A. O. Smith BTRC-154 User Manual

4 (1)
A. O. Smith BTRC-154 User Manual

Commercial Gas

® Tank-Type Water Heaters

MasterFit®

BTRC 120-500(A)

FEATURES

80+ % thermal efficiency affords lower operating costs on most models.

 

WATER CONNECTIONS - For ease of installation, BTRC's feature on most models water

 

connections on the top, front, and rear.

 

GLASS LINED TANK - Permaglas® Ultracoat is the proprietary ceramic coating

 

developed by A.O. Smith's ceramic engineers specifically for this heater. It is applied after

 

the complete tank has been assembled to give a seamless barrier against corrosion by

 

hot water. The maximum working pressure is 160 psi (1103 kPa).

 

FULLY AUTOMATIC CONTROLS WITH SAFETY SHUTOFF — Accurate, dependable

 

control system. Manual reset gas shutoff device for added safety. Maximum inlet gas

 

pressure is 14" W.C. Minimum gas pressure is 4.5" W.C. natural gas, 11" W.C. propane.

 

FOAM INSULATION —Saves fuel, helps reduce standby heat loss.

 

JACKET — Heavy gauge steel finished with a baked enamel finish over a bonderized undercoat.

 

EASY CLEANING — Handhole cleanout allows easy cleaning.

 

FULLY TESTED FOR SAFETY AND PERFORMANCE — Design certified by the Underwriters

 

Laboratory for 180°F (82°C) hot water service. Meets rigid requirements of the National Sanitation

 

Foundation when equipped with optional leg kit. Certified for use on combustible flooring.

 

INTERMITTENT IGNITION DEVICE — Eliminates standing pilot. Provides flame failure response

 

in less than one second. Power ON/OFF switch

 

EASY-TO-INSTALL — Completely factory-assembled. Only gas, water, vent and electric

 

connections need be made. Provided with drain valve.

 

FACTORY INSTALLED AND TESTED DRAFT DIVERTER — Low profile draft diverter with

 

automatic motorized flue damper to minimize standby losses.

 

ANODES — CoreGuard™ long-life, stainless steel core anode rods.

 

COMPLIANCE — All models comply with ANSI Z21.10.3 - CSA 4.3 Standards and meet or

 

exceed the thermal efficiency and/or standby loss requirements of the U.S. Department of

 

Energy and current edition of ASHRAE/IESNA 90.1.

 

LIMITED WARRANTY OUTLINE — If the tank should leak any time during the first three years,

 

under the terms of the limited warranty, A. O. Smith will furnish a replacement heater; installation,

 

labor, handling and local delivery extra. THIS OUTLINE IS NOT A WARRANTY. For complete

 

information, consult the written warranty or A. O. Smith Water Products Company. Warranty does

 

not apply to product installed outside of the United States of America or its territorial possessions

 

and Canada.

 

OTHER FEATURES

 

• Equipped with gas pressure regulator and pilot filter.

 

• Integral automatic gas shutoff system prevents excessive water temperature.

 

• CSA Certified and ASME Rated T&P relief valve.

ASME

• Maximum working pressure is 160 psi (1103 kPa) standard.

• Cathodic protection.

• Adjustable thermostat with a 120-180°F (49°C-82°C) range.

on selected models.

 

OPTIONS

 

• Power vent kits for side wall venting.

Approved to NSF

• Meets NSF Standard 5 with optional leg kit.

Standard 5

 

with Optional Leg Kit

 

Page 1 of 4

 

CANCG10000

ROUGH-IN DIMENSIONS - SIDE VIEW

Models BTRC 120-500

Gas Connection

Top View of BTRC

 

 

 

 

 

Clearance To

 

 

 

Clearance To

 

 

 

 

 

Combustibles

 

 

Non-Combustibles

Model

 

Sides & Rear

 

Top Cover

 

Sides & Rear

 

Top Cover

BTRC -120

 

 

1"

 

 

 

 

12"

 

 

 

0"

 

12"

 

 

 

 

(2.54 cm)

 

 

(30.48 cm)

 

 

(0cm)

 

(50.8cm)

BTRC -154

 

 

1"

 

 

 

 

12"

 

 

 

0"

 

12"

 

 

 

 

(2.54 cm)

 

 

(30.48 cm)

 

 

(0cm)

 

(50.8cm)

BTRC -180

 

 

1"

 

 

 

 

12"

 

 

 

0"

 

12"

 

 

 

 

(2.54 cm)

 

 

(30.48 cm)

 

 

(0cm)

 

(50.8cm)

BTRC -197

 

 

1"

 

 

 

 

12"

 

 

 

0"

 

12"

 

 

 

 

(2.54 cm)

 

 

 

(30.48 cm)

 

 

(0cm)

 

(50.8cm)

BTRC -199

 

 

1"

 

 

 

 

12"

 

 

 

0"

 

12"

 

 

 

 

(2.54 cm)

 

 

(30.48 cm)

 

 

(0cm)

 

(50.8cm)

BTRC -200A

 

 

1"

 

 

 

 

12"

 

 

 

0"

 

12"

 

 

 

 

(2.54 cm)

 

 

(30.48 cm)

 

 

(0cm)

 

(50.8cm)

BTRC -250A

 

 

2"

 

 

 

 

12"

 

 

 

0"

 

12"

 

 

 

 

(5.1 cm)

 

 

(30.48 cm)

 

 

(0cm)

 

(50.8cm)

BTRC -251(A)

 

 

2"

 

 

 

 

12"

 

 

 

0"

 

12"

 

 

 

 

(5.1 cm)

 

 

(30.48 cm)

 

 

(0cm)

 

(50.8cm)

BTRC -275A

 

 

2"

 

 

 

 

12"

 

 

 

0"

 

12"

 

 

 

 

(5.1 cm)

 

 

(30.48 cm)

 

 

(0cm)

 

(50.8cm)

BTRC -305(A)

 

 

2"

 

 

 

 

12"

 

 

 

0"

 

12"

 

 

 

 

(5.1 cm)

 

 

(30.48 cm)

 

 

(0cm)

 

(50.8cm)

BTRC -365(A)

 

 

4"

 

 

 

 

4"

 

 

 

4"

 

12"

 

 

 

(10.16 cm)

 

(10.16 cm)

 

(10.16cm)

 

(50.8cm)

BTRC -400A

 

 

3"

 

 

 

 

12"

 

 

 

0"

 

12"

 

 

 

 

(7.8 cm)

 

 

(30.48 cm)

 

 

(0cm)

 

(50.8cm)

BTRC -500A

 

 

5"

 

 

 

 

24"

 

 

 

0"

 

12"

 

 

 

 

(12.7 cm)

 

 

 

(61 cm)

 

 

(0cm)

 

(50.8cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Water Connections in Inches (NPT)

 

 

 

 

 

 

 

 

 

 

Inlet

 

 

 

 

 

 

 

Outlet

 

 

 

 

Model

 

 

Top

 

Front

 

Rear

 

Top

 

Front

Rear

 

 

BTRC-120

1.50"

 

1.50"

1.50"

1.50"

1.50"

1.50"

 

 

 

 

 

 

1.50"

 

1.50"

 

1.50"

 

1.50"

 

1.50"

1.50"

 

 

BTRC-154

1.50"

 

1.50"

1.50"

1.50"

1.50"

1.50"

 

 

 

 

 

 

1.50"

 

1.50"

 

1.50"

 

1.50"

 

1.50"

1.50"

 

 

BTRC-180

1.50"

 

1.50"

1.50"

1.50"

1.50"

1.50"

 

 

 

 

 

 

1.50"

 

1.50"

 

1.50"

 

1.50"

 

1.50"

1.50"

 

 

BTRC-197

1.50"

 

1.50"

1.50"

1.50"

1.50"

1.50"

 

 

 

 

 

 

1.50"

 

1.50"

 

1.50"

 

1.50"

 

1.50"

1.50"

 

 

BTRC-199

1.50"

 

1.50"

1.50"

1.50"

1.50"

1.50"

 

 

 

 

 

 

1.50"

 

1.50"

 

1.50"

 

1.50"

 

1.50"

1.50"

 

 

BTRC-200

1.50"

 

2.00"

2.00"

1.50"

2.00"

2.00"

 

 

 

 

 

 

1.50"

 

2.00"

 

2.00"

 

1.50"

 

2.00"

2.00"

 

 

BTRC-250

1.50"

 

2.00"

2.00"

1.50"

2.00"

2.00"

 

 

 

 

 

 

1.50"

 

2.00"

 

2.00"

 

1.50"

 

2.00"

2.00"

 

 

BTRC-251

 

NA

 

1.50"

 

1.50"

 

 

NA

 

1.50"

1.50"

 

 

 

 

 

 

NA

 

1.50"

 

1.50"

 

 

NA

 

1.50"

1.50"

 

 

BTRC-275

1.50"

 

2.00"

2.00"

1.50"

2.00"

2.00"

 

 

 

 

 

 

1.50"

 

2.00"

 

2.00"

 

1.50"

 

2.00"

2.00"

 

 

BTRC-305

 

NA

 

1.50"

 

1.50"

 

 

NA

 

1.50"

1.50"

 

 

 

 

 

 

NA

 

1.50"

 

1.50"

 

 

NA

 

1.50"

1.50"

 

 

BTRC-365

 

NA

 

1.50"

 

1.50"

 

 

NA

 

1.50"

1.50"

 

 

 

 

 

 

NA

 

1.50"

 

1.50"

 

 

NA

 

1.50"

1.50"

 

 

BTRC-400

1.50"

 

2.00"

2.00"

1.50"

2.00"

2.00"

 

 

 

 

 

 

1.50"

 

2.00"

 

2.00"

 

1.50"

 

2.00"

2.00"

 

 

BTRC-500

1.50"

 

1.50"

1.50"

1.50"

1.50"

1.50"

 

 

 

 

 

 

1.50"

 

1.50"

 

1.50"

 

1.50"

 

1.50"

1.50"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas Pressure Requirements

 

Natural Gas

Propane Gas

Max. Supply Pressure

13.8" w.c.

13.8" w.c.

Min. Supply Pressure

4.5" w.c.

11" w.c.

Manifold Pressure

3.5" w.c.

10" w.c.

 

 

 

Electrical Specifications

 

Volts

Amps

BTRC

120VAC

.7

 

 

 

BTRC with Power Venter

120VAC

3.0 FLA

 

 

 

Page 2 of 4