The RISCO Seismic Detector is used for the protection against break-in attempts of
vaults, safes, reinforced concrete walls, steel armored cabinets and doors. The
seismic detector monitors the vibration and temperature of a specific surface and
will react to all known types of intruder attacks, such as sledge hammers, diamond
head drills, explosives, hydraulic pressure tools and thermal tools.
The detector can operate both as a regular relay detector connected to any control
panel, or as a BUS accessory when connected to RISCO Group's control panels
via the RS485 BUS, empowering it with unique remote control and diagnostic
capabilities.
The instructions set forth below describe the RISCO seismic detector in Stand
Alone & BUS mode. For BUS installation programming, see RISCO System
installation manuals
Main Features:
• Piezo sensor
• Low/High temperature detection
• Detection range up to 5 meters (16 feet) radius
• Tamper protection
• Anti drilling shield
• Remote sensitivity control
• Analogue signal output
• Bar graph LED indicator
• Remote self test
• Stand-alone or RISCO BUS connection
2
INSTALLATION KIT
Each kit includes:
Wall structure fastening sets:
Metallic structure fastening sets:
External Test Generator
Detector Mounting Plate
Expanding plugs M6 x 16
Flat head machining screw M6 X 16
Inner Tooth Washer M4
Pan Head Machining Screw M4 X 10
(Mandatory
for surfaces
like concrete)
EN
Seismic Detector 3
PCB LAYOUT
LD1
LD2
LD3
LD4
1
2
3
Bar Graph LEDs
123
Tamper EOL
456
Jumper
Tamper (Front )
78
LD5
LD6
LD7
ON
LD8
LD9
1 2 3 4ON 1 2 3 4ON 1 2 3 4
2
1
6
5
4
3
W
W
W
W
W
W
S
S
S
S
S
S
+ 12V - YEL GRN NO C NC TAMPER SENS A.OUT TEST
Dipswitches
(default state)
Alarm EOL
Jumper
External Test
Generator
Connector
2
0
1
8
7
9
1
1
1
W
W
W
W
W
W
S
S
S
S
S
S
Tamper EOL
J15
J13
J12
Alarm EOL
S.A/ Bu s
Ext. Test
J2
4
5
6
7
8
9
Terminal Blocks
Stand
Alone/BUS
Jumper
Tamper (Back)
(not visible)
4
Seismic Detector
MOUNTING THE DETECTOR
•Determine the mounting position. Potential false alarm sources must be
accounted for when installing RK66S, Therefore:
•Attach the sensor to a surface as isolated as possible from extraneous
vibrations, with close contact between the concrete surface and the detector.
For metallic surfaces, remove residual paint from sensor installation site. Do
not use silicon grease between sensor and object!
•For maximum vibration detection, the concrete surface should be smooth.
Use the mounting plate (see Figure 2) when mounting on drill-resistant steel,
brick or concrete surfaces. The plate can also be welded onto metallic
surfaces.
•Adjust dipswitch settings for sensitivity; time and other parameters (see
Dipswitch settings, below) for background vibration – bearing in mind the
inverse relation between detection range and sensitivity and the construction
material of the object to be monitored. Detectors with high sensitivity can be
spaced up to 5m apart on secure protected surfaces (for example, steel),
confirmed by hammer or scratch tests.
•Hinged doors, such as those on safes or ATM, and other attachments without
continuous acoustic transmission paths, should be protected with their own
detectors.
•Remove the cover fixing screws to separate the cover from the base, see
Figure 1(A) / 2(B).
•Drill holes on the mounting surface, using the detector base or mounting
plate as a guide, as follows:
B
EN
A
Figure 1: Mounting the detector directly onto a metallic surface
Direct mounting on a metallic surface (Figure. 1)
a. Ensure that the mounting surface is level to within 1/128”
(0.1mm).
b. Use the detector base as a drilling template for the three holes
(3.2 mm dia.) and tap M4 thread at least ¼” (6 mm) deep.
Deburr threaded holes in metal.
c. Fit the detector using the supplied fixing screws, see Figure 1(B).
Seismic Detector 5
C
Figure 2: Mounting the detector using the mounting plate. (Note: Affix the mounting
plate using fixing screws or optionally, by welding the plate to a metallic surface.)
Installation using mounting plate (Figure 2):
a. (Optional metal welding) Weld the mounting plate along the two
provided vertical oblong cutout surfaces. Tap off slag and
remove weld splatter from the plate surface.
b. (On concrete) :
Never install the detector directly on a bare or plastered concrete
surface, since bending forces may cause damage to the seismic
sensor. Plaster of less than 10mm need not be removed.
i. Drill four holes for mounting plate (8 mm dia, min 35
mm depth for anchor; using a sintered carbide bit.
ii. Also, use the mounting plate as a drilling template
for the three threaded detector holes (5 mm dia) at
least 3 mm deep.
iii. Insert supplied metal plugs into drilled hole flush
with the concrete surface
iv. Ensure that the mounting plate is correctly
positioned. Press the mounting plate onto surface,
knock in screw with plug and tighten well. The plate
should not be capable of rotation.
v. Fit the detector using the supplied fixing screws, see
c. (On metal) :
6
Figure 2(C).
i. Use the mounting plate as a drilling template for the
four holes (5 mm dia.) and tap M6 thread at least 10
mm deep. Deburr threaded holes in metal.
ii. Also, use the mounting plate as a drilling template
for the three threaded detector holes (5 mm dia) at
least 3 mm deep.
iii. Affix the mounting plate with the supplied screws.
The plate should not be capable of rotation
Seismic Detector
B
iv. Fit the detector using the supplied fixing screws, see
• Connect wiring; Refer to Terminal Blocks section.
• Set Jumpers; Refer to Jumper Selection section.
• Set Dipswitches; Refer to Dipswitch Settings section.
• To verify detector operation, perform:
• Replace the cover and tighten the cover fixing screws; See Figure 1(A) / 2(B).
a. A self test (See Testing the Detector section).
b. Sensitivity calibration using an external test generator (See
External Test Generator section).
Figure 2(C).
TERMINAL BLOCK LAYOUT
EN
Terminal
Block
+12V (RED) Power supply positive (+) input voltage
- (BLK) Power supply negative (-) input voltage
YEL Used for data communication with RISCO panels (only for
GRN Used for data communication with RISCO panels (only for
NO Alarm Normally Opened relay output, 24VDC.0.1A
C Alarm Common relay output
NC Alarm Normally Closed relay output, 24VDC.0.1A
TAMPER N.C. Tamper Switch, 24VDC.0.1A
SENS Remote sensitivity control for lowering vibration sensitivity for
A.OUT Analog signal output: Connect a multimeter/scope or an
TEST A short between TEST and GND activates the Remote Test
Figure 3: Terminal Block Layout
Description
BUS connection)
BUS connection)
ATM-type dispensers when cash is being disbursed and
internal vibration generated.
GND = Low sensitivity
Not Connected = Reguler sensitivity
analogic tester between the A.OUT and -12V terminals, to
view the noise and signal voltage levels (in parallel to the LED
bar representation). In the absence of vibrations, the voltage
signal is 0V, and it increases as it detects vibrations.
If the voltage measured (in absence of vibrations) doesn't
remain stable but continues to increase, it means that
environmental noise is being captured and therefore the
detector sensitivity must be reduced.
(see Dipswitch Settings 8 and 9).
(Not relevant for BUS mode.)
Seismic Detector 7
LED DISPLAY DURING NORMAL MODE
LED ON Color SeverityDescription
LD1 Red Temperature alarm
LD2 Red
LD3 Yellow
LD4-8 Green
detection
Vibration alarm
detection: Bar graph
(from LED8–2) indicating
signal power.
LD9 Green Power On
NOTE:
During Test mode th e LED displ ays have a d ifferent mean ing. Refer to the section :
Testing the detector.
8
Seismic Detector
w
DIPSWITCH SETTINGS
STANDALONE MODE
Dipswitch Description (SW7 OFF)
SW1
SW2
SW3
SW4
SW5
SW6
SW7 Used to determine Stand Alone or BUS mode (Ensure that the J12
SW8
SW9
Used to determine the detector's sensitivity. Sensitivity is a function
of coverage area and surface material.
SW1 SW2 SW3
*OFF *OFF *OFF
ON OFF OFF
OFF ON OFF
ON ON OFF
OFF OFF ON
ON OFF ON
OFF ON ON
ON ON ON
Used to detect single and extremely brief and intense signals
(including explosions and sledge hammers).
ON: Enable
*OFF: Disable
Used to adjust the integration time. In combination with SW1-3 they
establish a threshold value; SW5-6 establishes a cumulative alarm
signal value which, when exceeding the threshold value, triggers
an alarm event.
SW5 SW6 Duration (in sec.)
*OFF *OFF 10 (example: vending machine)
ON OFF 26
OFF ON 46
ON ON 80 (example: bank vault)
position (as below) matches the SW7 spec. )
ON: BUS
*OFF: Stand Alone
Used to determine Local or Remote Test
ON: Local. An internal self test is performed every 24 hours from
power-up. Test failure lights up the LEDs (see the Testing the Detector section) and the LEDs remain lit until the next self test.
*OFF: Remote. A test is activated whenever the TEST input is
connected to GND. If the test passes, the alarm relay opens for
three seconds.
External test generator
ON: Enable External Test Generator
*OFF: Disable (internal test)
Lo
Sensitivity
High
Sensitivity
Low
Sensitivity
High
Sensitivity
EN
Seismic Detector 9
Dipswitch Description (SW7 OFF)
SW10
SW11
SW12
Used to enable the temperature sensor (alarm temperature
threshold of +85°C (+185°F))
ON: Enable *OFF: Disable (No temp. threshold is set)
Used to determine LEDs operation
ON: Enable *OFF: Disable
Not used
BUS MODE
Dipswitch Description
SW1-5
SW7
SW6,8-12
BUS Address
ON: BUS
Not Applicable
10
Seismic Detector
JUMPER SELECTION
Jumper Function
S.A (Stand Alone) /BUS
J12
J13: Alarm EOL
J15: Tamper EOL
TAMPER EOL JUMPERS (J15)
Used to enable tamper indication during Stand Alone
or BUS mode.
Jumpers J13 and J15 allow for the selection of Alarm
and Tamper resistance (1K, 2.2K, 4.7K, 5.6K and
6.8K) according to the control panel. Follow the
terminal block connection diagram in Figure 4 when
connecting the detector to a Double End Of Line
(DEOL) zone.
EN
Stand Alone mode (Default).
BUS connection mode.
(See RISCO system
programming manuals).
NO
RESISTOR
(Defau lt)
NO
RESISTOR
(Default)
1K 2.2K 4.7K 5.6K 6.8K
ALARM E OL JUMPERS (J13)
2.2K 4.7K 5.6K 6.8K
1K
Figure 4: Schematic of EOL Resistors
ALARM
TAMPER
C NC TAMPER
Panel DEOL
Seismic Detector 11
TESTING THE DETECTOR
RISCO recommends performing a self test after installation and before final cover
mounting. The test can be performed manually (locally or remotely) or automatically
every 24 hours
Remote self-test (Manual Test)
This test requires that a command be given in order to be performed.
To activate the remote self-test:
• Ensure that the Dipswitch SW8 is set to OFF.
• Short the TEST terminal block to GND.
• All LEDs will turn on to indicate test commencement and sequentially turn off
after each successful parameter test.
The detector unit self test examines the following parameters:
LED Trouble
1 External power supply failure
2 Internal voltage faulty
4 Piezo sensor failure
5 Temperature sensor failure
3, 6-9 Not Applicable
All LEDs will turn off at the end of a successful test, except the POWER LED
(LED9) and the alarm relay opens for three seconds. If a malfunction occurs, one of
the LEDs remains lit.
Local self-test (Automatic Test)
Ensure that the Dipswitch SW8 is set to ON.
The RK66S detector runs a local/automatic SELF-TEST every 24 hours from the
time of initial power on. Test procedure and result presentation is as per the
Remote self-test above.
12
Front view Rear view
Seismic Detector
Attach to the concrete surface, using the supplied mounting screw in this hole
opening.
The external test generator can be used to:
♦ Periodically verify proper functioning of the detector
♦ Observe the detector’s sensitivity during installation
To use the test generator:
•Connect the test generator to J2 on the PC board (with the polarity resulting
from the red wire connected to the plug pin closest to the terminal block, in
other words, the lowest)
• Switch SW9 to ON.
• Attach the test generator to the concrete surface.
• Perform test, as follows:
a. For remote test, see the DIPSWITCH Settings section
b. For calibration test, Switch SW8 to ON and observe the LEDs
EN
Seismic Detector 13
Specifications
Coverage Up to 5 meters (16 feet) radius
Operating voltage 9 to 16 VDC
Current consumption Typically 20mA @ 12VDC
RFI immunity
Alarm contacts 24VDC, 0.1A, N/C and N/O
Tamper contacts 24VDC, 0.1A
Alarm contact hold time 2.5 seconds
Operating temperature -40°C to +70°C (-40°F to 158°F)
Storage temperature -50°C to +70°C (-58°F to 158°F)
Ingress protection (IP) rating IP43
Impact Rating IK08
RFI immunity According to EN50130-4
Dimensions (L x H x W) 102 X 27.5 X 80.2 mm
Weight 220 g ( 7.7 oz)
Supervision Time
In order to continue improving the product, RISCO Group reserves the right to
change specifications and/or designs without prior notice.
• According to EN50130-4
(4.0” X 1.1” X 3.2”)
15 min. for 868.65 MHz /
65 min. for 433.92 MHz
Certifications:
Ordering Information
Model Description
RK66S Seismic Detector
14
Seismic Detector
MICROFONO SELETTIVO
MODELLO: RK66S
ISTRUZIONI DI INSTALLAZIONE
IT
15
INTRODUZIONE
Il microfono selettivo di RISCO è utilizzato per la protezione di caveau, casseforti,
mura di cemento armato, armadi e porte blindate. Il microfono selettivo rileva la
vibrazione e la temperatura di una specifica superficie e reagisce a tutte le
tipologie di attacco conosciute come ad esempio punte di diamante, esplosivi, colpi
di mazza, lancia termica e dispositivi idraulici di pressione.
Il rivelatore può funzionare sia tramite connessione a relè ad una qualsiasi centrale
antifurto o tramite connessione BUS RS485 con le centrali antifurto RISCO. In
quest’ultimo caso il microfono selettivo può essere configurato e testato tramite
tastiera del sistema o tramite PC.
Le istruzioni che seguono descrivono il microfono selettivo RISCO sia nella
modalità a Relè che in quella BUS. Per il collegamento via BUS far riferimento
anche al manuale di installazione della centrale RISCO utilizzata.
Caratteristiche principali
• Sensore piezoelettrico
• Rilevazione temperatura Bassa/Alta
• Portata fino a 5 metri di raggio
• Protezione tamper
• Schermo anti-perforazione
• Controllo remoto della sensibilità
• Uscita segnale analogico
• Indicatore grafico a LED
• Auto-test remoto
• Collegamento a relè o via BUS RISCOCaratteristiche principali
KIT KIT DI INSTALLAZIONE
Ogni kit include:
Set di fissaggio comprendente:
Set metallico di fissaggio comprendente:
Dispositivo esterno di test
Tasselli per viti M6 x 16
Viti a testa piatta tipo M6 X 16
Rondella dentata per viti M4
Viti per metallo a testa cilindrica
tipo M4 X 10
IT
Rivelatore
Piastra di fissaggio
(Obbligatoria per
l’installazione su
superfici in cemento
armato)
Détecteur Sismique 17
PCB LAYOUT DESCRIZIONE DELLA SCHEDA
LD1
LD2
LD3
LD4
1
LD5
LD6
LD7
ON
LD8
LD9
1 2 3 4ON 1 2 3 4ON 1 2 3 4
2
1
5
4
3
W
W
W
W
W
S
S
S
S
S
8
7
6
9
W
W
W
W
S
S
S
S
2
3
+ 12V - YEL GRN NO C NC TAMPER SENS A.OUT TEST
Indicatori LED
123
Ponticello
456
Tamper EOL
Tamper
78
(Apertura)
Microinterruttori
(default)
Ponticello
Allarme EOL
Connettore Test
esterno
Tamper EOL
J15
Alarm EOL
J13
2
0
1
1
1
1
W
W
W
S
S.A/ Bu s
S
S
J12
Ext. Test
J2
4
5
6
7
8
9
(non visibile)
Morsettiera
Ponticello
Relè/BUS
Tamper
(Rimozione)
18
Détecteur Sismique
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.