Metrohm E1612 Instruction Manual

E1612 EARTH TESTER
INSTRUCTION MANUAL
GENERAL SAFETY INFORMATION: Always read before proceeding.
Warning These instructions contain both information and warnings that are necessary for the safe operation and maintenance of this product. It is recommended that you read the instructions carefully and ensure that the contents are fully understood. Failure to understand and to comply with the warnings and instructions can result in serious injury, damage or even death.
In order to avoid the danger of electrical shock, it is important that proper safety measures are taken when working with voltages exceeding 30V AC RMS, 42V AC peak or 60V DC.
This product must only be used by a competent person capable of interpreting the results under the conditions and for the purposes for which it has been constructed. Particular attention should be paid to the Warnings, Precautions and Technical Specifications. Always check the unit is in good working order before use and that there are no signs of damage to it. Do not use if damaged.
Where applicable other safety measures such as use of protective gloves, goggles etc. should be employed.
Please keep these instructions for future reference. Updated instructions and product information are available at: www.martindale-electric.co.uk
REMEMBER: SAFETY IS NO ACCIDENT
MEANING OF SYMBOLS:
Equipment complies with relevant EU Directives
End of life disposal of this equipment should be in accordance with relevant Local Directives
Caution - risk of danger and refer to instructions
Caution - risk of electric shock
Equipment protected by double or reinforced insulation (Class II)
Earth (ground)
Thank you for buying one of our products. For safety and full understanding of its benefits please read this manual before use. Technical support is available from 01923 441717 and support@martindale-electric.co.uk.
CONTENTS
1 Introduction 1
1.1 Inspection 1
1.2 Description 1
1.3 Accessories 1
1.4 Battery Installation 1
2 Product Specific Safety Information 2
2.1 Precautions 2
3 Operation 4
3.1 General 4
3.2 Low Battery Indication 4
3.3 Description of Terminals 4
3.4 Description of Press Buttons 4
3.5 Display and LED Indications 5
3.6 Earth Voltage Measurement 5
3.7 Earth Resistance Measurement 6
4 Maintenance 14
4.1 Battery Replacement 14
4.2 Fuse Replacement 14
4.3 Calibration 14
4.4 Cleaning 15
4.5 Repair & Service 15
4.6 Storage Conditions 15
5 Warranty 16
Specifications
1
1. INTRODUCTION
1.1 Inspection
Examine the shipping carton for any sign of damage. Inspect the unit and any accessories for damage. If there is any damage then consult your distributor immediately.
1.2 Description
The E1612 is an earth resistance tester with the following features:
• Microprocessor controlled with advanced safety features
• Large LCD display
• Earth resistance auto ranging, 0-2kin 4 ranges
• Earth voltage measurement: 0-30V AC
• 2, 3 & 4 pole test modes selectable.
• Auto power off
• Indoor and outdoor use
1.3 Accessories
The following accessories are supplied with the E1612:
Set of test leads with integral crocodile clips (red 15m, black 10m,
yellow 10m and green 5m)
Carrying case
Set of 4 x spikes
Shoulder strap
8 x 1.5V alkaline AA batteries
Spare F100mA 250V 5 x 20mm fuse
Instructions
1.4 Battery Installation
Refer to Section 4.1 (Battery Replacement) for the battery
installation instructions for the E1612.
2
2. PRODUCT SPECIFIC SAFETY INFORMATION
Measurement Category III (CAT III) is applicable to test and measuring equipment connected to the distribution part of the building’s low-voltage MAINS installation.
Measurement Category IV (CAT IV) is applicable to test and measuring equipment connected at the source of the building’s low-voltage MAINS installation.
2.1 Precautions
This product has been designed with your safety in mind, but please pay attention to the following warnings and cautions before use.
Warnings
Before use check the unit for cracks or any other damage. Make sure the unit is free from dust, grease and moisture. Also check any associated leads and accessories for damage. Do not use if damaged.
Do not use if the battery/fuse cover is not fitted.
When this unit is used in combination with test leads, the measurement category of the combination is the lower measurement category of either this unit or the test leads used. Likewise if test lead accessories such as crocodile clips are also used, the measurement category will be the lowest measurement category in that combination.
Always test this unit on an appropriate proving device or a known voltage source before using it to determine if a hazardous voltage exists in a circuit to be tested.
3
Measuring/testing for a voltage that exceeds the specified limits of the earth resistance tester may damage the unit and expose the operator to a shock hazard. Always check the earth resistance tester’s specified limits before use.
The earth resistance tester must only be used on CAT IV, CAT III and CAT II installations up to 300V to earth, and within the operating temperature and humidity range specified.
When using the integral lead/crocodile clip set provided always keep your fingers behind the crocodile clip finger guards.
Cautions
Avoid severe mechanical shock or vibration and extreme temperature.
To avoid corrosion from leaking batteries, remove the batteries when not in use for an extended period.
4
3. OPERATION
3.1 General
For safety and measurement accuracy only the lead set
supplied with the E1612 should be used.
The measured results may be influenced by induction if measurements are made with the test leads twisted together. When making connections they should be separated.
3.2 Low Battery Indication
If Battery: Low is displayed on the LCD after the E1612 has been turned on, or at any time during use, replace the batteries (see section 4.1).
3.3 Description of Terminals
3.4 Description of Press Buttons
E/C1 Terminal for the earth electrode (black test lead)
ES/P1
Terminal for the probe placed nearest to the earth electrode (green test lead)
S/P2 Terminal for a probe (yellow test lead)
H/C2 Terminal for the auxiliary ear th electrode (red test lead)
2P Selects 2 pole earth resistance measurement mode
3P Selects 3 pole earth resistance measurement mode
4P Selects 4 pole earth resistance measurement mode
ACV
Selects AC voltage measuring function to check earth voltage
ON/OFF Turns on/off the E1612
TEST/
STOP
Starts and stops earth resistance and earth voltage measurements.
5
3.5 Display and LED Indications
3.6 Earth Voltage Measurement
Connect the test leads as shown in figure 1 or on the inside of the E1612 lid.
On the E1612 press ON/OFF to turn the unit on, press ACV and TEST/STOP. The earth voltage will be displayed.
Note: An earth voltage greater than 10V may result in errors in the earth resistance measurement. Make sure that the earth voltage is less than 10V.
Battery: Low
Indicates the batteries need to be replaced. (See 4.1). The battery level in volts is normally indicated
Rc/Rc Error
The C1 or C2 leads are open circuit or the resistance in the C1 or C2 leads is greater than 10kΩ. Check the auxiliary earth spikes are connected correctly
P1 Line Fail!
The P1 lead is open circuit or the resistance in the P1 lead is greater than 20k
P2 Line Fail!
The P2 lead is open circuit or the resistance in the P2 lead is greater than 20k
Rp
The Rp LED indicates an earth resistance > 2kΩ. The LCD will display > 2kΩ
Vp Error
When making a ‘4P measurement’, if the LCD shows ‘Vp Error’ short circuit C1 (black) and P1 (green)