Burnham 8B Installation and Operation Manual

0 (0)
ROFSNOITCURTSNIECIVRES
SEIRESB8
RELIOBDERIF-SAG
DNAGNITAREPO,NOITALLATSNI
,reliobnonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp
rebmuNledoMrelioBrebmuNlaireSrelioBetaDnoitallatsnI
____-_____8________6
rotcartnoCgnitaeH rebmuNenohP
8141602R14-1/04
1
Price - $5.00
IMPORTANT INFORMATION - PLEASE READ THIS PAGE CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations enforced in the area where the
installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or local regulations.
All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or local regulations.
This Series 8B Boiler has been approved by the Massachusetts Board of Plumbers and Gas Fitters: Approval No. G1-0202-11A. The Commonwealth of Massachusetts requires this product to be installed by a licensed Plumber or Gas Fitter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
REGNAD
noitautissuodrazahyltnenimminasetacidnI
,htaednitluserlliw,dediovatonfi,hcihw
ytreporplaitnatsbusroyrujnisuoires
.egamad
.egamad
GNINRAW
noitautissuodrazahyllaitnetopasetacidnI
,htaednitluserdluoc,dediovatonfi,hcihw
ytreporplaitnatsbusroyrujnisuoires
.egamad
NOITUAC
noitautissuodrazahyllaitnetopasetacidnI
nitluseryam,dediovatonfi,hcihw
ytreporproyrujnironimroetaredom
ECITON
nosnoitcurtsnilaicepssetacidnI
ecnanetniamro,noitarepo,noitallatsni
otdetalertontubtnatropmierahcihw
.sdrazahyrujnilanosrep
REGNAD
rosihtfoytinicivehtnisdiuqilrosropavelbammalfrehtoroenilosagesuroerotsTONOD
.ecnailpparehtoyna
lacirtceleynahcuotTONOD-ecnailppaynaetarepootyrtTONOD,sropavsagllemsuoyfI
yletomeramorfreilppussagehtllac,yletaidemmI.gnidliubehtnienohpynaesurohctiws
,elbaliavanusireilppusehtfirosnoitcurtsnis'reilppussagehtwolloF.enohpdetacol
.tnemtrapederifehttcatnoc
elbitsubmocrevoetercnoc,teprac,gniroolfelbitsubmocnoreliobsihtllatsniTONOD
rognipipcitsalpsahcuslairetamdetceffataehynarevoetercnocnoron,doowrogniroolf
.dleihsroolfelbitsubmocdellatsniylreporpatuohtiwgniriw
2
GNINRAW
ehtwolloF.ylefasetarepootecivresdnaecnanetniamralugerseriuqerreliobsihT
.launamsihtnideniatnocsnoitcurtsni
ytreporpesuacnacecnanetniamroecivres,noitaretla,tnemtsujda,noitallatsnireporpmI
erofeblaunameritneehtdnatsrednudnadaeR.efilfossolroyrujnilanosrep,egamad
ebtsumecivresdnanoitallatsnI.ecivresro,noitarepopu-trats,noitallatsnignitpmetta
.ycnegaecivresrorellatsnidelliksdna,decneirepxe,elbaegdelwonkaybylnodemrofrep
.detnevylreporpebtsumreliobsihT
snoisivorperaerehtosdellatsniebtsumdnanoitarepoefasrofriahserfsdeenreliobsihT
.rianoitalitnevdnanoitsubmocetauqedarof
ehtfotratsehterofebdenaelcdnadetcepsniebtsummetsysgnitnevehtforoiretniehT rofnosaesgnitaehehttuohguorhtyllacidoirepdetcepsniebdluohsdnanosaesgnitaeh
suoixonwollaotyrassecensimetsystnevdetcurtsbonudnanaelcA.snoitcurtsboyna
drawotetubirtnoclliwdnaylefastnevotefilfossolroyrujniesuacdluoctahtsemuf
.ycneiciffes'reliobehtgniniatniam
gnippatehtotnidellatsnisievlavfeilererusserpasselnuetelpmoctonsinoitallatsnI
roflaunamsihtfonoitceSmirTdnagnipiPretaWehteeS-reliobfopotehtnodetacol
.sliated
dnanwodtuhsotreliobehtesuacyamhcihwsecivedytefashtiwdeilppussireliobsihT
gnitaeheht,ytilibissopasisepipnezorfoteudegamadfI.ecivrestuohtiwtrats-erton
dnasdraugefasetairporpparo;rehtaewdlocnidednettanutfelebtondluohsmetsys
sireliobehtfiegamadtneverpotmetsysgnitaehehtnodellatsniebdluohssmrala
.evitareponi
sgnittifepipynawercsnutonoD.erusserphgihrednuretawtohyrevsniatnocreliobsihT
ehtgnirussaylevitisoptuohtiwreliobsihtfostnenopmocynatcennocsidottpmettaron
nehwtnempiuqednagnihtolcevitcetorpraewsyawlA.erusserponsahdnaloocsiretaw
ehtnoylertonoD.seirujnidlacstneverpotreliobsihtgnicivresropugnitrats,gnillatsni
.reliobehtfoerusserpdnaerutarepmetehtenimretedotseguagerutarepmetdnaerusserp
oD.gnitareposireliobehtnehwtohyrevemocebhcihwstnenopmocsniatnocreliobsihT
.loocerayehtsselnustnenopmocynahcuotton
,animulaniatnocleufehtdnanoitsubmocfostcudorp,noitcurtsnocfoslairetamrelioB
rocixotrehtoro/dnasedyhedla,sedixonegortin,edixonomnobrac,slatemyvaeh,acilis
ehtotnwonkerahcihwdnayrujnisuoiresrohtaedesuacnachcihwsecnatsbuslufmrah
esusyawlA.mrahevitcudorperrehtodnastcefedhtrib,recnacesuacotainrofilaCfoetats
ehtybraengnikrowrognicivresnehwtnempiuqednasrotaripser,gnihtolcytefasreporp
.ecnailppa
.htaedroyrujnilanosrepesuacnacredroreporpehtnisnoitcurtsnillawollofoteruliaF
slaunamsrerutcafunamtnenopmocnideniatnocesohtllagnidulcni,snoitcurtsnilladaeR
rogniniatniam,gnitarepo,pugnitrats,gnillatsnierofebreliobehthtiwdedivorperahcihw
.gnicivres
elbammalfrehtodnaenilosag,slairetamelbitsubmocmorfeerfdnaraelcaerareliobpeeK
.sdiuqilrosropav
.retawottcejbusneebsahhcihwlortnochtiwreliobetarepotonoD
.semitllataecalpniebtsumsdraugdnaserusolcne,setalprevocllA
ECITON
.launamsihtfokcabehtnodetnirpsihcihwfoypoca,ytnarrawdetimilasahreliobsihT
yltcerroceraslortnocllatahteesotrotcartnocgnillatsniehtfoytilibisnopserehtsitI
.etelpmocsinoitallatsniehtnehwylreporpgnitarepoeradnadellatsni
evahlevelaesevobateef000,2nahtretaergsedutitlatanoitallatsniroftliubsreliobASU
replevelaesevobateef000,1reptnecrep4etartupnisagecuderotdecifiroyllaicepsneeb
naidanaC.FxidneppAdna2.1.8noitceS,1.322ZISNA/45APFN,edoCsaGleuFlanoitaNeht
.lebalgnitarehtnodetacidnisignizisecifiro'sreliob
3
Table of Contents
I. Pre-Installation ................................................ 6
II. Boiler Assembly ................................................ 8
III. Gas Control System Assembly ....................... 15
(Knockdown Boilers)
IV. Water Trim and Piping .................................... 27
V. Gas Piping ....................................................... 31
VI. Venting ............................................................33
VII. Electrical .......................................................... 36
VIII. System Start-up ............................................... 59
IX. Service ............................................................. 68
X. Repair Parts ..................................................... 75
4
Table 1: Dimensional Data
Figure 1: Dimensional Data
relioB
ledoM
ABC
.oN
B50802017 61/31-4261/31-428/1-618/1-61.tf51x.aid"79.11096 B6084/3-328/7-118 61/31-724/3-528161.tf51x.aid"89.31077 B7082/1-724/3-319 61/31-824/3-528161.tf51x.aid"99.51578 B8084/1-138/5-519 61/31-0361/11-620261.tf51x.aid"99.71089 B908532/1-71012/1-3361/7-622251.tf51x.aid"019.910801 B0184/3-838/3-91012/1-3361/7-622251.tf51x.aid"019.120021
)1(
.)"4/1-73silenap )2( )3( )4(
DE
ASUadanaCASUadanaC
TPN1:ezisnoitcennocsaG
)sehcnI(snoisnemiD
)ylnOretaW(isp05:erusserPgnikroWelbawollAmumixaM
.rellatsniybdeilppussenilneddihninwohssmetI
dednemmoceR
eziSyenmihC
)dnuoR(
retaW
tnetnoC
)snollaG(
5
.xorppA gnippihS
thgieW
)BL(
pottekcajotroolf(thgiehreliobot"4/3-4sdda;gniroolfelbitsubmocnosnoitallatsnirofderiuqeresablaicepS
I. Pre-Installation
GNINRAW
erofebsnoitcurtsnilladaerylluferaC
llawollofoteruliaF.reliobgnillatsni
esuacnacredroreporpnisnoitcurtsni
.htaedroyrujnilanosrep
A. Inspect shipment carefully for any signs of damage.
All equipment is carefully manufactured, inspected and packed. Our responsibility ceases upon delivery of boiler to carrier in good condition. Any claim for damage or shortage in shipment must be filed immediately against carrier by consignee. No claims for variances or shortages will be allowed by Boiler Manufacturer, unless presented within sixty (60) days after receipt of equipment.
B. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such requirements, installation must conform to the National Fuel Gas Code, NFPA 54/ANSI Z223.1 and/ or CAN/CGA B149 Installation Codes. Where required by the authority having jurisdiction, the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers, ANSI/ASME No. CSD-1.
C. Provide clearance between combustible material
and boiler jacket (following clearances are minimums):
1. USA, 805B-807B: listed for Alcove installation
a. Front: 18" b. Top: 36" c. Draft hood, rear, sides and flue connector: 6"
2. USA, 808B-810B: for installation in room which is large in comparison with size of boiler. a. Front: 18" b. Top: 51½" c. Draft hood, rear, sides, and flue connector: 6"
3. Canada, 805B-810B: a. Top and front: 18" (45.7cm) b. Flue, rear and sides: 6" (15.2cm)
D. Provide clearance for servicing and proper operation
(following clearances are recommended and may be reduced to minimum clearances shown above):
1. Single boiler, 805B-807B, Front/Top: 24" (61cm)
2. Single boiler, 808B-810B, Front/Top: 48" (122cm)
3. Multiple/modular boiler, USA/Canada, Sides: 1" (2.5cm)
E. Install boiler on level floor as close to chimney as
possible. For basement installation provide a solid base such as concrete or masonry construction if floor is not level or if water may be encountered on floor around boiler.
F. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, control replacement, etc.).
GNINRAW
noitallatsnirofdeifitrecngisedsiecnailppA
roF.ylnogniroolfelbitsubmocnonno
ylnogniroolfelbitsubmocnonoitallatsni
elbaTnidetsilesablaicepsnodellatsninehw .gnitepracnodellatsniebtontsumrelioB.2 sihcihwetercnocnodellatsnisireliobnehW
gnitlemottcejbussitahtlairetamarevo
laicepseht,).cte,gnibuttnaidarXEP,CVP(
tonsidapetercnocA.desuebtsumesab
.gniroolfelbitsubmoctcetorpottneiciffus
Table 2: Special Base Required for Installation on
Combustible Flooring
.oNledoMrelioBrebmuNtraPesaBlaicepS
B50855061816 B60856061816 B70857061816 B80858061816 B90859061816 B01850161816
G. Provide combustion and ventilation air in
accordance with applicable provisions of local building codes, or the National Fuel Gas Code, NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and Ventilation; or CAN/CGA B149 Installation Codes, Part 5, Venting Systems and Air Supply for Appliances.
GNINRAW
rianoitalitnevdnanoitsubmocetauqedA
reporperussaotdedivorpebtsum
.noitsubmoc
The following guideline is based on the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms communicating directly with space (through permanent openings not furnished with doors) are considered part of space.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space.
Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total Input.
6
a. If result is greater than or equal to 50 ft³ per 1,000
Btuh, space is considered an unconfined space.
b. If result is less than 50 ft³ per 1,000 Btuh, space is
considered a confined space.
4. Determine building type. A building of unusually tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and
b. Weather-stripping has been added on openable
windows and doors, and
c. Caulking or sealants applied in joints around
window and door frames, between sole plates and floors, between wall-ceiling joints, between wall panels, at plumbing and electrical penetrations, and at other openings.
5. For boiler located in an unconfined space in a building of other than unusually tight construction, adequate combustion and ventilation air is normally provided by fresh air infiltration through cracks around windows and doors.
6. For boiler located in an unconfined space in a
building of unusually tight construction or in a confined space, provide outdoor air through
permanent opening(s) which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Minimum dimension of air opening(s) is 3" (7.6cm).
a. Two permanent openings: Locate one opening
within 12 " (30.5cm) of top of space. Locate remaining opening within 12" (30.5cm) of bottom of space. Size each opening per following:
i. Minimum free area of 1 square inch per 3,000
Btu per hour input of all equipment in space.
ii. Free area shall not be less than the sum of
the areas of all vent connectors in the confined space.
Alternate method for boiler located within confined space. Use indoor air if two permanent openings
communicate directly with additional space(s) of sufficient volume such that combined volume of all spaces meet criteria for unconfined space. Size each opening for minimum free area of 1 square inch per 1,000 Btu per hour input of all equipment in spaces, but not less than 100 square inches.
7. Ventilation Duct Louvers and Grilles. Equip outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects and rodents. Louvers and grilles must be fixed in open position or interlocked with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers, grilles and screens when calculating the opening size to provide the required free area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
8. For Specially Engineered Installations. The above requirements shall be permitted to be waived where special engineering, consistent with good engineering practice and approved by the authority having jurisdiction, provides an adequate supply of air for combustion, ventilation, and dilution of flue gases.
i. Direct communication with outdoors.
Minimum free area of each opening must be 1 square inch per 4,000 Btu per hour input of all equipment in space.
ii. Vertical ducts. Minimum free area of each
opening must be 1 square inch per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
iii. Horizontal ducts. Minimum free area of
each opening must be 1 square inch per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
b. One permanent opening shall be permitted where
the boiler has clearances of at least 1" (2.5cm) from the sides and rear and 6" (15.2cm) from the front. Locate the opening within 12 " (30.5cm) of top of space. Size opening per following:
GNINRAW
rehtoroenilosagerehwreliobllatsnitonoD
fosecruosro,sdiuqilrosropavelbammalf
,srenaelc,sehcaelb.e.i(snobracordyh
cirbaf,srevomertniap,syarps,slacimehc
.derotsrodesuera).cte,srenetfos
ECITON
ehtotdragerhtiwreliobehtfognizis-siM
evissecxenitluserlliwdaolmetsysgnitaeh
tnenopmocdetareleccadnagnilcycreliob
tnarrawTONSEODmahnruB.eruliaf
reliobdezis-simybdesuacseruliaf
otreliobehtezisrevoTONOD.snoitacilppa
yltaergsreliobelpitlum/raludoM.metsyseht
.gnizisrevoreliobfodoohilekilehtecuder
7
II. Boiler Assembly
A. Remove Crate (Semi-Pak and Packaged Only)
1. Remove all fasteners at crate skid.
2. Lift outside container and remove with all other inside protective spacers and bracing.
B. Remove boiler from skid. See Figure 2. Exercise care
to avoid dropping boiler.
1. Place boiler in approximate location. Refer to Section I: Pre-Installation. Remove base hold down bolts.
2. Using pry bar under rear corner of Base End Panel, raise boiler and install 1½" wood blocks under rear corners. Install ¾" pipe roller between Base and skid.
3. Remove 1½" wood blocks. Place 3" pipe roller on floor behind skid.
4. Roll boiler off skid. Move skid out of way.
Figure 2: Skid Removal
Table 3: Purpose of Tappings
gnippaTeziSesopruP
A"2ylppuS B"2nruteR C"¾evlaVfeileR D"¾timiL E"¾timiLyrailixuA F"¾tuohsaW G"¾niarD
Figure 3: Tapping Locations
8
5. Roll boiler until 3" roller is located as shown. Use pry bar to install wood blocks under front corners of base. Remove 3" roller.
6. Lift boiler with pry bar. Remove wood blocks. Lower boiler.
C. For Packaged Boiler only, proceed to Paragraph E.
D. Test Section Assembly for leaks before connecting to
system and installing controls, trim and jacket. Refer to Figure 3 and Table 3.
1. Plug Tappings C & E (¾ NPT) and Return Tapping B (2 NPT).
2. Insert ¾" NPT x ¼" NPT bushing in Tapping D. Install pressure gauge capable of indicating 50 psi.
3. Insert 2" NPT x ¾" NPT bushing in Supply Tapping A. Install purge valve with a hose that runs to a drain.
4. Connect fill valve and piping to Drain Tapping G.
GNINRAW
.reliobtsetkaelotriaesutonoD
5. Fill boiler completely with water by venting air through purge valve. Close purge valve and apply water pressure of at least 10 psi but less than 50 psi gauge pressure.
6. Examine boiler for leaks or damage due to shipment or handling.
7. Remove plugs from Return Tapping B, Tapping C, and Tapping E (if second limit or operating control is used). Also remove fill valve and piping, purge valve and piping, and pressure gauge.
E. Install special base if installation is on combustible
flooring. See Figure 4. Floor shield adds 4¾" to boiler height.
1. Place special base on combustible floor with surface marked "FRONT" in upward position.
2. Locate special base with spacing to combustible materials as shown in Figure 4.
3. Place boiler on special base. Boiler must rest inside locating brackets. Boiler jacket panels will overhang special base.
4. Do not enclose boiler (including special base) on all four sides. Models 805B - 807B may be enclosed
Figure 4: Installation of Special Base for Combustible Flooring
9
Figure 5: General Assembly (Knockdown Boilers)
on three sides (alcove) while maintaining clearances shown in Figure 4.
F. Move boiler to permanent location by sliding or
walking. DO NOT DROP.
For Packaged Boiler proceed to Section IV: Trim and Piping.
G. Install Canopy on section assembly. See Figure 5.
Canopy and hardware are located in Combination Boiler Parts and Control Carton.
1. Position Canopy on top of Section Assembly. Locate between end sections and sealing ledge on front and back of each section.
2. Fasten each end with ¼" - 20 x 1" carriage bolts, washers and nuts.
3. Seal between Canopy and Section Assembly with furnace cement.
H. Inspect joints between sections. They were factory
sealed. If any openings resulted during shipment or handling, reseal with furnace cement. Confirm tie rods are only hand tight to allow for thermal expansion.
I. Install Base Front Panel. See Figure 5. Panel and
hardware located in Combination Boiler Parts and Control Carton.
1. Attach Base Front Panel to Section Assembly using ¼" - 20 x 1¼" carriage bolts, washers and nuts.
2. Seal between top of Base Front Panel and Section Assembly with furnace cement (shipped in Combination Boiler Parts and Control Carton).
3. Seal between top of Base Rear Panel and Section Assembly with furnace cement.
J. Install Pilot/Main Burner Assembly. See Figure 7.
Assembly is located in Combination Boiler Parts and Control Carton. Verify assembly is properly located on support bracket in Base Rear Panel, seated on Main Burner Orifice, and secured with hitch pin clip.
K. Attach Flame Roll-out Switch to Burner Access
Panel. See Figure 6. Flame Roll-out Switch and hardware are located in Combination Boiler Parts and Control Carton. Flame Roll-out Switch is a single use device - do not test with heat - switch cannot be reset.
10
Figure 6: Flame Roll-out Switch Installation
Figure 7: Burner/Burner Access Panel Installation
11
1. Cut insulation from semicircular notch at right end of the burner access panel. Models 808B - 810B have two (2) burner access panels. Remove insulation from notch of right side burner access panel only.
2. Attach Flame Roll-out Switch Mounting Bracket to burner access panel with (1) #8 x ½" lg. sheet metal screw.
3. Attach Flame Roll-out Switch to mounting bracket with (1) #8 x ¾" lg. sheet metal screw.
L. Install Burner Access Panel(s). Locate Burner
Access Panel(s) in Combination Boiler Parts and Control Carton. Engage Burner Access Panel holes with projections on Base Front Panel. See Figure 6.
M. Install Immersion Well(s).
1. Remove Immersion Well(s) from Combination Boiler Parts and Control Carton..
2. Insert Immersion Well in Tapping D. See Figure 3.
3. If second limit or operating control is used, insert immersion well in Tapping E. If vertical gas piping is to be installed inside of boiler jacket, it is recommended that second limit be installed in system piping.
7. Attach Lower Front Tie Bar to Left Side and Right Side Panels.
8. Engage Upper Front Panel in slots on Left Side and Right Side Panels. Place Top Panel in position. Attach Top Panel to Left Side, Right Side and Upper Rear Panels.
9. Tighten all jacket screws.
10. Affix Lighting/Operating Instructions Label and Wiring Diagram Label to inside of Front Removable Door. Labels are located in Combination Boiler Parts and Control Carton.
O. Install Junction Box. See Figure 8. Attach junction
box to inside of Left Side Panel with ¼" - 20 x ¼" lg. machine screw (located in Combination Boiler Parts and Control Carton).
P. Install Limit Control. Locate limit in Combination
Boiler Parts and Control Carton. Insert limit probe into left immersion well as far as possible. Tighten set screw.
Q. Install Auxiliary Limit or operating control (if used).
Insert control probe into right immersion well as far as possible. Tighten set screw.
N. Install Jacket. See Figure 8.
1. Locate four (4) Jacket Attachment Brackets in Combination Boiler Parts and Control Carton. Attach to Front Base Panel and Rear Base Panels with #8 sheet metal screws. See Figure 5.
2. Hang Left Side Panel and Right Side Panel onto Jacket Attachment Brackets.
3. Attach Lower Rear Panel to Left and Right Side Panels. Do not tighten sheet metal screws.
4. Attach Upper Rear Panel to Lower Rear Panel. Do not install three (3) upper screws.
5. Remove Rating Label and Combustible Clearance Label from Combination Boiler Parts and Control Carton. Attach to Vestibule Panel in locations shown.
6. Attach Vestibule Panel to Left Side and Right Side Panels.
R. Install Gas Control Assembly. Refer to Section III,
Gas Control System Assembly (Knockdown Boilers).
S. EP and OP System: See Figure 9.
1. Install pre-wired EP/OP Control Cabinet Assembly to right front corner of jacket top panel.
2. Install Honeywell RM7890 Control (located in RM7890 Control Carton).
3. Remove RM7890's Dust Cover. With a pair of side cutters, carefully snip both wire leads to the brown resistor labelled "JR2" and discard it. Replace Dust Cover.
4. Install Honeywell R7847 Flame Amplifier.
5. Install heat shield.
12
Figure 8: Jacket Assembly
13
Figure 9: EP/OP Control Installation
14
III. Gas Control System Assembly (Knockdown Boilers)
A. 24V Standing Pilot Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 10. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.
2. Install pilot burner piping and controls. See Figure
10.
3. Connect Thermocouple Lead to Gas Valve.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4" nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
B. EI (Intermittent Ignition)
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 11. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.
2. Install pilot burner piping and controls.
a. Honeywell EI
i. USA - See Figure 12.
ii. Canada - See Figure 13.
b. Johnson EI
i. USA - See Figure 14.
ii. Canada - See Figure 15.
3. Install Ignition Module.
a. Attach Ignition Control Mounting Bracket to
Jacket Vestibule Panel using two (2) #8 x ½" sheet metal screws.
b. Attach Johnson Ignition Module to Mounting
Bracket using two (2) #6 x ¾" sheet metal screws or attach Honeywell Ignition Module to Mounting Bracket using two (2) #8 x ½" sheet metal screws.
c. Connect pilot ground wire and ignitor/sensor
lead(s) to ignition module. Refer to "Section VII: Electrical" for connection details.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box. See Figure 8.
a. Canada only - loop 4" nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
C. OP Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 16. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.
2. Install pilot burner piping and controls. See Figure
16.
3. Connect Thermocouple Lead to Gas Valve.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4" nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
D. OP-CSD-1 Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 17. Use thread (joint) compound (pipe dope) resistant to action of liquefied petroleum gas.
2. Mount pilot switch.
3. Install pilot burner piping and controls. See Figure
17.
4. Connect Thermocouple lead to pilot switch.
5. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
6. Attach transformer/control center to junction box.
E. EP Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 18.
2. Install pilot burner piping and controls. See Figure
18.
3. Install Ignition Transformer.
a. Attach Ignition Transformer to Jacket Vestibule
Panel using four (4) #8 x ½" lg. sheet metal screws.
b. Connect Ignition Lead from Pilot to Ignition
Transformer.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4" nylon cable tie between
junction box and transformer/control center.
15
b. Attach transformer/control center to junction
box.
Panel using four (4) #8 x ½" lg. sheet metal screws.
F. EP-CSD-1 Control System
Install Gas Control System. All components are
located in Combination Boiler Parts and Control Carton.
1. Install Gas Control Assembly on Manifold. See Figure 19.
2. Install pilot burner piping and controls. See Figure
19.
3. Install Ignition Transformer.
a. Attach Ignition Transformer to Jacket Vestibule
b. Connect Ignition Lead from Pilot to Ignition
Transformer.
4. Mount Transformer (continuous circulation) or Control Center (intermittent circulation) to Junction Box.
a. Canada only - loop 4" nylon cable tie between
junction box and transformer/control center.
b. Attach transformer/control center to junction
box.
16
17
Figure 10: Schematic Gas Piping, 24V Standing Pilot, 806B & 807B
18
Figure 11: Main Gas Piping, Intermittent Ignition (EI)
19
Figure 12: Schematic Pilot Piping (Honeywell EI), USA
20
Figure 13: Schematic Pilot Piping (Honeywell EI)
Canada: Natural Gas, 805B - 810B; LP Gas, 806B - 807B
21
Figure 14: Schematic Pilot Piping (Johnson EI), USA
22
Figure 15: Schematic Pilot Piping (Johnson EI)
Canada: Natural Gas, 805B - 810B; LP Gas, 806B - 807B
23
Figure 16: Schematic Gas Piping, OP Control System, 806B - 810B
24
Figure 17: Schematic Gas Piping, OP-CSD-1 Control System, 808B - 810B
25
Figure 18: Schematic Gas Piping, EP Control System (Natural Gas Only), 806B - 810B
26
Figure 19: Schematic Gas Piping, EP-CSD-1 Control System, 808B - 810B
IV. Water Trim and Piping
.erutcurts
.retawfonoitidda
GNINRAW
roreliobotegamaddnanoitareporeporpminitluseryamreliobepipylreporpoteruliaF
reliobleetsdnanorifonoisorrocesuaclliwretawreliobfonoitanimatnocnegyxO
smelborprevoctonseodytnarraWs'mahnruB.eruliafreliobotdaelnacdna,stnenopmoc
tneuqerfybdesuacpu-dliub)emil(elacsroretawreliobfonoitanimatnocnegyxoybdesuac
A. Design and install boiler and system piping to prevent
oxygen contamination of boiler water and frequent water additions.
1. There are many possible causes of oxygen contamination such as:
a. Addition of excessive make-up water as a result
of system leaks.
b. Absorption through open tanks and fittings.
c. Oxygen permeable materials in the distribution
system.
2. In order to insure long product life, oxygen sources must be eliminated. This can be accomplished by taking the following measures:
a. Repairing system leaks to eliminate the need for
addition of make-up water.
b. Eliminating open tanks from the system.
c. Eliminating and/or repairing fittings which allow
oxygen absorption.
d. Use of non-permeable materials in the
distribution system.
e. Isolating the boiler from the system water by
installing a heat exchanger.
f. Use properly designed and operating air
elimination devices in water piping.
B. Design system to obtain a 20°F temperature rise through
the boiler (see Table 4). If a temperature rise greater than 40°F is desired, consult Burnham.
C. Install Safety Relief Valve. See Figure 20. Components
are located in Water Trim Carton. Safety Relief Valve must be installed with spindle in vertical position.
1. Install ¾" NPT x 3½" lg. nipple in tapping "C". See Figure 3.
2. Install safety relief valve on ¾" NPT nipple.
GNINRAW
.tnemegnarragnipip
Table 4: Flow Rate, Temperature Rise, and
Pressure Drop
RELIOB
EZIS
B508
B608
B708
B808
B908
B018
WOLF
ETAR
)MPG(
12 41 01
62 71 31
13 12 51
73 42 81
24 82 12
74 13 32
.PMET
ESIR
URHT
RELIOB
F°02 F°03 F°04
F°02 F°03 F°04
F°02 F°03 F°04
F°02 F°03 F°04
F°02 F°03 F°04
F°02 F°03 F°04
.NIM
RELIOB
GNIPIP
)TPN(
"½1 "¼1 "¼1
"½1 "½1 "¼1
"2
"½1 "¼1
"2
"½1 "½1
"2 "2
"½1
"2 "2
"½1
tsumgnipipegrahcsidevlavfeilererusserP
erevesfolaitnetopehttahthcusdepipeb
ynaniepipTONOD.detanimilesisnrub
TONOD.ruccodluocgnizeerferehwaera
.spacrosgulp,sevlavffotuhsynallatsni
egrahcsidreporprofsedoClacoLtlusnoC
RELIOB
ERUSSERP
PORD
'3 '2 '1
'3 '2 '1
'3 '2 '1
'3 '2 '1
'3 '2 '1
'3 '2 '1
27
Figure 20: Safety Relief Valve Installation
Figure 21: Drain Piping Installation
b. Insert Temperature-Pressure Gauge. Tighten by
applying pressure to square shank on back of gauge. DO NOT APPLY PRESSURE ON GAUGE CASE since this may ruin gauge calibration.
2. Alternate Temperature-Pressure Gauge Piping. See Figure 23.
a. Install 2 NPT x 10" Nipple into Supply Tapping
"A". See Figure 3.
b. Install 2 NPT x ¾ NPT x 2 NPT Tee (provided) or
2 NPT x 2 NPT x ¾ NPT Tee (installer furnished). ¾" NPT leg should face forward.
c. Install ¾ NPT x ¼ NPT Bushing.
d. Insert Temperature-Pressure Gauge. Tighten by
applying pressure to square shank on back of gauge. DO NOT APPLY PRESSURE ON GAUGE
CASE since this may ruin gauge calibration.
F. Connect system supply and return piping to boiler. See
Figure 25. Also consult I=B=R Installation and Piping Guides. Maintain minimum ½ inch clearance from hot water piping to combustible materials.
1. If boiler is used in connection with refrigeration systems, boiler must be installed with chilled medium piped in parallel with heating boiler using appropriate valves to prevent chilled medium from entering boiler. See Figure 24. Also consult I=B=R Installation and Piping Guides.
2. If boiler is connected to heating coils located in air handling units where they may be exposed to refrigerated air, boiler piping must be equipped with flow control valves to prevent gravity circulation of boiler water during cooling system operation.
3. Use boiler bypass if boiler is operated in system which has a large volume or excessive radiation where low boiler water temperatures may be encountered (i.e. converted gravity circulation system, etc.). See Figure 25.
4. A hot water boiler installed above radiation level must be provided with a low water cutoff device as part of installation.
D. Install Drain Valve in rear of Left End Section, Tapping
"G". See Figure 21. Components are located in Water Trim Carton.
E. Install Temperature-Pressure Gauge. Components are
located in Water Trim Carton.
1. Standard Temperature - Pressure Gauge Piping. See Figure 22.
a. Install 2" NPT x 10" lg. nipple with gauge tapping
into Supply Tapping "A". See Figure 3. Gauge tapping should face forward.
5. A start-up strainer is recommended for practically all modular installations (new and replacement alike) to prevent system debris and sediment from ending up in the boilers where it will inhibit heat transfer and may eventually cause a cast iron section to crack from overheating.
G. Alliance Water Heater (if used). Refer to Alliance
Installation, Operating and Service Instructions for additional information. Install in same manner as space heating zone.
28
Figure 22: Temperature-Pressure Gauge
Installation
Figure 23: Alternate Temperature-Pressure
Gauge Installation
Figure 24: Recommended Piping for Combination
Heating & Cooling (Refrigeration) System
29
30
Figure 25: Recommended Boiler Piping for Circulator Zoned Heating Systems
Loading...
+ 70 hidden pages