KROHNE OPTISOUND 3020 C Operating Manual

Operating Instructions
OPTISOUND 3020 C 4 ... 20 mA/HART - four-wire

Contents

Contents
1 About this document
1.1 Function .............................
1.2 Target group ..........................
1.3 Symbolism used .......................
2.1 Authorised personnel....................
2.2 Appropriate use........................
2.3 Warning about misuse ...................
2.4 General safety instructions ................
2.5 CE conformity .........................
2.6 Compatibility acc. to NAMUR NE 53 .........
2.7 Safety information for Ex areas.............
3 Product description
3.1 Conguration..........................
3.2 Principle of operation ....................
3.3 Adjustment ...........................
3.4 Storage and transport ...................
4 Mounting
4.1 General instructions.....................
4.2 Mounting information ....................
5 5 5
6 6 6 6 6 6 7
8 9 9 9
11 13
5 Connecting to power supply
5.1 Preparing the connection .................
5.2 Connection procedure ...................
5.3 Wiring plans, double chamber housing .......
5.4 Switch on phase .......................
6 Setup with the indicating/adjustment module
6.1 Short description .......................
6.2 Installation of the indicating/adjustment module .
6.3 Adjustment system .....................
6.4 Setup procedure .......................
6.5 Menu schematic .......................
7 Maintenance and fault rectication
7.1 Maintenance ..........................
7.2 Fault rectication .......................
7.3 Exchanging the electronics................
7.4 Instrument repair .......................
2 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
19 20 21 23
24 24 26 27 31
34 34 35 36
30508-EN-050914
8 Dismounting
8.1 Dismounting procedure ..................
8.2 Disposal .............................
9 Supplement
9.1 Technical data.........................
9.2 Dimensions ...........................
9.3 Certicate ............................
Contents
37 37
38 42 43
Supplementary operating instructions manuals
Information:
OPTISOUND 3020 C is available in dierent versions and is supplied specically acc. to the order. Depending on the selected version, supplementary operating instructions man­uals come with the shipment. The supplementary operating instructions are stated in paragraph "3. Product description".
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 3
About this document

1 About this document

1.1 Function

This operating instructions manual has all the information you need for quick setup and safe operation of OPTISOUND 3020 C. Please read this manual before you start setup.

1.2 Target group

This operating instructions manual is directed to trained personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbolism used

Information, tip, note
This symbol indicates helpful additional information.
Caution, warning, danger
This symbol informs you of a dangerous situation that could occur. Ignoring this cautionary note can impair the person and/ or the instrument.
Ex applications
This symbol indicates special instructions for Ex applications.
l List
The dot set in front indicates a list with no implied sequence.
à Action
This arrow indicates a single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
4 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
For your safety

2 For your safety

2.1 Authorised personnel

All operations described in this operating instructions manual must be carried out only by trained, specialised personnel authorised by the operator. For safety and warranty reasons, any internal work on the instruments must be carried out only by personnel authorised by the manufacturer.

2.2 Appropriate use

OPTISOUND 3020 C is a sensor for continuous level measurement.

2.3 Warning about misuse

Inappropriate or incorrect use of the instrument can give rise to application-specic hazards, e.g. vessel overll or damage to system components through incorrect mounting or adjustment.

2.4 General safety instructions

OPTISOUND 3020 C is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country-specic installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and accident prevention rules.

2.5 CE conformity

OPTISOUND 3020 C is in CE conformity with EMC (89/336/ EWG), fulls the NAMUR recommendation NE 21 and is in CE conformity with LVD (73/23/EWG).
Conformity has been judged acc. to the following standards:
l EMC:
- Emission EN 61326: 1997 (class A)
- Susceptibility EN 61326: 1997/A1: 1998
l LVD: EN 61010-1: 2001
2.6 Compatibility acc. to NAMUR NE 53
OPTISOUND 3020 C meets NAMUR recommendation NE 53.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 5
For your safety
The parameter adjustment of the basic sensor functions is
independent of the software version. The range of available functions depends on the respective software version of the individual components.
The software version of OPTISOUND 3020 C can be determined as follows:
l on the type label of the electronics l via the indicating/adjustment module.
You can nd all software histories on our website www.krohne. com.
2.7 Safety information for Ex areas
Please note the Ex-specic safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex­approved instruments.
6 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914

3 Product description

3.1 Conguration
Product description
Scope of delivery
Components
The scope of delivery encompasses:
l OPTISOUND 3020 C ultrasonic sensor l Documentation
- this operating instructions manual
- Ex-specic safety instructions (with Ex versions) and, if
necessary, further certicates
- Operating instructions manual "Indicating and adjust- ment module" - optional
OPTISOUND 3020 C consists of the following components:
l Process tting with transducer l Housing with electronics l Housing cover, optionally available with indicating/adjust-
ment module
The components are available in dierent versions.
1
2
3
Fig. 1: OPTISOUND 3020 C, version with plastic housing 1 Housing cover, optionally available with indicating/adjustment module 2 Housing with electronics 3 Process tting with transducer
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 7
Product description

3.2 Principle of operation

Area of application
Physical principle
Power supply
OPTISOUND 3020 C is an ultrasonic sensor for continuous level measurement. It is suitable for liquids and solids in virtually all industries, particularly in water and waste water management.
The transducer of the ultrasonic sensor emits short ultrasonic pulses to the measured product. These pulses are reected by the product surface and received by the transducer as echoes. The running time of the ultrasonic pulses from emission to reception is proportional to the distance and hence to the level. The determined level is converted into an appropriate output signal and outputted as measured value.
Four-wire electronics with separate power supply.
The power supply range can dier depending on the instru-
ment version. The exact range is stated in the "Technical data" in the "Supplement".
Measured value transmission is carried out via the 4 ... 20 mA/ HART output, which is separated from the power supply.

3.3 Adjustment

OPTISOUND 3020 C can be adjusted with two dierent adjustment media:
l the indicating/adjustment module l a HART handheld
The entered parameters are generally saved in OPTISOUND 3020 C, optionally also in the indicating/adjustment module.

3.4 Storage and transport

Packaging
Storage and transport tem-
perature
8 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test acc. to DIN EN 24180.
The packaging of standard instruments consists of environ-
ment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
l Storage and transport temperature see "Supplement –
Technical data – Ambient conditions"
30508-EN-050914
l Relative humidity 20 85 %
Product description
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 9
Mounting

4 Mounting

4.1 General instructions

Installation position
Moisture
Select an installation position you can easily reach for mounting and connecting as well as later retrotting of an indicating and adjustment module. The housing can be rotated by 330° without the use of any tools. You can also install the indicating and adjustment module in four dierent positions (each displaced by 90°).
Use the recommended cable (see chapter "Connecting to power supply") and thighten the cable gland.
You can give your OPTISOUND 3020 C additional protection against moisture penetration by leading the connection cable downward in front of the cable entry. Rain and condensation water can thus drain off. This applies mainly to mounting outdoors, in areas where moisture is expected (e.g. by cleaning processes) or on cooled or heated vessels.
Fig. 2: Measures against moisture penetration
Measuring range
The reference plane for the measuring range is the lower edge of the transducer.
Make sure that the min. distance, corresponding to the so called dead band, is maintained below the reference plane ­measurement is not possible in this areas. The exact value of the dead band is stated in chapter "Technical data" in the Supplement.
10 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Mounting
2
1
Fig. 3: Min. distance to the max. level 1 Dead zone 2 Reference plane
Information:
If the product reaches the transducer, buildup can form on it over a period of time and later cause measurement errors.
132
100%
0%
Fig. 4: Measuring range (operating range) and max. measuring distance 1 full 2 empty (max. measuring distance) 3 Measuring range
Pressure/Vacuum
Gauge pressure in the vessel does not inuence OPTISOUND
3020 C. Low pressure or vacuum, however, damp the ultrasonic pulses. This inuences the measuring result, particularly if the level is very low. With pressures under -
0.2 bar (-20 kPa) you should use a dierent measuring principle, e.g. radar or guided microwave.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 11
Mounting

4.2 Mounting information

Screwing in
Installation position
Screw OPTISOUND 3020 C into the mounting socket with an appropriate spanner applied to the hexagon of the process tting. Max. torque see chapter "Technical data".
Warning:
The housing must not be used to screw the instrument in! Applying tightening force to the housing can damage its
internal mechanical components.
When mounting OPTISOUND 3020 C, keep a distance of at least 200 mm (7.9 in) to the vessel wall. If the sensor is installed in the center of dished or rounded vessel tops, multiple echoes can arise. These can, however, be faded out by an appropriate adjustment (see chapter "Setup").
If this distance cannot be maintained, a false echo storage should be carried out during setup. This applies particularly if buildup on the vessel wall is expected. In this case, we recommend repeating the false echo storage later on with existing buildup.
2
1
> 200 mm
Fig. 5: Mounting on dished vessel tops 1 Reference plane 2 Vessel center or symmetry axis
In vessels with conical bottom it can be advantageous to mount the sensor in the center of the vessel, as measurement is then possible down to the lowest point of the vessel bottom.
12 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Fig. 6: Vessel with conical bottom
Mounting
Socket
The mounting socket should preferably be dimensioned to allow the lower edge of the transducer to protrude at least 10 mm out of the socket.
ca. 10 mm
Fig. 7: Recommended socket mounting
If the reective properties of the medium are good, you can mount OPTISOUND 3020 C on sockets higher than the transducer length. You will nd recommended values for socket heights in the following illustration. The socket end should be smooth and burr-free, if possible also rounded. Carry out a false echo storage.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 13
Mounting
Sensor orientation
d
100 mm/4"
h
> 10 mm
150 mm/6"
h
300 mm/12" 400 mm/16"
d
Fig. 8: Deviating socket dimensions
In liquids, direct the sensor as perpendicular as possible to the product surface to achieve optimum measurement results.
Fig. 9: Orientation in liquids
To reduce the min. distance to the medium, you can also mount OPTISOUND 3020 C with a beam deector. By doing this, it is possible to ll the vessel nearly to maximum. This arrangement is particularly suitable for open vessels such as e. g. overow basins.
~400x400
°
45
~200
Fig. 10: Beam deector
14 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914