Milton CAT G25LTA User Manual

4 (1)
Milton CAT G25LTA User Manual

G25LTA

Liquid Cooled Gas Engine Generator Sets

Standby Power Rating

25 kW 60 Hz

STANDARD EQUIPMENT

All input connections in one single area

High coolant temperature shutdown

Low oil pressure shutdown

Low coolant level automatic shutdown

Overspeed automatic shutdown

Crank timer

Exercise timer

Oil drain extension

Cool flow radiator

Closed coolant recovery system

UV/Ozone resistant hoses

Watertight state of the art electrical connectors

FEATURES

Innovative design and fully prototype tested

UL2200 Listed

Solid state frequency compensated voltage regulator

Dynamic and static battery charger

Sound attenuated acoustically designed enclosure

Low noise level exercise mode

Acoustically designed engine cooling system

High flow low noise factory engineered exhaust system

2.4L ENGINE

Naturally Aspirated

Gaseous Fueled

G25LTA

Meets 2009 EPA Emission Regulations

Mainline circuit breaker

Radiator drain extension

Battery charge alternator

10 Amp static battery charger

Battery and battery cables

Battery rack

Fan and belt guards

Isochronous governor

Flex fuel line

Coolant heater

State of the art digital control system with H100 digital control panel

Watertight electrical connectors

Rodent proof construction

High efficiency, low distortion alternator

Vibration isolated from mounting base

All components easily accessible for maintenance

Electrostatically applied powder paint

APPLICATION

& ENGINEERING DATA

GENERATOR SPECIFICATIONS

TYPE............................................................................................................

Synchronous

ROTOR INSULATION..........................................................................................

Class H

STATOR INSULATION.........................................................................................

Class H

TOTAL HARMONIC DISTORTION............................................................................

<5%

TELEPHONE INTERFERENCE FACTOR (TIF).........................................................

<50

ALTERNATOR OUTPUT LEADS 3 PHASE............................................................

4 wire

BEARINGS.....................................................................................................

Sealed Ball

COUPLING..................................................................................................

Flexible Disc

LOAD CAPACITY (STANDBY RATING).................................................................

25 kW

EXCITATION SYSTEM............................................................................................

Direct

NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046, and DIN6271 standards.

VOLTAGE REGULATOR

TYPE................................................................................................................

Full Digital

SENSING............................................................................................................

3 Phase

REGULATION.......................................................................................................

± 1/4%

FEATURES.......................................................................

Built into H-100 Control Panel

 

V/F Adjustable

 

Adjustable Voltage and Gain

 

G25LTA

ENGINE SPECIFICATIONS

 

ENGINE............................................................................................................

Gaseous

TYPE........................................................................................................................

Inline

CYLINDERS....................................................................................................................

4

DISPLACEMENT.................................................................................................

2.4 Liter

BORE.........................................................................................................................

3.41

STROKE....................................................................................................................

3.94

COMPRESSION RATIO............................................................................................

8.5:1

INTAKE AIR SYSTEM........................................................................

Naturally Aspirated

VALVE SEATS...................................................................................................

Hardened

LIFTER TYPE....................................................................................................

Hydraulic

GOVERNOR SPECIFICATIONS

 

TYPE.................................................................................................................

Electronic

FREQUENCY REGULATION........................................................................

Isochronous

STEADY STATE REGULATION..............................................................................

± 0.25

ADJUSTMENTS FOR:

 

Speed......................................................................................................

Yes

Droop.......................................................................................................

Yes

GENERATOR FEATURES

Revolving field heavy duty generator

Directly connected to the engine

Operating temperature rise 120 °C above a 40 °C ambient

Insulation is Class H rated at 150 °C rise

All prototype models have passed three phase short circuit testing

ENGINE LUBRICATION SYSTEM

OIL PUMP.................................................................................................................

Gear

OIL FILTER.............................................................................

Full flow spin-on cartridge

CRANKCASE CAPACITY...................................................................................

4 Quarts

CONTROL PANEL FEATURES

TWO FOUR LINE LCD DISPLAYS READ:

• Voltage (all phases)

• Current (all phases)

• Power factor

• kW

• kVAR

• Transfer switch status

• Engine speed

• Low fuel pressure

• Run hours

• Service reminders

• Fault history

• Oil pressure

• Coolant temperature

• Time and date

• Low oil pressure shutdown

• High coolant temperature shutdown

• Overvoltage

• Overspeed

• Low coolant level

• Low coolant level

• Not in auto position (flashing light)

• Exercise speed

INTERNAL FUNCTIONS:

I2T function for alternator protection from line to neutral and line to line short circuits

Emergency stop

Programmable auto crank function

2 wire start for any transfer switch

Built-in 7 day exerciser

Adjustable engine speed at exerciser

RS232 port for GenLink® control

RS485 port remote communication

Canbus addressable

Governor controller and voltage regulator are built into the master control board

Temperature range -40 °C to 70 °C

ENGINE COOLING SYSTEM

TYPE......................................................................................................................

Closed

WATER PUMP.................................................................................................

Belt driven

FAN SPEED..............................................................................................................

2150

FAN DIAMETER................................................................................................

18 inches

FAN MODE...........................................................................................................

Pusher

COOLANT HEATER.....................................................................................

1500W 120V

FUEL SYSTEM

FUEL TYPE...........................................................................

Natural gas, propane vapor

CARBURETOR...............................................................................................

Down Draft

SECONDARY FUEL REGULATOR...................................................................

Standard

FUEL SHUT OFF SOLENOID...........................................................................

Standard

OPERATING FUEL PRESSURE..................................................................

5” - 14” H2O

ELECTRICAL SYSTEM

BATTERY CHARGE ALTERNATOR.

............................................................12V 30 Amp

STATIC BATTERY CHARGER.............................................................................

10 Amp

BATTERY...........................................................................................

Group 26, 525CCA

SYSTEM VOLTAGE..............................................................................................

12 Volts

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).

Loading...
+ 2 hidden pages