DELTA DVP04AD-SL User Manual

5 (1)

2010-06-29

5011696001-A4L1

DVP-1050130-02

………………………………………………………………… ENGLISH …………………………………………………………………

Thank you for choosing Delta’s DVP series PLC. The analog input module of DVP04AD-SL series can read/write the data of analog input module by using instructions FROM/TO via DVP SV/EH2-L MPU program. The analog input module receives 16bit digital data of 4 groups from PLC MPU and converts it into 4 points analog input signal either in voltage or in current. Users can select input from voltage or current via wiring. Voltage input range is -10V~10VDC (resolution is 312.5μV). Current input range is -20mA ~ 20mA (resolution is 625nA).

This instruction sheet provides only information on the electrical specification, general functions, installation and wiring. For detailed program design and applicable instructions, please refer to “DVP-ES2 Operation Manual: Modules”. For details of the optional peripheral, please refer to the instruction sheet enclosed in the package. This is an OPEN TYPE I/O module and therefore should be installed in an enclosure free of airborne dust, humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the device (e.g. key or specific tools are required for operating the enclosure) in case danger and damage on the device may occur.

DO NOT connect the input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check all the wiring again before switching on the power. Make sure the ground terminal is correctly grounded in order to prevent electromagnetic interference.

Tightening torque for I/O terminal block is 1.95 kg-cm (1.7 in-lbs) and please uses 60/75°C copper conductors only.

Product Profile & Dimension

1

2

4

 

6

 

 

 

 

 

 

 

[3.543]

 

 

7

 

 

 

 

8

 

 

90

 

 

 

[2.496]63.4

 

DVP-04AD

 

 

9

 

3

 

 

 

 

 

 

 

 

5

 

 

3 [0.118]

5

60 [2.362]

 

33.1 [1.303]

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit: mm [inch]

 

 

 

 

 

 

 

 

[ Figure 1 ]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

I/O module connection port

6.

 

Mounting hole of the I/O module

 

2.

Status indicator

 

 

 

 

 

 

 

 

 

7.

 

I/O module connection port

 

 

 

(POWER, RUN and ERROR)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

Model name

 

 

 

 

 

 

 

 

 

8.

 

Mounting slot (35mm)

 

4.

I/O terminals

 

 

 

 

 

 

 

 

 

9.

 

I/O module clip

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

Mounting slot clip

 

 

 

 

 

 

 

 

 

10.

 

DC power input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I/O Terminal Layout

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V1+

 

I1+

 

V1-

 

FG

 

V2+

 

I2+

 

V2-

 

FG

 

 

 

V3+

 

I3+

 

V3-

 

FG

 

V4+

 

I4+

 

V4-

 

FG

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CH1

 

 

 

 

 

Ch2

 

 

 

 

 

 

 

 

 

Ch3

 

 

 

 

 

Ch4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DVP04AD-SL (4AI)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- 1 -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DELTA DVP04AD-SL User Manual

External Wiring

yActive-type

Voltage input

CH1

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V1+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UIN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*5

 

 

I1+

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Shielded cable*1

 

 

 

 

 

 

 

VI1-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FE

 

 

Current input

CH4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V4+

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

*2

 

UIN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I4+

 

 

 

 

 

 

 

 

VI4-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FE

 

 

 

 

 

 

 

Shielded cable*1

*3

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal of

 

 

 

 

 

 

 

 

 

 

 

 

 

power module

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*4

 

 

 

 

 

 

 

0V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System

 

 

 

 

24V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

grounding

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Grounding (100 or less)

y Passive-type

 

AG

1M

 

250

CH1

1M

 

 

AG

1M

 

250

CH4

1M

 

DC/DC

+15V

AG

Converter

 

-15V

[ Figure 2 ]

Voltage input

 

 

 

 

 

AG

 

 

 

 

 

 

+

 

CH1

V1+

 

1M

 

UIN

 

 

250

 

CH1

 

*5

I1+

1M

-

 

 

 

 

 

VI1-

 

 

 

 

 

 

 

 

 

 

Shielded cable*1

FE

 

 

 

 

 

 

 

AG

 

 

 

 

 

 

Current input

 

CH4

V4+

 

1M

 

 

*2

250

 

CH4

 

 

 

-

 

I4+

1M

 

 

 

 

+

 

 

VI4-

 

 

 

Shielded cable*1

FE

 

 

 

 

 

 

 

 

 

 

*3

 

 

 

 

Terminal of

 

 

 

 

 

 

power module

*4

 

0V

 

DC/DC

+15V

 

 

 

AG

 

System

24V

 

Converter

 

grounding

 

-15V

Grounding (100

or less)

 

 

 

[ Figure 3 ]

 

 

 

 

 

 

Note 1: When performing analog input, please isolate other power wirings.

Note 2: When the A/D module is connected to current signals, make sure you short-circuit “V+” and “I+” terminals.

Note 3: If the noise is too significant, please connect FE to the grounding terminal.

Note 4: Please connect the terminal on both the power module and A/D module to the system earth point and ground the system contact or connect it to the cover of power distribution cabinet.

Note 5: If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the wiring to 0.1 ~ 0.47μF 25V capacitor.

Electrical Specifications

Analog / Digital module

Voltage input

 

 

Current input

 

Power supply voltage

24VDC (-15% ~ +20%) / 3.5W

 

 

 

DVPPS01(PS02): input 100-240VAC, output 24VDC/1A(PS02: 2A)

 

Analog input channel

4 channels / each module

 

 

 

Range of analog input

±10V

±5V

 

±20mA

0 ~ 20mA

4 ~ 20mA

Range of digital

±32,000

±32,000

 

±32,000

0 ~ 32,000

0 ~ 32,000

conversion

 

 

 

 

 

 

 

- 2 -

Analog / Digital module

Voltage input

 

 

 

 

Current input

 

Hardware Resolution

16 bits

 

16 bits

 

16 bits

 

15 bits

 

 

15 bits

Input impedance

 

< 0.5Ω

 

 

 

 

 

 

 

 

 

 

Overall accuracy

 

±0.3% when in full scale (25°C, 77°F)

 

 

 

 

 

 

 

±0.5% when in full scale within the range of 0 ~ 55°C (32 ~ 131°F)

 

 

 

 

 

Response time

 

250μs / each channel

 

 

 

 

 

 

 

 

 

Max. output current

1KΩ ~ 2MΩ

 

 

 

 

 

 

 

Tolerance carried

 

 

 

 

 

 

0Ω~500Ω

 

impedance

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Digital data format

2’s complement of 16 bits, 15 significant bits

 

 

 

 

 

 

 

 

 

Optical coupler isolation between digital circuits and analog circuits.

 

 

 

 

 

No isolation among analog channels.

 

 

 

 

 

 

Isolation method

 

500VDC between digital circuits and Ground

 

 

 

 

 

500VDC between analog circuits and Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500VDC between analog circuits and digital circuits

 

 

 

 

 

 

500VDC between 24VDC and Ground

 

 

 

 

 

 

Series connection to

Connectable to the left side of MPU, numbered from 100 to 107

according to the position of module from the closest to farthest to

DVP-PLC MPU

 

 

MPU.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation/storage

Operation: 0°C~55°C (temp.), 50~95% (humidity), Pollution degree2

temperature

 

Storage: -25°C~70°C (temp.), 5~95% (humidity)

 

Vibration/shock

 

International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/

immunity

 

 

 

IEC61131-2 & IEC 68-2-27 (TEST Ea)

 

 

 

 

 

 

Control Register

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CR#

Attrib.

 

 

Register name

 

 

 

 

Explanation

 

#0

O

R

 

Model name

 

Set up by the system:

 

 

 

 

 

 

DVP04AD-SL model code = H’4400

 

 

 

 

 

 

 

 

#1

O

R

 

Firmware version

 

Display the current firmware version in hex.

#2

X

R/W

 

CH1 input mode setting

 

Input mode: Default = H’0000.

 

 

 

Take CH1 for example:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mode 0 (H’0000): Voltage input (±10V)

 

 

 

 

 

 

 

 

#3

X

R/W

 

CH2 input mode setting

 

Mode 1 (H’0001): Current input (±20mA)

 

 

Mode 2 (H’0002): Current input (0~+20mA)

 

 

 

 

 

 

 

 

#4

X

R/W

 

CH3 input mode setting

 

Mode 3 (H’0003): Current input (+4~+20mA)

 

 

Mode 4 (H’0004): Voltage input (±5V)

 

 

 

 

 

 

 

 

Mode 5 (H’0005): Voltage input (0V~+5V)

 

 

 

 

 

 

 

 

#5

X

R/W

 

CH4 input mode setting

 

Mode 6 (H’0006): Voltage input (1V~+5V)

 

 

Mode -1 (H’FFFF): Channel 1 unavailable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b15 ~ b12

b11 ~ b8

b7 ~ b4

 

b3 ~ b0

 

 

 

 

 

 

 

 

CH4

 

CH3

CH2

 

CH1

#6

X

R/W

 

History mode

 

Only average values are recorded.

 

 

 

Default = H’0000. Take CH1 for example:

 

 

 

 

 

 

 

 

K0: Disable (Default). K1: Single. K2: Auto.

 

 

 

 

 

 

 

 

K3: Rising Edge Triggered

 

 

 

 

 

 

 

 

 

K4: Falling Edge Triggered

 

#7

X

R/W

 

History command

 

Refer to table of history command for detail.

 

 

Default = H’0000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- 3 -

CR#

Attrib.

Register name

Explanation

#8

X

R/W

CH1 sampling range

Set sampling range in CH1 ~ CH4:

#9

X

R/W

CH2 sampling range

Range = K1 ~ K20

#10

X

R/W

CH3 sampling range

Default = K10

#11

X

R/W

CH4 sampling range

 

#12

X

R

CH1 average input value

 

#13

X

R

CH2 average input value

Average value of input signals at CH1 ~ CH4

#14

X

R

CH3 average input value

 

#15

X

R

CH4 average input value

 

#16

X

R

CH1 present input value

 

#17

X

R

CH2 present input value

Present value of input signals at CH1 ~ CH4

#18

X

R

CH3 present input value

 

#19

X

R

CH4 present input value

 

#20

X

R/W

Set value of CH1 upper bound

 

#21

X

R/W

Set value of CH2 upper bound

Set value of CH1~CH4 upper bound.

#22

X

R/W

Set value of CH3 upper bound

Default = K32767.

#23

X

R/W

Set value of CH4 upper bound

 

#24

X

R/W

Set value of CH1 lower bound

 

#25

X

R/W

Set value of CH2 lower bound

Set value of CH1~CH4 lower bound.

#26

X

R/W

Set value of CH3 lower bound

Default = K-32768.

#27

X

R/W

Set value of CH4 lower bound

 

#28

X

R/W

Adjusted Offset value of CH1

Set the adjusted Offset value of CH1 ~ CH4.

 

 

 

 

Default = K0

#29

X

R/W

Adjusted Offset value of CH2

Definition of Offset in DVP04AD-SL:

#30

X

R/W

Adjusted Offset value of CH3

The corresponding voltage (current) input

#31

X

R/W

Adjusted Offset value of CH4

value when the digital input value = 0.

#34

X

R/W

Adjusted Gain value of CH1

Set the adjusted Gain value in CH1 ~ CH4.

#35

X

R/W

Adjusted Gain value of CH2

Default = K16,000

Definition of Gain in DVP04AD-SL:

 

 

 

 

#36

X

R/W

Adjusted Gain value of CH3

The corresponding voltage (current) input

#37

X

R/W

Adjusted Gain value of CH4

value when the digital input value = 16,000.

#38

X

R/W

CH1 Edge value

 

#39

X

R/W

CH2 Edge value

Default = K0

#40

X

R/W

CH3 Edge value

 

#41

X

R/W

CH4 Edge value

 

 

 

 

 

b0 ~ b3: reset CH1 ~ CH4

 

 

 

Function: Return to default

b4 ~ b15: reserved

#42

X

R/W

Default = H’0000. Give CH1 setting for

setting

 

 

 

 

example: When b0 is set to 1, all settings are

 

 

 

 

reset to default setting.

 

 

 

 

Register for storing all error status. Refer to

#43

X

R

Error status

table of error status for more information.

 

 

 

 

Default = H’0000.

#44

X

R

History status

Refer to table of history status for detail.

Default = K1

 

 

 

 

- 4 -

CR#

Attrib.

Register name

 

Explanation

 

#46

X

R

CH1 History timer

 

Set history timer in CH1 ~ CH4:

 

#47

X

R

CH2 History timer

 

 

 

Range = K1 ~ K32767

 

#48

X

R

CH3 History timer

 

 

 

Default = K1

 

#49

X

R

CH4 History timer

 

 

 

 

 

#100 ~ #199

CH1 ~ CH4 history

 

 

 

Symbols: O means latched. X means not latched.

 

 

 

 

R means can read data by using FROM instruction.

 

 

 

 

W means can write data by using TO instruction.

 

 

 

 

LSB (Least Significant Bit):1. Voltage input: 1LSB=10V/32,000=312.5μV

 

 

 

 

 

 

2. Current input: 1LSB=20mA/32,000=625nA

 

CR#7 History command. See the table below.

 

 

 

 

 

 

 

 

 

 

 

 

 

CMD

 

 

 

History Command

 

 

 

H’1000 ~ H’1003

 

 

CH1 ~ CH4 start

 

 

 

H’2000 ~ H’2003

 

 

CH1 ~ CH4 stop

 

 

 

H’4000 ~ H’4003

 

Reset history buffers of CH1 ~ CH4

 

 

 

H’6000 ~ H’6003

 

Read histories of CH1 ~ CH4

 

Note: Please use pulse instruction for executing history commands When the instruction is completed, the CR will be reset to 0.

CR#43: Error status value. See the table below.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit

Error Status

Content Value

Bit

 

Error Status

 

Content Value

 

b0

K1 (H’0001)

Power supply error

b1

K2 (H’0002)

Hardware error

 

 

 

 

 

 

 

 

 

b2

K4 (H’0004)

Mode setting error

 

 

b3 ~ b7 Reserved

 

b8

K256 (H’0100)

CH1 Conversion error

b9

K512 (H’0200)

CH2 Conversion error

 

 

 

 

 

 

 

 

b10

K1024 (H’0400)

CH3 Conversion error

b11

K2048 (H’0800)

CH4 Conversion error

 

 

 

 

 

 

 

 

 

 

b12

K4096 (H’1000)

CH1 Upper / lower

b13

K8192 (H’2000)

CH2 Upper / lower

 

bound error

bound error

 

b14

K16384

CH3 Upper / lower

b15

K32768

CH4 Upper / lower

 

(H’4000)

bound error

(H’8000)

bound error

Note: Each error status is determined by the corresponding bit and there may be more than 2 errors occurring at the same time. 0 = normal; 1 = error.

CR#44: History status. See the table below.

 

 

 

 

 

 

 

 

 

b15

b14

b13

b12

b11

b10

b9

b8

b7

b6

b5

b4

b3

b2

b1

b0

Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ch4 Ch3 Ch2 Ch1 Ch4 Ch3 Ch2 Ch1 Ch4 Ch3 Ch2 Ch1 Ch4 Ch3 Ch2 Ch1

0

Not Ready

 

 

Not Full

 

 

Empty

 

 

Stop

 

1

Ready

 

 

Full

 

 

Not Empty

 

 

Run

 

Note: History Command for reading will be executed only when a set of full 100 records are ready. If there are less than 100 records, Not Ready will be indicated.

bit 8 ~ bit11 = 1: History buffer full. bit12 ~ bit15 = 1: History buffer ready.

Adjust A/D Conversion Curve

Users can adjust the conversion curves according to the actual needs by changing the Offset value (CR#28 ~ CR#31) and Gain value (CR#34 ~ CR#37).

- 5 -

Gain: The corresponding voltage/current input value when the digital output value = 16,000.

Offset: The corresponding voltage/current input value when the digital output value = 0. y Equation for voltage input Mode0: 0.3125mV = 20V/64,000 = 10V/32,000

 

X (V )

 

(Gain Offset )

Y =16000 ×

 

×32000 Offset

 

10(V )

 

Y=Digital output, X=Voltage input

yEquation for voltage input Mode4 / Mode5 / Mode6: 0.15625mV = 10V/64,000 = 5V/32,000

 

X (V )

 

(Gain Offset)

Y =16000 ×

 

×32000 Offset

 

5(V )

 

Y=Digital output, X=Voltage input

y Equation for current input Mode1 / Mode2: 0.625μA = 40mA/64,000 = 20mA/32,000

 

X (mA)

 

(Gain Offset)

Y =16000 ×

 

×32000 Offset

 

20(mA)

 

Y=Digital output, X=Current input

yEquation for current input Mode3: 0.5μA = 16mA/32,000

Adopt the Equation of current input Mode3, substitute Gain for 19200 (12mA) and Offset for 6400 (4mA)

 

X (mA)

×32000

 

(19200 6400)

 

 

Y =16000 ×

20(mA)

6400

 

 

 

 

 

 

 

Y=Digital output, X=Current input

y Mode 0:

 

 

 

 

y Mode 1:

 

 

 

+32384

 

 

 

 

+32384

 

 

+32000

 

 

 

 

+32000

 

Digital

 

 

 

 

Digital

 

 

output

+16000

 

 

 

output

+16000

 

 

 

 

 

 

 

-10V

0

 

5V

 

-20mA

0

10mA

 

 

 

 

 

 

 

 

10V

 

 

20mA

 

 

Offset

Gain

 

 

Offset

Gain

 

 

-16000

 

 

 

-16000

 

 

 

Voltage input

 

Current input

 

 

-32000

 

 

 

-32000

 

 

 

-32384

 

 

 

-32384

 

Mode 0 of CR#2 ~ CR#5

-10V ~ +10V Gain = 5V (16,000) Offset = 0V (0)

Mode 1 of CR#2 ~ CR#5

20mA ~ +20mA Gain = 10mA (16,000) Offset = 0V (0)

Range of digital conversion

-32,000 ~ +32,000

Max./Min. range of digital

-32,384 ~ +32,384

conversion

 

y Mode 2:

 

 

 

y Mode 3:

 

 

 

 

+32384

 

 

 

+32384

 

 

 

+32000

 

 

 

+32000

 

 

Digital

 

 

 

Digital

 

 

 

output

+16000

 

 

output

+16000

 

 

 

 

 

 

 

 

 

 

Gain

 

 

 

Gain

 

0

 

 

 

0

 

 

 

-384

10mA

20mA

 

-384

4mA 12mA

20mA

 

 

Offset

 

 

 

Offset

 

 

 

Current input

 

 

Current input

 

 

 

 

- 6 -

 

 

 

Loading...
+ 15 hidden pages