Rockwell Automation 1738-OW4M12AC User Manual

Installation Instructions
D
ArmorPoint Relay Output Modules, Series A
(Cat. No. 1738-OW4M12 and -OW4M12AC)
The ArmorPoint I/O family (Cat. no. 1738) consists of modular I/O modules. The sealed IP67 housing of these modules requires no enclosure. (Note that environmental requirements other than IP67 may require an additional appropriate housing.) I/O connectors are sealed M12 with either DC or AC keyed (micro) styles. The moun ting base ships with the module. The 1738-OW4M12 and -OW4M12AC modules are shown below.
1738-OW4M12
1738-OW4M12/A
Form A
Isolated Relay Out
1
0
Connector M12-A
Connector M12-B
Connector M12-C
1738-OW4M12AC
Connector M12-A
Connector M12-C
MOD
NET
3
2
1738-OW4M12AC/A
Form A
Isolated Relay Out
0
2
0 1
2 3
43717
Connector M12-
Connector M12-B
M O
1
D N
E T
LED Indicators
0 1
2
3
3
LED Indicators
Connector M12-D
43716
1 Publication 1738-IN008A-EN-E - June 2004
2 ArmorPoint Relay Output Modules, Series A
SHOCK HAZARD
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.ab.com/manuals/gi) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
WARNING
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, proper ty damage, or economic loss.
IMPORTANT
ATTENTION
BURN HAZARD
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you:
identify a hazard
avoid a hazard
recognize the consequence
Labels may be located on or inside the equipment to alert people that dangerous voltage may be present.
Labels may be located on or inside the equipment to alert people that surfaces may be dangerous temperatures.
.
Publication 1738-IN008A-EN-E - June 2004
ArmorPoint Relay Output Modules, Series A 3
ATTENTION
Environment and Enclosure
This equipment is intended for use in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters without derating.
This equipment is considered Grou p 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as "enclosed" equipment. It should not require additional system enclosure when used in locations consistent with the enclosure type ratings stated in the Specifications section of this publication. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings, beyond what this product provides, that are required to comply with certain product safety certifications.
NOTE: See NEMA Standards publication 250 and IEC publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure. Also, se e the appropriate sections in this publication, as well as the Allen-Bradley publication 1770-4.1 ("Industrial Automation Wiring and Grounding Guidelines"), for additional installation requirements pertaining to this equipment.
Publication 1738-IN008A-EN-E - June 2004
4 ArmorPoint Relay Output Modules, Series A
1.9 in.
2.0 in.
0.87 in.
2.0 in.
0.87 in.
2.0 in.

Mount the I/O Base

ATTENTION
Preventing Electrostatic Discharge
This equipment is sensitive to electrostatic dischar ge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component
boards.
Do not touch circuit components inside the equipment.
If available, use a static-safe workstation.
When not in use, store the equipment in
appropriate static-safe packaging.
To mount the ArmorPoint I/O base on a wall or panel, use the screw holes provided in the ArmorPoint base.
Adapter
4.02 in. 102 mm
A mounting illustration for the ArmorPoint base with an adapter is shown below.
47.2 mm
1.81 in. 46 mm
Install the mounting base as follows:
50 mm
22 mm
50 mm
22 mm
1. Lay out the required points as shown above in the drilling dimension drawing.
2. Drill the necessary holes for #8 (M4) machine or self-tapping screws.
50 mm
43769
Publication 1738-IN008A-EN-E - June 2004
ArmorPoint Relay Output Modules, Series A 5
Mounting base
Module will bridge two bases.
3. Mount the base using #8 (M4) screws.
4. Ground the system using the ground lug connection. (The
ground lug connection is also a mounting hole.)
Keyswitch­Set to position 7 for the 1738 Relay output modules
Ground lug connection
43675
Latching mechanism

Install the ArmorPoint Relay Output Module

To install the ArmorPoint relay output module, proceed as follows.
1. Using a bladed screwdriver, rotate the keyswitch on the mounting base clockwise until the number 7 aligns with the notch in the base.
2. Position the module vertically above the mounting base. The module will bridge two bases.
1738-OW4M12/A
Form A
Isolated Relay Out
1
0
MOD NET
3
2
0 1
2 3
43779
Publication 1738-IN008A-EN-E - June 2004
Loading...