KROHNE OPTISOUND 3020 C Operating Manual

Page 1
Operating Instructions
OPTISOUND 3020 C 4 ... 20 mA/HART - four-wire
Page 2

Contents

Contents
1 About this document
1.1 Function .............................
1.2 Target group ..........................
1.3 Symbolism used .......................
2.1 Authorised personnel....................
2.2 Appropriate use........................
2.3 Warning about misuse ...................
2.4 General safety instructions ................
2.5 CE conformity .........................
2.6 Compatibility acc. to NAMUR NE 53 .........
2.7 Safety information for Ex areas.............
3 Product description
3.1 Conguration..........................
3.2 Principle of operation ....................
3.3 Adjustment ...........................
3.4 Storage and transport ...................
4 Mounting
4.1 General instructions.....................
4.2 Mounting information ....................
5 5 5
6 6 6 6 6 6 7
8 9 9 9
11 13
5 Connecting to power supply
5.1 Preparing the connection .................
5.2 Connection procedure ...................
5.3 Wiring plans, double chamber housing .......
5.4 Switch on phase .......................
6 Setup with the indicating/adjustment module
6.1 Short description .......................
6.2 Installation of the indicating/adjustment module .
6.3 Adjustment system .....................
6.4 Setup procedure .......................
6.5 Menu schematic .......................
7 Maintenance and fault rectication
7.1 Maintenance ..........................
7.2 Fault rectication .......................
7.3 Exchanging the electronics................
7.4 Instrument repair .......................
2 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
19 20 21 23
24 24 26 27 31
34 34 35 36
30508-EN-050914
Page 3
8 Dismounting
8.1 Dismounting procedure ..................
8.2 Disposal .............................
9 Supplement
9.1 Technical data.........................
9.2 Dimensions ...........................
9.3 Certicate ............................
Contents
37 37
38 42 43
Supplementary operating instructions manuals
Information:
OPTISOUND 3020 C is available in dierent versions and is supplied specically acc. to the order. Depending on the selected version, supplementary operating instructions man­uals come with the shipment. The supplementary operating instructions are stated in paragraph "3. Product description".
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 3
Page 4
About this document

1 About this document

1.1 Function

This operating instructions manual has all the information you need for quick setup and safe operation of OPTISOUND 3020 C. Please read this manual before you start setup.

1.2 Target group

This operating instructions manual is directed to trained personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbolism used

Information, tip, note
This symbol indicates helpful additional information.
Caution, warning, danger
This symbol informs you of a dangerous situation that could occur. Ignoring this cautionary note can impair the person and/ or the instrument.
Ex applications
This symbol indicates special instructions for Ex applications.
l List
The dot set in front indicates a list with no implied sequence.
à Action
This arrow indicates a single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
4 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 5
For your safety

2 For your safety

2.1 Authorised personnel

All operations described in this operating instructions manual must be carried out only by trained, specialised personnel authorised by the operator. For safety and warranty reasons, any internal work on the instruments must be carried out only by personnel authorised by the manufacturer.

2.2 Appropriate use

OPTISOUND 3020 C is a sensor for continuous level measurement.

2.3 Warning about misuse

Inappropriate or incorrect use of the instrument can give rise to application-specic hazards, e.g. vessel overll or damage to system components through incorrect mounting or adjustment.

2.4 General safety instructions

OPTISOUND 3020 C is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country-specic installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and accident prevention rules.

2.5 CE conformity

OPTISOUND 3020 C is in CE conformity with EMC (89/336/ EWG), fulls the NAMUR recommendation NE 21 and is in CE conformity with LVD (73/23/EWG).
Conformity has been judged acc. to the following standards:
l EMC:
- Emission EN 61326: 1997 (class A)
- Susceptibility EN 61326: 1997/A1: 1998
l LVD: EN 61010-1: 2001
2.6 Compatibility acc. to NAMUR NE 53
OPTISOUND 3020 C meets NAMUR recommendation NE 53.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 5
Page 6
For your safety
The parameter adjustment of the basic sensor functions is
independent of the software version. The range of available functions depends on the respective software version of the individual components.
The software version of OPTISOUND 3020 C can be determined as follows:
l on the type label of the electronics l via the indicating/adjustment module.
You can nd all software histories on our website www.krohne. com.
2.7 Safety information for Ex areas
Please note the Ex-specic safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex­approved instruments.
6 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 7

3 Product description

3.1 Conguration
Product description
Scope of delivery
Components
The scope of delivery encompasses:
l OPTISOUND 3020 C ultrasonic sensor l Documentation
- this operating instructions manual
- Ex-specic safety instructions (with Ex versions) and, if
necessary, further certicates
- Operating instructions manual "Indicating and adjust- ment module" - optional
OPTISOUND 3020 C consists of the following components:
l Process tting with transducer l Housing with electronics l Housing cover, optionally available with indicating/adjust-
ment module
The components are available in dierent versions.
1
2
3
Fig. 1: OPTISOUND 3020 C, version with plastic housing 1 Housing cover, optionally available with indicating/adjustment module 2 Housing with electronics 3 Process tting with transducer
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 7
Page 8
Product description

3.2 Principle of operation

Area of application
Physical principle
Power supply
OPTISOUND 3020 C is an ultrasonic sensor for continuous level measurement. It is suitable for liquids and solids in virtually all industries, particularly in water and waste water management.
The transducer of the ultrasonic sensor emits short ultrasonic pulses to the measured product. These pulses are reected by the product surface and received by the transducer as echoes. The running time of the ultrasonic pulses from emission to reception is proportional to the distance and hence to the level. The determined level is converted into an appropriate output signal and outputted as measured value.
Four-wire electronics with separate power supply.
The power supply range can dier depending on the instru-
ment version. The exact range is stated in the "Technical data" in the "Supplement".
Measured value transmission is carried out via the 4 ... 20 mA/ HART output, which is separated from the power supply.

3.3 Adjustment

OPTISOUND 3020 C can be adjusted with two dierent adjustment media:
l the indicating/adjustment module l a HART handheld
The entered parameters are generally saved in OPTISOUND 3020 C, optionally also in the indicating/adjustment module.

3.4 Storage and transport

Packaging
Storage and transport tem-
perature
8 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test acc. to DIN EN 24180.
The packaging of standard instruments consists of environ-
ment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
l Storage and transport temperature see "Supplement –
Technical data – Ambient conditions"
30508-EN-050914
Page 9
l Relative humidity 20 85 %
Product description
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 9
Page 10
Mounting

4 Mounting

4.1 General instructions

Installation position
Moisture
Select an installation position you can easily reach for mounting and connecting as well as later retrotting of an indicating and adjustment module. The housing can be rotated by 330° without the use of any tools. You can also install the indicating and adjustment module in four dierent positions (each displaced by 90°).
Use the recommended cable (see chapter "Connecting to power supply") and thighten the cable gland.
You can give your OPTISOUND 3020 C additional protection against moisture penetration by leading the connection cable downward in front of the cable entry. Rain and condensation water can thus drain off. This applies mainly to mounting outdoors, in areas where moisture is expected (e.g. by cleaning processes) or on cooled or heated vessels.
Fig. 2: Measures against moisture penetration
Measuring range
The reference plane for the measuring range is the lower edge of the transducer.
Make sure that the min. distance, corresponding to the so called dead band, is maintained below the reference plane ­measurement is not possible in this areas. The exact value of the dead band is stated in chapter "Technical data" in the Supplement.
10 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 11
Mounting
2
1
Fig. 3: Min. distance to the max. level 1 Dead zone 2 Reference plane
Information:
If the product reaches the transducer, buildup can form on it over a period of time and later cause measurement errors.
132
100%
0%
Fig. 4: Measuring range (operating range) and max. measuring distance 1 full 2 empty (max. measuring distance) 3 Measuring range
Pressure/Vacuum
Gauge pressure in the vessel does not inuence OPTISOUND
3020 C. Low pressure or vacuum, however, damp the ultrasonic pulses. This inuences the measuring result, particularly if the level is very low. With pressures under -
0.2 bar (-20 kPa) you should use a dierent measuring principle, e.g. radar or guided microwave.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 11
Page 12
Mounting

4.2 Mounting information

Screwing in
Installation position
Screw OPTISOUND 3020 C into the mounting socket with an appropriate spanner applied to the hexagon of the process tting. Max. torque see chapter "Technical data".
Warning:
The housing must not be used to screw the instrument in! Applying tightening force to the housing can damage its
internal mechanical components.
When mounting OPTISOUND 3020 C, keep a distance of at least 200 mm (7.9 in) to the vessel wall. If the sensor is installed in the center of dished or rounded vessel tops, multiple echoes can arise. These can, however, be faded out by an appropriate adjustment (see chapter "Setup").
If this distance cannot be maintained, a false echo storage should be carried out during setup. This applies particularly if buildup on the vessel wall is expected. In this case, we recommend repeating the false echo storage later on with existing buildup.
2
1
> 200 mm
Fig. 5: Mounting on dished vessel tops 1 Reference plane 2 Vessel center or symmetry axis
In vessels with conical bottom it can be advantageous to mount the sensor in the center of the vessel, as measurement is then possible down to the lowest point of the vessel bottom.
12 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 13
Fig. 6: Vessel with conical bottom
Mounting
Socket
The mounting socket should preferably be dimensioned to allow the lower edge of the transducer to protrude at least 10 mm out of the socket.
ca. 10 mm
Fig. 7: Recommended socket mounting
If the reective properties of the medium are good, you can mount OPTISOUND 3020 C on sockets higher than the transducer length. You will nd recommended values for socket heights in the following illustration. The socket end should be smooth and burr-free, if possible also rounded. Carry out a false echo storage.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 13
Page 14
Mounting
Sensor orientation
d
100 mm/4"
h
> 10 mm
150 mm/6"
h
300 mm/12" 400 mm/16"
d
Fig. 8: Deviating socket dimensions
In liquids, direct the sensor as perpendicular as possible to the product surface to achieve optimum measurement results.
Fig. 9: Orientation in liquids
To reduce the min. distance to the medium, you can also mount OPTISOUND 3020 C with a beam deector. By doing this, it is possible to ll the vessel nearly to maximum. This arrangement is particularly suitable for open vessels such as e. g. overow basins.
~400x400
°
45
~200
Fig. 10: Beam deector
14 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 15
Mounting
Vessel installations
The ultrasonic sensor should be installed at a location where no installations cross the ultrasonic beam.
Vessel installations such as for example, ladders, limit switches, heating spirals, struts etc. can cause false echoes superimposed on the useful echo. Make sure when planning your measuring site that the ultrasonic signals have "free access" to the measured product.
If there are existing vessel installations, a false echo storage should be carried out during setup.
If large vessel installations such as struts or supports cause false echoes, these can be attenuated through supplementary measures. Small, inclined sheet metal or plastic baes above the installations scatter the ultrasonic signals and avoid direct false echoes.
Fig. 11: Cover smooth proles with deectors
Agitators
If there are agitators in the vessel, a false echo storage should be carried out with the agitators in motion. This ensures that the interfering reections from the agitators are saved with the blades in dierent positions.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 15
Page 16
Mounting
Fig. 12: Agitators
Inowing material
Foam
Do not mount the instruments in or above the lling stream. Make sure that you detect the product surface and not the
inowing product.
Fig. 13: Inowing liquid
Through the action of lling, stirring and other processes in the vessel, dense foams which considerably damp the emitted signals may form on the product surface.
If foams are causing measurement errors, the sensor should be used in a standpipe or, alternatively, the more suitable guided radar sensors (TDR) should be used.
30508-EN-050914
16 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
Page 17
Mounting
Guided radar is not inuenced by foam generation and is
particularly suitable for such applications.
Air ow
Standpipe measurement
If there are strong air currents in the vessel, e.g. due to strong winds in outdoor installations, or because of air turbulence, e. g. through cyclone exhausting, you should mount OPTI- SOUND 3020 C in a standpipe or use a dierent measuring principle, e.g. radar or guided radar (TDR).
By using a standpipe (surge or bypass tube), the inuence of vessel installations, foam generation and turbulence is excluded.
Standpipes must extend all the way down to the requested min. level, as measurement is only possible within the tube.
max.
1
min.
Fig. 14: Standpipe in a tank 1 Vent hole ø 5 10 mm
OPTISOUND 3020 C can be used from tube diameters of 50 mm.
Avoid large gaps and thick welding joints when connecting the tubes. Generally carry out a false echo storage.
Measurement in a standpipe is not recommended for very adhesive products.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 17
Page 18
Connecting to power supply

5 Connecting to power supply

5.1 Preparing the connection

Note safety instructions
Take note of safety
instructions for Ex applications
Select power supply
Selecting the connection ca-
ble
Always observe the following safety instructions:
l Connect only in the complete absence of line voltage l If overvoltages are expected, overvoltage arresters should
be installed.
In hazardous areas you should take note of the appropriate regulations, conformity and type approval certicates of the sensors and power supply units.
Power supply and current output are transmitted via separate two-wire connection cables. The power supply range can dier depending on the instrument version. The exact range is stated in the "Technical data" in the Supplement.
The standard version can be operated with an earth­connected current output, the Exd version must be operated with a oating output.
This instrument is designed in protection class I. To maintain this protection class, it is absolutely necessary that the ground conductor be connected to the internal ground terminal. Take note of the general installation regulations.
As a rule, connect OPTISOUND 3020 C to vessel ground (potential equalisation), or in case of plastic vessels, to the
next ground potential. There is a ground terminal on the side of the instrument housing.
For power supply, an approved installation cable with PE conductor is necessary.
The 4 ... 20 mA current output is connected with standard two­wire cable without screen. An outer cable diameter of 5 ... 9 mm ensures the seal eect of the cable entry. If electro­magnetic interference is expected, we recommend the use of screened cable.
Cable screening and ground­ing
Connect the cable screen on both ends to ground potential. In the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal outside on the housing must be connected to the potential equalisation (low impedance).
18 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 19
Connecting to power supply
If potential equalisation currents are expected, the connection
on the evaluation side must be made via a ceramic capacitor (e.g. 1 nF, 1500 V). The low frequency potential equalisation currents are thus suppressed, but the protective eect against high frequency interference signals remains.
Select connection cable for Ex applica- tions
Take note of the corresponding installation regulations for Ex applications. In particular, make sure that no potential equal­isation currents ow over the cable screen. In case of grounding on both sides this can be achieved by the use of a capacitor or a separate potential equalisation.

5.2 Connection procedure

Proceed as follows:
1 Unscrew the housing cover
2 Loosen compression nut of the cable entry
3 Remove approx. 10 cm (4 in) of the cable mantle (current
output), strip approx. 1 cm (0.4 in) insulation from the ends of the individual wires
4 Insert the cable into the sensor through the cable entry
5 Lift the opening levers of the terminals with a screwdriver
6 Insert the wire ends into the open terminals according to
the wiring plan
7 Press down the opening levers of the terminals, you will
hear the terminal spring closing
8 Check the hold of the wires in the terminals by lightly
pulling on them
9 Connect the screen to the internal ground terminal and the
external ground terminal to potential equalisation
10 Tighten the compression nut of the cable entry, the seal
ring must completely encircle the cable
11 Connect the lead cable for power supply in the same way
acc. to the wiring plan, in addition connect the ground conductor to the inner ground terminal.
12 Screw the housing cover back on
The electrical connection is nished.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 19
Page 20
Connecting to power supply
Housing overview
Fig. 15: Connection steps 5 and 6

5.3 Wiring plans, double chamber housing

1 2 3
4
Fig. 16: Double chamber housing 1 Housing cover, connection compartment 2 Blind stopper 3 Housing cover, electronics compartment 4 Filter element for pressure compensation 5 Cable gland
5
20 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 21
Electronics compartment
Connecting to power supply
Connection compartment
Display
I2C
12 5678
Fig. 17: Electronics compartment, double chamber housing 1 Internal connection cable to the connection compartment
Display
1
12
I2C
1
2
Fig. 18: Connection compartment, double chamber housing 1 Spring-loaded terminals for power supply 2 Ground terminal for connection of the cable screen
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 21
Page 22
3
Connecting to power supply
Wiring plan
Switch on phase
L1 N
12
/ L
1 2
/ N PE
Fig. 19: Wiring plan, double chamber housing 1 Supply voltage 2 Signal output
4...20mA IS GND
4 ... 20 mA

5.4 Switch on phase

After OPTISOUND 3020 C is connected to power supply, the instrument carries out a self-test for approx. 30 seconds. The following steps are carried out:
l Internal check of the electronics l Indication of the instrument type, the rmware version as
well as the sensor TAGs (sensor name)
l Output signal jumps briey (approx. 10 seconds) to the set
fault current
Then the actual measured value is displayed and the corresponding current is transmitted to the cable.
1)
1)
The values correspond to the actual level as well as to the settings already carried out, e.g. default setting.
22 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 23

Setup with the indicating/adjustment module

6 Setup with the indicating/adjustment
module

6.1 Short description

The indicating/adjustment module is used for measured value display, adjustment and diagnosis. It can be mounted in all sensors of the OPTISOUND instrument family, in the single as well as double chamber housing (optionally in the electronics or connection compartment).
6.2 Installation of the indicating/adjustment
module
The indicating/adjustment module can be inserted or removed at any time. It is not necessary to interrupt the power supply.
To mount, proceed as follows:
1 Unscrew the housing cover
2 Place the indicating/adjustment module in the desired
position on the electronics (you can choose any one of four dierent positions - each displaced by 90°)
3 Press the indicating and adjustment module onto the
electronics and turn it to the right until it snaps in.
4 Screw housing cover with inspection window tightly back
on
Removal is carried out in reverse order.
The indicating/adjustment module is powered by the sensor,
an additional connection is not necessary.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 23
Page 24
Setup with the indicating/adjustment module
Fig. 20: Installation of the indicating/adjustment module
Note:
If you intend to retrot OPTISOUND 3020 C with an indicating/ adjustment module for continuous measured value indication, a higher cover with an inspection glass is required.
24 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 25
Setup with the indicating/adjustment module

6.3 Adjustment system

Key functions
Adjustment system
1
1.1
2
3
Fig. 21: Indicating and adjustment elements 1 LC display 2 Indication of the menu item number 3 Adjustment keys
l [OK] key:
- move to the menu overview
- conrm selected menu
- edit parameter
- save value
l [–>] key to select:
- menu change
- list entry
- editing position
l [+] key:
- modify value of a parameter
l [ESC] key:
- interrupt input
- jump to the next higher menu
The sensor is adjusted via the four keys of the indicating and adjustment module. The LC display indicates the individual menu items. The functions of the individual keys are shown in the above illustration. Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not conrmed with [OK] will not be saved.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 25
Page 26
Setup with the indicating/adjustment module

6.4 Setup procedure

Address setting HART-Multi-
drop
Parameter adjustment
In HART-Multidrop mode (several sensors on one input) the address must be set before continuing with the parameter adjustment. You will nd a detailed description in the operating instructions manual of the indicating/adjustment module.
HART mode
Standard
Address 0
Because OPTISOUND 3020 C is a distance measuring instrument, its primary task is to measure the distance from the sensor to the product surface. In order to indicate the actual lling level, the measured distance must be allocated to a specic height percentage. To make this adjustment, the full and empty distances in the vessel are entered. If these values are not known, it is also possible to carry out the adjustment with other distances, e.g. 10 % and 90 %. The origin of these distance values is always the lower edge of the ange (with ange versions) or the lower edge of the transducer (all other versions).
The actual level is then calculated on the basis of these entered values. At the same time, the operating range of the sensor is limited from maximum range to the requested range.
The real product level during this adjustment is not important, because the min./max. adjustment is always carried out without changing the product level. These settings can be made ahead of time without the instrument having to be installed.
In the main menu item "Basic adjustment", the individual submenu items should be selected one after the other and provided with the correct parameter values.
Start your parameter adjustment with the following menu items of the basic adjustment:
Carrying out min. adjustment
Proceed as follows:
1
Move from the measured value display to the main menu by pushing [OK].
26 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 27
Setup with the indicating/adjustment module
Basic adjustment Display Diagnostics Service Info
2 Select the menu item "Basic adjustment" with [–>] and
conrm with [OK]. Now the menu item "Min. adjustment" is displayed.
Min. adjustment
0.00 %
=
5.000 m(d)
4.000 m(d)
3 Prepare the % value for editing with [OK] and set the
cursor to the requested position with [–>]. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value.
4 Enter the appropriate distance value in m (corresponding
to the percentage value) for the empty vessel (e.g. distance from the sensor to the vessel bottom).
5 Save the settings with [OK] and move to "Max. adjustment"
with [–>].
Carrying out max. adjustment
Proceed as follows:
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
1 Prepare the % value for editing with [OK] and set the
cursor to the requested position with [–>]. Set the requested percentage value with [+] and save with [OK]. The cursor jumps now to the distance value.
2 Enter the appropriate distance value in m (corresponding
to the percentage value) for the full vessel. Keep in mind that the max. level must lie below the dead band.
3 Save the settings with [OK] and move to "Medium
selection" with [–>].
Medium selection
Each product has dierent reective properties. In addition, there are various interfering factors which have to be taken into account: agitated product surfaces and foam generation (with liquids); dust generation, material cones and echoes from the
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 27
Page 28
Setup with the indicating/adjustment module
vessel wall (with solids). To adapt the sensor to these dierent conditions, you should rst select in this menu item "Liquid" or
"Solid".
Medium
Liquid
With solids, you can also choose between "Powder/Dust", "Granular/Pellets" or "Ballast/Pebbels".
Through this additional selection, the sensor is adapted perfectly to the product and measurement reliability, partic­ularly in products with bad reective properties, is considerably increased.
Enter the requested parameter via the appropriate keys, save your settings and jump to the next menu item with the [–>] key.
Vessel shape
Damping
Apart from the medium also the vessel form can inuence the measurement. To adapt the sensor to these conditions, this menu item oers (depending on either liquid or solid is detected) dierent options. For Liquid these are Storage tank,
Stilling tube, Open vessel or Stirred vessel, for Solid Silo or Bunker.
Vessel shape
Storage tank
Enter the requested parameter via the appropriate keys, save your settings and jump to the next menu item with the [–>] key.
To suppress uctuation in the measured value display, e.g. caused by a turbulent product surface, an integration time can be set. This time can be between 0 and 999 seconds. Please note that the reaction time of the entire measurement will be longer and the sensor will react to quick changes of the measured value with a corresponding delay. In general, a time of a few seconds is sucient to smooth the measured value display.
Damping
0 s
30508-EN-050914
28 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
Page 29
Setup with the indicating/adjustment module
Enter the requested parameter via the appropriate keys, save
your settings and jump to the next menu item with the [–>] key.
Linearization curve
Sensor-TAG
A linearization is necessary for all vessels in which the vessel volume does not increase linearly with the level – e.g. in a cylindrical or spherical tank -–and the indication or output of the volume is requested. Corresponding linearization curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. By activating the appropriate curve, the volume percentage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set in the menu item "Display".
Linearization curve
Linear
Enter the requested parameter via the appropriate keys, save your settings and jump to the next menu item with the [–>] key.
In this menu item you can enter an unambiguous designation for the sensor, e.g. the measurement loop name or the tank or product designation. In digital systems and in the documen­tation of larger plants, a singular designation should be entered for exact identication of individual measuring sites.
Sensor-TAG
Sensor
With this menu item, the Basic adjustment is nished and you can now jump to the main menu with the [ESC] key.
False signal suppression
High sockets or vessel installations, such as e.g. struts or agitators as well as buildup and weld joints on the vessel walls cause interfering reections which can impair the measure­ment. A false signal suppression detects, marks and saves these false signals, so that they are no longer taken into account for the level measurement. This false signal sup­pression should be created with empty vessel so that all potential interfering reections will be detected.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 29
Page 30
Setup with the indicating/adjustment module
False signal suppression
Change now?
Proceed as follows:
1 Move from the measured value display to the main menu
by pushing [OK].
2 Select the menu item "Service" with [–>] and conrm with
[OK]. Now the menu item "False signal suppression" is
displayed.
3 Conrm "False signal suppression - Change now" with
[OK] and select in the below menu "Create new". Enter the actual distance from the sensor to the product surface. All false signals in this area are detected by the sensor and saved after conrming with [OK].
Note:
Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as false signal. The lling level would then no longer be detectable in this area.
Optional settings
Additional adjustment and diagnosis options such as e.g. scaling, simulation or trend curve presentation are shown in the following menu schematic. You will nd a detailed description of these menu items in the operating instructions manual of the indicating and adjustment module.
30 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 31
Basic adjustment
Basic adjustment Display Diagnostics Service Info
Setup with the indicating/adjustment module

6.5 Menu schematic

1
Min. adjustment
0.00 %
=
4.000 m(d)
3.000 m(d)
Damping
0 s
Display
Basic adjustment
Display Diagnostics Service Info
Displayed value
scaled
Diagnostics
Basic adjustment Display
Diagnostics Service Info
1.1
1.5
2.1
2
3
Max. adjustment
100.00 %
=
1.000 m(d)
2.000 m(d)
Linearization curve
Linear
Display units
Volume m³
1.2
1.6
2.2
Medium
Liquid
Sensor-TAG
Scaling
0 %=0.0 m³
100 %=100.0 m³
Sensor
1.3
1.7
2.3
Vessel shape
Storage tank
1.4
Peak values Distance-min.: 0.234 m(d) Distance-max: 5.385 m(d) T-min.: 16.5°C T-min.: 37.5°C
3.1
Meas. reliability
36dB
Sensor status
OK
3.2
Choose curve
Echo curve
3.3
Echo curve
Presentation of the echo
curve
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 31
3.4
Page 32
Setup with the indicating/adjustment module
Service
Basic adjustment Display Diagnostics
Service Info
4
False signal suppression
Change now?
Reset
Reset?
Copy sensor data
Copy sensor data?
Info
Basic adjustment Display Diagnostics Service
Info
Sensor type
OPTISOUND 30x0 C
Serial number
12345678
4.1
4.5
4.9
5.1
5
Addl. adjustments
none
Units of measurement
m(d)
select?
PIN
Enable?
Date of manufacture
26. July 2005 Software version
3.26
4.2
4.6
4.10
5.2
Current output
Output mode 4-20 mA Failure mode: <3.6mA Min-current 3.8mA
Language
Deutsch
Date of last change using PC
26. July 2005
4.3
4.7
5.3
Simulation
Start simulation?
HART mode
Standard
Address 0
Sensor details
Display now?
4.4
4.8
5.4
32 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 33
Maintenance and fault rectication
7 Maintenance and fault rectication

7.1 Maintenance

When used as directed in normal operation, OPTISOUND 3020 C is completely maintenance-free.
7.2 Fault rectication
Causes of malfunction
Fault rectication
Checking the 4 20 mA sig-
nal
OPTISOUND 3020 C oers maximum reliability. Nevertheless faults can occur during operation. These may be caused by the following, e.g.:
l Sensor l Process l Power supply l Signal processing.
The rst measures to be taken are to check the output signal and evaluate fault messages via the indicating/adjustment module. The procedure is described below.
Connect a hand-held multimeter with a suitable measuring range acc. to the wiring plan.
? 4 20 mA signal not stable
l level uctuations
à set integration time via the indicating/adjustment
module
? 4 20 mA signal missing
l wrong connection
à Check connection acc. to chapter "Connection proce-
dure" and correct, if necessary, acc. to chapter "Wiring plans"
l no power supply
à check cables for line break, repair, if necessary
l load resistance too high
à check and adapt, if necessary
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 33
Page 34
Maintenance and fault rectication
? Current signal greater than 22 mA or less than 3.6 mA
l Electronics module defective
à Exchange instrument or return it for repair
In Ex applications, the regulations for the wiring of intrinsically safe circuits must be observed.
Fault messages via the indi­cating/adjustment module
? E013
l no measured value available
à sensor in boot phase
à sensor does not nd an echo, e.g. because of faulty
installation or incorrect parameter adjustment
? E017
l adjustment span too small
à Carry out a fresh adjustment and increase the distance
between min. and max. adjustment
? E036
l no operable sensor software
à carry out a software update or return instrument for
repair
? E041
l hardware error, electronics defective
à Exchange instrument or return it for repair

7.3 Exchanging the electronics

If the electronics module is defective, it can be replaced by the user.
In Ex applications, only instruments and electronics modules with appropriate Ex approval may be used.
34 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 35
Maintenance and fault rectication
If there is no electronics module available on site, it can be ordered from the responsible Krohne agency.

7.4 Instrument repair

If a repair is necessary, please proceed as follows:
You can download a return form from our Internet homepage http://www.krohne-mar.com/leadmin/media-lounge/PDF- Download/Specimen_e.pdf.
By doing this you help us carry out the repair quickly and
without having to call back for needed information.
l Print and ll out one form per instrument l Clean the instrument and pack it damage-proof l Attach the completed form and possibly also a safety data
sheet to the instrument.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 35
Page 36
Dismounting

8 Dismounting

8.1 Dismounting procedure

Warning:
Before dismounting, be aware of dangerous process con­ditions such as e.g. pressure in the vessel, high temperatures, corrosive or toxic products etc.
Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order.

8.2 Disposal

OPTISOUND 3020 C consists of materials which can be recycled by specialised recycling companies. We have purposely designed the electronic modules to be easily separable. Mark the instrument as scrap and dispose of it according to national government regulations (e.g. in G ermany acc. to the EU Directive on Waste Electrical and Electronic
Equipment, WEEE).
Materials: see "Technical data"
If you cannot dispose of the instrument properly, please
contact us about disposal methods or return.
36 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 37
Supplement

9 Supplement

9.1 Technical data

General data
Materials, wetted parts
- Process tting thread G 2A and 2 NPT: PVDF
- Transducer PVDF
- seal transducer/thread EPDM
Materials, non-wetted parts
- Housing plastic PBT (Polyester), Alu-die casting pow-
der-coated, 316L (1.4435)
- Seal ring between housing and
housing cover
- Inspection window in housing cover Polycarbonate
- Ground terminal 316Ti/316L (1.4571/1.4435)
NBR (stainless steel housing), silicone (Alu/ plastic housing)
Weight 1.8
4.0 kg (4.0 8.8 lbs), depending on
process tting and housing
Max. torque mounting boss 25 Nm
Output variable
Output signal 4 … 20 mA/HART Resolution 1.6 µA Fault signal current output unchanged; 20.5 mA; 22 mA;
<3.6 mA (adjustable) Current limitation 22 mA Load max. 500 Ohm Integration time (63 % of the input
0 999 s, adjustable
2)
variable) Fullled NAMUR recommendation NE 43
Input variable
Parameter distance between lower edge of the transducer
and product surface
Dead zone 0.4 m (1.3 ft) Measuring range
- Liquids up to 8 m (26.2 ft)
- Solids up to 3.5 m (11.5 ft)
2)
With inductive load, ohmic share at least 25 Ohm/mH.
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 37
Page 38
Supplement
Accuracy (similar to DIN EN 60770-1)
Reference conditions acc. to DIN EN 61298-1
- Temperature 18 … +30°C (64 +86°F)
- Relative humidity 45 75 %
- Atmospheric pressure 860 1060 mbar (86 106 kPa/
12.5 … 15.4 psi)
Characteristic curve deviation and measurement characteristics
Average temperature coecient of the
0.06 %/10 K
3)
zero signal (temperature error)
Resolution, general max. 1 mm Ultrasonic frequency 55 kHz Interval > 2 s (dependent on the parameter adjustment) Beam angle at -3 dB 5.5° Adjustment time
4)
>3 s (dependent on the parameter adjustment)
Accuracy better than 0.2 % or ±4 mm (see diagram)
16 mm
10 mm
4 mm
-4 mm
-10 mm
-16 mm
Fig. 22: Accuracy OPTISOUND 3020 C
8 m4 m3 m2 m 7 m6 m5 m1 m
3)
Relating to the nominal range, incl. hysteresis and repeatability, determined acc. to the limit point method.
4)
Time to output the correct level (with max. 10 % deviation) after a sudden level change.
38 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 39
Supplement
Ambient conditions
Ambient, storage and transport temperature
- without indicating/adjustment mod-
-40 +80°C (-40 +176°F)
ule
- the indicating/adjustment module -20 +70°C (-4 +158°F)
Process conditions
Vessel pressure -20 200 kPa (-0.2 2.0 bar/-2.9 29 psi) Process temperature (transducer tem-
-40 +80°C (-40 +176°F)
perature) Vibration resistance mechanicalvibrations with 4 g and 5
100 Hz
Electromechanical data
Cable entry
- Double chamber housing
l 1x cable entry M20x1.5 (cable-ø 5 9 mm),
1x blind stopper M20x1.5
or:
l 1x closing cap ½ NPT, 1x blind stopper
½ NPT
Spring-loaded terminals for wire cross sections up to 2.5 mm²
Indicating and adjustment module
Power supply and data transmission through sensor via gold-plated sliding contacts
(I²C bus)
Indication LC display in full dot matrix Adjustment elements 4 keys Protection
- unassembled IP 20
- mounted into the sensor without
IP 40
cover
5)
Materials
- Housing ABS
- Inspection window Polyester foil
Supply voltage
Supply voltage
- non-Ex and Exd instrument 20 … 72 VDC, 20 253 VAC, 50/60 Hz Power consumption max. 4 VA; 2.1 W
5)
Tested acc. to the regulations of German Lloyd, GL directive 2
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 39
Page 40
Supplement
Electrical protective measures
Protection IP 66/IP 67 Overvoltage category III Protection class I
Approvals
6)7)
ATEX ATEX II 1G, 1/2G, 2GEExiaIIC T6
6)
Deviating data with Ex applications: see separate safety instructions.
7)
Depending on order specication.
40 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 41

9.2 Dimensions

OPTISOUND 3020 C
") /
25
")
32
/
1
20mm (
153mm (6
32
") /
31
63mm
(2
Supplement
60mm
(2 23/64")
G2A / 2"NPT
64
1 2
ø 50mm
31
(1
/32")
ø 74mm
58
(2
/64")
Fig. 23: OPTISOUND 3020 C 1 Dead zone: 0.4 m (1.3 ft) 2 Meas. range: in liquids up to 8 m (26.2 ft), in solids up to 3,5 m (11.5 ft)
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 41
Page 42
Supplement
9.3 Certicate
CE declaration of conformity
Fig. 24: CE declaration of conformity
42 OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire
30508-EN-050914
Page 43
Supplement
30508-EN-050914
OPTISOUND 3020 C - 4 ... 20 mA/HART - four-wire 43
Page 44
Subject to change without notice
30508-EN-050914