General 800 Owner's Manual

R
RESIDENTIAL AIR TREATMENT PRODUCTS
GENERALAire
INST ALLER: PLEASE FILL OUT AND MAIL GUARANTEE CARD AFTER INSTALLATION IS COMPLETE. LEAVE INSTALLATION
PRECAUTION: The installer should be an experienced service technician. Disconnect electrical power before beginning installation. Do not install where temperatures fall below 32 degrees F or where plenum temperatures exceed 200 degrees F.
INSTALLATION: The humidifier may only be mounted on the warm air plenum or furnace bonet. Humidifier extends into duct 7 1/2 inches. See Typical Installations.
INSTRUCTIONS WITH HOME OWNE R
WARM AIR
HIGH BOY
RETURN AIR
GENERALAire
HIGH EFFICIENCY AIR CLEANER
R
AC SERIES
MODEL 800
AUTOMATIC HUMIDIFIER
FOR INSTALLATION ON A
VERTICAL SURFACE OF ANY
RETURN AIR
WARM AIR
LOW BOY
1
Top Of Template
TEMPLATE FOR INSTALLING
GENERAL "800" HUMIDIFIER
FOLLOW INSTRUCTIONS PACKED WITH HUMIDIFIER
1. REMOVE PROTECTIVE PAPER FROM BACK OF TEMPLATE AND STICK IN LEVEL POSITION.
2. CENTER PUNCH AND DRILL THE FOUR SIDE MOUNTING HOLES WITH A 1/8 " DIA. DRILL.
3. HANG HUMIDIFIER FROM FOUR SIDE SCREWS AND INSTALL DRAIN PAN, EVAPORATOR PAD AND DISTRIBUTOR TROUGH.
4. TIGHTEN SCREWS AND ADJUST HUMIDIFIER UNTIL LEVEL.
5. REMARK FOUR REMAINING HOLES IF NECESSARY.
6. REMOVE HUMIDIFIER, DRILL REMAINING HOLES AND CUT OUT CENTER SECTION OF TEMPLATE.
CUT ON THIS LINE
TEMPLATE NO. 1042-25
2
Select location on vertical surface of warm air plenum for mounting humidifier. Stick mounting template in place making sure the template is level. Do not install humidifier where the blanked off ends of a cooling coil will restrict air flow to the humidifier.
3 4
Center punch the four side mounting holes on the template and drill with an 1/8" drill bit. Cut out center section of template. Remove the template and insert the four sheet metal screws until the heads project about 1/8".
COPPER TUBING
Install evaporator plates in pan. Insert the humidifier in the plenum such that the four screws project through the keyhole slots. Slide the humidifier down level and tighten four screws.
PLASTIC TUBING
Mount the self tapping saddle valve on either a cold or a hot water pipe. A side or top mount is best to avoid clogging from pipe sediment. Connect 1/4” O.D. tubing to the saddle valve. Copper tubing requires a brass compression nut and brass sleeve. Plastic tubing requires a brass insert inside the tubing, a plastic sleeve on the outside with a brass compression nut.
NOTE: DO NOT USE PLASTIC TUBING ON HOT WATER OR IN CONTACT WITH ANY HOT PLENUM SURFACE OR DUCT. INSTALLATION OF THIS SADDLE VALVE MUST MEET OR EXCEED LOCAL CODES AND ORDINANCES.
SADDLE VALVE INSTALLATION INSTRUCTIONS
Copper Pipe
1. Retract piercing pin into valve body by turning handle counterclockwise.
2. Screw valve body into upper bracket and tighten.
3. Place rubber gasket over piercing pin.
4. Assemble saddle valve over copper pipe using enclosed screws, nuts and lower bracket.
5. Tighten screws evenly and firmly. Brackets should be parallel.
6. Complete compression connection to saddle valve outlet.
7. Turn handle clockwise to pierce tubing and close saddle valve.
8. Turn handle counterclockwise to several seconds to flush dirt from pipe and tubing.
Steel, Brass or Hard Plastic Pipe
1. Shut off water supply and drain pipe.
2. Turn handle clockwise to expose piercing pin and close saddle valve.
3. Place rubber gasket over piercing pin.
4. Drill 1/8" hole in pipe using a hand crank drill to avoid shock hazard.
5. Assemble saddle valve over steel, brass or hard plastic pipe using enclosed screws, nuts and lower bracket.
6. Tighten screws evenly and firmly. Brackets should be parallel.
7. Complete compression connection to saddle valve outlet.
8. Turn handle counterclockwise to several seconds to flush dirt from pipe and tubing.
Threaded Pipe Fittings
1. Turn handle clockwise to expose piercing pin and close saddle valve.
2. Seal valve body threads using pipe tape or sealant.
3. Install valve into 1/8" NPT fitting.
4. Complete compression connection to saddle valve outlet.
5. Turn handle counterclockwise to several seconds to flush dirt from pipe and tubing.
open saddle valve, leave open for
open saddle valve, leave open for
open saddle valve, leave open for
5
Connect 1/4" water supply tube to humidifier. Copper tubing requires a brass compression nut and brass sleeve. Plastic tubing requires a brass insert inside the tubing, a plastic sleeve on the outside with a brass compression nut.
DO NOT USE PLASTIC TUBING IN CONTACT WITH ANY HOT PLENUM SURFACE OR DUCT. IF USING PLASTIC TUBING, USE TUBE SUPPORT PROVIDED.
PARTS LIST FOR HUMIDIFIER
FACE PLATE
800-M
VALVE BODY REPAIR KIT
896
SCREEN DISC
800-N
VALVE DIAPHRAGM
800-DM
INSPECTION PLATE
800-E
ADJUSTING SCREW
800-L
6
880
EVAPORATOR
PLATES
(Set of 5)
DRIP TUBE 800-K
EVAPORATOR PAN
800-IJ ACTUATOR PLATE & PAN DIAPHRAGM ASSEMBLY
800-GMF
Turn on water supply and check operation of humidifier. Check flow of water by removing inspection plate and observe drip tube. Humidifier will gradually fill 3/4 inch to 1 inch deep and shut off. To accelerate filling, move valve actuator plate toward pan through inspection opening. NOTE: THIS HUMIDIFIER HAS BEEN FACTORY ADJUSTED TO OPERATE ON WATER PRESSURES FROM 20 TO 150 P.S.I. NO ADJUSTMENT SHOULD BE NECESSARY.
NOTE: 800-IJ phenolic evaporator pan with cast in plate rack and pan baffle is interchangeable with 800-I pan.
FORM NO. 800-II Rev. C (FILE 10238) Litho in U.S.A.
Loading...
+ 2 hidden pages