Burnham 79A, 53A, AL-26A, 40A User Manual

0 (0)
®
Y 9
Price - $3.00
AND
SERVICE INSTRUCTIONS
TM
ALLIANCE
INDIRECT-FIRED WATER HEATERS
MODELS AL-26A, 40A, 53A, 79A and 119A
SERIES
for SINGLE W ATER HEATER INSTALLATIONS
For serv ice or repairs to the water heater, call your heating c ontractor. When s eek ing information on water heater, provide Model N umber and Serial Number as shown on Rating Label.
Model Number
_ AL _____ __
Serial Number
_ _ _ _ _
Installation Date
Heating C ontractor Phone Number
Address
8140817R3-3/00
AMERICA’S BOILER COMPAN
BurnhamCorporation
1
Lancaster, PA 17604-307
IMPORTANT INFORMATION - READ CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations required in the area where the
installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring on water heaters installed in the USA shall be in accordance with the National Electrical Code and/or local regulations.
All wiring on water heaters installed in Canada shall be in accordance with the Canadian Electrical Code and/or local regulations.
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning the life of the water heater.
DA NGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious inju ry or substa ntial proper t y dama ge.
WARNING
Indicat es a potentia ll y hazardo us situ ation which, if not avoided, could result in death, serious injury or substantial property damage.
CAUTION
Ind icates a poten tially h aza rdous si tuation which, if not avoided, may result in moderate or minor injury or prop erty damage .
NO TIC E
Indi cates spec ial ins truction s o n ins tall ation, op e ratio n, or m ai nt enan c e whi ch are impor tant b ut not relate d to persona l injury ha zards .
DA NGE R
DO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance. If you smell g as vapors, DO NOT try to o perate any ap pliance - DO NOT touch any electrical switch or use any phone in the building. Immediately, call the gas supplier from a remotely located phone. Follow the g as su pp lier's instructions or if the supplier is un availab le, contact the fire department.
2
I. General Information
WAR N IN G
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Read and understand the entire manual before attempting installation, start-up operation, or service. Installation and service must be perfo rmed on ly by an exp erienced, s killed ins taller or serv ice ag ency.
Installation is not complete unless a pressure and temperature relief valve is installed into the side of the water heater. See Piping Section of this manual for details.
This water heater contains very hot water under high pressure. D o not unscrew any pipe fittings nor attempt to disconnect any components of this water heater w ithout positively assuring the water is cool and has no pressure. Always wear protective clothing and equipment when installing, starting up or servicing this water heater to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the water heater. This water heater contains components which become very hot when the boiler is operating. Do not touch any components unless they are cool.
Water heater materials of construction contain urethane, heavy metals and/or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing, respirators and equipm ent when servicing or working nearby this water heater.
Failure to follow all instructions in the proper order can cause personal injury or death. Read all instructions, including all those contained in component manufacturers' manuals which are provided with the water heater before installing, starting up, operating, maintaining or servicing.
NOTICE
The A lliance wa ter hea ter must be installe d with a pre ssure a nd tempe rature relief valve. Th e valve is not supplied with the water heater and must be provided by the installer.

T able of Contents

Section I - General Information ............................ 3
Ratings, Capacities, Weights, & Dimensions....... 4
Section V - Operation.......................................... 16
Section VI - Service Instructions ........................ 17
Section II - Pre-Installation................................... 5
Section III - Piping ................................................ 8
Section IV - Electrical ......................................... 15
Section VII - Trouble Shooting........................... 18
Section VIII - Repair Parts.................................. 19
Warranty ..............................................Back Cover
3
Table 1: Alliance Water Heater Dimension (Inches)
ALLIANCE
MOD EL
AL26A 40 20-1/4 31-1/2 22-1/2 9-3/4 2 3/4 3/4 3/4 3/4 3/4 AL40A 55 20-1/4 46-1/2 25-3/4 9-3/4 2 3/4 3/4 3/4 3/4 3/4 AL53A 70-5/8 20-1/4 62-1/8 28-3/4 9-3/4 2 3/4 3/4 3/4 3/4 3/4 AL7 9A 69-3/8 23-3/4 60-7/8 29-1/4 10-1/4 1-5/8 1 3/4 3/4 1 1
AL119A 66 29-1/2 52-3/4 39-1/4 12-3/4 2-1/2 1-1/4 1-1/4 1-1/4 1-1/4 1
ABCDEFGH I JK
Table 2: Alliance Water Heater Capacities
M AXIMU M
ALLOWA BLE
WOR KI NG
P RESSUR E ( PSI)
HYDROSTATIC
DESIGN
P RESSUR E ( PSI)
ALLI ANC E
MOD EL
TANK
VOL UME
(GA L )
COIL
VOL UME
(GA L )
DRY
WEIGHT
(LBS)
WET
WEIGHT
(LBS)
COIL HEAT TRANSFER
AREA ( SQ. F T. )
AL26A 26.4 1. 0 49 269 6.5 150 300 AL40A 39.6 1. 2 66 396 8.6 150 300 AL53A 52.8 1. 4 82 522 9.7 150 300 AL79A 79.3 2. 2 170 831 15.1 150 300
AL119A 119.4 2.9 183 1178 24.3 150 300
Table 3: Alliance Water Heater Performance
MAXIMUM FIRST
MO DEL
AL2 6A 142 197 1.93 2.84 110,000 8.0 2.5 2.4 AL4 0 A 175 242 2.26 3.38 133,000 11.4 6.1 7.2 AL5 3 A 224 310 2.85 4.29 164,000 10.9 6.5 9.0 AL7 9 A 253 350 2.90 4.51 190,000 10.6 8.4 9.1
AL11 9A 350 409 3.84 4.83 386,000 15.4 11.6 16.4
NOTES:
tank (when applicable).
HO UR RAT ING
GAL/HR @
14 0F 115F 14 0F 115F
All ra tings based o n 200F bo iler w ate r tem pera ture, 50F d omestic w ater inlet tempera ture, and a fully recovered
CONTINUOUS
RATING
GAL/MIN @
BOILER D OE
H E AT IN G C A PA CI TY
NEEDED FOR
R ATING S (BTU/HR )
MINIMUM BOILER
WATER FLO W
THROUGH HEATER
C O IL ( GA L / M IN )
PRESSURE
DRO P THROUGH
COIL AT MIN.
FLOW (F T. W .C .)
MINUTES OF
140F WATER AVAILABLE AT 5 GPM DRAW
4
CA UTION
The heat transfer m edium must be water or other non-toxic fluid having a toxicity rating or class of 1, as listed in clinical Toxicolog y of Commercial Products, 5th edition. The pressur e of the heat tran sfer m edium must be limited to a maxim um of 30 psig b y an approved safety or relief valve.
NOTICE
This water heater has a limited warranty, a copy of which is printed on the back o f this m anu al. It is the respon sibility of the in stalling cont ractor to see th at all contro ls a re correctly installed and are operating properly when the installation is complete.
II. Pre-Installation
Inspect shipment carefully for any sign of damage. All equipment is carefully manufactured, inspected and packed. Burnham Corporation's responsibility ceases upon delivery of water heater to the carrier in good condition. Any claim for damage or shortage in shipment must be filed immediately against the carrier by the consignee. No claims for variances or shortages will be allowed by Manufacturer, unless presented within sixty (60) days after receipt of equipment.
Installation must conform to the requirements of the authority having jurisdiction. In the absence of such requirements, installation must conform to National Plumbing Code and National Electrical Code, ANSI/NFPA No. 70, current edition.
present. Consult Burnham for size recommendations for
installation with unusual water demand. Refer to Table 3 for water heater performance
specifications.
2. Boiler DOE Heating Capacity The Alliance™
water heater will provide the rated performance only if used in conjunction with a boiler with a DOE heating capacity at least as much as the minimum noted in Table 3. If the boiler has less capacity, the output of the tank will be reduced. To determine the approximate reduction in output from the tank use the following formula:
IMPORTANT DECISIONS REQUIRED BEFORE INSTALLATION:
A. Sizing
1. Alliance™ Model - Choose the Alliance™ model
based on the expected water usage of the building. The average residence with one shower or more will require a model AL40A or larger. The AL26A should only be considered for residences with minimal water demand or for commercial application where showers are not present.
Factors which dramatically increase water demand include high flow shower heads, whirlpool tubs, and the use of multiple showers at the same time. Upsize the tank size if any of these factors are
For example, what would the first hour rating be if a model AL53A were installed with a boiler having a DOE heating capacity of 120,000 BTU/h?
Increasing the boiler DOE heating capacity above the values listed in Table 3 will not increase the rating of the water heater.
3. Circulator Sizing - Refer to Table 3 for the
minimum flow rate through the water heater coil and the corresponding pressure drop through the coil. Calculate the pressure drop of all straight pipe and fittings on the supply and return of the water heater at the minimum flow rate. Add the piping/ fitting pressure drop to the pressure drop through the water heater coil.
5
Select a circulator which will provide at least the minimum flow rate at combined pressure drop.
B. System Zone Control The Alliance
heater must be installed as a zone separate from the space heating system. The domestic hot water zone's piping and circulator must be sized for a minimum flow rate with all zones in use and a maximum flow rate with only the water heater in use. For this reason, the preferred method of zone control is with circulators.
1. Circulators - With space heating zones using
circulators, the Alliance™ should be added as an additional zone with a circulator.
2. Zone Valves - Select a valve with low pressure
drop to assure adequate flow through the water heater.
3. Hybrid - The space heating zone can be zoned
using zone valves and Alliance™ zoned with a circulator. Refer to Figures 3 and 5.
TM
water
C. Domestic Hot Water Priority Two options are
available, Priority and Non-Priority.
during simultaneous space and domestic hot water heating operations, depending on such factors as boiler output, boiler over sizing, number of space heating zones calling for heat and ratio of domestic hot water load to space heating load.
D. Component Location
1. Alliance™ Location
When such a location cannot be avoided, a suitable drain pan must be installed under the water heater. The drain pan must be connected to a drain.
Adequate clearance from combustible materials and for service must be provided.
1. Priority Demand for space heating is interrupted
or postponed until the domestic hot water demand is satisfied. This option provides maximum delivery of domestic hot water. Priority is recommended when:
a. Boiler net output is 100,000 Btu per hour or
less, or
b. When boiler output required to satisfy domestic
hot water demand is at least 50% of the boiler output required to satisfy space heating demand, or
c. When an interruption in space heating can be
tolerated during a long domestic hot water draw.
The delay in space heating may not be noticed due to the fast recovery time of the AllianceTM water heater. Certain water heater system malfunctions (such as domestic hot water zone circulator failure) could delay space heating indefinitely.
When zoning with zone valves, priority can be provided with a three-way valve. Carefully size the valve for proper flow to all zones.
The AllianceTM is design certified for installation on combustible flooring.
The Alliance™ may be installed in a closet or alcove.
2. Boiler Location - Locate the boiler as close to the
Alliance™ as practical.
3. Fixture Locations - For fastest delivery of hot
water, place AllianceTM close to points of use.
E. Additional Recommended Components
2. Non-Priority Boiler output is divided between
space heating and domestic hot water heating. Delivery of domestic hot water can be reduced
1. Shut-off Valves - Allows isolation of water heater
from domestic water system and/or boiler system during service.
2. Unions - Allows water heater movement during
service if adequate clearance cannot be provided.
3. Vacuum Breaker - Protects water heater's tank
from possible collapse if a hot tank is allowed to
6
cool to room temperature, or if tank is drained without opening a hot water faucet. A Watts Model No. N36 is an appropriate vacuum relief valve.
4. Thermal Expansion Tank If water heater is
installed in a closed water supply system, such as one having a back-flow preventer in the cold water line, provide thermal expansion control. Contact the water supplier or local plumbing inspector for additional information. An Amtrol Model ST-12 is an appropriate diaphragm style thermal expansion tank for most installations.
F. Removal of Existing Domestic Water
Heating System
1. External Tankless Heater - Disconnect from
boiler piping and domestic water system.
2. Tankless and Storage Heaters - Disconnect from
domestic water system. Heater does not need to be removed from boiler. If left in place, do not plug
®
inlet and outlet tappings.
G. Water Quality Improper water quality will reduce
the expected life of the Alliance™ water heater. Hard water, sediment, high or low water Ph, and high levels of chlorides in the domestic water should be avoided. Sediment and hard water will coat the water heater coil surfaces and reduce the rating of the water heater and may, eventually, cause a failure. High or low Ph and/ or high chloride concentrations will cause the stainless steel water heater components to corrode and eventually fail. A filter is strongly recommended where sediment is present in the water. A water softening system is recommended for areas with hard water. In areas where water quality is unknown, a water quality test should be performed.
WARN I N G
Do not operate ALLIANCE™ water heater in areas where water Ph is above 8.0 or below 6.0, and/or with chloride concentra tions g reater than 80 parts p er million (pp m). Bu rnham' s Standard Warranty does not cover problems caused by improper water Ph or excessive levels of chlorides.
7
Loading...
+ 15 hidden pages