Van Air Systems PD-7 User Manual

INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
PRESSURE DIFFERENTIAL GAUGE KIT
RECOMMENDED FOR INSTALLATION ON VME SERIES MIST ELIMINATORS
SPECIFICATIONS
MAX. OPERATING PRESSURE ..................... 3000 PSIG
MAX. OPERATING TEMPERATURE .............. 175
OPERATING RANGE ...................................... 0-5 PSID
DIMENSIONS ................... 4"L, 1-1/2"W, 2-1/16"H
PRESSURE PORT CONNECTIONS .............. 1/8" NPT
INSTALLATION
FIGURE 1 INSTALLATION
DECEMBER 2004
P/N 32-0247-A
FOR
PD-7
O
F
WARNING
CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLING THE PRESSURE DIFFERENTIAL KIT.
MAKE SURE THAT THE COMPONENT OR PIPING IS DEPRESSURIZED BEFORE INSTALLING THE PRESSURE DIFFERENTIAL KIT.
Completely depressurize the piping and component that the kit is to be installed on.
Figure 1 shows a typical assembly/installation of the PD-7 series pressure differential gauge on a VAN AIR VME series Mist Eleminator.
Mount the PD-7 on the mounting bracket. Use the fasteners provided with the kit. Mount the kit to the desired surface. The VME vessel has a angle bracket on the front for the installation of the PD-7 and bracket.
MAINTENANCE
MAINTENANCE IS PER THE GAUGE INSTRUCTION SHEET.
To ensure an accurate reading, make sure that both tubing lines
IMPORTANT
to the PD-7 are equal in length. Use as few as possible bends in the tubing lines.
Install the necessary tubing from the inlet side of the vessel or piping to be measured to the HIGH PRESSURE port of the PD-7. Use the tubing and fittings as shown in FIGURE 1. Use pipe sealant on all threaded pipe connections.
Complete the tubing connection from the outlet side of the vessel or piping to be measured to the LOW PRESSURE port of the PD-7. Use the tubing and fittings as shown in FIGURE 1. Use pipe sealant on all threaded pipe connections.
Loading...
+ 1 hidden pages