Pilz PNOZ X9 Data Sheet

E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X9
Safety relay for monitoring E-STOP pushbuttons, safety gates and light barriers.

Approvals

PNOZ X9

Unit features

` Positive-guided relay outputs:
– 7 safety contacts (N/O), instanta-
neous
– 2 auxiliary contacts (N/C), in-
stantaneous
` 2 semiconductor outputs ` Connection options for:
– E-STOP pushbutton – Safety gate limit switch – Reset button – Light barriers
` LED indicator for:
– Switch status channel 1/2 – Supply voltage – Reset circuit – Input circuits
` Semiconductor output signals:
– Supply voltage is present – Switch status channel 1/2
` See order reference for unit types

Unit description

The safety relay meets the require­ments of EN 60204-1 and IEC 60204­1 and may be used in applications with
` E-STOP pushbuttons
` Safety gates ` Light barriers

Safety features

The relay conforms to the following safety criteria:
` The circuit is redundant with built-in
self-monitoring.
` The safety function remains effecti-
ve in the case of a component failu­re.
` The correct opening and closing of
the safety function relays is tested automatically in each on-off cycle.
` The tranformer is short circuit-
proof. An electronic fuse is used on a DC supply.

Block diagram

B1 B2 S52 13 23 33 43
=
=
A1 A2 Y1 Y2
Power
S11 S12 S21 S22
=
Feed-
back
~
InputInput
0 V 24 V
Y30 Y31 Y32 Y35
Input
Reset/
Start
S37S33 S34
Reset/
Start
K1
K2
K3
14 24 34 44
53 63 73 81 91
54 64 74 82 92
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-037-11/04
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X9

Function description

` Single-channel operation: no red-
undancy in the input circuit, earth faults in the reset and input circuit are detected.
` Dual-channel operation without de-
tection of shorts across contacts: redundant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too.

Timing diagram

1 2
POWER
Reset/Start
Input
Output safe
Output aux.
Out semi RUN
Out semi CH
t1 t2
t1 t2
` Dual-channel operation with detec-
tion of shorts across contacts: red­undant input circuit, detects – earth faults in the reset and input
circuit,
– short circuits in the input circuit
and, with a monitored reset, in the reset circuit too,
– shorts between contacts in the
input circuit.
` Automatic start: Unit is active once
the input circuit has been closed.
ab
t1
t1
t2
` Manual reset: Unit is active once
the input circuit is closed and then the reset circuit is closed.
` Monitored reset: Unit i s ac t iv e o nc e
– the input circuit is closed and
then the reset circuit is closed and opened again.
– the reset circuit is closed and
then opened again once the in­put circuit is closed.
` Increase in the number of available
contacts by connecting contact ex­pander modules or external contac­tors/relays.
ab
t2
t1
3
t2
t1
t2
Key
` Power: Supply voltage ` Reset/start: Reset circuit S33-S34 ` Input: Input circuits S11-S12, S21-
S22, S52
` Output safe: Safety contacts 13-14,
23-24, 33-34, 43-44, 53-54, 63-64, 73-74

Wiring

Please note:
` Information given in the “Technical
details” must be followed.
` Outputs 13-14, 23-24, 33-34, 43-
44, 53-54, 63-64, 73-74 are safety contacts, outputs 81-82, 91-92 are auxiliary contacts (e.g. for display).
` To prevent contact welding, a fuse
should be connected before the output contacts (see technical de­tails).
` Calculation of the max. cabling runs
in the input circuit:
l
max
` Output aux: Auxiliary contacts 81-
82, 91-92
` Out semi RUN: Semiconductor out-
put supply voltage Y35
` Out semi CH: Semiconductor out-
put switch status Y32
` c: Automatic reset ` d: Manual reset
R
lmax
=
I
max
Rl / km
R
= max. overall cable resi-
lmax
stance (see technical details)
/km = cable resistance/km
R
l
` Use copper wire that can withstand
60/75 °C.
` Sufficient fuse protection must be
provided on all output contacts with capacitive and inductive loads.
` e: Monitored reset ` a: Input circuit closes before reset
circuit
` b: Reset circuit closes before input
circuit
: Switch-on delay
` t
1
` t2: Delay-on de-energisation
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
NSG-D-2-037-11/04Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
-2
E-STOP relays, safety gate monitors
Up to Category 4, EN 954-1
PNOZ X9

Preparing for operation

` Supply voltage

Supply voltage AC DC
A1
A2
B2 PE
L1
N

` Input circuit

Input circuit Single-channel Dual-channel E-STOP
without detection of shorts across contacts
S21 S22
S11 S12 S52
S1
S21 S22
E-STOP with detection of shorts across con­tacts
S11 S52
Safety gate without detection of shorts across contacts
S21 S22
S11 S12 S52
S1
S21 S22
B1
B2
S11
S12 S52
S11
S12 S52
S11 S21
S22 S12
S1
L+
L-
S1
S1
S2
Safety gate with detection of shorts across con­tacts
Pilz GmbH & Co. KG, Sichere Automation, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: pilz.gmbh@pilz.de
S11 S52
S11 S12 S21 S22
S1
NSG-D-2-037-11/04