The tekmar Snow Detector & Melting Control 662 is a microprocessor-based control which,
OUTSIDE
FC
Supply
Return
Slab
Boiler Return
To change between
°F and °C, press and
hold for 1 sec.
Item
Snow Detector & Melting Control 662
Mixing Operation
Power
Remote
CWCO
WWCO
Idling
Melting
Maximum
Water
Target ∆T
Actual ∆T
% Output
∆T
Maximum
Minimum
Supply
Return
Pump 1
Pump 2
Closing
Opening
Boiler
Warning
R
LR 58223
NRLT/C
together with the Snow/Ice Sensor 090, activates and controls the rate of heat delivery to a snow
melt system. This versatile control has three modulating outputs to control the heat delivery for
most pump and/or valve arrangements. Protection of both the snow melt slab and the boiler is
achieved through several safety features. Faster pick up times are also ensured through a
viscosity compensation function which optimizes the rate of heat delivery to the slab during start
up. The 662 combines all the necessary features to make snow melting safe and trouble free.
Sequence of Operationpg. 2
Installation . . . . . . . . . . pg. 3
Settings . . . . . . . . . . . . pg. 7
Display Operation . . . . pg. 8
D 662
07/99
Testing . . . . . . . . . . . . . pg. 9
Error Messages . . . . . . pg. 10
Technical Data . . . . . . . pg. 12
Limited Warranty. . . . . pg. 12
Relative Energy
usage in ∆T x Hours
Boiler return
temperature
Target slab ∆T
Actual slab ∆T
Supply temperature to slab
Slab surface temperature
Boiler pump is on
System pump is on
Valve is
opening/closing
LCD display
item select
Boiler operating
Fault warning
Output:
Melt relay is closed
when control is
in melting mode.
Output:
Warning relay is
activated if sensor
fault is detected
Water is detected
by the sensor
Current % Heat
Output to slab
Slab
Supply
Actual ∆T
Target ∆T
The Snow/Ice Sensor is installed in a hostile environment.
It should be cleaned and checked on a regular basis.
Snow Detector & Melting Control 662
Floating / Variable Speed / 4-20 mA
Use Nº 20 AWG or larger copper conductors rated for at least 75°C / 300V
1
3
2
4
Warning
Melt
Slab is warm enough,
no snow melting is required
Snow detected:
control is in
Melting mode
To change between
°F and °C, press and
hold for 1 sec.
Item
5
78
6
Com
Power
P1
Pmp
Pmp
N
Pmp
L
OUTSIDE
FC
% Output
Usage (∆T x hrs)
Boiler Return
9
10
P2
Var
Pmp
Remote Enable
Signal present
1000Ω
1112131415
4-20
Boiler
+–
120 Vac power
supply is on
Power
Remote
WWCO
Melting
Water
Maximum
Supply
Pump 1
Opening
Boiler
Warning
R
LR 58223
NRTL/C
16
Com
4-20
Opn
Mix
Mix
Control is limiting supply
temperature to Max.
Supply setting
Power
System Pumps
Variable Pump
Mix Relays
Other Relays
Enclosed Energy Management Equipment
Manufactured
in Canada by
CWCO
Idling
Maximum
∆T
Minimum
Return
Pump 2
Closing
17
18 19 202122 23
Cls
Red
Mix
Sen
39°F
3444
Melting
Test
30°F
10
∆T Max.
Do not apply power here
Brn
Blu
Yel
Blk
Sen
Sen
Sen
Sen
Weather is too cold,
snow melting is off
Control is in
Idling mode
120 V ac 50/60 Hz 300 VA
120 V ac 6 A 1/3 hp, pilot duty 240 VA 2 A
120 V ac 50/60 Hz 2.2 A 1/6 hp, internally fused
24 V ac 10 A, pilot duty 48 VA 2 A
120 V ac 10 A 1/3 hp, pilot duty 240 VA 2 A
29°F
24
Off35
Idling
Surface
150°F
100200
Max. Supply
0°F
-20
50
Off
CWCO
24 25
Com
Bret
Rem
Sen
Sen
En
26
Com
Sen
25
27 28
Ret
Sen
2094
1234567
50 %
2080
Sensitivity
100°F
60
Off150
Min. Boil Return
130 sec
30
Motor Speed /
Pump Response
29
Sup
Out
Sen
Sen
Control is limiting heat
output to Max ∆T setting
Control is maintaining
Min. boiler return temperature
Desired slab surface
temperature during
melting mode
Desired slab surface
temperature during
idling mode
H11002
Input: Outdoor
Sensor Sensitivity to
water
Test button to initiate
test sequence
Maximum Supply
temperature
Min. Boiler Return
temperature
Max. Temperature
drop across slab
Cold Weather Cut-off
temperature
Motor Speed setting
Terminal Plugs
Sensor 070
(Included)
Date
S/N
230
tekmar
motor
Output: Turn on
system pump P1
Output: Turn on
boiler pump P2
120 Vac
Power Supply
Output:
operate pump at
varying speeds
Output:
Turn on boiler
OR
Output: control
4-20 mA device
M
M
Output: control
Floating Action
Input: System Supply
Sensor 071
Input: System Return
Sensor 071
Input: Boiler Return
Sensor 071
Input: Remote Enable
Signal.
OR
Input: Slab Sensor 072
Detects slab temperature
Input: Snow/Ice Sensor 090 installed with Sensor Socket 091.
Both of these components must be ordered separately.
only. Does not detect Snow/Ice.
(Included)
(Included)
(Included)
(Optional)
(Included)
(Optional)
In order for this control to operate effectively, it must be installed in a well designed melting system. The Application Brochures A 662
provide a series of schematics which can be used with this control. Any deviations from these drawings must be discussed with a tekmar
factory representative to ensure that system performance is not compromised. The application drawings are not final designs - each
component within the system must be correctly sized for the control to operate effectively. It is important that the sequence of operation
and the application drawings for this control are fully understood to ensure that the control selected is compatible with its intended use.
Sequence of Operation
Powering up the control
After the Snow Detector & Melting Control 662 is powered up, the red status lights and the LCD segments are turned on for 7 seconds.
The control then displays the “Outdoor” temperature.
Melting Mode
Operation using a Snow/ Ice Sensor 090 - The control continually monitors the Snow/Ice Sensor
090. When water is detected, the “Water” light turns on and if the control is not in WWCO or
CWCO (see page 3 for an explanation of these terms), melting mode begins.
Operation using a Remote Enable - Melting mode can also be initiated if a remote enable signal
is present (terminals Com Sen and Rem Sen shorted together) and the control is not in WWCO
or CWCO. The remote enable is typically used with multiple Snow Melting Controls and Snow/
Ice Sensors. It can be also be used to manually turn the melting system on by wiring a switch
between the remote terminals. A remote enable switch must be installed when a Slab
Opening light is
on if the melting
system requires
more heat
Sensor 072 is used as this sensor cannot detect water.
Once the control is in melting mode, the Melting relay and boiler pump (relay P2 Pmp) are turned
on. After a 4 second delay, the system pump (relay P1 Pmp) is turned on and after 8 seconds, heat is applied to the snow melt system
through either a variable speed pump, a floating action mixing valve or a 4-20 mA device. The opening and closing lights indicate
whether the control is increasing or decreasing the heat applied to the snow melt system. Essay E 021 compares the use of these
devices for controlling the system temperature and also discusses the sizing and operation of the variable speed pump. Information
on floating action can be found in Essay E 000. The 4-20 mA, variable speed pump and mixing valve outputs operate simultaneously.
The 4-20 mA output can therefore be used to provide a remote readout of the pump or valve operation. The control remains in melting
mode until no water is detected for at least 30 seconds and the slab is up to temperature for at least 30 minutes. Cold Weather or
Warm Weather Cut Off can also terminate melting mode. When the control exits melting mode the boiler and system pumps are
operated for an additional 90 seconds to purge the boiler. If the control switches from melting to idling mode, the boiler is not purged.
Idling Mode
When the melting system starts off from a cold temperature, the time required for the slab to reach
“Melting” temperature can be excessive. To decrease this start up time, the slab can be maintained
at an “Idling” temperature until melting is required. The idling feature is also useful for preventing
frost and light ice formation. When the control is in idling mode, control operation is similar to melting
mode except the “Melting” and “Water” lights are off and the “Idling” light is on.
Opening light is
on if the melting
system requires
more heat
Snow melt system protection features
The 662 control has several features for protection of the snow melt system:
- to protect the slab from cracking due to thermal stresses, the control limits the rate of heat applied to the slab through a “∆T Max”
setting. The ∆T represents the difference between the slab supply and return fluid temperatures which are measured by the control.
If this temperature difference approaches the “∆T Max” setting, the “Maximum ∆T” light turns on and the control operates the valve
or pump to maintain the ∆T at the “∆T Max” setting.
- to protect the piping and other components in the system, the control limits the supply temperature to a “Max. Supply” setting. When
the melt system supply temperature approaches the maximum supply setting, the “Maximum Supply” light turns on and the control
operates the valve or pump to reduce the supply temperature.
- to prevent the flue gases in the boiler from condensing, the control limits the boiler return temperature to a “Min. Boil. Return” setting.
When the boiler return temperature approaches this setting, the “Minimum Return” light turns on and the control operates the valve
or pump to increase the boiler return temperature.
∆T compensation for changes in fluid viscosity
Glycol solutions used in snow melt systems have widely varying viscosities between high and low temperatures. As the glycol solution
temperature drops, viscosity increases causing a reduction in flow rate. This reduction in flow rate reduces the rate of heat output
if the fluid temperature drop across the slab (∆T) remains constant. To compensate for this, the control increases the Maximum ∆T.
This compensation is only applied when the fluid temperature is below 30°F, which is the temperature at which the viscosity of a typical
40% ethylene glycol / 60% water solution starts to increase significantly. The compensation feature is designed for fluids containing
40% ethylene glycol or 30 % propylene glycol; however, if the glycol percentage in the solution is lower than these values, the quality
of heat regulation is not significantly affected. When the control is compensating for viscosity changes, the “Maximum ∆T” light flashes.
Ramping the ∆T during melting system start up
When the control turns on the melting system, the “Target ∆T” is slowly ramped up to the maximum ∆T to prevent thermal shock of
the slab. If the temperature of the fluid returning to the boiler (source) is sufficient, the ramping time is less than 17 minutes. If the
heat source is not dedicated to snow melting and there are other heat demands on the source, the ramping time may be longer.
2
Power
Remote
WWCO
Melting
Water
Maximum
Supply
Pump 1
Opening
Boiler
Warning
Power
Remote
WWCO
Melting
Water
Maximum
Supply
Pump 1
Opening
Boiler
Warning
If a remote signal is
present, the Remote
light turns on
CWCO
Idling
Maximum
∆T
Minimum
Return
Pump 2
Closing
Closing light is on
if the melting
system requires
less heat
CWCO
Idling
Maximum
∆T
Minimum
Return
Pump 2
Closing
Closing light is on
if the melting
system requires
less heat
Warm Weather Cut Off (WWCO)
n
If the “Slab” and “Outdoor” temperatures rise above the “Melting” temperature, heating the slab is
no longer required. The control therefore shuts down the melting system and enters WWCO.
During WWCO the “Closing” light remains on continuously and the heat supplied through the valve
or variable speed pump is reduced to zero. When the “Outdoor” or “Slab” temperature drops below
the “Melting” temperature, the control exits WWCO and continues with normal operation.
Cold Weather Cut Off (CWCO)
Maintaining the slab at a “Melting” or “Idling” temperature in extremely cold weather can be
expensive and may even be impossible. When it does snow at these colder temperatures, the snow
is usually dry, light and less slippery. The control therefore turns the melting system off when the
“Outdoor” temperature drops below the “CWCO” setting. During CWCO the “Closing” light remains
on continuously and the heat supplied through the valve or pump is reduced to zero. The heater
If a remote
signal is
present, the
Remote light
turns on
If water is
detected the
Water light
turns on
Power
Remote
WWCO
Melting
Water
Maximum
Supply
Pump 1
Opening
Boiler
Warning
Note:
In Cold Weather Cut
Off, the CWCO light is
on and the WWCO
light is off
CWCO
Idling
Maximum
∆T
Minimum
Return
Pump 2
Closing
Closing light is o
to turn off the
melting system
in the Snow/ Ice Sensor 090 is kept on during CWCO until the control detects snow. If snow is detected, the heater is turned off but
the control retains the snow detected information. When the outdoor temperature rises above the “CWCO” temperature, the control
exits CWCO and if the Snow/Ice Sensor 090 detected snow during CWCO, the control initiates melting mode.
Warning Light and Relay
Pump 2
If a sensor fault occurs, the Warning relay and light are turned on and an error message is given. The look-up
table provided on pages 10 and 11 can be used to determine which sensor has the fault.
Pump 1
Opening
Boiler
Warning
Closing
Exercising of the Pumps and Valves
To prevent the pumps or valves from seizing after long inactive periods, the pumps
and valves are operated after every 3 days of no operation. The Pump P1 and Pump
P2 relays are turned on for 20 seconds and the mixing valve or variable speed pump
output is run fully open and/or fully closed. During exercising, the LCD screen
alternates between two special characters as illustrated in the diagram.
Slab
Supply
Actual ∆T
Target ∆T
% Output
Usage (∆T x hrs)
Boiler Return
Slab
Supply
Actual ∆T
Target ∆T
% Output
Usage (∆T x hrs)
Boiler Return
Installation
Caution
Improper installation and operation of this control could result in damage to equipment and possibly even personal
injury. It is your responsibility to ensure that this control is safely installed according to all applicable codes and
standards. This electronic control is not intended for use as a primary limit control. Other controls that are intended
and certified as safety limits must be placed into the control circuit.
Step OneGetting ready
Check the contents of this package. If any of the contents listed are missing or damaged, please refer to the Limited Warranty
and Product Return Procedure on the back of this brochure and contact your wholesaler or tekmar sales agent for assistance.
Type 662 includes:
• One Snow Detector & Melting control 662 • One Outdoor Sensor 070
• Three Universal Sensors 071 • One Slab Sensor 072
• One Data Brochure D 662 • Application Brochures A 662 • One Data Brochure D 001
Other information available:
• Essay E 021 • Essay E 000 • Essay E 600
Read Brochures A 662 and select the correct Application for your job.
Note: This control can be installed with EITHER a Snow/Ice Sensor 090 and Sensor Socket 091 OR a Slab Sensor 072. The
Snow/Ice Sensor 090 and Sensor Socket 091 are not included with the type 662 and must be ordered separately.
Carefully read the details of the Sequence of Operation sections in all applicable brochures to ensure that you have chosen the
proper control and understand its functions within the operational requirements of your system.
Step TwoMounting of the base
The control should be removed from its base by pressing down on the release clip in the wiring chamber and sliding upwards
on the control. The base is then mounted in accordance with the instructions in the Data Brochure D 001.
Step ThreeRough-in Wiring
All electrical wiring terminates in the control base wiring chamber. It has standard 7/8" (22mm) knock-outs that accept all common
wiring hardware and conduit fittings. Before breaking out the knock-outs, check the wiring diagram and select those sections of
the chamber with common voltages. Do not allow the wiring to cross over sections as safety dividers, installed later, prevent this.
Power should not be applied to any of the wires during the rough-in wiring stage.
•
EITHER:
base.
•
OR:
See page 5 for very important details on sensor location and installation.
• Run the wiring from the other system components to the base.
• Run 120 V ac to the power terminals on the control.
• Multi-strand 16 AWG wire is recommended for the 120 V ac wiring due to its superior flexibility and ease of installation into the
terminal.
Install the Snow/Ice Sensor 090 according to the instructions in Data Brochure D 090 and run the wiring back to the
See Data Brochure 090 for very important details on sensor location and installation.
Install the Slab Sensor 072 according to the instructions in the Data Brochure D 001 and run the wiring back to the base.
Use a clean 120 V ac power source to ensure proper operation.
3
Step FourElectrical connections to the control
Power and output connections
• The installer should test to confirm no voltage is present at any of the wires.
• Install the control back into the base by sliding it down until it snaps in firmly.
• Connect the 120 V ac power supply to terminals
Melt Output
• Connect the melting device to terminals
Melt
(dry) relay contact inside the control which closes when the control enters melting mode. The
most common devices to be enabled by the 662 are pumps, heating devices or other controls.
Warning
• If desired, connect a warning device to terminals
a dry relay contact inside the control which closes when there is a sensor or wiring fault.
Caution
: The 662 is an operating control and is not certified as a safety device. If safety
considerations are critical, a separate alarm system must be installed.
Pump Power Supply
• Terminal
and
Com Pmp
P2 Pmp
(7) is the common power supply terminal for both terminals
(9).
• If the pumps P1 and P2 are operated from the same 120 V ac power supply as the control,
connect the terminal
Power L (6)
to the terminal
• If a separate power supply is required for P1 and/or P2, contact tekmar for details.
System Pump P1
• Connect the System Pump to terminals
Power N — P1 Pmp
to a dry relay contact which closes when the control requires System Pump operation.
Boiler Pump P2
• Connect the Boiler Pump to terminals
Power N — P2 Pmp
to a dry relay contact which closes when the control requires Boiler Pump operation.
Variable Speed
• Connect the variable speed pump to terminals
operated by this circuit must be permanent capacitor, impedance protected with a locked rotor
current less than 2.2 amps. The Snow Detector & Melting Control 662 has an internal 2.5 amp
fuse for overload protection.
This fuse is not field replaceable.
return and repair procedures if this fuse is blown.
Boiler
• Connect the boiler or the boiler control to the terminals
lead to a dry relay contact which closes when the control requires boiler operation.
4-20 mA Device
• Connect the positive 4 - 20 mA lead to terminal
resistance allowed in the 4 - 20 mA circuit is 1000 Ω. The 4 - 20 mA output can be converted to a voltage output by connecting
a resistor between terminals 13 and 14.
Power N — L
(5 and 6).
(1 and 2). These terminals lead to an unpowered
Warning
Com Pmp (7)
(3 and 4). These terminals lead to
.
(5 and 8). These terminals lead
(5 and 9). These terminals lead
Power N —Var Pmp
(5 and 10).
Contact tekmar for details on
Boiler
(11 and 12). These terminals
4-20 +
(13) and the negative 4 - 20 mA lead to terminal
P1 Pmp
Pumps
(8)
11
Boiler
56
Power
N L
5
Power
N L
Power
N L
Power
N L
Power
N L
13
12
4-20
+
4 - 20 –
89
7
Com
P1
Pmp
Pmp
2
1
Melt
2
1
Melt
89
7
6
Com
P1
Pmp
Pmp
7
Com
Pmp
7
Com
Pmp
7
Com
Pmp
8
P1
Pmp
8
P1
Pmp
8
P1
Pmp
65
65
65
14
Com
4-20
Mix
–
(14). Maximum
10
Var
P2
Pmp
Pmp
34
Warning
34
Warning
10
Var
P2
Pmp
Pmp
9
10
Var
P2
Pmp
Pmp
10
9
Var
P2
Pmp
Pmp
9
10
Var
P2
Pmp
Pmp
1615
17
Opn
Cls
Mix
Mix
1413
1
4-20
C
4-20
–
+
M
+
–
4 - 20 mA
Actuating Motor
Connection to Operate
a 4 - 20 mA Device
Operate a 1 - 5 Vdc or 2 - 10 Vdc Device
1413
1
4-20
4-20C
–
+
M
500 Ω resistor
4-20 mA converted
to 2-10 Vdc output
OR
250 Ω resistor
4-20 mA converted
to 1-5 Vdc output
+
–
1-5 or 2-10 Vdc
Actuating Motor
Converting the 4 - 20 mA Output to
Floating Action Mixing Valve
• Connect one side (R) of a 24 V ac transformer to terminal
• Connect the (C) side of the transformer to terminal
N/C
Com Mix
(15).
on the tekmar 010 Actuating Motor.
For other makes of actuating motors, refer to the manufacturers' installation instructions.
• Connect the OPEN terminal of the Actuating Motor (CCW) to the terminal
Opn Mix
the control. This terminal leads to a relay contact which closes to provide 24 V ac to open
the valve.
• Connect the CLOSE terminal of the Actuating Motor (CW) to the terminal
Cls Mix
the control. This terminal leads to a relay contact which closes to provide 24 V ac to close
the valve.
4
(16) on
(17) on
14
13
1
4-20
C
4-20
–
+
M
66.5 Ω resistor
237 Ω resistor
B
R
W
0 - 135Ω "Slidewire"
Actuating Motor
Converting the 4 - 20 mA Output to
Operate a 0 - 135Ω Actuating Motor
13
12
24Vac
4-20
R
C
14
4-20
+
–
11
Boiler
Separate Class II
Transformer
L
N
15
Com
Mix
16
17
Opn
Cls
Mix
Mix
N
12
C
M
type 010
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.