Rockwell Automation 1746-FIO4V User Manual

SLC 500 Fast Analog I/O Module
Catalog Numbers 1746-FIO4I and 1746-FIO4V
User Manual

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com
) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
IMPORTANT
ATTENTION
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
SHOCK HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Rockwell Automation, Allen-Bradley, TechConnect, RSLogix500, SLC, SLC 500, and SLC 5/02 are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Quick Start
Install and Wire the Modules

Table of Contents

Preface
About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . 5
Additional Resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Chapter 1
Required Tools and Equipment . . . . . . . . . . . . . . . . . . . . . . . 7
Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Chapter 2
Determine the Module’s Power Requirements . . . . . . . . . . . 11
Determine Compatibility with Other I/O Modules. . . . . . . . . 12
Configure Input Channels . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Select the I/O Rack Slot. . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Install the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Considerations When Wiring . . . . . . . . . . . . . . . . . . . . . . . . 16
Minimize Electrical Noise Interference . . . . . . . . . . . . . . . . . 18
Wire the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Minimize Ground Loops . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Label the Terminal Block. . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Access Files to Configure I/O
Processor and Module Considerations
Write Ladder Logic
Chapter 3
Click and Drag Configuration . . . . . . . . . . . . . . . . . . . . . . . 23
Read IO Config Method. . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Chapter 4
Processor Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Module Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Chapter 5
Retentive and Non-retentive Programming . . . . . . . . . . . . . . 39
Detect an Out-of-range Input. . . . . . . . . . . . . . . . . . . . . . . . 41
Overview of Scaling Inputs and Outputs . . . . . . . . . . . . . . . 42
Scale an Analog Input and Detect an Out-of-range Condition 44
Scale an Analog Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Scale Offsets When >32,767 or <32,768. . . . . . . . . . . . . . . . 49
Range-check an Analog Input and Scale It for an Output . . . 52
PID Control with Analog I/O Scaling . . . . . . . . . . . . . . . . . . 56
3 Publication 1746-UM009B-EN-P - September 2007
4 Table of Contents
Calibrate the Module
Test Module Operation
Maintenance and Safety
Module Specifications
2’s-complement Binary Numbers
Chapter 6
Calibration Tradeoffs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Calibrate an Analog Input Channel . . . . . . . . . . . . . . . . . . . 62
Chapter 7
Test the SLC 500 System . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Test the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Chapter 8
Preventive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Safety Considerations When Troubleshooting. . . . . . . . . . . . 76
Appendix A
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Appendix B
Use 2’s-complement Binary Numbers. . . . . . . . . . . . . . . . . . 83
Module Input and Output Circuits
Appendix C
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Index
Publication 1746-UM009B-EN-P - September 2007

Preface

About This Publication

Read this preface to familiarize yourself with the rest of the manual. This preface covers the following topics:
Who should use this manual
The purpose of this manual
Terms and abbreviations
Conventions used in this manual
Allen-Bradley support
This manual is a reference guide for the 1746-NR4 RTD/Resistance Input Module. The manual:
gives you an overview of system operation.
explains the procedures you need to install and wire the module
at the customer site.
provides ladder programming examples.
provides an application example of how this input module can
be used to control a process.

Who Should Use This Manual

Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Allen-Bradley small logic controllers.
You should have a basic understanding of SLC 500 products. You should understand programmable controllers and be able to interpret the ladder logic instructions required to control your application. If you do not, contact your local Allen-Bradley representative for information on available training courses before using this product.
5 Publication 1746-UM009B-EN-P - September 2007
6 Preface

Additional Resources

The following documents contain information that may be helpful to you as you use Allen-Bradley SLC products.
Resource Description
SLC 500 Systems Selection Guide, publication 1747-SG001
SLC 500 Module Hardware Style User Manual, publication 1747-UM011
Installation & Operation Manual for Fixed Hardware Style Programmable Controllers, publication 1747-6.21
SLC 500 Instruction Set Reference Manual, publication 1747-RM001
SLC 500 4-Channel Analog I/O Modules User’s Manual, publication 1746-UM005
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Application Considerations for Solid-State Controls. publication SGI-1.1
National Electrical Code, published by the National Fire Protection Association of Boston, MA
An overview of the SLC 500 family of products
A description on how to install and use your modular SLC 500 programmable controller
A description on how to install and use your fixed SLC 500 programmable controller
A reference manual that contains status file data, instruction set, and troubleshooting information about the software
A resource manual and user’s guide containing information about the analog modules used in your SLC 500 system.
In-depth information on grounding and wiring Allen-Bradley programmable controllers
A description of important differences between solid-state programmable controller products and hard-wired electromechanical devices
An article on wire sizes and types for grounding electrical equipment

Conventions

You can view or download publications at http://literature.rockwellautomation.com
. To order paper copies of technical documentation, contact your local Rockwell Automation distributor or sales representative.
The following conventions are used throughout this manual:
Bulleted lists such as this one provide information, not procedural steps.
Numbered lists provide sequential steps or hierarchical information.
Publication 1746-UM009B-EN-P - September 2007
Chapter
1
Quick Start
This chapter presents an overview of installation and start-up procedures to help you get the module working quickly.
It refers to full procedures in corresponding chapters of this manual or in other SLC documentation that may be helpful if you are unfamiliar with programming techniques or system installation.
We recommend that you use this chapter in either of two ways.
Use as a fast installation and start-up guide for the experienced users.
Use as an overview for using the entire manual for the first-time user.

Required Tools and Equipment

IMPORTANT
Have the following tools and equipment ready.
Medium flat-head screwdriver
Medium Phillips-head screwdriver
Wire strippers
Utility knife
Hot-air blower
Shrink wrap
Belden 8761 cable or equivalent
Analog I/O devices for your application
I/O modules (1746-FIO4I and/or 1746-FIO4V)
Programming software
If you have any questions about the abbreviated procedures presented in this chapter, always read the referenced chapters and other recommended documentation before trying to apply the information.
7 Publication 1746-UM009B-EN-P - September 2007
8 Quick Start

Procedures

Follow these steps to get your module running in your SLC system.
1. Plan the inclusion of analog I/O modules in your SLC system.
If a new system, specify the type of processor, number of I/O racks, I/O modules, and power supply. If adding to an existing system:
assign modules to slot locations in the I/O rack.
verify that the power supply for the I/O rack can handle the
increased load.
See SLC 500 Systems Selection Guide, publication 1747-SG001, for more information.
2. Configure module input channels for current or voltage
operation.
Locate the 2-switch assembly on the module’s circuit board, and set each channel as follows.
Current (ON)
12
O N
Switch 1 = Channel 0 Switch 2 = Channel 1
Voltage (OFF)
3. Connect I/O devices with cables.
IMPORTANT
Connect only one end of the cable shield to earth ground.
Channels are not isolated from each other. All analog commons are
connected together internally.
The module does not provide loop power for analog inputs.
Use a power supply that matches the transmitter (sensor)
specifications.
Refer to Install and Wire the Modules on page 11.
Publication 1746-UM009B-EN-P - September 2007
For Differential Inputs
+
Analog Sensor
Earth Ground
Load
For Single-ended Input with 3-wire Transmitter
+
Power
Supply
Transmitter
GND
Important: Jumper unused inputs.
Important: Do not jumper unused outputs.
SignalSupply
Earth Ground
Quick Start 9
Module
0 1 2
3 4 5
6 7 8
9 10 11
Module
3
4
5
IN 0 + IN 0 – ANL COM
IN 1 + IN 1 – ANL COM
Not Used OUT 0 ANL COM
Not Used OUT 1 ANL COM
IN + IN – ANL COM
4. Configure the system I/O and module ID.
With the software, configure the processor, I/O racks, slots, and I/O modules.
When assigning an I/O module to a slot location, select the module from the displayed list. If not listed, select OTHER at the bottom of the list and enter the module’s ID code at the prompt.
ID code for 1746-FIO4I is 3224 ID code for 1746-FIO4V is 3218
5. Understand A/D & D/A converter resolution on input and
output words.
The module’s I/O channel converters limit bit usage to less than a full 16-bit word.
The input channel converter resolution is 12 bits, where the highest four bits are always zero.
The output channel converter resolution is 14 bits, where the lowest two bits are never used.
Publication 1746-UM009B-EN-P - September 2007
10 Quick Start
The lowest two bits have no effect on the output value.
Refer to Processor and Module Considerations on page 29 for more information.
SLC 500 Processor Data Files
Input Image (2 words)
Output Image (2 words)
Address
I:1.0 I:1.1
lsb
Channel 0 Input Word
Channel 1 Input Word
Address
O:1.0 O:1.1
0000
Bit 15 Bit 11 Bit 0
Channel 0 Output Word
Channel 1 Output Word
(variable input data)msb
variable output data)msb lsb
Bit 15 Bit 2 Bit 0
6. Write ladder logic to process the module’s analog data.
We provide several programming examples that include the following:
Clear the output when changing mode or cycling power
Detect an out-of-range input
Scale analog outputs
Scale offsets
Scale and range-check analog inputs and outputs
PID control with analog I/O scaling
X
X = not used
X
Publication 1746-UM009B-EN-P - September 2007
Study these examples to understand how to program the module.
Refer to Write Ladder Logic on page 39.
7. (Optional) Write ladder logic to maintain calibrated inputs.
We show you how to write ladder logic that provides a calibrated input reference during runtime, and lets you periodically calibrate module inputs. We suggest that you modify the logic examples to suit your application and add them to your application program.
Refer to Calibrate the Module on page 61 for more information.
Chapter
2
Install and Wire the Modules
This chapter describes procedures to install fast analog I/O modules in an SLC 500 system. The procedures include the following tasks.
determine the module’s power requirements
determine compatibility with other I/O modules
configure input channels
select the I/O rack slot
install the module
consider when wiring
using system wiring guidelinesgrounding the cabledetermining cable length
minimize electrical noise interference
wire the module
minimize ground loops
label the terminal block

Determine the Module’s Power Requirements

Analog modules require power from the 5V dc and 24V dc backplane power supplies of the SLC 500 system. This table shows the backplane power requirements for fast analog I/O modules.
Current Load
Catalog Number Current at 5V dc Current at 24V dc
1746-FIO4I 55 mA 150 mA
1746-FIO4V 55 mA 120 mA
Use this table to compute the module’s portion of total load on the modular system power supply.
For more information, refer to SLC 500 Systems Selection Guide, publication 1747-SG001.
11 Publication 1746-UM009B-EN-P - September 2007
12 Install and Wire the Modules

Determine Compatibility with Other I/O Modules

Use the I/O Compatibility chart when using the expansion rack of a fixed controller (1747-L20, 1747-L30, and 1747-L40). The chart determines compatibility of other I/O modules with fast analog modules. Compatibility is solely based on current drawn from the backplane.
For more information, refer to the SLC 500 Fixed Hardware Style Installation and Operation Manual, publication 1747-6.21.
I/O Compatibility
1746-FIO4I 1746-FIO4V 1746 Module
FIO4I
FIO4V
(1)
•• IB8, IB16
•• IB32
•• IG16
•• IM4, IM8, IM16
IA4, IA8, IA16
•• IN16
•• IO4
IO8
IO12
•• ITB16, ITV16
•• IV8, IV16, IV32
NIO4I, NIO4V
(2)
•• NR4
•• NT4
•• OA8
•• OB8
•• OG16
OBP16
NO4I, NO4V
NI4
OA16
OB16, OB32
Publication 1746-UM009B-EN-P - September 2007
•• OV8
OV16
OV32
Install and Wire the Modules 13
I/O Compatibility
1746-FIO4I 1746-FIO4V 1746 Module
OW4
OW8, OW16
BASIC
KE
(1)
The symbol indicates an allowable combination of 1746 I/O modules.
(2)
The symbol indicates an auxiliary 24V dc power supply may be needed.
OX8
BASn
DCM
HS
KEn

Configure Input Channels

Your fast analog I/O modules have a two-switch assembly to configure the input channels for either current or voltage operation. The switches are on the module’s circuit board. Switch orientation is shown on the nameplate of the module.
Switch Orientation
ON – Configures channel for current input
OFF – Configures channel for voltage input
Switches labeled 1 and 2 control the input mode of channels 0 and 1 respectively.
Channels 0 and 1 Input Mode
Current (ON)
12
O N
Voltage (OFF)
Switch 1 = Channel 0 Switch 2 = Channel 1
Publication 1746-UM009B-EN-P - September 2007
14 Install and Wire the Modules

Select the I/O Rack Slot

Install the Module

Two factors determine where you should locate the module in the I/O rack: ambient temperature and electrical noise. Consider the following conditions when selecting an I/O rack slot for the module. Position the module:
in a slot away from ac or high voltage dc modules.
away from the rack power supply if installed in a modular system.
in the I/O rack lowest in the enclosure for a cooler ambient.
When installing the module in an I/O rack, you do not need to remove the terminal block from the module. However, if the terminal block is removed, use the write-on label located on the side of the terminal block to identify the module location and type. To remove the terminal block, grasp it on the top and bottom and pull outward and down.
ATTENTION
Never install, remove, or wire modules with power applied to the I/O rack. Rid yourself of electrostatic charge before handling the module. Electrostatic discharge can degrade module performance or destroy analog circuitry.
IMPORTANT
Follow these steps when installing or removing the module.
1. Verify that input configuration switches 1 and 2 are set correctly.
ATTENTION
2. Align the module’s circuit board with the rack’s card guide.
See Installing the Module on page 15.
3. Slide the module in until top and bottom retaining clips are
secured.
Do not tamper with the module’s factory-sealed potentiometer. It does not require any adjustments.
Take care to avoid connecting a voltage source to a channel configured for current input. This could result in improper module operation or damage to the module.
Publication 1746-UM009B-EN-P - September 2007
Install and Wire the Modules 15
4. To remove the module, press the retaining clips at the top and
bottom of the module and slide the module out.
Installing the Module
Card Guide
Self-locking tabs secure the module in the I/O rack.
Publication 1746-UM009B-EN-P - September 2007
16 Install and Wire the Modules

Considerations When Wiring

This section provides guidelines on wiring the system, grounding the cables, determining cable length.
ATTENTION
Before wiring the module, disconnect SLC system power, I/O rack power, and module power.
System Wiring Guidelines
Use the following guidelines in planning the system wiring to the module.
Analog common terminals (ANL COM) are electrically interconnected inside the module, but not internally connected to earth.
Voltages on IN+ and IN– terminals must be within 0…20V with respect to ANL COM to ensure proper input channel operation. This is true for current and voltage input channel operation.
Voltage outputs (OUT 0 and OUT 1) of the 1746-FIO4V module are referenced to ANL COM. Load resistance (R1) for a voltage output channel must be equal to or greater than 1 KΩ.
Current output channels (OUT 0 and OUT 1) of the 1746-FIO4I module source current that returns to ANL COM. Load resistance (R1) for a current output channel must be within 0…500 Ω.
Input connections for single-ended or differential input are the same.
Publication 1746-UM009B-EN-P - September 2007
Install and Wire the Modules 17
Ground the Cable
Signal cable such as Belden cable #8761 (or equivalent) has two signal wires (black and clear), one drain wire, and a foil shield. The drain wire and foil shield must be grounded at only one end of the cable, not at both ends.
Typical Signal Cable
Foil Shield
Insulation
Shrink Wrap
Clear Wire
Drain Wire
Black Wire
IMPORTANT
Ground the cable shield at one end having a good earth-ground connection, such as at an I/O chassis mounting bolt or nearest ground bus in the I/O enclosure. Make this connection as short as possible. Do not ground the cable at the module’s terminal block.
Determine Cable Length
When you determine the length of cable required to connect an I/O device, remember to include additional length to route the drain wire and foil shield to earth ground. Route your cable long enough to avoid areas of high radiated electrical noise, but short enough to avoid signal attenuation.
Publication 1746-UM009B-EN-P - September 2007
18 Install and Wire the Modules

Minimize Electrical Noise Interference

Wire the Module

Because high-speed analog signals are particularly vulnerable to electrical noise, take precautions when routing your signal cables. To help reduce the effects of electrical noise on analog signals, we recommend that you do the following:
Install the SLC 500 system in a NEMA rated enclosure.
Make sure that the SLC 500 system is properly grounded.
Use Belden cable #8761 (or equivalent) for signal wiring.
Ground the cable properly.
Route signal cables away from other wiring or in grounded
conduit.
Group these modules away from ac or high-voltage dc modules.
We recommend re-checking system operation after installing new machinery or other sources of electrical noise near the system.
For additional information on this subject, refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Follow this procedure when wiring your modules.
ATTENTION
Before wiring a module, disconnect power from the SLC 500 system and from any other source to the module.
1. Strip about 7.6 cm (3 in.) of casing to expose the wires at each
end of the cable.
2. Twist the drain wire and foil shield together and bend them
away from the cable at the grounded end of the cable.
Grounded End
Ungrounded End
Casing
Casing
Shrink Wrap
Shrink Wrap
Twisted Foil Shield and Drain Wire
Black Wire
Clear Wire
Black Wire
Clear Wire
Publication 1746-UM009B-EN-P - September 2007
Install and Wire the Modules 19
3. Apply shrink wrap where wires leave the casing with the hot-air
blower.
4. Cut off the drain wire and foil shield at the other end of the
cable.
5. Apply shrink wrap to the junction where wires leave the casing.
6. Trim the signal wires to 5 cm (2 in.) lengths. Strip about
4.76 mm (3/16 in.) of insulation away to expose the copper strands for your connections.
7. Decide where you will connect the cable to earth ground, and
ground it.
Refer to Ground the Cable on page 17.
8. Connect signal wires (black and clear) to the terminal block and
to the input or output device.
Wiring Diagram for Module, Sensor, and Load (showing differential inputs)
Important: Channels are not isolated from each other.
All analog commons are connected together internally.
+ Analog Sensor
Load
Earth Ground
Important: Jumper unused inputs.
Earth Ground
Important: Do not jumper unused outputs.
0
IN 0 +
1
IN 0 –
2
ANL COM
3
IN 1 +
4
IN 1 –
5
ANL COM
6
not used
7
OUT 0
8
ANL COM
9
not used
10
OUT 1
11
ANL COM
Publication 1746-UM009B-EN-P - September 2007
20 Install and Wire the Modules
IMPORTANT
Single-ended inputs are less immune to noise than are differential inputs.
Wiring Schematic for Single-ended Current-loop Analog Input Connections
Important: The module does not provide loop power for analog inputs.
Use a power supply that matches the transmitter specifications.
2-wire Transmitter
Transmitter
+
Power
Supply
3-wire Transmitter
+
Power
Supply
4-wire Transmitter
+
Power Supply
+
Transmitter
GND
Transmitter
+
SignalSupply
SignalSupply
+
Module
IN + IN – ANL COM
Module
IN + IN – ANL COM
Module
IN + IN – ANL COM

Minimize Ground Loops

Publication 1746-UM009B-EN-P - September 2007
9. Repeat steps 1…6 for each channel. For each unused input
channel, jumper together the plus (+), minus (–), and common (ANL COM) terminals. For each unused output channel, do not connect terminals.
To keep the ground-loop currents of input circuits to a minimum, we recommend that you:
use the same power supply to power both input channels of a module.
otherwise, tie together the grounds of separate power supplies.
See Wiring Schematic for Single-ended Current-loop Analog Input Connections for more information.
Install and Wire the Modules 21

Label the Terminal Block

The terminal block has a write-on label. Use it to ensure that you install the correct terminal block on the corresponding module.
Termin a l B l ock
Note: The black dot on the label indicates the position of terminal 0.
SLOT ____ RACK ____
MODULE _____
Publication 1746-UM009B-EN-P - September 2007
22 Install and Wire the Modules
Publication 1746-UM009B-EN-P - September 2007
Chapter
3
Access Files to Configure I/O
There are two ways to configure the SLC Chassis for a 1746-FIO4I/V module. You can either click and drag items from the list or you can use the Read IO Config method.

Click and Drag Configuration

Follow these steps to configure the SLC chassis by clicking and dragging modules.
1. Double-click the menu item to open the IO Configuration menu
in RSLogix500 software.
2. Place the 1746-FIO4I/V module into the correct slot by clicking
and dragging from the list.
23 Publication 1746-UM009B-EN-P - September 2007
24 Access Files to Configure I/O
The I/O Configuration is now complete. Each slot shows the corresponding module that is located on the rack. In this example the 1746-FIO4V is in slot 1.

Read IO Config Method

Follow these steps to configure the SLC chassis by using the Read IO configuration method.
1. Double-click the menu item to open the IO Configuration menu
in RSLogix500 software.
Publication 1746-UM009B-EN-P - September 2007
Access Files to Configure I/O 25
2. Place the 1746-FIO4I/V module into the correct slot by clicking
Read IO Config.
The following screen appears.
3. Select either the driver and processor node number or use the
Who Active button to browse for the device.
If you selected the driver and node number, proceed to step 5.
If you clicked Who Active, the following screen appears.
Publication 1746-UM009B-EN-P - September 2007
26 Access Files to Configure I/O
The Who Active screen lets you browse for the SLC device.
4. Locate the SLC Chassis under the appropriate driver and click
OK.
You are brought back to the Read IO Config screen.
5. Click Read IO Config and the rack is populated automatically.
Publication 1746-UM009B-EN-P - September 2007
Access Files to Configure I/O 27
The I/O Configuration is now complete. Each slot shows the corresponding module on the rack. In this example the 1746-FIO4V is in slot 1.
Publication 1746-UM009B-EN-P - September 2007
28 Access Files to Configure I/O
Publication 1746-UM009B-EN-P - September 2007
Chapter
Processor and Module Considerations
This chapter describes concepts that you need to understand to program the fast analog I/O module in an SLC 500 system.
The following are processor considerations.
Update processor analog I/O data
Monitor analog I/O data
Address I/O image words
The following are module considerations.
Resolve data of the module’s I/O channel converters
Convert analog input data
Compute the analog input signal level
Convert analog output data
Compute the analog output
Filter input channel
Compute time delay for A/D conversion
Determine response to slot disable
Determine safe state for outputs
Enter module ID code
4
29 Publication 1746-UM009B-EN-P - September 2007
Loading...
+ 65 hidden pages