A.O. Smith BTH-120A, BTH-150A, BTH-199A, BTH-250A, BTH-300A User Manual

...
0 (0)
A.O. Smith BTH-120A, BTH-150A, BTH-199A, BTH-250A, BTH-300A User Manual

Commercial Gas

Water Heaters

CYCLONE® Mxi MODULATING

MODULATING BURNER ADVANCES THE CYCLONE TO HIGHER LEVELS OF EFFICIENCY

The full line of A. O. Smith Cyclone Mxi condensing water heaters has been designed to provide years of dependable service and feature industry leading technology. Models are available from 120,000 to 500,000 Btu/h and all deliver thermal efficiencies of 95% and higher. The unique helical coil heat exchanger limits weld joints for optimal service life while maximizing heat transfer.

Cyclone is the industry leader in high efficiency commercial water heating. The current Mxi modulating models adjust firing rate to the specific demand further increasing efficiency and money savings.

INTELLIGENT CONTROL SYSTEM WITH LCD DISPLAY AND iCOMM CONNECTIVITY

Exclusive A. O. Smith designed touch display control system

Provides detailed water heater status information

Precise temperature control adjustable from 90 to 180 degrees

Built-in diagnostics

Run history information

Cyclone® Mxi Modulating water heaters are compatible with the iCOMMremote monitoring system. Call 1.888.928.3702 for information.

COMING SPRING 2017

Remote monitoring capability utilizing the iCOMM app. Wi-Fi connectivity kit requited for models 120-250, standard on models 300-500.

SUBMERGED COMBUSTION CHAMBER, WITH HELICAL HEAT EXCHANGER COIL

Positioned in center of tank, surrounded by water to virtually eliminate radiant heat loss from chamber

Direct spark ignition

Spiral heat exchanger keeps hot burner gases swirling, uses centrifugal force to maximize efficiency of heat transfer to water in tank

Spiral heat exchanger reduces lime scale from forming on water-side surfaces, which maintains energy efficiency over time

POWERED ANODES STANDARD ON ALL

MODELS

Provides long-lasting tank protection in varying water conditions

Powered anodes are non-sacrificial

Automatically adjusts output needed to properly protect the tank

PERMAGLAS® ULTRA COATGLASS LINING

Glass coating is applied using a liquid slush coating technique to ensure uniform coating

Heat exchanger coil is glassed both externally and internally for optimum protection

MECHANICAL VENTING VERSATILITY

Conventional power venting or direct venting

Vents vertically or through a sidewall

Front located exhaust and condensate connections allow for easy install and access

Vents with low cost PVC Schedule 40 intake and exhaust pipe. Approved for optional CPVC Schedule 40, Polypropylene and AL29-4C stainless steel vent materials

Direct-vent intake and exhaust pipe can terminate separately outside building or through single opening, using concentric vent assembly

Canadian installations require ULC S636 PVC/ CPVC, ULC S636 Polypropylene and AL29-4C stainless steel pipe for intake and exhaust

HIGH EFFICIENCY MODULATING PREMIX POWERED BURNER

Down-fiired pre-mix burner provides optimum efficiency and quiet operation

Top-mounted burner position prevents condensation from affecting burner operation

3-YEAR LIMITED TANK / 1-YEAR LIMITED PARTS WARRANTY

For complete warranty information, consult written warranty or go to hotwater.com.

BTH-120(A) THROUGH BTH-500(A)

MODEL SHOWN:

BTH-199(A) SERIES 300/301

© April 2017 A. O. Smith Corporation. All Rights Reserved

Page 1 of 6

www.hotwater.com | 800-527-1953 Toll-Free USA | A. O. Smith Corporation | 500 Tennessee Waltz Parkway | Ashland City, TN 37015

AOSCG10210

Commercial Gas

Water Heaters

OTHER FEATURES:

SPACE-SAVING DESIGN FOR INSTALLATION FLEXIBILITY

Easy-to-remove top cover for convenient access to serviceable parts

0˝ installation clearances on sides and rear, 1-1/2˝ installation clearance on top

Handhole cleanout allows easy access to tank interior for cleaning

0˝ clearance to combustibles, approved for installation on combustible floors

CODES AND STANDARDS

CSA certified and ASME rated T&P relief valve

Maximum hydrostatic working pressure: 160 psi

All models are design certified by Underwriters Laboratories (UL), Inc., to ANSI Z21.10.3 - CSA 4.3 Standards

Meets the thermal efficiency and standby loss requirements of the U.S. Department of Energy and current edition ASHRAE/IES 90.1

Design Certified by Underwriters Laboratories to NSF standard 5 for 180°F (62°C) water

Complies with SCAQMD Rule 1146.2 and other Air Quality Management Districts with similar requirements for ultra low-NOx emissions

ASME tank construction optional on 120-500 model sizes

VENT REQUIREMENTS FOR BTH 120(A) - 250(A)

Number of 90°

3 Inch Pipe

4 Inch Pipe

Maximum Feet

Maximum Feet

Elbows Installed

 

(Meters)

(Meters)

One (1)

45 feet (13.7 meters)

115 feet (35 meters)

Two (2)

40 feet (12.2 meters)

110 feet (33.5 meters)

Three (3)

35 feet (10.7 meters)

105 feet (32 meters)

Four (4)

30 feet (9.1 meters)

100 feet (30.5 meters)

Five (5)

N/A

95 feet (29 meters)

Six (6)

N/A

90 feet (27.4 meters)

VENT REQUIREMENTS FOR BTH 300(A) - 500(A)

Number of 90°

4 Inch Pipe

6 Inch Pipe

Maximum Feet

Maximum Feet

Elbows Installed

 

(Meters)

(Meters)

One (1)

65 feet (19.8 meters)

115 feet (35 meters)

Two (2)

60 feet (18.2 meters)

110 feet (33.5 meters)

Three (3)

55 feet (16.8 meters)

105 feet (32 meters)

Four (4)

50 feet (15.2 meters)

100 feet (30.5 meters)

Five (5)

45 feet (13.7 meters)

95 feet (29 meters)

Six (6)

40 feet (12.2 meters)

90 feet (27.4 meters)

GAS PRESSURE REQUIREMENTS

Model Number

Manifold Pressure

Minimum Supply Pressure

Maximum Supply Pressure

 

 

 

 

 

 

Natural Gas

Propane Gas

Natural Gas

Propane Gas

Natural Gas

Propane Gas

 

 

 

 

 

 

 

 

BTH-120(A)

0"W.C. (0 kPa)

0"W.C. (0 kPa)

3.5"W.C. (1.10 kPa)

8.5"W.C. (2.12 kPa)

14"W.C. (3.49 kPa)

14"W.C. (3.49 kPa)

 

 

 

 

 

 

 

BTH-150(A)

0"W.C. (0 kPa)

0"W.C. (0 kPa)

3.5"W.C. (1.10 kPa)

8.5"W.C. (2.12 kPa)

14"W.C. (3.49 kPa)

14"W.C. (3.49 kPa)

 

 

 

 

 

 

 

BTH-199(A)

0"W.C. (0 kPa)

0"W.C. (0 kPa)

3.5"W.C. (1.10 kPa)

8.5"W.C. (2.12 kPa)

14"W.C. (3.49 kPa)

14"W.C. (3.49 kPa)

 

 

 

 

 

 

 

BTH-250(A)

0"W.C. (0 kPa)

0"W.C. (0 kPa)

3.5"W.C. (1.10 kPa)

8.5"W.C. (2.12 kPa)

14"W.C. (3.49 kPa)

14"W.C. (3.49 kPa)

 

 

 

 

 

 

 

BTH-300(A)

0"W.C. (0 kPa)

0"W.C. (0 kPa)

4.8"W.C. (1.19 kPa)

8.5"W.C. (2.12 kPa)

14"W.C. (3.49 kPa)

14"W.C. (3.49 kPa)

 

 

 

 

 

 

 

BTH-400(A)

0"W.C. (0 kPa)

0"W.C. (0 kPa)

4.8"W.C. (1.19 kPa)

8.5"W.C. (2.12 kPa)

14"W.C. (3.49 kPa)

14"W.C. (3.49 kPa)

 

 

 

 

 

 

 

BTH-500(A)

0"W.C. (0 kPa)

0"W.C. (0 kPa)

4.8"W.C. (1.19 kPa)

8.5"W.C. (2.12 kPa)

14"W.C. (3.49 kPa)

14"W.C. (3.49 kPa)

 

 

 

 

 

 

 

Depending on the installed equivalent length, and/or the number of appliances connected, the supply gas line size may need to be increased beyond the minimum required size.

Page 2 of 6

AOSCG10210

Loading...
+ 4 hidden pages