Rockwell Automation 1746-HSCE Installation Instructions

Page 1
Installation Instructions

High-Speed Counter Module

(Catalog Number 1746-HSCE)
Inside ................................................................................................Page
For More Information............................................................................... 3
Hazardous Location Considerations ........................................................ 4
Environnements dangereux ..................................................................... 4
Dip Switch and Jumper Locations........................................................... 6
Install the Module.................................................................................. 10
Remove the Terminal Block.................................................................... 11
Wire the Removable Terminal Block...................................................... 11
Important Wiring Considerations .......................................................... 12
Input and Output Connections ............................................................... 13
Outputs................................................................................................... 14
Encoders................................................................................................. 15
Single-Ended Wiring (Discrete Devices)................................................ 18
Limit Switch Wiring............................................................................... 19
Specifications ........................................................................................ 20
Publication 1746-IN011C-EN-P - April 2005
Page 2
2 High-Speed Counter Module
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
identify a hazard
avoid a hazard
recognize the consequence
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that dangerous voltage may be present.
Labels may be located on or inside the equipment (e.g., drive or motor) to alert people that surfaces may be dangerous temperatures.
Publication 1746-IN011C-EN-P - April 2005
Page 3
High-Speed Counter Module 3

For More Information

Related Publications
For Refer to this Document Pub. No.
A more detailed description on how to configure and program the High-Speed Counter Module.
A more detailed description on how to install and use your modular SLC™ 500 system.
A reference manual that contains status file data, instruction set, and troubleshooting information.
To view and download pdfs, go to Literature Library at http://www.rockwellautomation.com/literature.
High-Speed Counter Module User Manual
SLC 500 Modular Hardware Style Installation and Operation Manual
SLC 500 Instruction Set Reference Manual
1746-6.5
1747-UM011
1747-RM001
To order printed copies, contact your Allen-Bradley® Distributor or Rockwell
®
Automation
Sales Office.
Publication 1746-IN011C-EN-P - April 2005
Page 4
4 High-Speed Counter Module

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.
WARNING
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I, Division 2.
Do not replace components or disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
Do not connect or disconnect components unless power has been switched off or the area is known to be non-hazardous.
All wiring must comply with N.E.C. article 501-4(b).

Environnements dangereux

Cet équipement est conçu pour être utilisé dans des environnements de Classe I, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
AVERTISSEMENT
DANGER D’EXPLOSION
La substitution de composants peut rendre cet équipement impropre à une utilisation en environnement de Classe I, Division 2.
Ne pas remplacer de composants ou déconnecter l'équipement sans s'être assuré que l'alimentation est coupée.
Ne pas connecter ou déconnecter des composants sans s'être assuré que l'alimentation est coupée.
Publication 1746-IN011C-EN-P - April 2005
Page 5
High-Speed Counter Module 5

High-Speed Counter Module Overview

The High-Speed Counter Module, Catalog Number 1746-HSCE is an SLC 500 family compatible device except with the 1747-ASB Remote I/O Adapter Module. It can be used with SLC 5/02 (and above) processors.
The module’s bidirectional counting ability allows it to detect movement in either direction. In addition, x2 and x4 counting modes are provided to fully use the capabilities of high-resolution quadrature encoders.
High-speed inputs from quadrature encoders and various high-speed switches are supported. Accepting input pulse frequencies of up to 50k Hz allows precise control of fast motions.
In addition, an Accumulated Counter, the module provides a Rate Counter to determine Rate Measurement by indicating the pulse input frequency in Hz. (See the block diagram on page 6.) The Rate Measurement is determined by accumulating input pulses over a fixed period of time. You set the Rate Period to best match your application requirements.
Background Rate calculation is provided in Sequencer and Range Modes. This operation accepts input rates up to 32,767 Hz. The dynamically configurable Rate Period ranges from 10 ms to 2.55 seconds.
The module’s four current sink (open collector) outputs can be controlled in the user program or the module.
Control of the counter reset is configured through user-set parameters. The counter can be reset from any combination of the Z input, Limit Switch input, or Soft Reset control bits.
Module operation is determined by selections made in the Setup and Control Word (M0:e.1). Setting the Function Control bit to 1 triggers the module to start the proper pulse counter, rate measurement, and output control functions. Many parameters are dynamic and can be changed without disrupting counter operation.
The module’s block diagram is shown on page 6. Inputs from the terminal block enter the diagram at the left, outputs to the terminal block exit at the right. M0 and Output file parameters from the SLC enter the logic blocks from the top. Input file data to the SLC exit the logic blocks from the bottom.
Publication 1746-IN011C-EN-P - April 2005
Page 6
6 High-Speed Counter Module

Dip Switch and Jumper Locations

Counter
Input
Parameters
Input
Logic
Reset Parameters
Reset Logic
alues (M0:e.10 – 33)
alues (M0:e.10 – 33) –d
Pulse and Direction
Reset
1)
A B
Z
From Terminal Block
LS
LS
Filter (JW1)
Counter
Input Parameters
Input T
ype (M0:e.1/9–1
Up/Down Count Direction (M0:e.1/3)
Reset Parameters
Soft Reset bit (M0:e.1/4) –d Reset Mode (M0:e.1/5–7)
Rate Period Parameters
Rate Period (M0:e.9/0–7 or M0:e.16/0–7)
Operating Mode Parameters
Operating Mode (M0:e.1/14–15) Function Control Bit (M0:e.1/12) Range Definitions:
Range Starting V Range Ending V Range Outputs (M0:e.3 – 8) –d V
alid Ranges (M0:e.2) –d
Sequencer Definitions:
V
alid Steps (M0:e.2 and M0:e.3/0–7) –d Step Presets (M0:e.17 – 40) Step Outputs (M0:e.4 – 15) Initial Outputs (M0:e.3/8–15) Sequencer Reset (M0:e.1/0)
Reset Input
Condition
Bit
–d
–d
–d
–d
Rate Period Parameters
Pulse Counter Parameters
–d
–d
–d
Rate Measurement
Rate
Counter
Rate
Counter
Inputs
Accumulated Count
Pulse
Counter
Pulse
Counter
Inputs
Pulse Counter Parameters
Reset V
alue (M0:e.34 or M0:e.41) –d Maximum Count V Counter Hold bit (M0:e.1/2) Counter Type bit (M0:e.1/13)
Output Control Parameters
Direct Outputs (O:e.0/0–7) Output Source Select (M0:e.0/0–7) Enable Outputs bit (M0:e.1/1)
Rate Counter Inputs
Rate Valid (I:e.0/3) Rate Counter Overflow (I:e.0/4) Rate Measurement Overflow (I:e.0/5) Zero Rate Period Count (I:e.0/2) Rate Period Count (I:e.2) Rate Measurement (I:e.3)
Pulse Counter Inputs
Accumulated Count (I:e.1) Overflow/Underflow (I:e.0/13) Pulse Counter State (I:e.0/14–15)
Operating
Mode Parameters
Operating Mode Logic
Rate
Sequencer
Range
alue (M0:e.34 or M0:e.41)
–d
–d
–d
–d
Output Control
Parameters
Operating
Mode
Output
Outputs
Control
Logic
Output Status Inputs
Operating
Mode Inputs
Reset Input bit
Operating Mode Inputs
Output Status Inputs (
Error Inputs
(I:e.0/12)
Sequencer Inputs
Current Sequencer Step (I:e.5/0–7) Next Sequencer Step (I:e.5/8–15) Sequence Done (I:e.0/6)
Range inputs
Ranges Active (I:e.6/0–1
I:e.4/8–15)
Critical Error (I:e.0/10) Configuration Error bit (I:e.0/1 Configuration Error Code (I:e.4/0–7)
4 Physical Outputs
1)
1)
–d indicates a dynamic parameter
To Terminal Block
Two dip switches (SW1 and SW2) and one jumper (JW1) are located on the side of the module.
SW1 selects the type of input (single ended or differential).
SW2 selects the output voltage range (4.5 to 10V dc or 10 to 30V dc).
JW1 selects the filtering rate (300 µs or 10 ms) used to debounce the limit
switch input.
Publication 1746-IN011C-EN-P - April 2005
Page 7
Default settings are shown below:
g
N
O
SW2 Default 10 to 30V dc
3
JW1
1
JW1 Default
10 ms filter
N
SW 1
SW1 Default Sin
le-ended
1 234
O
1234
SW 2
High-Speed Counter Module 7
SW 2
JW 1
JW 1
ATTENTION
Use a small screwdriver to change dip switch positions. Graphite from pencils will damage the switch.
Publication 1746-IN011C-EN-P - April 2005
Page 8
8 High-Speed Counter Module
SW2 Settings
Select an output voltage range that coincides with your supply voltage. The selections are 4.5 to 10V dc or 10 to 30V dc.
ON
OFF
ON
OFF
ATTENTION
1234
10 to 30V dc
1234
4.5 to 10V dc
Switch 1234
Output 0123
All switches of SW2 must be ON or all switches must be OFF. Permanent damage may result if some are ON and some are OFF.
Operating in the 10 to 30V dc range with the switches set for the
4.5 to 10V dc range damages the module.
SW1 Settings
Select a single-ended or differential input connection.
ON
OFF
1234
Dip switch SW1
Switch 1234
Channel A B Z not used
Position Input Connection Input ON Range
ON
OFF
differential 2.8 to 4.5V dc
single-ended 3.1 to 5.5V dc
You can configure different inputs in different modes. For example, input A (CHA) can be configured as differential and input Z (CHZ) can be configured as single-ended.
Publication 1746-IN011C-EN-P - April 2005
Page 9
High-Speed Counter Module 9
JW1 Settings
Select 300 µs or 10 ms filtering to debounce the limit switch input. Position the jumper as follows:
321 32 1
JW 1
10 ms filter
The LS input allows you to make a direct connection to nominal voltage levels of 5, 12, or 24V dc. The ON voltage ranges are as follows:
Wiring Terminal ON Range
LS (24V dc) 16.5 to 30V dc
LS (12V dc) 9.4 to 16.5V dc
LS (5V dc) 3.8 to 5.5V dc
See page 19 for limit switch wiring instructions.
JW 1
300 µs filter
ATTENTION
Connect only one LS input range at a time, or the module will be damaged.
Publication 1746-IN011C-EN-P - April 2005
Page 10
10 High-Speed Counter Module

Install the Module

Installation procedures for this module are the same as for any other discrete I/O or specialty module.
IMPORTANT
ATTENTION
Set the dip switches before installing the module.
Disconnect power before attempting to install, remove, or wire the module.
Make sure your SLC power supply has adequate reserve current capacity. The module requires 320 mA at 5V dc.
Top and Bottom
Module Release(s)
Card Guide
1. Align the full-size circuit board with the chassis card guide. The first slot of the first chassis is reserved for the CPU.
2. Slide the module into the chassis until the top and bottom latches are latched.
Make sure the removable terminal wiring block is attached to the module and all wires are connected to the terminal block.
3. Insert the cable tie in the slots and secure the cable.
4. Cover all unused slots with the Card Slot Filler, Catalog Number 1746-N2.
Publication 1746-IN011C-EN-P - April 2005
Page 11
High-Speed Counter Module 11

Remove the Terminal Block

The removable terminal wiring block eliminates the need to rewire a module if it is removed from the chassis. Each terminal accepts two #14 AWG wires.
ATTENTION
Remove the terminal block by turning the slotted terminal block release screws counterclockwise. The screws are attached to the terminal block, so it will follow as the screws are turned out.
Disconnect power before attempting to install, remove, or wire the removable terminal wiring block.
To avoid cracking the removable terminal block, alternate the removal of the slotted terminal block release screws.

Wire the Removable Terminal Block

Use a flat or cross slot screwdriver to tighten terminal screws. Each screw should be turned tight enough to immobilize the wire’s end. Overtightening can strip the terminal screw. Do not exceed 0.7 to 0.9 Nm (6 to 8 in-lbs.).
Publication 1746-IN011C-EN-P - April 2005
Page 12
12 High-Speed Counter Module

Important Wiring Considerations

Use the following guidelines when planning the system wiring for the module:
Install the SLC 500 system in a NEMA-rated enclosure.
Disconnect power to the SLC processor and the module before wiring.
Make sure the SLC 500 system is properly grounded.
Group this module and low-voltage DC modules away from AC I/O or
high-voltage DC modules.
Shielded cable is required for high-speed input signals A, B, and Z. We recommend Belden 9503 or equivalent for lengths up to 305 m (1000 ft).
When the LS input is driven by an electromechanical device, route the wiring away from other inputs. In addition, JW1 should be set for the 10 ms filter.
When the LS input is driven by a solid-state device, use a shielded cable. You do not have to route the cable away from other inputs.
Shields should be grounded only at the end of the signal source end of the cable. Ground the shield to the case of the signal source, so energy coupled to the shield will not be delivered to signal source’s electronics.
Publication 1746-IN011C-EN-P - April 2005
Page 13
High-Speed Counter Module 13

Input and Output Connections

Input and output wiring terminals are located on the front of the module, behind the terminal cover. When you connect input and output devices, you must also be concerned with the settings of dip switch SW1 (input connections), dip switch SW2 (output connections), and jumper JW1 (limit switch input connections). The location and description of these are shown on pages
OUTPUT INPUT
Upper Retaining Screw Maximum Torque = 0.7 to 0.9 Nm (6 to 8 in-lbs)
HSCE
6 through 9.
4
0ABZ 1
5 6
2 3
7
LS
FAULT
Discrete Output Wiring
NOTE: V dc must be externally supplied by the user. See page 14 for output wiring.
Terminal Wiring
max. 2 wires per terminal max. torque: 0.9 Nm (8 in-lbs)
Limit Switch and Encoder Input Wiring
See pages 15 through 19 for input wiring.
Lower Retaining Screw Maximum Torque = 0.7 to 0.9 Nm (6 to 8 in-lbs)
VDC OUT 0 OUT 1 OUT 2 OUT 3
DC COM
Not used
Not used
LS (24 V DC )
LS (12 V DC )
LS COM
LS (5 VDC )
A+ B+ A­B-
Z+
VDC
OUT 0
OUT 1
OUT 2
OUT 3
DC
COM
A+
B+
A-
B-
Not
Not
Used
Used
Z+
LS
Z-
Z-
LS
COM
(24V dc)
LS
(12V dc)
LS
(5V dc)
Publication 1746-IN011C-EN-P - April 2005
Page 14
14 High-Speed Counter Module

Outputs

The module features four physical outputs. They can be controlled by the module when certain counter conditions are met, or they can be controlled from the user program (refer to the High-Speed Counter Module User Manual, publication 1746-6.5 for M0:e.0 information).
The outputs are bipolar transistors connected in a sinking (open collector sinking) configuration. When the output is energized, it sinks the current.
ATTENTION
Do not use incandescent lamps as output indicators. The high peak inrush current required to heat the filament can damage the module’s output circuits. Use LED indicators that satisfy the output circuit ratings, such as Allen-Bradley 800A and 800T LED indicators.
You can select an output voltage range of 4.5 to 10V dc or 10 to 30V dc. Refer to page 21 for the maximum current specifications for each voltage range. Dip switch SW2, located on the PC board, is used to select the voltage range. See pages 6 and 8 for switch SW2 location and settings.
The figure below indicates wiring connections for four 24V dc outputs. All switches of SW2 are OFF for this output voltage.
VDC
OUT 0
User Supplied 24V dc
+
-
OUT 1
OUT 2
OUT 3
DC COM
wiring terminals
All switches OFF
ON
OFF
HSCE module
1234
Dip Switch SW2
The outputs are not electrically isolated from each other. (They are referenced to the same output common terminal.) However, outputs are isolated from the rest of the circuitry to a level of 1500 volts.
Publication 1746-IN011C-EN-P - April 2005
Page 15
High-Speed Counter Module 15
Z

Encoders

The wiring diagrams on the following pages are provided to support the Allen-Bradley encoders you may already have. Differential encoders provide the best immunity to electrical noise.
Differential Encoder Wiring
(1)
cable
VS
GND
Belden 9503 or equivalent
305m (1000ft) max length
(2)
Shield
Allen-Bradley 845H Series differential encoder
A
A
B
B
Z
Z
encoder connector
Earth
(1) Refer to your encoder manual for proper cable type and length.
(2) Due to the topology of the module’s input circuits, terminating the shield at the encoder end provides the highest immunity
to EMI interference. Connect EARTH ground directly to the encoder connector housing.
Differential Encoder Output Waveforms
The illustration below shows the different encoder output waveforms. If your encoder matches these waveforms, the encoder signals can be directly connected to the associated screw terminals on the module. For example, the A lead from the encoder is connected to the module’s A+ screw. If your encoder does not match these waveforms, some wiring modifications may be necessary. Refer to the High-Speed Counter Module User Manual, publication 1746-6.5 for a description of these modifications.
+VDC
COM
A(+)
A(-)
B(+)
B(-)
Z(+)
Z(-)
Power Supply
SW1
ON
1 2 3 4
OFF
(all switches
Module Inputs
A A
B B
Z
Publication 1746-IN011C-EN-P - April 2005
Page 16
16 High-Speed Counter Module
Single-Ended Encoder Wiring (Open Collector)
(1)
VS
GND
(3)
R
A
B
cable
Shield
(2)
Allen-Bradley 845H Series
Z
single-ended encoder
Belden 9503 or equivalent 305m (1000tft) max length
encoder connector housing
Earth
(1) Refer to your encoder manual for proper cable type and length.
(2) Due to the topology of the module’s input circuits, terminating the shield at the encoder end provides the highest immunity
to EMI interference. Connect EARTH ground directly to the encoder connector housing.
(3) The pullup resistor (R) value depends on the power supply value (VS). The table below lists the resistor values for typical
power supply values. These resistors must be located at the encoder end of the cable.
+VDC
COM
A(+) A(-)
B(+) B(-) Z(+) Z(-)
Power Supply
ON
SW1
OFF
(All switches OFF)
Module Inputs
1 2 3
4
VS Value R Value Maximum Output Leakage
+5V dc 150 ohm 1/4W 5% 6.3 mA
+12V dc 1800 ohm 1/4W 5% 1.5 mA
+24V dc 4700 ohm 1/4W 5% 1.2 mA
Single-Ended Encoder Output Waveforms
The figure below shows the single-ended encoder output waveforms. When the waveform is low, the encoder output transistor is ON.
low = transistor ON high = transistor OFF
Publication 1746-IN011C-EN-P - April 2005
A
B
Z
Page 17
High-Speed Counter Module 17
Single-Ended Encoder Wiring (Sourcing)
(1)
Shield
(2)
cable
R
R
R
+VDC
(3)
(3)
(3)
COM
A(+) A(-) B(+)
B(-) Z(+) Z(-)
Power Supply
ON
SW1
OFF
(All switches OFF)
Module Inputs
12 34
VS
GND
Belden 9503 or equivalent 305m (1000tft) max length
A
single ended
(4)
encoder
(1) Refer to your encoder manual for proper cable type and length.
(2) Due to the topology of the module’s input circuits, terminating the shield at the encoder end provides the highest immunity
(3) The resistor (R) value depends on the power supply value (VS). The table below lists the resistor values for typical power
supply values. These resistors must be located at the encoder end of the cable.
B
Z
Earth
(4) The Allen-Bradley 845H sourcing encoder is not compatible with this module.
VS Value R Value Maximum Output Leakage
+5V dc no resistor needed 100 µA
+12V dc 1800 ohm 1/4W 5% 100 µA
+24V dc 4700 ohm 1/4W 5% 100 µA
Single-Ended Encoder Output Waveforms (Sourcing)
The figure below shows the single-ended encoder output waveforms. When the waveform is low, the encoder output transistor is OFF.
low = transistor OFF high = transistor ON
A
B
Z
Publication 1746-IN011C-EN-P - April 2005
Page 18
18 High-Speed Counter Module

Single-Ended Wiring (Discrete Devices)

proximity sensor with sourcing output
VS OUT COM
VS
OUT CO M
solid-state switch (5V output)
R2
R1
VS OUT COM
+VDC
CO M
A(+)
A(-)
B(+)
B(-)
Z(+)
Z(-)
Power Supply
photoelectric sensor with open collector sinking output
IMPORTANT
ON
SW1
1 2 34
OFF
(All switches OFF)
Module Inputs
This diagram shows the sensors operation from a common power supply. Separate power supplies for each circuit can be used.
The resistor (R1) value depends on the power supply value (VS). The table on page
17 provides the resistor values for typical power supply values. These resistors must be located at the module end of the cable.
The pull-up resistor (R2) value depends on the power supply value (VS). The table on page
16 provides the resistor values for typical power supply values. These resistors must be located at the sensor end of the cable.
Publication 1746-IN011C-EN-P - April 2005
Page 19

Limit Switch Wiring

High-Speed Counter Module 19
ATTENTION
Connect only one LS input range at a time, or the module will be damaged.
24V dc Hard Contact
Hard Contact Limit Switch
VS
24V dc
+
-
COM
Do not connect LS (5V dc) or LS (12V dc) Terminals
12V dc Hard Contact
Hard Contact Limit Switch
VS
12V dc
+
-
COM
Do not connect LS (5V dc) or LS (12V dc) Terminals
LS (24V dc)
LS (12V dc)
LS (5V dc)
LS COM
LS (24V dc)
LS (12V dc)
LS (5V dc)
LS COM
HSCE module
Jumper placed for 10 ms filtering
HSCE module
Jumper placed for 10 ms filtering
321
JW1
321
JW1
5V dc Solid State
VS
5V dc
+
-
COM
Solid State Limit Switch
COM
OUT
LS (24V dc)
VS
Do not connect LS (12V dc) or LS (24V dc) Terminals
LS (12V dc)
LS (5V dc)
LS COM
HSCE module
Jumper placed for 300 µs filtering
321
JW1
Publication 1746-IN011C-EN-P - April 2005
Page 20
20 High-Speed Counter Module

Specifications

General
Description Specification
Operating Temperature 0° C to +60° C (+32° F to +140° F)
Storage Temperature -40° C to +85° C (-40° F to +185° F)
Humidity 5 to 95% without condensation
Backplane Current Consumption (power supply loading)
Maximum Cable Length
Agency Certification (when product or packaging is marked)
(1) Belden 9503 or equivalent
(1)
Inputs A, B, and Z
320 mA at +5V dc 0 mA at +24V dc
305 m (1000 ft)
CSA certified
CSA Class I, Division 2 Groups A, B, C, D
UL® listed
CE marked for all applicable directives
Differential (Switch 1 on)
Input Voltage ±5V dc
On-State Voltage 2.8 to 4.5V dc 3.1 to 5.5V dc
Off-State Voltage -5.5 to 0.8V dc 0 to 0.8V dc
Max Off-State Leakage Current 100 µA 600 µA
Input Current (mA) 2.5 mA at 2.8V dc
7.5 mA at 4.5V dc
Nominal Input Impedance 700 825
Min. Pulse Width 10 µs
Min. Phase Separation
Max. Input Frequency Sequencer and Range Rate
Isolation (from backplane) 1500 volts
(1) 12 and 24 volts must be used with a pull-up resistor.
(2) Channel A to channel B.
(1)
4.5 µs
50k Hz
32.767k Hz
Single Ended (Switch 1 off)
0 to 5V dc
2.5 mA at 3.1V dc
7.5 mA at 5.5V dc
Publication 1746-IN011C-EN-P - April 2005
(2)
Page 21
High-Speed Counter Module 21
Limit Switch Input
5V dc 12V dc 24V dc
On-State Voltage 3.8 to 5.4V dc 9.4 to 16.5V dc 16.5 to 30V dc
Off-State Voltage 0 to 1.2V dc 0 to 2.4V dc 0 to 3.9V dc
Input Current minimum nominal maximum
Max. Off-State Leakage Current 1 mA (all ranges)
Isolation (from backplane) 1500 volts
4.6 mA
6.8 mA
9.2 mA
Outputs (Open Collector, Sinking)
4.5 to 10V dc (Switch 2 on)
Max. On-State Output Current 16 mA at 4.5V dc
40 mA at 10V dc
Max. On-State Voltage Drop 0.4V dc 1.0V dc
Max. Off-State Leakage Current 100 µA
Isolation (from backplane) 1500 volts
10 to 30V dc (Switch 2 off)
40 mA at 10V dc 125 mA at 30V dc
Publication 1746-IN011C-EN-P - April 2005
Page 22
22 High-Speed Counter Module
Publication 1746-IN011C-EN-P - April 2005
Page 23
High-Speed Counter Module 23
Publication 1746-IN011C-EN-P - April 2005
Page 24
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running.
, you can find
United States 1.440.646.3223
Outside United States
Monday – Friday, 8am – 5pm EST
Please contact your local Rockwell Automation representative for any technical support issues.
New Product Satisfaction Return
Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning, it may need to be returned.
United States Contact your distributor. You must provide a Customer Support case number
Outside United States
Rockwell Automation, Allen-Bradley, SLC 500, SLC, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1746-IN011C-EN-P - April 2005 PN 40071-130-01(3)
Supersedes Pub lication 1746-IN011B-EN -P - April 1999 Copyright © 2007 Rockwell Autom ation, Inc. All rights res erved. Printed in Singapore.
(see phone number above to obtain one) to your distributor in order to complete the return process.
Please contact your local Rockwell Automation representative for return procedure.
Loading...