Mitsubishi SUZ-KA25VA2.TH, SUZ-KA35VA2.TH, SUZ-KA50VA2.TH, SUZ-KA60VA2.TH, SUZ-KA71VA2.TH Service Manual

0 (0)

SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS

TECHNICAL & SERVICE MANUAL

May 2010

No.OCH472

HFC

utilized

R410A

R410A

Outdoor unit

[model names] [Service Ref.]

SUZ-KA25VA2 SUZ-KA35VA2 SUZ-KA50VA2 SUZ-KA60VA2 SUZ-KA71VA2

SUZ-KA25VA2.TH SUZ-KA35VA2.TH SUZ-KA50VA2.TH SUZ-KA60VA2.TH SUZ-KA71VA2.TH

Indication of

model name

SUZ-KA25VA2.TH

SUZ-KA35VA2.TH

NOTE:

This service manual describes technical data of the outdoor units.

RoHS compliant products have <G> mark on the spec name plate.

For servicing of RoHS compliant products, refer to the RoHS Parts List.

CONTENTS

1.

COMBINATION OF INDOOR AND OUTDOOR UNITS

.......

 

2

2. TECHNICAL CHANGES

....................................

 

 

 

 

 

3

3. PART NAMES AND FUNCTIONS

......................

 

 

6

4.

SPECIFICATION.................................................7

5.

NOISE CRITERIA CURVES............................... 9

6. OUTLINES AND DIMENSIONS

........................

 

 

 

 

10

7. WIRING DIAGRAM

...........................................

 

 

 

 

 

 

 

13

8.

REFRIGERANT SYSTEM DIAGRAM..............

17

9. ACTUATOR CONTROL....................................21

10. SERVICE FUNCTIONS

.....................................

 

 

 

 

 

 

22

11. TROUBLESHOOTING......................................

22

12. DISASSEMBLY INSTRUCTIONS

.....................

63

 

 

 

PARTS CATALOG (OCB472)

1 COMBINATION OF INDOOR AND OUTDOOR UNITS

1-1. INDOOR UNIT SERVICE MANUAL

 

 

 

 

 

Outdoor unit

 

 

 

Indoor unit

 

Heat pump type

 

 

 

Service

 

 

SUZ-

 

 

 

Service Ref.

KA25VA2.TH

KA35VA2.TH

KA50VA2.TH

KA60VA2.TH

KA71VA2.TH

 

Manual No.

 

 

 

 

 

 

 

 

SLZ-KA25VA(L).TH

 

 

heater

SLZ-KA35VA(L).TH

OC320

 

SLZ-KA50VA(L).TH

 

 

electric

SEZ-KD25VA(L).TH

 

 

SEZ-KD35VA(L).TH

 

 

without

HWE0711

 

SEZ-KD50VA(L).TH

 

 

 

SEZ-KD60VA(L).TH

 

 

pump

 

 

SEZ-KD71VA(L).TH

 

 

 

 

 

 

 

 

 

Heat

MFZ-KA25VA-E4

 

 

MFZ-KA35VA-E4

OB409

 

 

 

 

MFZ-KA50VA-E4

 

 

(NOTE) • Please refer to the service manual of indoor unit or the technical data book for the combination data.

2

Refrigerant

2 TECHNICAL CHANGES

INFORMATION FOR THE AIR CONDITIONER WITH R410A REFRIGERANT

This room air conditioner adopts an HFC refrigerant (R410A) which never destroys the ozone layer.

Pay particular attention to the following points, though the basic installation procedure is same as that for R22 conditioners.

1As R410A has working pressure approximate 1.6 times as high as that of R22, some special tools and piping parts/ materials are required. Refer to the table below.

2Take sufficient care not to allow water and other contaminations to enter the R410A refrigerant during storage and installation, since it is more susceptible to contaminations than R22.

3For refrigerant piping, use clean, pressure-proof parts/materials specifically designed for R410A. (Refer to 2. Refrigerant piping.)

4Composition change may occur in R410A since it is a mixed refrigerant. When charging, charge liquid refrigerant to prevent composition change.

 

 

 

 

New refrigerant

Previous refrigerant

 

Refrigerant

 

 

R410A

R22

 

Composition (Ratio)

 

 

HFC-32: HFC-125 (50%:50%)

R22 (100%)

 

Refrigerant handling

 

 

Pseudo-azeotropic refrigerant

Single refrigerant

 

Chlorine

 

 

Not included

Included

 

Safety group (ASHRAE)

 

 

A1/A1

A1

Refrigerant

Molecular weight

 

 

72.6

86.5

Saturated steam density [25

](Kg/*)

 

64

44.4

 

Boiling point ( )

 

 

-51.4

-40.8

 

Steam pressure [25 ](Mpa)

 

1.557

0.94

 

 

 

 

 

 

 

Combustibility

 

 

Non combustible

Non combustible

 

ODP +1

 

 

0

0.055

 

GWP +2

 

 

1730

1700

 

Refrigerant charge method

 

 

From liquid phase in cylinder

Gas phase

 

Additional charge on leakage

 

Possible

Possible

Refrigerant oil

Kind

 

 

Incompatible oil

Compatible oil

Smell

 

 

None

None

 

Color

 

 

None

Light yellow

 

 

 

 

 

 

+1: Ozone Depletion Potential

: based on CFC-11

 

+2: Global Warming Potential

: based on CO2

 

 

Compressor

 

New Specification

Current Specification

The incompatible refrigerant oil easily separates from

Since refrigerant and refrigerant oil are compatible with

refrigerant and is in the upper layer inside the suction muffler.

each other, refrigerant oil backs to the compressor through

Raising position of the oil back hole enables to back the

the lower position oil back hole.

refrigerant oil of the upper layer to flow back to the

 

 

 

 

 

 

 

compressor.

 

 

 

 

 

 

Suction muffler

 

 

 

 

 

 

Suction muffler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Oil back hole

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

Refrigerant oil

 

 

 

 

 

 

Oil back hole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant oil /Refrigerant

NOTE : The unit of pressure has been changed to MPa on the international system of units (SI unit system). The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm2 [Gauge])

3

Conversion chart of refrigerant temperature and pressure

(MPa [Gauge])

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

R410A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

 

 

 

 

 

 

R22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

liquid

2.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: The unit of pressure has been changed to MPa on the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Saturated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

international system of units (SI unit system).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The conversion factor is: 1 (MPa [Gauge]) =10.2 (kgf/cm2 [Gauge])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-30

-20 -10 0 10 20 30 40 50 60 ( )

1. Tools dedicated for the air conditioner with R410A refrigerant

The following tools are required for R410A refrigerant. Some R22 tools can be substituted for R410A tools.

The diameter of the service port on the stop valve in outdoor unit has been changed to prevent any other refrigerant being charged into the unit. Cap size has been changed from 7/16 UNF with 20 threads to 1/2 UNF with 20 threads.

R410A tools

Can R22 tools be used?

Description

 

 

R410A has high pressures beyond the measurement range of existing

Gauge manifold

No

gauges. Port diameters have been changed to prevent any other refrigerant

 

 

from being charged into the unit.

Charge hose

No

Hose material and cap size have been changed to improve the pressure

resistance.

 

 

Gas leak detector

No

Dedicated for HFC refrigerant.

Torque wrench

Yes

6.35 mm and 9.52 mm

No

12.7 mm and 15.88 mm

 

Flare tool

Yes

Clamp bar hole has been enlarged to reinforce the spring strength in the tool.

Flare gauge

New

Provided for flaring work (to be used with R22 flare tool).

Vacuum pump

New

Provided to prevent the back flow of oil. This adapter enables you to use

adapter

vacuum pumps.

 

Electronic scale for

New

It is difficult to measure R410A with a charging cylinder because the

refrigerant charging

refrigerant bubbles due to high pressure and high-speed vaporization

 

No: Not substitutable for R410A Yes: Substitutable for R410A

4

2. Refrigerant piping

1Specifications

Use the refrigerant pipes that meet the following specifications.

Pipe

Outside diameter

Wall thickness

Insulation material

mm

mm

 

 

For liquid

6.35

0.8

Heat resisting foam plastic

9.52

0.8

 

 

9.52

0.8

Specific gravity 0.045 Thickness

For gas

12.7

0.8

8 mm

 

15.88

1.0

 

Use a copper pipe or a copper-alloy seamless pipe with a thickness of 0.8 mm. Never use any pipe with a thickness less than 0.8mm, as the pressure resistance is insufficient.

2Flaring work and flare nut

Flaring work for R410A pipe differs from that for R22 pipe.

For details of flaring work, refer to Installation manual “FLARING WORK”.

Pipe diameter (mm)

Dimension of flare nut (mm)

 

 

 

R410A

R22

6.35

17

17

9.52

22

22

12.7

26

24

15.88

29

27

3. Refrigerant oil

Apply the special refrigerant oil (accessories: packed with indoor unit) to the flare and the union seat surfaces.

4. Air purge

Do not discharge the refrigerant into the atmosphere.

Take care not to discharge refrigerant into the atmosphere during installation, reinstallation, or repairs to the refrigerant circuit.

Use the vacuum pump for air purging for the purpose of environmental protection.

5. Additional charge

For additional charging, charge the refrigerant from liquid phase of the gas cylinder.

If the refrigerant is charged from the gas phase, composition change may occur in the refrigerant inside the cylinder and the outdoor unit. In this case, ability of the refrigerating cycle decreases or normal operation can be impossible. However,

charging the liquid refrigerant all at once may cause the compressor to be locked. Thus, charge the refrigerant slowly.

Indoor unit

Refrigerant gas cylinder operating valve

Union

 

Stop valve

Liquid pipe

 

Gas pipe

Outdoor unit

Service port

Gauge manifold valve (for R410A)

Charge hose (for R410A)

Refrigerant gas cylinder for R410A with siphon

Refrigerant (liquid)

Electronic scale for refrigerant charging

5

3 PART NAMES AND FUNCTIONS

SUZ-KA25VA2.TH SUZ-KA35VA2.TH

Air inlet (back and side)

Piping

Drain hose

Air outlet

Drain outlet

SUZ-KA50VA2.TH SUZ-KA60VA2.TH

Air inlet (back and side)

Piping

Drain hose

Air outlet

Drain outlet

SUZ-KA71VA2.TH

Air inlet (back and side)

 

 

Piping

 

 

 

Drain hose

 

 

 

Air outlet

 

 

 

Drain outlet

 

Model

SUZ-KA25/35VA2.TH

SUZ-KA50/60VA2.TH

SUZ-KA71VA2.TH

Drain socket

1

1

1

Drain cap

-

2

-

6

4 SPECIFICATION

 

 

Outdoor Service Ref.

 

SUZ-KA25VA2.TH

SUZ-KA35VA2.TH

SUZ-KA50VA2.TH

SUZ-KA60VA2.TH

SUZ-KA71VA2.TH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

Cooling Heating

Cooling

Heating

Cooling

Heating

Cooling

Heating

Cooling

Heating

 

 

Power supply

 

Single phase

Single phase

Single phase

Single phase

Single phase

 

 

 

230V, 50Hz

230V, 50Hz

230V, 50Hz

230V, 50Hz

230V, 50Hz

 

 

 

 

 

 

Electrical data

Starting current

*1

A

3.65

4.75

6.75

9.75

8.89

Fan motor current

*1

A

0.31

0.28

0.33

 

0.33

0.30

0.30

0.83

 

0.82

 

 

Compressor motor current *1

A

2.74

3.37

4.22

 

4.42

6.45

6.05

8.05

9.45

8.00

 

8.07

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

Model

 

 

 

KNB073FFDH(C)

KNB092FFAH(C)

SNB130FGBH(T)

SNB130FGBH(T)

SNB172FEKMT

resistance (at 20

 

)

W

V-W 1.70

V-W 1.91

V-W 0.98

V-W 0.98

V-W 1.04

 

 

Output

 

 

550

650

900

900

1200

 

 

Winding

 

 

 

U-V 1.70

 

U-W 1.70

U-V 1.91

 

U-W 1.91

U-V 0.98

 

U-W 0.98

U-V 0.98

 

U-W 0.98

U-V 1.04

 

U-W 1.04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan motor

Model

 

 

 

RC0J50-DB

RC0J50-DB

RC0J60-AA

RC0J60-AA

RC0J60-BC

Winding

 

 

 

WHT-BLK 37.0

WHT-BLK 37.0

WHT-BLK 15.2

WHT-BLK 15.2

WHT-BLK 15.0

 

 

BLK-RED 37.0

BLK-RED 37.0

BLK-RED 15.2

BLK-RED 15.2

BLK-RED 15.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

resistance(at 20

)

 

RED-WHT 37.0

RED-WHT 37.0

RED-WHT 15.2

RED-WHT 15.2

RED-WHT 15.0

 

 

 

 

 

 

 

 

Air flow(High/Low+)

*/h

2,058

 

1,938

2,004

2,940/1,650+

2,940/2,210+

2,940/1,650+

2,940/2,210+

3,.425/3,006

 

2,892/2,892

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

/1,512+

 

/2,280+

 

 

Dimensions W H D

mm

800%550%285

800%550%285

840%850%330

840%850%330

840%880%330

 

 

Weight

 

 

kg

 

30

 

33

 

53

 

53

53

 

 

Sound level *1

 

 

dB

 

46

47

 

48

53/51+

 

55/53+

53/51+

 

55/53+

55+

 

55+

Special remarks

 

Fanspeed(High+/Low+,High+/Med+/Low+) rpm

810+/650+880+/810+/650+

840+/760+

880+/800+/630+

840/480+

800/620+

840/480+

800/620+

950/840/450+

 

810/810/650+

 

Refrigerant filling

 

 

kg

0.80

1.05

1.60

1.80

1.80

 

 

Fan speed regulator

 

2

3

2

3

 

2

 

2

 

3

 

 

capacity(R410A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerating oil (Model)

cc

320 (NEO22)

320 (NEO22)

450 (NEO22)

450 (NEO22)

400 (FV50S)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE : Test conditions are based on ISO 5151

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cooling : Indoor

D.B. 27: W.B. 19:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor D.B. 35: W.B. 24:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating : Indoor

D.B. 20: W.B. 15:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor D.B. 7: W.B. 6:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant piping length (one way): 5m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*1 Measured under rated operating frequency.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

w Reference value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

Specifications and rating conditions of main electric parts

SUZ-KA25VA2.TH SUZ-KA35VA2.TH

SUZ-KA50VA2.TH SUZ-KA60VA2.TH

SUZ-KA71VA2.TH

 

Model

SUZ-KA25VA2.

SUZ0KA35VA2.

SUZ-KA50VA2.

SUZ-KA60VA2.

SUZ-KA71VA2.

Item

 

TH

 

TH

 

TH

TH

 

TH

 

(CT)

 

 

20A

 

 

-

 

-

Current

(CT1, 2)

 

-

 

 

ETQ19Z68AY

 

-

transformer

(CT61)

 

-

 

 

ETQ19Z53AY

 

-

 

(CT761, CT781)

 

 

15A

 

 

-

 

-

Smoothing

(C61)

 

-

 

620+ 420V

-

 

-

(C62, C63)

 

 

620+ 420V

 

 

-

 

-

capacitor

 

 

 

 

 

(CB1, 2, 3)

 

-

 

 

560μF 450V

 

560μF 350V

 

 

 

 

 

Diode module

(DB61)

15A 600V

 

25A 600V

-

 

-

(DB65)

 

 

25A 600V

 

 

-

 

-

 

 

 

 

 

 

 

(F61)

 

 

T20A L250V

 

 

-

 

-

 

(F62)

 

-

 

 

-

 

T20A L250V

Fuse

(F63)

 

-

 

 

-

 

-

(F64)

 

-

 

 

250V 2A

 

-

 

 

 

 

 

 

(F701, F801, F901)

 

 

T3.15A L250V

 

 

-

 

(F911)

 

-

 

 

250V 1A

 

-

Inteligent power

(IPM)

15A 600V

 

20A 600V

15A 600V

 

20A 600V

(HC930)

 

-

 

 

3A 450V

 

-

module

 

 

 

 

(IC932)

 

 

 

-

 

 

5A 600V

 

 

 

 

 

 

Power factor

(PFC)

 

-

 

 

PS51259-A

 

20A 600V

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

Expansion valve

(LEV)

 

 

 

 

DC12V

 

 

 

coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High pressure

(HPS)

 

-

 

 

ACB-DB156

 

-

switch

 

 

 

(for R2)

 

 

 

 

 

 

 

 

 

Reactor

(L61)

 

 

23mH

 

 

 

-

(L)

 

-

 

 

340μH 20A

 

340μH

 

 

 

 

 

 

(R61)

45mΩ 5W

 

100mΩ 5W

 

 

-

 

 

 

(1 element)

 

(2 elements)

 

 

 

 

 

 

 

 

 

 

 

 

 

(R61, R62)

 

-

 

180mΩ 5W

 

-

Current-detecting

 

 

(2 elements)

 

 

 

 

 

 

 

 

 

resistor

(R64A, R64B)

 

-

 

 

10Ω 10W

 

 

 

(R825)

 

 

25mΩ 5W

 

 

 

-

 

(R937, R938, R939)

430mΩ 2W

 

 

-

 

 

 

(R937A, R937B)

 

-

 

1.1Ω 2W

1.1Ω 2W 2%

 

-

Resistor

(RS1~4)

 

-

 

 

0.04Ω 7W

 

-

Current-Limiting

(PTC64, PTC65)

 

 

33Ω

 

 

-

 

33Ω

PTC thermistoe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal block

(TB1, TB2)

 

 

 

 

3P

 

 

 

 

(X63)

 

 

3A 250V

 

 

 

-

Relay

(X64)

 

 

20A 250V

 

 

20A 250V

 

20A 250V

(X601)

 

 

 

-

 

 

3A 250V

 

 

 

 

 

 

 

(X602)

 

 

 

-

 

 

3A 250V

Solenoid coil relay

(SSR61)

 

-

 

 

TLP3506

 

-

R.V. coil

(21S4)

 

 

 

 

AC220-240V

 

 

 

IGBT

(TR821)

 

 

30A 600V

 

 

-

 

-

8

Mitsubishi SUZ-KA25VA2.TH, SUZ-KA35VA2.TH, SUZ-KA50VA2.TH, SUZ-KA60VA2.TH, SUZ-KA71VA2.TH Service Manual

5 NOISE CRITERIA CURVES

SUZ-KA25VA2.TH

 

FAN SPEED

FUNCTION

SPL(dB(A))

 

LINE

 

 

 

 

 

 

 

 

High

COOLING

46

 

 

 

 

 

 

Med.

HEATING

46

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Test conditions,

 

 

 

 

 

 

Cooling : Dry-bulb temperature 35

Wet-bulb temperature (24 )

Heating : Dry-bulb temperature 7

Wet-bulb temperature 6

BAR

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0002 MICRO

80

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

NC-70

dB re

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

50

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

SOUND

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

BAND

 

 

 

 

 

 

 

 

NC-30

20

APPROXIMATE

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

THRESHOLD OF

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

CONTINUOUS

 

 

 

 

 

 

10

NOISE

 

 

 

 

 

 

 

 

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

SUZ-KA35VA2.TH

 

FAN SPEED

FUNCTION

SPL(dB(A))

 

LINE

 

 

 

 

 

 

 

 

High

COOLING

47

 

 

 

 

 

 

Med.

HEATING

48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Test conditions,

 

 

 

 

 

 

Cooling : Dry-bulb temperature 35

Wet-bulb temperature (24 )

Heating : Dry-bulb temperature 7

Wet-bulb temperature 6

BAR

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0002 MICRO

80

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

NC-70

dB re

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

50

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

SOUND

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

BAND

 

 

 

 

 

 

 

 

NC-30

20

APPROXIMATE

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

THRESHOLD OF

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

CONTINUOUS

 

 

 

 

 

 

10

NOISE

 

 

 

 

 

 

 

 

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

SUZ-KA50VA2.TH SUZ-KA60VA2.TH

SUZ-KA71VA2.TH

FAN SPEED FUNCTION SPL(dB(A))

LINE

COOLING 53

High

HEATING 55

FAN SPEED FUNCTION SPL(dB(A))

LINE

COOLING 55

High

HEATING 55

Test conditions,

 

 

Cooling : Dry-bulb temperature 35

 

Wet-bulb temperature (24 )

Heating : Dry-bulb temperature 7

 

Wet-bulb temperature 6

BAR

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0002 MICRO

80

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

NC-70

dB re

60

 

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

50

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

SOUND

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

BAND

 

 

 

 

 

 

 

 

NC-30

20

APPROXIMATE

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

THRESHOLD OF

 

 

 

 

 

 

 

HEARING FOR

 

 

 

 

 

NC-20

 

CONTINUOUS

 

 

 

 

 

 

10

NOISE

 

 

 

 

 

 

 

 

63

125

250

500

1000

2000

4000

8000

 

 

Test conditions,

 

 

Cooling : Dry-bulb temperature 35

 

Wet-bulb temperature (24 )

Heating : Dry-bulb temperature 7

 

Wet-bulb temperature 6

BAR

90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MICRO

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0002

70

 

 

 

 

 

 

NC-70

 

 

 

 

 

 

 

0dB re

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

LEVEL,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

50

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

SOUND

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

BAND

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

OCTAVE

 

 

 

 

 

 

 

 

 

 

 

NC-10

 

NC-20

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

125

250

500

1000

2000

4000

8000

 

63

BAND CENTER FREQUENCIES, Hz

 

BAND CENTER FREQUENCIES, Hz

Test conditions

 

OUTDOOR UNIT

Cooling: Dry-bulb temperature 35°C

 

Heating: Dry-bulb temperature

7°C

1 m

Wet-bulb temperature

6°C

MICROPHONE

9

6 OUTLINES AND DIMENSIONS

SUZ-KA25VA2.TH SUZ-KA35VA2.TH

REQUIRED SPACE

Unit: mm

Basically open 100mm or more without any obstruction in front and on both sides of the unit.

344.5

285

Air

44 in

400

Drain hole :42

Air in

 

Bolt pitch for installation 304~325

100mm

or

 

more

ormore 200mm

ormore 100mm

350mm

or

 

more

2-Oval holes 10×21

40

17.5

 

 

 

22.3

Air out

23

 

Handle

550

280

10

 

164.5

 

150

69

99.5

 

 

302.5

 

 

 

500 Bolt pitch for installation

800

Open two sides of left, right, or rear side.

Service panel

Liquid refrigerant pipe joint

Refrigerant pipe (flared) :6.35

35

43

Gas refrigerant pipe joint

Refrigerant pipe (flared) :9.52

170.5

Service port

10

SUZ-KA50VA2.TH SUZ-KA60VA2.TH

Unit: mm

REQUIRED SPACE

66

 

51 34

330

Air in

 

4-Oval holes 10×21

850

430

Drain holes :33

Open as a rule

500mm or more if

515

the front and both

299

sides are open

40

 

Air in

Air out 500

840

121

 

100mm or more

100mm or more

200mm or more if

there are obstacles

Bolt pitch for installation 360

to both sides

 

81 Open as a rule

500mm or more if the back, 350mm or more both sides and top are open

 

Service panel

 

Liquid refrigerant

 

pipe joint

 

Refrigerant pipe(flared)

 

:6.35

 

30

 

35

155 90

Gas refrigerant

 

pipe joint

198

Refrigerant pipe(flared)

:12.7·····(SUZ-KA50VA2.TH)

:15.88···(SUZ-KA60VA2.TH)

11

SUZ-KA71VA2.TH

417.5

Air in

50 330 Air in

Air out

175 500

840

109

880

452

Unit: mm

REQUIRED SPACE

Open as a rule

 

500mm or more if

 

the front and both

 

sides are open

Drain hole

42

40

 

 

Bolt pitch for installation 360

2-Oval holes 10 21

81

100

mm

 

 

or

 

more

 

350

mm

 

 

 

 

Open as a rule

 

or

more

 

 

500mm or more if the back, both sides and top are open

Service panel

Liquid refrigerant pipe joint Refrigerant pipe (flared) Ø 9.52

35

44

164.5

99.5

Gas refrigerant

195pipe joint Refrigerant pipe

(flared) Ø 15.88

100mm or more

200mm or more if there are obstacles to both sides

12

7 WIRING DIAGRAM

SUZ-KA25VA2.TH

SUZ-KA35VA2.TH

About the indoor side electric wiring, refer to

the indoor unit electric wiring diagram for servicing. Use copper conductors only. (For field wiring)

Symbols below indicate.

: Terminal block

NOTES:1.

2.

3.

 

13

W

RED 3

MS V WHT

3~

BLK

MC U

1

14

 

 

 

 

 

 

 

 

ORN

 

L61

YLW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21S4

 

 

 

 

 

 

LD70

LD66

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

CN721

 

 

 

 

 

DB65

DB61

C63

C62

C61

 

 

 

 

 

 

 

 

 

 

 

 

 

X63

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X64

 

 

 

 

 

 

 

 

 

 

 

IC802

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T801

 

 

 

 

 

 

 

 

 

F701

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PTC64

 

 

 

 

 

 

 

R825

 

 

 

F801

 

 

 

 

 

 

 

 

 

 

 

 

LD63

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LD-E1

 

 

 

3

RED

TR821

R61

 

 

 

R937A

 

R937B

 

 

 

 

 

 

 

 

CT

 

PTC65

BLK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LDW

W

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB1

 

 

WHT

V

 

 

 

F901

 

 

HC930

 

 

 

 

 

 

 

 

 

U

 

 

 

 

GRN/YLW

 

 

BLK

LDV

 

 

 

 

 

 

 

 

INVERTER P.C. BOARD

 

 

 

DSA

 

 

1

 

LDU

U

P

 

 

 

 

 

 

 

 

 

L62

 

N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IPM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

 

 

CN931

3

1

CN642

 

CN644

CN643

 

CN641

CN724

 

U

 

U

 

 

 

CIRCUIT

 

 

 

 

 

 

 

 

 

 

LD-S

BLU BRN

 

BREAKER

 

 

 

 

1

 

5

CN932

 

1

2

1

3

1

2

1

 

4

1

6

LD61

 

LD62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TB2

12-24V

 

 

 

 

 

 

 

MS

 

 

RT64

 

RT68

 

RT65

 

RT61

RT62

6

 

 

 

 

 

 

RED S3

 

 

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

 

 

 

S2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3~

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLU

230V~

 

 

 

 

 

 

 

MF

 

 

 

 

 

 

 

 

 

 

LEV

 

BRN

 

 

F61

 

BRN

S1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TH.KA50VA2-SUZ

POWER SUPPLY

~/N 230V 50Hz

TO INDOOR

UNIT CONNECTING

SYMBOL

NAME

CT

CURRENT TRANSFORMER

C61,62,63 SMOOTHING CAPACITOR DB61,DB65 DIODE MODULE

DSA

SURGE ABSORBER

F61

FUSE (T20AL 250V)

F701,F801,F901

FUSE (T3.15AL 250V)

HC930,IPM

INTELLIGENT POWER MODULE

IC802

INTELLIGENT POWER DEVICE

L61

REACTOR

L62

REACTOR

SYMBOL

NAME

SYMBOL

NAME

LEV

EXPANSION VALVE COIL

R61

CURRENT-DETECTING RESISTOR

MC

COMPRESSOR

R825

CURRENT-DETECTING RESISTOR

MF

FAN MOTOR

R937A, B CURRENT-DETECTING RESISTOR

PTC64,PTC65

CIRCUIT PROTECTION

TB1,TB52 TERMINAL BLOCK

RT61

DEFROST THERMISTOR

TR821 SWITCHING POWER TRANSISTOR

RT62

DISCHARGE TEMP. THERMISTOR

T801

TRANSFORMER

RT64

FIN TEMP. THERMISTOR

X63,X64 RELAY

RT65

AMBIENT TEMP. THERMISTOR

21S4

REVERSING VALVE COIL

RT68

OUTDOOR HEAT EXCHANGER

 

 

 

TEMP. THERMISTOR

 

 

NOTES: 1. About the indoor side electric wiring, refer to the indoor unit electric wiring diagram for servicing.

2.Use copper conductors only (for field wiring).

3.Symbols below indicate.

:Terminal block

TH.KA60VA2-SUZ

15

SYMBOL

NAME

SYMBOL

NAME

SYMBOL

NAME

NOTES: 1. About the indoor side electric wiring

CB1~3

SMOOTHING CAPACITOR

LEV

EXPANSION VALVE

RT65

AMBIENT TEMP. THERMISTOR

refer to the indoor unit electric wiring

CT1, 2

CURRENT TRANSFORMER

MC

COMPRESSOR

RT68

OUTDOOR HEAT EXCHANGER TEMP. THERMISTOR

diagram for servicing.

CT61

CURRENT TRANSFORMER

MF

FAN MOTOR

R64A,B RESISTOR

2. Use copper conductors only (for field wiring).

F64

FUSE (T2AL 250V)

NF

NOISE FILTER

R937A, B RESISTOR

3. Symbols below indicate.

F801

FUSE (T3.15AL 250V)

NR64

VARISTOR

SSR61 SOLENOID COIL RELAY

:Terminal block

F911

FUSE (T1AL 250V)

PFC

POWER FACTOR CONTROLLER

TB1

TERMINAL BLOCK

 

HC930 INTELLIGENT POWER MODULE

RS1~4 RESISTOR

TB2

TERMINAL BLOCK

 

HPS

HIGH PRESSURE SWITCH

RT61

DEFROST THERMISTOR

T801

TRANSFORMER

 

IPM

INTELLIGENT POWER MODULE

RT62

DISCHARGE TEMP. THERMISTOR

X64

RELAY

 

L

REACTOR

RT64

FIN TEMP. THERMISTOR

21S4

REVERSING VALVE COIL

 

SUZ-KA71VA2.TH

16

8 REFRIGERANT SYSTEM DIAGRAM

SUZ-KA25VA2.TH

Unit: mm

Refrigerant pipe

ø9.52

4-way valve

 

 

 

(with heat insulator)

 

 

 

 

 

 

 

 

 

 

Muffler

 

 

 

Outdoor heat

 

 

 

 

 

 

 

 

Stop valve

 

 

 

exchanger

 

 

 

 

 

temperature

 

 

(with service port)

 

 

 

Flared connection

Discharge

Muffler

Outdoor

thermistor

 

 

heat

RT68

 

 

 

temperature

 

exchanger

 

 

 

 

thermistor

 

 

 

 

 

 

RT62

Compressor

 

Ambient

 

 

 

 

 

 

 

 

 

 

 

temperature

 

 

 

 

 

 

thermistor

 

 

 

 

Defrost

 

RT65

 

 

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

 

RT61

 

 

 

 

 

 

 

Strainer

Flared connection

 

 

 

#100

 

Capillary tube

LEV

 

 

 

 

 

 

R.V. coil

 

 

ø3.0×ø2.0×240

 

 

 

 

 

 

heating ON

 

 

Stop valve

 

 

cooling OFF

 

 

 

 

 

 

Refrigerant pipe

ø6.35 (with strainer)

 

 

Refrigerant flow in cooling

(with heat insulator)

 

 

 

Refrigerant flow in heating

Unit: mm

SUZ-KA35VA2.TH

Refrigerant pipe ø9.52

4-way valve

 

 

 

(with heat insulator)

 

 

 

 

 

 

 

 

 

Muffler

 

 

 

Outdoor heat

 

 

 

 

 

 

Stop valve

 

 

 

exchanger

 

 

 

 

temperature

 

(with service port)

 

 

 

Flared connection

 

Muffler

Outdoor

thermistor

Discharge

 

heat

RT68

 

temperature

exchanger

 

 

thermistor

 

 

 

 

RT62

 

Compressor

 

Ambient

 

 

 

 

 

 

 

 

 

temperature

 

 

 

 

 

thermistor

 

 

 

Defrost

 

RT65

 

 

 

 

 

 

 

 

thermistor

 

 

 

 

RT61

 

 

 

 

 

Capillary tube

 

 

 

 

 

ø3.0×ø1.8×600(×2)

 

 

 

 

 

Strainer

Flared connection

 

LEV

 

#100

 

Capillary tube

 

 

 

 

 

R.V. coil

 

ø3.0×ø2.0×240

 

 

 

 

 

 

heating ON

 

Stop valve

 

 

cooling OFF

 

 

 

 

 

Refrigerant pipe ø6.35

(with strainer)

 

 

Refrigerant flow in cooling

(with heat insulator)

 

 

 

Refrigerant flow in heating

17

SUZ-KA50VA2.TH

 

 

 

 

 

 

 

 

Unit: mm

 

 

Muffler

 

 

4-way valve

#100

 

 

Refrigerant pipe ø12.7

 

 

 

 

(with heat insulator)

 

 

 

 

Stop valve

 

 

 

 

(with service port)

 

 

Outdoor

 

Flared connection

 

Discharge

heat

Ambient

 

 

temperature

exchanger

temperature

 

 

thermistor

Defrost

thermistor

 

 

RT62

thermistor

RT65

 

 

 

RT61

 

 

 

Compressor

 

 

 

 

Outdoor heat

 

 

 

 

exchanger

 

 

 

 

temperature

 

 

 

 

thermistor

 

Flared connection

 

 

RT68

 

 

LEV

Strainer

 

 

 

 

Receiver

 

#100

 

Stop valve

 

 

R.V. coil

 

Capillary tube

heating ON

(with strainer)

ø3.6×ø2.4×50

cooling OFF

Refrigerant pipe ø6.35

 

 

 

 

(with heat insulator)

 

 

 

 

Refrigerant flow in cooling

Refrigerant flow in heating

SUZ-KA60VA2.TH

 

 

 

Unit: mm

Refrigerant pipe :15.88

Muffler

 

 

 

(with heat insulator)

4-way valve #100

 

 

 

 

Stop valve

High-pressure

 

 

 

(with service port)

Outdoor

 

Flared connection

Discharge

switch

 

heat

Ambient

 

 

temperature

Defrost

exchanger

temperature

 

thermistor

 

thermistor

 

RT62

thermistor

 

RT65

 

 

RT61

 

 

 

 

Compressor

Outdoor heat

 

 

 

 

 

 

 

 

exchanger

 

 

 

 

temperature

 

 

 

 

thermistor

Flared connection

 

 

 

RT68

Strainer

LEV

Strainer

 

 

R.V. coil

Receiver #100

 

#100

 

 

 

 

heating ON

Stop valve

Capillary tube

 

cooling OFF

Refrigerant pipe :6.35

:3.6 :2.4 50

 

Refrigerant flow in cooling

 

 

 

(with heat insulator)

 

 

 

Refrigerant flow in heating

18

 

 

SUZ-KA71VA2.TH

Unit: mm

Refrigerant pipe ø15.88

 

Muffler

4-way valve

#100

(with heat insulator)

 

 

Stop valve

 

 

 

 

(with service port)

 

 

Outdoor

 

Flared connection

Discharge

 

heat

Ambient

 

temperature

Defrost

exchanger

temperature

 

thermistor

 

thermistor

 

RT62

thermistor

 

RT65

 

 

RT61

 

 

 

Compressor

Outdoor heat

 

 

 

 

 

 

 

 

exchanger

 

 

 

 

temperature

 

 

 

 

thermistor

 

Flared connection

 

 

RT68

 

LEV

Strainer

 

 

Strainer

R.V. coil

 

#100

 

#100

 

 

 

 

heating ON

 

Stop valve

Capillary tube

 

cooling OFF

 

Refrigerant pipe ø9.52

ø4.0×ø2.4×100

Refrigerant flow in cooling

 

(with heat insulator)

 

Refrigerant flow in heating

19

SUZ-KA25VA2.TH SUZ-KA35VA2.TH SUZ-KA50VA2.TH

SUZ-KA60VA2.TH SUZ-KA71VA2.TH

MAX. REFRIGERANT PIPING LENGTH

Models

Refrigerant piping: m

Piping size O.D: mm

Max. Length A

Max. Height difference B

Gas

Liquid

 

SUZ-KA25VA2.TH

20

12

9.52

 

SUZ-KA35VA2.TH

6.35

 

 

 

SUZ-KA50VA2.TH

30

30(15)

12.7

 

SUZ-KA60VA2.TH

15.88

 

SUZ-KA71VA2.TH

 

 

9.52

 

 

 

( ): MFZ-KA50VA-E4

MAX. HEIGHT DIFFERENCE

Indoor

unit

+Max. Height difference B

Max. Length

A

Outdoor unit

+ Height difference limitations are binding regardless of which unit, indoor or outdoor, is position high.

ADDITIONAL REFRIGERANT CHARGE (R410A: g)

Models

Outdoor unit

 

 

 

 

 

Refrigerant piping length (one way)

 

 

 

precharged

5m

 

6m

7m

 

8m

 

9m

10m

11m

12m

13m

14m

15m

20m

 

 

 

 

SUZ-KA25VA2.TH

800

0

 

0

0

 

90

 

120

150

180

210

240

270

300

450

SUZ-KA35VA2.TH

1,050

0

 

0

0

 

90

 

120

150

180

210

240

270

300

450

 

 

 

 

 

 

 

 

 

Calculation: Xg=30g/mo(Refrigerant piping length(m)-5)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Models

Outdoor unit

 

 

 

 

 

Refrigerant piping length (one way)

 

 

 

precharged

 

7m

10m

 

15m

20m

25m

30m

 

 

 

SUZ-KA50VA2.TH

1,600

 

0

60

 

 

160

260

360

460

SUZ-KA60VA2.TH

1,800

 

0

60

 

 

160

260

360

460

 

 

 

 

 

 

 

 

Calculation : Xg=20g/m o (Refrigerant piping length(m)–7)

 

 

 

 

 

 

 

 

 

 

 

Models

Outdoor unit

 

 

 

 

 

Refrigerant piping length (one way)

 

 

 

precharged

 

7m

10m

 

15m

20m

25m

30m

 

 

 

SUZ-KA71VA2.TH

1,800

 

0

165

 

 

440

715

990

1,265

Calculation : Xg=55g/m o (Refrigerant piping length(m)-7)

20

9 ACTUATOR CONTROL

SUZ-KA25VA2.TH SUZ-KA35VA2.TH SUZ-KA50VA2.TH SUZ-KA60VA2.TH SUZ-KA71VA2.TH

9-1. Outdoor fan motor control

The fan motor turns ON/OFF, interlocking with the compressor.

[ON] The fan motor turns ON 5 seconds before the compressor starts up.

[OFF] The fan motor turns OFF 15 seconds after the compressor has stopped running.

5 seconds

15 seconds

ON

Compressor

OFF

ON

Outdoor fan

OFF

9-2. R.V. coil control

Heating . . . . . . . . . . . . . . . . . ON

Cooling . . . . . . . . . . . . . . . . . OFF Dry . . . . . . . . . . . . . . . . . . . . OFF

<COOL>

5 seconds

ON

Compressor OFF

R.V.coil ON

OFF

Outdoor fan ON motor OFF

NOTE: The 4-way valve reverses for 5 seconds right before start-up of the compressor.

<HEAT>

5 seconds

9-3. Relation between main sensor and actuator

Sensor

Purpose

 

 

Actuator

 

Compressor

LEV

 

Outdoor fan

R.V.coil

 

 

 

motor

 

 

 

 

 

 

 

 

 

 

 

 

 

Discharge temperature

Protection

 

 

 

thermistor

 

 

 

 

 

 

 

Indoor coil temperature

Cooling: Coil frost prevention

 

 

 

 

thermistor

 

 

 

 

Heating: High pressure protection

 

 

 

 

 

Defrost thermistor

Heating: Defrosting

 

 

 

 

 

 

Fin temperature thermistor

Protection

 

 

 

 

 

 

 

 

Ambient temperature

Cooling: Low ambient temperature operation

 

 

thermistor

 

 

Outdoor heat exchanger tem-

Cooling: Low ambient temperature operation

 

 

perature thermistor

Cooling: High pressure protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

21

10 SERVICE FUNCTIONS

SUZ-KA25VA2.TH SUZ-KA35VA2.TH

CHANGE IN DEFROST SETTING

<JS> When the JS wire of the outdoor Inverter P.C. board is cut/ soldered, the defrost finish temperature is changed. (Refer to 11-6-1)

 

Jumper wire

Defrost finish temperature

 

SUZ-KA25VA2.TH

SUZ-KA35VA2.TH

 

 

 

 

 

soldered

5:

10:

JS

 

(Initial setting)

 

 

 

 

none

8:

13:

 

 

 

 

(cut)

 

 

 

 

11 TROUBLESHOOTING

SUZ-KA25VA2.TH

SUZ-KA35VA2.TH

SUZ-KA71VA2.TH

SUZ-KA50VA2.TH

SUZ-KA60VA2.TH

11-1. Cautions on troubleshooting

1.Before troubleshooting, check the following:

1)Check the power supply voltage.

2)Check the indoor/outdoor connecting wire for miswiring.

2.Take care the following during servicing.

1)Before servicing the air conditioner, be sure to turn OFF the main unit first with the remote controller, and turn off the breaker.

2)Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the electronic control P.C. board.

3)When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.

4)When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the components.

5)When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lead wire

Housing point

3.Troubleshooting procedure

1)First, check if the OPERATION INDICATOR lamp is blinking on and off to indicate an abnormality. To make sure, check how many times the abnormality indication is blinking on and off before starting service work.

2)Before servicing check that the connector and terminal are connected properly.

3)If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the components for bursting and discoloration.

4)When troubleshooting, refer to 11-2. and 11-3.

22

Number of blinks/beeps in pattern indicates the check code in the next page (i.e., n=5 for “P5”)

11-2. Failure mode recall function

As this air conditioner has a function to memorize all the failures that had happened, the latest failure detail can be recalled by following the procedures below.

Use this function when the check code is not displayed with wired remote controller or the remote controller at use is wireless type.

11-2-1. Flow chart of the indoor/outdoor unit failure mode recall function

Operational procedure (For wireless remote controller)

Setting up the failure mode recall function

Turn ON the power supply.

While pressing both OPERATION SELECT button and TOO COOL button on the remote controller at the same time, press RESET button.

First, release RESET button.

And release the other two buttons since all LCD in operation display section of the remote controller is displayed after 3 seconds.

TOO

TOO

COOL

 

 

FAN

SELECT

 

 

 

 

L

 

TIME

AUTO COO

VANE

HEAT

DRY

 

 

 

 

 

 

RESET

While pressing both OPERATION SELECT button and TOO COOL button on the

remote controller at the same time, press RESET button.

First, release RESET button.

And release the other two buttons since all LCD

in operation display section of the remote controller is displayed after 3 seconds.

1

Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed).

h

ON/OFF

TOO

TOO

 

WARM

COOL

1. Regardless of normal or abnormal, a short beep is emitted once as the signal is received.

Does OPERATION INDICATOR lamp on the indoor unit blink at the interval of 0.5 seconds?

Blinks: Either indoor or outdoor unit is abnormal. Beep sounds are emitted at the same timing of the blinking of OPERATION INDICATOR lamp. 2

Yes Judgment of indoor/outdoor abnormality (Blinks)

No (OFF)

Indoor unit is normal.

There is a possibility that the plasma or outdoor unit is abnormal. Confirm the failure detail on the LED display of the outdoor

controller board.(refer to 11-2-4.)

Before blinking, does POWER

Yes

lamp stay ON for 3 seconds?

 

Stays ON for 3 seconds (without beep):

 

The outdoor unit is abnormal.

 

 

No

 

 

 

The indoor unit is abnormal.

Check the blinking pattern, and confirm the abnormal point.

Make sure to check at least two consecutive blinking cycles. 2

The outdoor unit is abnormal.

Check the blinking pattern, and confirm the abnormal point(11-2.3.).

Make sure to check at least two consecutive blinking cycles. 3

Releasing the failure mode recall function

 

Release the failure mode recall function by the following procedures.

 

With the remote controller headed towards the indoor unit, press any button

 

that is not used in this failure mode recall function (e.g. TIMER button) .

 

OR

 

Turn OFF the power supply and turn ON it again.

 

Press RESET button of the remote controller.

OPERATION INDICATOR lamp

 

Repair the defective parts.

Note1. Make sure to release the failure mode recall function once it is set up, otherwise the unit cannot operate properly. 2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

2. Blinking pattern when the indoor unit is abnormal:[Output pattern A]

Beeper sounds

Beep

 

Beep

Beep

Beep

OPERATION

 

 

 

 

 

 

1st

 

2nd

 

3rd

 

INDICATOR

 

 

 

 

 

 

 

 

 

 

 

 

lamp blink

 

 

 

Off

 

 

On

On

On

pattern

Self-check Approx. 2.5 sec.0.5 sec. 0.5 sec. 0.5 sec.

starts (Start signal received)

Beep

 

 

Beep

Beep

 

 

 

 

 

 

 

 

 

 

 

 

n th

 

 

 

 

 

1st

 

2 nd · · · Repeated

 

 

 

 

 

 

 

 

 

On

Off

 

 

On

On

0.5 sec. Approx. 2.5 sec.0.5 sec.

0.5 sec.

Number of blinks/beeps in pattern indicates the check code in the next page

3.Blinking pattern when the outdoor unit is abnormal:[Output pattern B]

Beeper sounds

Beep

OPERATION

 

INDICATOR

 

lamp blink

Off

pattern

Self-check Approx. 2.5 sec.

 

starts

 

(Start signal

 

received)

 

 

 

Beep

Beep

Beep

 

Beep

 

 

 

 

 

Beep

Beep

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st

 

2nd

 

3rd

 

 

 

nth

 

 

 

 

 

 

 

 

1st

 

2nd · · · Repeated

 

 

 

On

On

On

 

 

 

 

 

 

 

 

 

On

On

On

 

 

 

On

Off

 

On

 

Approx. 3 sec.

0.5 sec. 0.5 sec.0.5 sec.

 

0.5 sec. Approx. 2.5 sec.

 

Approx. 3 sec.

0.5 sec.

0.5 sec.

Number of blinks/beeps in pattern indicates the check

 

 

Number of blinks/beeps in pattern indicates

code in the next page (i.e., n=5 for “U2”)

 

 

 

 

 

the check code in the next page

23

Loading...
+ 51 hidden pages