Rockwell Automation 1734-IE4C User Manual

Installation Instructions
POINT I/O 4 Channel High Density Current Input Module
Catalog Number 1734-IE4C
Topic Page
Important User Information 2 Environment and Enclosure 3 Prevent Electrostatic Discharge 4 European Hazardous Location Approval 5 North American Hazardous Location Approval 6 Before You Begin 7 Install the Mounting Base 8 Install the I/O Module 9 Install the Removable Terminal Block (RTB) 11 Remove a Mounting Base 11 Communicating with Your Module 12 Wiring the Input Analog Module 14 Wiring Diagram 14 Interpret the Indicators 15 Specifications 17
2 POINT I/O 4 Channel High Density Current Input Module
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls Publication SGI-1.1
http://www.rockwellautomation.com/literature/
state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. b e responsi ble or liab le for indirect or conseq uential da mages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manua l, in whole or in part, wi thout writt en permi ssion of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
Identifies information about practi ces or cir cumstances t hat can cause a n explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard and recognize the consequences.
describes some important differences between solid
Publication
Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.
1734-IN032C-EN-P - June 2012
POINT I/O 4 Channel High Density Current Input Module 3
ATTENTION
WARNING
WARNING

Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication 1770-4.1 requirements.
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure.
When you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding. Repeated electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance that can affect module operation.
, for additional installation
When you connect or disconnect the Removable Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Publication
1734-IN032C-EN-P - June 2012
4 POINT I/O 4 Channel High Density Current Input Module
ATTENTION
ATTENTION
ATTENTION
ATTENTION
ATTENTION

Prevent Electrostatic Discharge

This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment.
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
POINT I/O is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum, plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
To comply with UL restrictions, field power and all connected devices must be powered from a single source compliant with the following: Class 2.
Publication
To comply with the CE Low Voltage Directive (LVD), field power and all connected I/O must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
1734-IN032C-EN-P - June 2012
POINT I/O 4 Channel High Density Current Input Module 5
WARNING

European Hazardous Location Approval

European Zone 2 Certification (The following applies whe n the produ ct bears the Ex Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in Zone 2 potentially explosive atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN 60079-15 and EN 60079-0.
Observe the following additional Zone 2 certification requirements.
• This equipment is not resistant to sunlight or other sources of UV radiation.
• The secondary of a current transformer shall not be open-circuited when applied in Zone 2 environments.
• This equipment must be installed in an enclosure providing at least IP54 protection when applied in Zone 2 environments.
• This equipment shall be used within its specified ratings defined by Rockwell Automation.
• Provision shall be made to prevent the rated voltage from being exceeded by transient disturbances of more than 40% when applied in Zone 2 environments.
• Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
Publication
1734-IN032C-EN-P - June 2012
6 POINT I/O 4 Channel High Density Current Input Module
WARNING
AVERTISSEMENT
WARNING
WARNING

North American Hazardous Location Approval

The following information applies when operating this equipment in hazardous locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in Class I Division 2 Groups A, B, C, D, Hazardous Locations and nonhazardous locations only. Each product is supplied with markings on the rating nameplate indicating the hazardous location temperature code. When combining products within a system, the most adverse temperature code (lowest "T" number) may be used to help determine the overall temperature code of the system. Combinations of equipment in your system are subject to investigation by the local Authority Having Jurisdiction at the time of installation.
EXPLOSION HAZARD –
• Do not disconnect equipment unless power has been removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless power h as been removed or the area is known to be nonhazardous. Secure any external connections that mate to this equipment by using screws, sliding latches, threaded connectors, or other means provided with this product.
• Substitution of components may impair suitability for Class I, Division 2.
• If this product contains batteries, they must only be changed in an area known to be nonhazardous.
If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Informations sur l'utilisation de cet équipement en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une utilisation en environnements de Classe I Division 2 Groupes A, B, C, D dangereux et non dangereux. Chaque produit est livré avec des marquages sur sa plaque d'identification qui indiquent le code de température pour les environnements dangereux. Lorsque plusieurs produits sont combinés dans un système, le code de température le plus défavorable (code de température le plus faible) peut être utilisé pour déterminer le code de température global du système. Les combinaisons d'équipements dans le système sont sujettes à inspection par les autorités locales qualifiées au moment de l'installation.
RISQUE D’EXPLOSION –
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non dangereux avant de débrancher les connecteurs. Fixer tous les connecteurs externes reliés à cet équipement à l'aide de vis, loquets coulissants, connecteurs filetés ou autres moyens fournis avec ce produit.
• La substitution de composants peut rendre cet équipement inadapté à une utilisation en environnement de Classe I, Division 2.
• S'assurer que l'environnement est classé non dangereux avant de changer les piles.
Publication
When you connect or disconnect the Removable Terminal Block (RTB) with field side power applied, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
1734-IN032C-EN-P - June 2012
POINT I/O 4 Channel High Density Current Input Module 7
Mechanical
keying (orange)
Module wiring
diagram
Module locking
mechanism
Insertable I/O module
Mounting base
Removable Terminal Block (RTB)
RTB removal handle
DIN rail locking
screw (orange)
Slide-in writable label
Interlocking side
pieces
44328

Before You Begin

Note that this series C product can be used with the following:
• DeviceNet and PROFIBUS adapters
• ControlNet and EtherNet/IP adapters, using RSLogix 5000 software, version 11 or later
See the figures to familiarize yourself with major parts of the module, noting that the wiring base assembly is one of the following:
• 1734-TB or 1734-TBS POINT I/O two-piece terminal base, which includes the 1734-RTB removable terminal block and 1734-MB mounting base
• 1734-TOP or 1734-TOPS POINT I/O one-piece terminal base
Module
Status
Network
Status
NODE:
0
1
2
3
Publication
1734-IN032C-EN-P - June 2012
8 POINT I/O 4 Channel High Density Current Input Module
44221
1734-TOP or 1734-TOPS One-piece terminal base with screw or spring clamp
Insertable I/O module
Slide-in writable label
Handle
Module locking
mechanism
Interlocking
side pieces
DIN rail locking
screw (orange)
Module wiring
diagram
Mechanical
keying (orange)

Install the Mounting Base

To install the mounting base on the DIN rail, proceed as follows:
1. Position the mounting base vertically above the installed units
(adapter, power supply or existing module).
2. Slide the mounting base down allowing the interlocking side pieces to
engage the adjacent module or adapter.
3. Press firmly to seat the mounting base on the DIN rail. The mounting
base will snap into place.
Publication
4. To remove the mounting base from the DIN rail, remove the module,
and use a small bladed screwdriver to rotate the base locking screw to a vertical position. This releases the locking mechanism. Then lift straight up to remove.
1734-IN032C-EN-P - June 2012