Installation Precautions - Adherence to the following will aid in problem-free
installation with long-term reliability: WARNING - Several different sources of power
can be connected to the fire alarm control panel. Disconnect all sources of power
before servicing. Control unit and associated equipment may be damaged by
removing and/or inserting cards, modules, or interconnecting cables while the unit is
energized. Do not attempt to install, service, or operate this unit until manuals are
read and understood. CAUTION - System Re-acceptance Test after Software
Changes: To ensure proper system operation, this product must be tested in
accordance with NFPA 72 after any programming operation or change in site-specific
software. Re-acceptance testing is required after any change, addition or deletion of
system components, or after any modification, repair or adjustment to system
hardware or wiring. All components, circuits, system operations, or software functions
known to be affected by a change must be 100% tested. In addition, to ensure that
other operations are not inadvertently affected, at least 10% of initiating devices that
are not directly affected by the change, up to a maximum of 50 devices, must also be
tested and proper system operation verified. This system meets NFPA requirements
for operation within the range of 0°C-49°C (32°F-120°F) or humidity within the range
of 10%-93% at 30°C (86°F) noncondensing. However, the useful life of the system's
standby batteries and the electronic components may be adversely affected by
extreme temperature ranges and humidity. Therefore, it is recommended that this
system and its peripherals be installed in an environment with a normal room
temperature of 15-27º C/60-80º F. Verify that wire sizes are adequate for all
initiating and indicating device loops. Most devices cannot tolerate more than a 10%
I.R. drop from the specified device voltage. Like all solid state electronic devices,
this system may operate erratically or can be damaged when subjected to lightning
induced transients. Although no system is completely immune from lightning
transients and interference, proper grounding will reduce susceptibility. Overhead or
outside aerial wiring is not recommended, due to an increased susceptibility to
nearby lightning strikes. Consult with the Technical Services Department if any
problems are anticipated or encountered. Remove DC power prior to removing or
inserting circuit boards. Failure to do so can damage circuits. Remove all electronic
assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When
possible, make all cable entries from the sides or rear. Before making modifications,
verify that they will not interfere with battery, transformer, or printed circuit board
location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may
damage threads, resulting in reduced terminal contact pressure and difficulty with
screw terminal removal. Fire alarm control panels contain static-sensitive
components. Always ground yourself with a proper wrist strap before handling any
circuits so that static charges are removed from the body. Use static suppressive
packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and programming manuals.
These instructions must be followed to avoid damage to the control panel and
associated equipment. FACP (Fire Alarm Control Panel) operation and reliability
depend upon proper installation.
Equipment used in the system may not be technically compatible with the control. It
is essential to use only equipment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central
monitoring station may be out of service or temporarily disabled. The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices
and system wiring should be tested and maintained by professional fire alarm
installers following written procedures supplied with each device. System inspection
and testing should be scheduled monthly or as required by national and/or local fire
codes. Adequate written records of all inspections should be kept.
Silent Knight Fire Product Warranty and Return Policy
Manufacturer Warranties and Limitation of Liability
Model SK-FFT Basic Operating Instructions
547112
Section 1
Overview
An SK-FFT Fire Fighter Telephone System provides supervision, annunciation, and
control for local and remote telephone handsets. The SK-FFT with keypad, provides
indications of phone activation, and corresponding trouble conditions. Additionally, up
to 48 telephone circuits can be annunciated at the SK-FFT by connecting the FFT-24
zone expander.
1.1Features
• One Form-C trouble relay:
System Trouble Relay - TB6
• SK-FFT Fire Fighter Telephone module for control and annunciation of up to 48
remote telephone jacks
•A maximum of 10 Fire Fighter Remote Handsets (FFT-RHS) can be used at one
time to communicate over the telephone circuit connected to the SK-FFT
•Fire Fighter Phone Jack (FFT-FPJ) provides a plug-in location for the FFT-RHS
•Single Telephone Station (FFT-STS)
•Fire Fighter Handset Cabinet (FFT-HSC) is used to store ten Fire Fighter
Handsets (FFT-RHS)
•System Status LEDs
•Supports a single FFT-24 zone expander
547111-1
SK-FFT Installation and Operation Manual
1.2Optional Accessories
This manual also contains information on how to install the following compatible
accessories with the FFT series equipment:
Model NumberDescription
FFT-2424 Zone Expander
FFT-FPJRemote Phone Jack
FFT-RHSFire Fighters Remote Hand Set
FFT-HSCFire Fighters Handset Cabinet
FFT-STSRSingle Telephone Station Recessed
FFT-STSSSingle Telephone Station Surface Mount
FFT-BGKBreak Glass Kit for FFT-STS
SK-MinimonAddressable Mini-Monitor Module
SK-ISOSLC Line Isolation Module
1.3Agency Requirements
The SK-FFT has the same requirements as the main control panel. These
requirements are listed in Silent Knight addressable FACP Installation Manuals.
Silent Knight Addressable FACP Installation Manuals can be found on Silent Knight’s
web site at www.silentknight.com.
1.4About This Manual
This manual is intended to be a complete reference for all installation and operations
tasks for the SK-FFT. Silent Knight Installation Manuals can be found on Silent
Knight’s web site at www.silentknight.com.
Please let us know if the manual does not meet your needs in any way. We value
your feedback!
1.5How to Contact Silent Knight
If you have a question or encounter a problem not covered in this manual, contact
Silent Knight Technical Support at 800-446-6444.
To order parts, contact Silent Knight Sales at 800-328-0103.
1-254711
Overview
Limitations of Fire Alarm Systems
Requirements and recommendations for proper use of fire alarm systems including smoke detectors and other fire alarm devices:
•To keep your fire alarm system in excellent working order, ongoing maintenance is
required per the manufacturer’s recommendations and UL and NFPA standards.
At a minimum the requirements of Chapter 14 of NFPA 72, 2010 Edition shall be
followed. A maintenance agreement should be arranged through the local
manufacturer’s representative. Maintenance should be performed annually by
authorized personnel only.
The most common cause of an alarm system not functioning when a fire occurs is
inadequate maintenance. As such, the alarm system should be tested weekly to
make sure all sensors and transmitters are working properly.
547111-3
SK-FFT Installation and Operation Manual
1-454711
Section 2
Before you Begin Installing
This section of the manual is intended to help you plan your tasks to complete the
installation. Please read this section thoroughly, especially if you are installing a SKFFT for the first time.
2.1Environmental Specifications
It is important to protect the SK-FFT control panel from water. To prevent water
damage, the following conditions should be AVOIDED when installing the units:
•Do not mount directly on exterior walls, especially masonry walls (condensation)
•Do not mount directly on exterior walls below grade (condensation)
•Protect from plumbing leaks
•Protect from splash caused by sprinkler system inspection ports
•Do not mount in areas with humidity-generating equipment (such as dryers,
production machinery)
When selecting a location to mount the SK-FFT, the unit should be mounted where it
will NOT be exposed to temperatures outside the range of 0°C- 49°C (32°F-120°F) or
humidity outside the range of 10% - 93% at 30°C (86°F) noncondensing.
2.2Preventing Water Damage
Water damage to the fire fighters phone system can be caused by moisture entering
the cabinet through the conduits. Conduits that are installed to enter the top of the
cabinet are most likely to cause water problems. Installers should take reasonable
precautions to prevent water from entering the cabinet. Water damage is not covered
under warranty.
2.2.1Removing the SK-FFT Assembly from the Housing
If it should ever be necessary to remove the control panel assembly from the cabinet
for repair, do so by removing the screws that hold the control panel in to the cabinet.
Do not attempt to disassemble the circuit boards.
547112-1
SK-FFT Installation and Operation Manual
JumpStart
Accept
Connector for FFT-24
Status LED’s
Local
Handset
PZT
Phone In
Phone Out
SLC IN
SLC Out
Mounting
stud
Mounting stud
Supervised
Power
Limited
All circuits inherently
power limited except the
trouble relay
DIP Switch
Not
Used
DC
Power
Non Power
Limited
Mounting
stud
Mounting stud
Mounting stud
Mounting stud
Power Status
LED
2.3SK-FFT Board Layout
Trouble
Relay
Figure 2-1 Back view of SK-FFT
Figure 2-1 shows the circuit board that attaches to the cabinet. If you should need to
remove the board assembly for repair, remove the seven mounting nuts which hold
the assembly in the cabinet. Then lift the control board out of the cabinet.
2-254711
Before you Begin Installing
Active
(green)
Trouble
(amber)
Zone 1-
Zone 8
Zone 9 Zone 16
Answer LED
General Trouble LED
Zone 17 -
Zone 24
Zone 25
-Zone 32
Zone 33 Zone 40
Zone
41-
Zone 48
Active
(green)
Trouble
(amber
)
Figure 2-2 SK-FFT Front View
Figure 2-3 FFT-24 Expander Front View for Zone 25 - 48
547112-3
SK-FFT Installation and Operation Manual
2.4Electrical Specifications
2.4.1Power Requirements
Voltage for the SK-FFT must be a power-limited, filtered, non resettable nominal 24
VDC source. The voltage source must be within the range of 17-29 VDC.
Table 2-1: Electrical Ratings
CircuitsVoltageCurrent
SLC Circuits32 V150 mA
Audio Circuits17 V53 mA
2.4.2Current Ratings
Maximum current ratings for determining backup battery requirements for alarm
(active) and standby conditions over the input voltage range of 17-29 VDC are shown
in Table 2-2.
Table 2-2: SK-FFT Current Draw
ActiveStandby
SK-FFT
FFT-2425 mA10 mA
230 mA120 mA
2-454711
Before you Begin Installing
2.5Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere
with telephone communication or cause false alarms. To avoid induced noise, follow
these guidelines:
•Isolate input wiring from high current output and power wiring. Do not pull one
multi-conductor cable for the entire panel. Instead, separate the wiring as follows:
SLC loopsAudio circuits
Relay circuit
•Do not pull wires from different groups through the same conduit. If you must run
them together, do so for as short a distance as possible or use shielded cable.
Twisted, shielded wire on the Audio Circuits is recommended for maximum
protection against EMI and AFI emissions and susceptibility. Connect the shield to
earth ground at the panel. You must route high and low voltages separately.
•Route the wiring around the inside perimeter of the cabinet. It should not cross the
circuit board where it could induce noise into the sensitive microelectronics or pick
up unwanted RF noise from the high speed circuits. See Figure 2-4 for an
example.
•High frequency noise, such as that produced by the inductive reactance of a
speaker or bell, can also be reduced by running the wire through ferrite shield
beads or by wrapping it around a ferrite toroid.
547112-5
SK-FFT Installation and Operation Manual
Non-Power limited
Relay Circuit
Power Limited
Non power limited wiring
must be run separately from
power limited wiring
2.6Wire Routing
You must follow power-limited wiring techniques, which include maintaining onequarter inch spacing between power-limited and non-power limited circuits and
separating high and low voltage circuits.
Figure 2-4 Wire Routing Example
2-654711
Section 3
Bottom Mounting Holes
20"
26-½”
Installation
3.1Mounting the Cabinet
Read the environmental specifications in Section 2.1 before mounting the SK-FFT
cabinet. This will ensure that you select a suitable location.
The cabinet can be surface or flush mounted. Do NOT flush-mount in a wall designed
as a fire break.
3.1.1Surface Mounting
The Cabinet can be mounted on the wall surface by using the mounting holes in the
back of the cabinet (see Figure 3-1).
1. Insert two screws level with each other, 14" apart for the top cabinet key shaped
holes. See Figure 3-1.
2. Hang the cabinet onto the two screws. Tighten the screws down.
3. Insert two screws into the two bottom mounting holes and tighten them snug to the
cabinet.
Key Shaped Holes
Figure 3-1 Cabinet Mounting Holes
547113-1
SK-FFT Installation and Operation Manual
Side View of Cabinet
Sheet Rock
Sheet Rock
Mounting
Studs
Cabinet
Mounting Hole
Trim Ring
Mounting
Hole
Cabinet
Mounting Hole
and Trim Ring
Trim Ring
1.5 to 1.75"
Trim Ring
Mounting
Hole
3.1.2Flush Mounting
This section describes how to flush mount the cabinet into a wall. To recess mount
the cabinet you will need to have the optional trim ring P/N VIP-TR (ordered
separately).
Follow these steps to recess mount the cabinet:
1. Remove the cabinet door and the dead front panel.
2. Cut a recess hole 20-1/4” W x 26-3/4” H (51.44 cm W x 67.95 cm H). There
should be 1.5" to 1.75" of cabinet extruding from the wall, this should be measured
from either the top edge or bottom edge to the exterior side of the sheet rock. (See
Figure 3-2.)
Important!
Do not insert the cabinet deeper than recommend above. If the cabinet is mounted to deep you will
not be able to re-attach the door assembly.
3. Mount the cabinet to wall studs by inserting a screw through the cabinets side
mounting holes into the wall stud.
Figure 3-2 Detail of Flush Mounting with Trim Ring
3-254711
Installation
Trim Ring
Cabinet
Cabinet Door
Dead
Front Panel
Dead Front
Panel Screws
Cabinet Door
Hex Nuts
4. Place the trim ring around the cabinet. See Figure 3-3.
Figure 3-3 Trim Ring Around cabinet
5. Secure the trim ring to the cabinet using the self-tapping sheet metal screws from
the inside of the cabinet into the trim ring.
6. Re-attach the cabinet door assembly.
3.1.2.1Cabinet Door and Dead Front Removal
While installing the cabinet it may be necessary to remove the cabinet door and the
dead front panel. This section provides instructions on how to remove the door and
dead front panel.
1. Using a Phillips head screw driver, remove the six screws that hold the dead front
panel in place. See Figure 3-4.
Figure 3-4 Cabinet Door and Dead Front Panel Removal
2. Using a 1/4” Hex drive, remove the six Hex nuts that hold the cabinet door in
place. See Figure 3-4.
547113-3
SK-FFT Installation and Operation Manual
Re-Attaching the Cabinet Door
To re-attach the cabinet door reverse the procedure in section 3.1.2.1.
3.2Installing the Fire Fighter’s Hand Set
FFT Local Handset installation involves the following steps:
1. Insert phone cord through hole of dead front panel. See Figure 3-5.
Figure 3-5 Handset Cord Inserted Through Dead Front Panel Hole
2. Attach strain relief clip to the phone cord. The strain relief clip should have about 2
¾” of phone cord though it. See Figure 3-6.
Figure 3-6 Installing Strain Relief Clip
3. Push the strain into the hole in the dead front panel.
3-454711
Installation
Mounting
Studs
Mounting
Studs
3.3FFT-24 Installation
The FFT-24 expander board lets you add additional zones to the SK-FFT. To add
Zone 25 - Zone 48 to the SK-FFT, you must use FFT-24 expander board.
To install the FFT-24:
1. Open Cabinet door and dead front panel.
2. Remove power. See Appendix A for compatible powering devices.
3. Remove blank plate and discard.
4. Mount the FFT-24 on the six mounting studs located on the inside of the dead front
panel and secure using the nuts removed from the blank plate. See Figure 3-7.
547113-5
Figure 3-7 Mounting locations for the FFT-24
5. Connect one end of the wiring harness (P/N 130398 supplied) to the SK-FFT and
SK-FFT Installation and Operation Manual
SK-FFT
the other end to the FFT-24 as shown in Figure 3-8.
Figure 3-8 Wire Harness Connection from SK-FFT to FFT-24 zones 25- 48
6. Restore power. See Section 3.5.
3-654711
Installation
3.4Installing the SK-FFT
SK-FFT installation involves the following steps:
•Make physical connection to any outputs that will power* the SK-FFT. (See
Section 3.5).
•Set the DIP switch ID for the SK-FFT (See Section 3.6.1).
*See Appendix A for compatible powering devices. Silent Knight Installation Manuals
can be found on Silent Knight’s web site at www.silentknight.com.
3.5Operating Power
This section provides instructions to install the appropriate DC power source.
1. Connect the SK-FFT to the appropriate DC power source. See Section 2.4.1 for
power requirements. For compatible product see Table A-1.
2. Use the on-board DIP switch to assign the configuration setting to the SK-FFT.
(See Section 3.6.1).
547113-7
SK-FFT Installation and Operation Manual
3.6DIP switch settings on SK-FFT
This section describes how to configure the DIP switch setting on the SK-FFT.
1. Refer to Figure 2-1 for location of the DIP switches on the SK-FFT board.
2. Configure the SK-FFT module by adding it to the system through JumpStart
feature. See Section 6.3 for JumpStart Operation. Table 3-1 list possible DIP switch
configurations.
3.6.1DIP Switch
Figure 3-9 DIP Switch
Table 3-1 SK-FFT DIP Switch Configurations
DIP SwitchONOFF
1
2Trouble PZT EnabledTrouble PZT Disabled
3SLC Class A Supervision SLC Class B Supervision
4Phone Circuit Class A
5First FFT-24 Expander
SLC Devices InstalledSLC Devices not Installed
Phone Circuit Class B Supervision
Supervision
First FFT-24 Expander not Installed
Installed
3-854711
Installation
To FFT - SLC
Terminal TB4
Connectors
or other SK-MM
The wiring between the
monitor module and FFT-FPJ
is supervised by the monitor
module. A 47K End-of-Line
resistor is built into
the FFT-
FPJ.
To FFT-Phone TB4 phone
In/Out + – connections or other
FFT-FPJ’s or FFT-STS’s
3.7SK-FFT Fire Fighter Telephone Module
Connection
The SK-FFT provides connection for a single Class B or Class A telephone audio
circuit. See Section 4 and Section 5 for examples of audio zone configurations. A
monitor module can be used to monitor the connection of the Fire Fighter Telephone
remote handset (FFT-RHS) into the FFT-FPJ, which is then displayed on the SK-FFT
active zone LED during the JumpStart feature.
Figure 3-10 SK-FFT Connections
547113-9
SK-FFT Installation and Operation Manual
3.8FFT-FPJ Installation
The FFT-FPJ Firefighter Phone Jack mounts to a single-gang electrical box
(4" x 2-1/8" x 2-½") or, when the addressable mini-monitor module is installed with it,
a deep single-gang electrical box (4" x 2-1/8” x 3-¾”).
Connect the telephone audio loop between the FFT-FPJ and FFT as detailed in
Figure 3-12.
All circuits are power-limited and supervised.
Figure 3-11 FFT-FPJ (phone jack) and FFT-RHS (handset)
Figure 3-12 FFT to FFT-FPJ Connection
3-1054711
Installation
Contact EOL set
to Connected
*See Figure 3-14
for EOL example
3.9Installation of FFT-STS
The Single Telephone Station comes in a series of parts. The telephone chassis,
backbox, breakglass kit and door with keylock are all ordered separately. Up to ten
remote handsets may be operated simultaneously.
3.9.1Assembly of Units with Coiled Cord Handsets
The following assembly steps are for telephones with coiled cord handsets. These
steps must be accomplished once the enclosure has been mounted and the system
wiring is in place
1. Attach system wiring to the terminal strip on the telephone chassis assembly
2. Install 6-32 nut in backbox. Do not tighten.
3. Install telephone chassis assembly in backbox.
4. Install trim ring on backbox with 6-32 wing nuts. Do not tighten.
5. Install door assembly. Tighten wing nuts.
Figure 3-13 FFT-STS Telephone Connection
Figure 3-14 EOL Example
547113-11
SK-FFT Installation and Operation Manual
3-1254711
SLC Device Installation
Section 4
SLC Device Installation
Caution!
To avoid the risk of electrical shock and damage to the unit, power should be
OFF at the control panel while installing or servicing.
4.1List of SLC Devices
The following SLC device can be used with the Fire Fighters Phone. See the device
installation instructions for more information (packaged with the device).
Section/
SK Part NumberModel Name/Description
Install Sheet
PN
SK-MinimonMini Monitor Module I56-3444-000
SK-ISOFault Isolator ModuleI56-3445-000
4.2Maximum Number of Devices
The SK-FFT supports up to 48 SK-Minimon devices on one FFT system.
547114-1
SK-FFT Installation and Operation Manual
4.3Wiring Requirements for SLC Device
The following information applies to the SK-Minimon - Mini Monitor module.
4.3.1Wiring SLC in Style 4 (Class B) Configuration
No special wire is required for addressable loops. The wire can be untwisted,
unshielded, solid or stranded as long as it meets the National Electric Code 760-51
requirements for power limited fire protective signaling cables. Wire distances are
computed using copper wire.
Maximum wiring resistance is 40 ohms to the farthest SLC device.
Maximum loop length depends on the wire gauge.
Wire GaugeMax. Distance
22 AWG1200 feet
18 AWG3100 feet
16 AWG4900 feet
14 AWG7900 feet
12 AWG10,000 feet
4-254711
SLC Device Installation
Figure 4-1 and Figure 4-2 show how length is determined for out and back tap T-Tap
style wiring.
Figure 4-1 Calculating wire run length for a simple out and back
When using T-taps, the total length of all taps and the main bus must not exceed
40,000 feet. This requirement must be met in addition to the maximum distance
requirements for the various wire gauges.
Figure 4-2 Calculating Wire Run Length for a T-tap
547114-3
SK-FFT Installation and Operation Manual
4.3.2Wiring SLC Devices in Style 6 & 7 (Class A)
Configuration
Figure 4-3 illustrates how to wire the SLC loop for Style 6 or Style 7 Class A
installations.
Note: Style 6 does not require the use of isolator modules.
Figure 4-3 Class A SLC Configuration
Note: No t-taps allowed on Class A SLC loops.
Caution
For proper system supervision do not use looped wire under terminals marked SLC + and –
of the SLC device connectors. Break wire runs to provide supervision of connections.
4-454711
SLC Device Installation
Example 1: Device set to 10
Example 2: Device Set to 42
4.4Addressing SK-Minimon SLC Devices
All SK-Minimon devices are addressed using the two rotary dials that appear on the
device board. Use the ONES rotary dial to set the ones place in a one or two digit
number, and use the TENS rotary dial to set the tens place in a two digit number.
SK-Minimon modules can be assigned any unique address from 1 to 48.
Example 1: To select device address 10, turn the ONES rotary dial to 0 and the
TENS rotary dial to 1 as shown in Figure 4-4.
Example 2: To select device address 42, turn the ONES rotary dial to 2 and the
TENS rotary dial to 4 as show in Figure 4-4.
Figure 4-4 SK-Minimon SLC Device Addressing using Rotary Dials
547114-5
SK-FFT Installation and Operation Manual
4-654711
Section 5
Audio Phone Circuit Installation
5.1List of Devices
Part NumberDescription
FFT-FPJFire Fighters Telephone Jack
5.2 Maximum Number of Devices
The SK-FFT supports up to 48 zones. Each zone consists of one addressable
monitor module (SK-Minimon) and a minimum of one Fire Fighter Telephone Jack
(FFT-FPJ).
5.3Wiring Requirements for the Audio Telephone
Circuit
The following information applies to the FFT-FPJ Fire Fighter Phone Jack.
5.3.1Single Phone Jack Audio Circuit in Class B
Configuration
No special wire is required for the Audio Telephone Circuit. The wire can be
untwisted, unshielded, twisted or shielded as long as it meets the National Electric
code 760-51 requirements for power limited fire protective signaling cables.
54 Ohm maximum impedance - 12 to 18 AWG.
Twisted, shielded wire is recommended for maximum protection against EMI and AFI
emissions and susceptibility.
If using shielded cable, attach the shield to Grounding Stud below TB6 of the FFT.
Note: Do not ground shield on both ends.
547115-1
SK-FFT Installation and Operation Manual
Contact EOL
Connected
(see Figure 5-2
for EOL
example)
Figure 5-1 illustrates single phone jack configuration wiring the audio circuit and SLC
for Class B Configuration. Audio circuits must be connected to FFT phone out
terminals for all Class B audio configurations.
Figure 5-1 Single Phone Jack Audio Circuit in Class B
Figure 5-2 EOL Example
5-254711
Audio Phone Circuit
Contact EOL
Connected
5.3.2Single Phone Jack Audio Circuit in Class A
Configuration
For wiring specifications see section 5.3.1.
Figure 5-3 illustrates phone jack audio circuit (Class A) and SLC for Style 6 & 7 (Class
A) configuration.
Figure 5-3 Single Phone Jack Audio Circuit in Class A
547115-3
SK-FFT Installation and Operation Manual
5.3.3Multi-Phone Jack Audio Circuit in Class B
Configuration
For wiring specifications see section 5.3.1.
Figure 5-4 illustrates how to wire the Multi-Phone Jack audio circuit (Class B) and
SLC for for Style 4 (Class B) configuration. In the Multi-Phone Jack configuration, the
maximum mini-monitor contact wiring resistance between to first and last FPJ must
be less that 100 ohms.
Figure 5-4 Multi-Phone Jack Audio Circuit in Class B
5-454711
Audio Phone Circuit
5.3.4Multi-Phone Jack Audio Circuit in Class A
Configuration
For wiring specifications see section 5.3.1.
Figure 5-5 illustrates how to wire the Multi-Phone Jack audio circuit (Class A) and
SLC for Style 6 & 7 (Class A) configuration. In the Multi-Phone Jack configuration, the
maximum Mini-Monitor Contact wiring resistance between to first and last FPJ must
be less that 100 ohms.
Figure 5-5 Multi-Phone jack Audio Circuit in Class A
547115-5
SK-FFT Installation and Operation Manual
5.3.5Telephone Jack Only Audio Circuit
The FFT can also be configured using only the Fire Fighters Phone Jack (FFT-FPJ).
In this configuration, the SK-Minimon module is not required for system operation. To
configure the FFT for Telephone Jack only, the DIP Switch position 1 must be off
(SLC Devices not Installed). See Table 3-1.
Audio wiring for this configuration is detailed below. See Figure 5-6 and Figure 5-7.
Figure 5-6 Telephone Jack Only Audio Circuit Class B
5-654711
Audio Phone Circuit
Figure 5-7 Telephone Jack Only Audio Circuit Class A
547115-7
SK-FFT Installation and Operation Manual
5-854711
Section 6
System Operation
The operation of the SK-FFT Fire Fighter Telephone system allows audio
communication from 24 remote connections through remote handsets from a single
local handset. Up to 10 remote handset can be connected and communicating at one
time. Remote audio connections can be expanded to 48 with the optional FFT-24
zone expander.
6.1Key Switch Operations
6.1.1JumpStart Key Switch (on inside of FFT dead front
panel).
JumpStart key will cause the FFT to search the SLC loop for devices. The Active LED
(green) will then blink for each zone where a device was found. Press and hold the
Jumpstart Key for 2 seconds in order to initiate Jumpstart.
6.1.2Accept Key Switch (on inside of FFT dead front
panel).
The Accept key is used after Jumpstart. It will save the current SLC device
configuration and re-initialize the FFT. If the user does not press the Accept key
within one minute after the JumpStart is complete, its configuration will be discarded
and the FFT will be restarted.
6.1.3Answer Switch
When a Remote Handset is connected to one of the FFT-FPJ phone jacks, the
Answer LED will blink and the FFT's PZT will sound. Pressing the Answer Switch will
connect the local handset to the phone circuit, turn the answer LED on solid, and
silence the PZT. Communication between the local and remote handset is now
possible. Up to six remote handsets can be connected to the phone circuit
simultaneously. After the initial remote handset, the connection of additional handsets
does not cause the PZT to sound or the Answer LED to blink.
6.1.4Silence Switch
The Silenced Switch is used to silence a system type trouble that has occurred in the
FFT system. Once pressed the PZT will silence.
547116-1
SK-FFT Installation and Operation Manual
6.2LED Operations
6.2.1Power Status LED
The Power Status LED is located on the left side of the FFT board. On Power-UP the
Power Status LED will blink at a 50% on/off rate until FFT initialization is complete
(which takes approximately 20 seconds). Once initialization is complete the Power
Status LED will blink at a 10% on and 90% off rate.
No key input will be valid until the FFT completes its initialization.
6.2.2Answer
When a Remote Handset connects to the audio channel the Answer LED will blink
and the PZT will sound. The operator at the FFT then picks up the local handset and
presses the Answer Switch which causes the Answer LED to remain on solid and the
PZT goes silent. Communication between the local and remote handset is now
established. Additional remote handsets can be attached to the audio connection
without any intervention at the FFT. Once the last remote handset has disconnected
from the FFT, the answer LED will go blank and the system will be back to normal.
6.2.3Power
The Power LED indicates that 24 VDC is connected to the FFT.
6.2.4Local Handset Trouble
The local handset trouble LED will activate and blink when there is a problem with the
local handset.
6.2.5 Remote Handset Trouble
The remote handset trouble LED will activate and blink when there is a problem with
the phone circuit.
6.2.6General Trouble
The General Trouble LED will blink active when system troubles are detected. When
the Silence Key is pressed, the General Trouble LED will become constant. Once all
system troubles have been restored, the General Trouble LED will deactivate.
6-254711
System Operation
6.2.7Status LEDs (on Inside of FFT dead front panel)
LED 1 - SLC Supervision*
LED 2 - SLC Extra Point Detected
LED 3 - FFT-24 missing
LED 4 - Audio Circuit Supervision
Note: * Troubles that will turn LED on: SLC shorted, SLC Class A open trouble and wrong device type.
547116-3
SK-FFT Installation and Operation Manual
Answer
LED
Active
(green)
Trouble
(amber)
6.2.8Zone Active
Each zone has an Active LED (see Figure 6-1). The zone's Active LED will illuminate
when a remote handset is plugged into that zone. The LED will turn off when the
handset is removed from the zone.
6.2.9Zone Trouble
Each zone has a Trouble LED (see Figure 6-1). The zone's Trouble LED will blink
when specific SLC issues occur such as a missing device or double address.
Pressing the Silence Key will cause the zone trouble LED to be on solid. Once the
zone trouble is corrected, the LED will turn off.
Figure 6-1 LED Operations
6-454711
System Operation
6.3JumpStart Operation
The JumpStart® feature will attempt to locate all SLC Mini-Monitor devices installed in
the system, indicate all devices found on the FFT and all FFT-24 Active LED's and
allow the user to accept the configuration, repeat the JumpStart or allow the
configuration to be discarded.
1. To perform the FFT Jumpstart press and hold the JumpStart button for 2 seconds.
2. The FFT will search for installed SLC devices and activate the Active LED’s of all
zone/point addresses found.
3. When the Jumpstart is complete, the first four status LED’s will blink. The user can
now press the ACCEPT key causing the FFT to save the configuration and
restart.
4. The user presses the JumpStart key again to repeat the SLC search process.
5. If the user does not press the Accept key within one minute after the JumpStart is
complete, its configuration will be discarded and the FFT will be restarted.
547116-5
SK-FFT Installation and Operation Manual
6-654711
Appendix A
Compatible Powering Devices
A.1Compatible Power Device
Table A-1 list the available Silent Knight compatible power devices used with SK-FFT.
Table A-1: Compatible Powering Devices
ModelManual PN
5820XL / 5820XL-EVS Addressable Fire Control Panel /
Emergency Voice System
5808 Addressable Fire Control Panel151274
5700 Addressable Fire Control Panel151295
5600 25-Point Addressable Fire Control Panel151450
5895XL Power Supply151142
151209 /
LS10061-001SK-E
54711A-1
SK-FFT Installation and Operation Manual
Notes:
A-254711
Silent Knight Fire Product Warranty and Return Policy
General Terms and Conditions
•All new fire products manufactured by Silent Knight have a limited warranty period
of 36 months from the date of manufacture against defects in materials and
workmanship. See limited warranty statement for details.
•This limited warranty does not apply to those products that are damaged due to
misuse, abuse, negligence, exposure to adverse environmental conditions, or
have been modified in any manner whatsoever.
Repair and RMA Procedure
•All products that are returned to Silent Knight for credit or repair require a RMA
(Return Authorization) number. Call Silent Knight Customer Service at
800-328-0103 or 203-484-7161 between 8:00 A.M. and 5:00 P.M. EST, Monday
through Friday to obtain a return authorization number.
•Silent Knight Technical Support is available at 800-446-6444 between 8:00 A.M.
and 5:00 P.M. CST, Monday through Friday.
•All returns for credit are subject to inspection and testing at the factory before
actual determination is made to allow credit.
•RMA number must be prominently displayed on the outside of the shipping box.
See return address example under Advanced Replacement Policy.
•Included with each return should be: a packing slip that has the RMA number, a
content list, and a detailed description of the problem.
•All products returned to Silent Knight must be sent freight pre-paid. After product
is processed, Silent Knight will pay for shipping product back to customer via UPS
ground.
•Return the Silent Knight product circuit board only. Products that are returned in
cabinets will be charged an additional $50 to cover the extra shipping and
handling costs over board only returns. Do not return batteries. Silent Knight has
the authority to determine if a product is repairable. Products that are deemed unrepairable will be returned to the customer.
•Product that is returned that has a board date code more than 36 months from
date of manufacture will be repaired and the customer will be assessed the
standard Silent Knight repair charge for that model.
547113
SK-FFT Installation and Operation Manual
Advanced Replacement Policy
•Silent Knight offers an option of advance replacement for fire product printed
circuit boards that fail during the first 6 months of the warranty period. These items
must be returned with transportation charges prepaid and must be accompanied
by a return authorization.
•For advance replacement of a defective board, contact your local Silent Knight
distributor or call Silent Knight at 800-328-0103 to obtain a RMA (Return
Authorization) number and request advanced replacement.
•A new or refurbished board will be shipped to the customer. The customer will
initially be billed for the replacement board but a credit will be issued after the
repairable board is received at Silent Knight. All returned products must comply
with the guidelines described under “General Terms and Conditions” and “Repair
and RMA Procedure”.
•The defective board must be returned within 30 days of shipment of replacement
board for customer to receive credit. No credit will be issued if the returned board
was damaged due to misuse or abuse.
•Repairs and returns should be sent to:
Silent Knight / Honeywell
Attn: Repair Department
12 Clintonville Road
Northford, CT 06472
USA
RA Number:___________________
454711
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein, Manufacturer
warrants that the Products manufactured by it in its Northford, Connecticut facility and
sold by it to its authorized Distributors shall be free, under normal use and service,
from defects in material and workmanship for a period of thirty six months (36)
months from the date of manufacture (effective Jan. 1, 2009). The Products
manufactured and sold by Manufacturer are date stamped at the time of production.
Manufacturer does not warrant Products that are not manufactured by it in its
Northford, Connecticut facility but assigns to its Distributor, to extent possible, any
warranty offered by the manufacturer of such product. This warranty shall be void if a
Product is altered, service repaired by anyone other than Manufacturer or its
authorized Distributors. This warranty shall also be void if there is a failure to maintain
the Products and the systems in which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY
AND ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH
RESPECT TO THE PRODUCTS,TRADEMARKS, PROGRAMS AND SERVICES
RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION,
INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR ANY
PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY
PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS
A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USES OF ITS
PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to its
products and replaces all previous warranties and is the only warranty made by
Manufacturer. No increase or alteration, written or verbal, of the obligation of this
warranty is authorized. Manufacturer does not represent that its products will prevent
any loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion,
each part returned by its authorized Distributor and acknowledged by Manufacturer to
be defective, provided that such part shall have been returned to Manufacturer with
all charges prepaid and the authorized Distributor has completed Manufacturer's
Return Material Authorization form. The replacement part shall come from
Manufacturer's stock and may be new or refurbished. THE FOREGOING IS
DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A
WARRANTY CLAIM.
Warn-HL-08-2009.fm
547115
SK-FFT Installation and Operation Manual
654711
Cut Along the Dotted Line
Model SK-FFT Basic Operating Instructions
These Instructions must be framed and displayed next to the SK-FFT
panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm
Systems. Test the system in accordance to NFPA 72. Refer to Installation
Manual P/N 54711 for more information regarding this control panel.
OperationTask to Perform
Answer CallWhen Remote handset is connected to the FFT-FPJ, the Answer LED will
blink and PZT will sound.
Press key and PZT will silence. Answer LED will be on solid and
audio connection will be established between local and remote handset.
Silence Trouble
For Service call:
P/N 54713 Rev. A
Press key and PZT will silence. General Trouble LED will be on
solid.
ECN 11-0003
Cut Along the Dotted Line
Silent Knight
12 Clintonville Road
Northford, CT 06472-1610
203-484-7161
Fax: 203-484-7118
www.silentknight.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.