERIAL NO.
1746 NT4
NT4±xxx x
THERMOCOUPLE/mV INPUT MODULE
SLC 500
SER
FRN
)
CLASS I, GROUPS A, B, C AND D, DIV.2
U
L
FOR HAZ. LOC. A196
LISTED IND. CONT . EQ.
SA
)
OPERA TING
TEMPERA TURE
CODE T3C
THERMOCOUPLE TYPES:
VOLTAGE:
INPUT SIGNAL RANGES
±100mVDC to +100mVDC
±50mVDC to +50mVDC
J, K, T, E, R, S, B, N
MADE IN USAFAC 1M
Hardware Features
Hardware Function
Channel Status LED Indicators Display operating and fault status of
channels 0 to 7
Module Status LED Displays operating and fault status of the
module
Side Label (Nameplate) Provides module information
Removable Terminal Block Provides electrical connection to input
devices

System Overview

Door Label Permits easy terminal identification
Cable Tie Slots Secure and route wiring from module
Self Locking Tabs Secure module in chassis slot
Diagnostic LEDs
The module contains diagnostic LEDs that help you identify the source of problems that may occur during power-up or during normal operation. Power-up and channel diagnostics are explained in Chapter 6, Testing Your Module.
The module communicates with the SLC 500 processor and receives +5V dc and +24V dc power from the system power supply through the parallel backplane interface. No external power supply is required. You may install as many thermocouple modules in the system as the power supply can support.
Publication 1746-UM022B-EN-P - January 2005
1-4 Module Overview
Each module channel can receive input signals from a thermocouple or a mV analog input device. You configure each channel to accept either one. When configured for thermocouple input types, the module converts analog input voltages into cold-junction compensated and linearized, digital temperature readings. The module uses National Institute of Standards and Technology (NIST) ITS-90 for thermocouple linearization.
When configured for millivolt analog inputs, the module converts analog values directly into digital counts. The module assumes that the mV input signal is linear.
System Operation
At power-up, the module checks its internal circuits, memory, and basic functions. During this time the module status LED remains off. If the module finds no faults, it turns on its module status LED.
Channel Data Word
Channel Status Word
Therm ocouple or mV Analog Signals
Thermocou ple
Input
Module
Channel Co nfiguration Word
SL C 5 00
P rocess or
After completing power-up checks, the module waits for valid channel configuration data from your SLC ladder logic program (channel status LEDs are off). After channel configuration data is transferred and channel enable bits are set, the enabled channel status LEDs turn on. Then the channel continuously converts the thermocouple or millivolt input to a value within the range you selected for the channel.
Each time the module reads an input channel, the module tests that data for a fault, i.e. over-range or under-range condition. If open circuit detection is enabled, the module tests for an open-circuit condition. If it detects an open-circuit, over-range, or under-range condition, the module sets a unique bit in the channel status word and causes the channel status LED to flash.
The SLC processor reads the converted thermocouple or millivolt data from the module at the end of the program scan, or when commanded by the ladder program. After the processor and module determine that the data transfer was made without error, the data can be used in your ladder program.
Publication 1746-UM022B-EN-P - January 2005
Module Overview 1-5
Module Operation
The module’s input circuitry consists of eight differential analog inputs, multiplexed into an A/D convertor. The A/D convertor reads the analog input signals and converts them to a digital value. The input circuitry also continuously samples the CJC sensors and compensates for temperature changes at the cold junction (terminal block).
Module Addressing
The module requires eight words each in the SLC processor’s input and output image tables. Addresses for the module in slot e are as follows:
I:e.0-7 thermocouple/mV or status data for channels 0 to 7, respectively (dependent on bit in configuration word).
O:e.0-7 configuration data for channels 0 to 7, respectively.
See Module Addressing on page 3-2 to see the module’s image table.
Publication 1746-UM022B-EN-P - January 2005
1-6 Module Overview
Block Diagram
ungrounded thermocouple
Wit hin
12.5V
grounded thermocouple
Terminal Block Module Circuitry
CJCA Sens or
+
-
+
-
Shield
+
-
+
-
Shield
+
-
Shield
multiplexer
Analog Ground
Analog to
Digital
Converter
User S elected Filter F requency
+
-
+
-
Shield
+
-
+
CJCB S ensor
-
Digital
Filter
Digital Va lue
Publication 1746-UM022B-EN-P - January 2005
IMPORTANT
When using multiple thermocouples, the potential between any two channels cannot exceed the channel-to-channel differential voltage (12.5 volts). For more information, see Appendix B.
Module Overview 1-7
Linear Millivolt Device Compatibility
(1)
A large number of millivolt devices may be used with the 1746-NT8 module. For this reason we do not specify compatibility with any particular device.
However, millivolt applications often use strain gage bridges. A resistive voltage divider using fixed resistors is recommended for this application. The circuit diagram below shows how this connection is made.
Strain Gage
Voc
+
variable
fixed
1746-NT8
Channel
Input
Bridge
fixed
+
-
fixed
TIP
The resistors should be selected to ensure that the differential input voltage is less than or equal to ±100 mV.
(1) Output impedance of input device must be less than 100 ohm to meet accuracy specifications.
Publication 1746-UM022B-EN-P - January 2005
1-8 Module Overview
Publication 1746-UM022B-EN-P - January 2005
Chapter

Installing And Wiring Your Module

Read this chapter to install and wire your module. This chapter covers:
avoiding electrostatic damage
determining power requirements
installing the module
wiring signal cables to the module’s terminal block
2

Electrostatic Damage

Electrostatic discharge can damage semiconductor devices inside this module if you touch backplane connector pins. Guard against electrostatic damage by observing the following precautions:
ATTENTION
Electrostatically Sensitive Components
Before handling the module, touch a grounded
object to rid yourself of electrostatic charge.
Handle the module from the front, away from the
backplane connector. Do not touch backplane connector pins.
Keep the module in its static-shield container
when not in use or during shipment.
Failure to observe these precautions can degrade the module’s performance or cause permanent damage.
1 Publication 1746-UM022B-EN-P - January 2005
2-2 Installing And Wiring Your Module

Power Requirements

The module receives its power through the SLC 500 chassis backplane from the fixed or modular +5 V dc/+24 V dc chassis power supply. The maximum current drawn by the module is shown in the table below.
Maximum Current Drawn by the Module
5Vdc Amps 24Vdc Amps
0.120 0.070
Considerations for a Modular System
Place your module in any slot of an SLC 500 modular, or modular expansion chassis, except for the left-most slot (slot 0) reserved for the SLC processor or adapter modules.
When using the module with a modular system, add the values shown above to the requirements of all other modules in the SLC to prevent overloading the chassis power supply. Refer to the SLC 500 Modular Hardware Style User Manual, publication 1747-UM011.
Publication 1746-UM022B-EN-P - January 2005
Fixed I/O Chassis - I/O Module Compatibility
The following chart depicts the range of current combinations supported by the fixed I/O expansion chassis. To use it, find the backplane current draw and operating voltage for both modules being used in the chassis. These specifications are found in the table alongside the chart.
Next, plot each of the currents on the chart below. If the point of intersection falls within the operating region, the combination is valid. If not, the combination cannot be used in a 2-slot, fixed I/O chassis.
OW16 and
450
400
350
300
250
Current
(mA)
at 5V dc
200
150
100
50
Example: Plot IN16 and NIO4V IN16 = 0.085 at 5V dc and 0A at 24V dc NIO4V = 0.055A at 5V dc and 0.115A at 24V dc
1. Add current draws of both modules at 5V dc to get
0.14 A (140 mA).
2. Plot this point on the chart above (140 mA at 5V dc.
3. Add current draws of both modules at 24V dc to get
0.115 A (115 mA).
4. Plot current draw at 24V dc (115 mA at 24V dc).
5. Note the point of intersection on the chart above (marked x). This combination falls within the valid operating region for the fixed I/O chassis.
(0, 455)
Valid Operating
Region
x
50 150 200
100
Current (mA) at 24V
OW16 and IA16
(180, 255)
Plotted from
Example
Shown Below
Installing And Wiring Your Module 2-3
Module Current Draw - Power Supply Loading
I/O Module
BAS .150 .040
BASn .150 .125
DCM .360 .000
FI O4I .055 .150
FI O4V .055 .120
HS .300 .000
HSTP 1 .200 .000
IA4 .035 .000
IA8 .050 .000 NR4 .050 .05 0
IA16 .085 .000
IB8 .050 .000
IB16 .085 .000
IB32 .106 .000
IC16 .085 .000
IG16 .140 .000
IH16 .085 .000
IM4 .035 .000
IM8 .050 .000
IM16 .085 .000
IN16 .085 .000
IO4 .030 .025
IO8 .060 .045
IO12 .090 .070
ITB16 .085 .000
ITV16 .085 .000
IV8 .050 .000
IV16 .085 .000
IV32 .106 .000
KE .150 .040
KEn .125
5V 24V I/O Module 5V 24V
NI4 .025 .085
NI8 .200 .100
NIO4I .055 .145
NIO4V .055 .115
NO4I .055 .195
NO4V .055 .145
120
100 55
120 70
.150
N08I N08V 120 160*
NR8
NT4 .060 .040
NT8
OA16 .370 .00 0
OA8 .185 .000
OAP 12 .370 .000
OB8 .135 .000
OB16 .280 .000
OB16E .135 .000
OB32 .452 .000
OBP8 .135 .000
OBP16 .250 .000
OG16 .180 .00 0
OV8 .135 .000
OV16 .270 .000
OV32 .452 .000
OVP 16 .250 .000
OW16 .170 .180
OW4 .045 .045
OW8 .085 .090
OX8 .085 .090
250*
* w/jumper set to rack, otherwise 0.0 mA.
Important: The 1747-NO4I and 1746-NO4V analog output modules may require an external power supply.
Publication 1746-UM022B-EN-P - January 2005
2-4 Installing And Wiring Your Module
When using the BAS or KE module to supply power to a 1747-AIC Link Coupler, the link coupler draws its power through the module. The higher current drawn by the AIC at 24V dc is shown in the table as BASn (BAS networked) and KEn (KE networked). Be sure to use these current draw values if the application uses the BAS or KE module in this way.

General Considerations

Most applications require installation in an industrial enclosure to reduce the effects of electrical interference. Thermocouple inputs are highly susceptible to electrical noises due to the small amplitudes of their signal (microvolt/°C).
Group your modules to minimize adverse effects from radiated electrical noise and heat. Consider the following conditions when selecting a slot for the thermocouple module. Position the module:
in a slot away from sources of electrical noise such as recontact
switches, relays, and AC motor drives
away from modules which generate significant radiated heat,
such as the 32-point I/O modules
In addition, route shielded twisted pair thermocouple or millivolt input wiring away from any high voltage I/O wiring.
Remember that in a modular system, the processor or communications adapter always occupies the first slot of the chassis.
Publication 1746-UM022B-EN-P - January 2005

Module Installation and Removal

ATTENTION
Installing And Wiring Your Module 2-5
Possible Equipment Operation
Before installing or removing your module, always disconnect power from the SLC 500 system and from any other source to the module (in other words, do not ’hot swap’ your module), and disconnect any devices wired to the module.
Failure to observe this precaution can cause unintended equipment operation and damage.
Top and Bottom Module Release(s)
Card Guide
To insert your module into the chassis, follow these steps:
1. Before installing the module, connect the ground wire to TB1.
See the figure on page 2-10.
2. Align the circuit board of your module with the card guides at
the top and bottom of the chassis.
3. Slide your module into the chassis until both top and bottom
retaining clips are secure. Apply firm even pressure on your module to attach it to its backplane connector. Never force your module into the slot.
Publication 1746-UM022B-EN-P - January 2005
2-6 Installing And Wiring Your Module
4. Cover all unused slots with the Card Slot Filler, Allen-Bradley
part number 1746-N2.
Terminal Block Removal
To remove the terminal block:
1. Loosen the two terminal block release screws. To avoid cracking
the terminal block, alternate between screws as you remove them.
2. Using a screwdriver or needle-nose pliers, carefully pry the
terminal block loose. When removing or installing the terminal block be careful not to damage the CJC sensors.
Publication 1746-UM022B-EN-P - January 2005
Terminal block diagram with CJC sensors
CJC Sensors
Recomm ended Torque: wiring screws: 0.25 Nm (2.2 in-lb) release scre ws: 0.25 Nm (2.2 in-lb)
Installing And Wiring Your Module 2-7
Terminal Block Release Screws
ATTENTION
CJC Sensors
Terminal Block Release Screws
Possible Equipment Operation
Before wiring your module, always disconnect power from the SLC 500 system and from any other source to the module.
Failure to observe this precaution can cause unintended equipment operation and damage.
Publication 1746-UM022B-EN-P - January 2005
2-8 Installing And Wiring Your Module

Wiring Your Module

Follow these guidelines to wire your input signal cables:
Power, input, and output (I/O) wiring must be in accordance
with Class 1, Division 2 wiring methods [Article 501-4(b) of the National Electrical Code, NFPA 70] and in accordance with the authority having jurisdiction.
Route thermocouple and millivolt signal wires as far as possible
from sources of electrical noise, such as motors, transformers, contactors, and ac devices. As a general rule, allow at least 6 in. (about 15.2 cm) of separation for every 120V ac of power.
Routing the field wiring in a grounded conduit can reduce
electrical noise further.
If the field wiring must cross ac or power cables, ensure that
they cross at right angles.
For high immunity to electrical noise, use Belden™ 8761
(shielded, twisted pair) or equivalent wire for millivolt sensors; or use shielded, twisted pair thermocouple extension lead wire specified by the thermocouple manufacturer. Using the incorrect type of convention thermocouple extension wire or not following the correct polarity may cause invalid readings.
Ground the shield drain wire at only one end of the cable. The
preferred location is at the shield connections on the terminal block. (Refer to IEEE Std. 518, Section 6.4.2.7 or contact your sensor manufacturer for additional details.)
Keep all unshielded wires as short as possible.
Excessive tightening can strip a screw. Tighten screws to 0.25
Nm (2.2 in-lb) or less, based on UL 1059, CSA C22.2 No. 158, VDE 0110B 2.79 standards.
Follow system grounding and wiring guidelines found in your
SLC 500 Modular Hardware Style User Manual, publication 1747-UM011 or 1747-SLC 500 Fixed Hardware Style User Manual, publication 1747-6.21.
Publication 1746-UM022B-EN-P - January 2005
Installing And Wiring Your Module 2-9
Preparing and Wiring the Cables
To prepare and connect cable leads and drain wires, follow these steps:
Cable
Signal Wires
(Remove foil shield and drain wire from sensor end of the cable.)
Drain Wire
Signal Wires
1. At each end of the cable, strip some casing to expose individual
wires.
2. Trim signal wires to 5-inch lengths beyond the cable casing.
Strip about 3/16 inch (4.76 mm) of insulation to expose the ends of the wires.
3. At the module end of the cables:
extract the drain wire and signal wires
remove the foil shield
bundle the input cables with a cable strap
4. Connect pairs of drain wires together:
Channels 0 and 1
Channels 2 and 3
Channels 4 and 5
Channels 6 and 7
Keep drain wires as short as possible.
5. Connect the drain wires to the shield inputs of the terminal
block if appropriate for thermocouple used.
Channel 0 and 1 drain wires to pin 5
Channel 2 and 3 drain wires to pin 10
Channel 4 and 5 drain wires to pin 15
Channel 6 and 7 drain wires to pin 20
Publication 1746-UM022B-EN-P - January 2005
2-10 Installing And Wiring Your Module
6. Connect the signal wires of each channel to the terminal block.
IMPORTANT
Only after verifying that your connections are correct for each channel, trim the lengths to keep them short. Avoid cutting leads too short.
7. Connect TB1 chassis ground connector to the nearest chassis
mounting bolt with 14 gauge wire. (Looking at the face of the module, TB1 is near the lower part of the terminal block on the primary side of the PCB.)
TB1
Connect ground wire to TB1 before installing module.
8. At the sensor end of cables from thermocouple/mV devices:
remove the drain wire and foil shield
apply shrink wrap as an option
connect to mV devices keeping the leads short.
IMPORTANT
If noise persists, try grounding the opposite end of the cable. Ground one end only.
Publication 1746-UM022B-EN-P - January 2005
Terminal Block Diagram with Input Cable
Thermocouple or mV Ca ble
Recommended Torque : TB 1 0.3 to 0.5 Nm (2.5 to 4.5 in-lb)
Installing And Wiring Your Module 2-11
CJC A+
CJC A­Channel 0+
Channel 0-
Shield for CH0 and CH 1
Channel 1+
Channel 1-
Channel 2+ Channel 2-
Shield for CH2 and CH 3
Channel 3+
Channel 3­Channel 4+
Channel 4­Shield for CH4 and CH 5
Channel 5+ Channel 5-
Channel 6+
Channel 6-
Shield for CH6 and CH 7
Channel 7+
Channel 7-
CJC B +
CJC B -
TB1
The module also has a ground terminal TB1, which should be grounded to a chassis mounting bolt with 14-gauge wire.
Cold-Junction Compensation (CJC)
ATTENTION
To obtain accurate readings from each of the channels, the cold-junction temperature (temperature at the module’s terminal junction between the thermocouple wire and the input channel) must be compensated for. Two cold-junction compensating sensors have been integrated in the removable terminal block. They must remain installed.
Possible Equipment Operation
Do not remove or loosen the cold-junction compensating temperature transducers located on the terminal block. Both CJCs are required to ensure accurate thermocouple input readings at each channel. The module will not operate in thermocouple mode if a CJC is not connected.
Failure to observe this precaution can cause unintended equipment operation and damage.
Publication 1746-UM022B-EN-P - January 2005
2-12 Installing And Wiring Your Module
Publication 1746-UM022B-EN-P - January 2005
Loading...
+ 80 hidden pages