SilentKnight SK-4 User Manual

MODELS
SK-2/E & SK-4/E
Fire Alarm Control Panels
Instruction Manual
Document 52604 9/14/2010 Rev:
P/N 52604:B ECN 09-722
B
Fire Alarm System Limitations
While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance!
An automatic fire alarm system—typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control panel with remote notification capability—can provide early warning of a develop­ing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire.
The Manufacturer recommends that smoke and/or heat detec­tors be located throughout a protected premise following the recommendations of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guides for Proper Use of System Smoke Detectors, which are made available at no charge to all installing dealers. These documents can be found at http://www.systemsen­sor.com/html/applicat.html. A study by the Federal Emer­gency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm sys­tem may not provide timely or adequate warning, or simply may not function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first­floor or basement fire.
Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow.
• Smoke particles may become “cold,” stratify, and not reach the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air outlets.
• Smoke particles may be drawn into air returns before reaching the detector.
The amount of “smoke” present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ion­izing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predeter­mined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire pro­tection specialist. Heat detectors are designed to protect property, not life.
IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the sys­tem for the connection of alarm transmission wiring, communi­cations, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crip­pling its ability to report a fire.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medica­tion. Please note that:
• Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsi­bility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.
Equipment used in the system may not be technically com­patible with the control panel. It is essential to use only equip­ment listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against tele­phone line failure, backup radio transmission systems are rec­ommended.
The most common cause of fire alarm malfunction is inade­quate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA stan­dards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A main­tenance agreement should be arranged through the local man­ufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Limit-C1-2-2007
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all
sources of power before servicing. Control unit and associ­ated equipment may be damaged by removing and/or insert­ing cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood.
CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product
must be tested in accordance with NFPA 72 after any pro­gramming operation or change in site-specific software. Re­acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All compo­nents, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0-49º C/32-120º F and at a relative humidity 93% ± 2% RH (non­condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic com­ponents may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27º C/60-80º F.
Verify that wire sizes are adequate for all initiating and indi­cating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to light­ning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Ser­vices Department if any problems are anticipated or encoun­tered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifi­cations, verify that they will not interfere with battery, trans­former, or printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs. Over­tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before han­dling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and pro­gramming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interfer­ence, in which case the user will be required to correct the interference at his or her own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Cana­dian Department of Communications.
Le present appareil numerique n'emet pas de bruits radi­oelectriques depassant les limites applicables aux appa­reils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
Silent Knight® is a registered trademark of Honeywell International Inc. Echelon® is a registered trademark and LonWorks™ is a trademark of Echelon Corporation. ARCNET® is a registered trademark of Datapoint Corporation. Microsoft® and Windows® are registered trademarks of the Microsoft Corporation.
©2010 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 3
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us.
Please include the following information:
•Product name and version number (if applicable)
•Printed manual or online Help
•Topic Title (for online Help)
•Page number (for printed manual)
•Brief description of content you think should be improved or corrected
•Your suggestion for how to correct/improve documentation
Send email messages to:
FireSystems.TechPubs@honeywell.com
Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.

Table of Contents

Section 1: Product Description ............................................................................................. 10
1.1: Product Features ..........................................................................................................................................10
1.2: Specifications...............................................................................................................................................11
1.3: Controls and Indicators................................................................................................................................12
1.4: Circuits.........................................................................................................................................................14
1.5: Components .................................................................................................................................................14
1.6: Optional Modules and Accessories .............................................................................................................14
Section 2: Installation.............................................................................................................17
2.1: Backbox Mounting ......................................................................................................................................17
2.2: Operating Power ..........................................................................................................................................19
2.3: Input Circuits ...............................................................................................................................................20
2.4: Output Circuits.............................................................................................................................................22
2.4.1: Notification Appliance Circuits.........................................................................................................22
2.4.2: Special Application DC Power Output Connections.........................................................................23
2.4.3: Relays ................................................................................................................................................23
2.5: Power-limited Wiring Requirements........................................................................................................... 24
2.6: Installation of Optional Modules .................................................................................................................25
2.6.1: CAC-4 Class A Converter Module (SK-4 only) ...............................................................................25
Installation ............................................................................................................................................25
Wiring NACs and IDCs for Class A ....................................................................................................25
2.6.2: 4XTMF, 4XLMF and 4XZMF Option Modules...............................................................................26
4XTMF Transmitter Module Installation .............................................................................................27
4XZMF Zone Relay Module (SK-4 only)............................................................................................29
4XLMF LED Interface Module (SK-4 only) .......................................................................................30
Section 3: Program Options via DIP Switch.........................................................................32
3.1: DIP Switch Settings.....................................................................................................................................33
3.1.1: SW1 DIP Switch Settings.................................................................................................................. 35
Silence Inhibit.......................................................................................................................................35
Auto-silence..........................................................................................................................................35
Temporal Coding.................................................................................................................................. 35
Selective Silence...................................................................................................................................35
Trouble Reminder.................................................................................................................................35
AC Trouble Delay ................................................................................................................................35
Autoresettable Supervisory ..................................................................................................................35
IDC Combination Circuit .....................................................................................................................36
3.1.2: SW2 DIP Switch Settings..................................................................................................................36
IDC1 Verification (SK-4 only)............................................................................................................36
IDC1 Supervisory (SK-4 only)............................................................................................................. 36
IDC1 Verification for SK-2 or IDC2 Verification for SK-4 ................................................................36
IDC1 Supervisory for SK-2 or IDC2 Supervisory for SK-4 ................................................................ 37
IDC2 Verification for SK-2 or IDC3 Verification for SK-4 ................................................................37
IDC2 Supervisory for SK-2 or IDC3 Supervisory for SK-4 ................................................................ 37
IDC4 Verification (SK-4 only).............................................................................................................37
IDC4 Supervisory (SK-4 only)............................................................................................................. 37
3.1.3: SW3 DIP Switch Settings..................................................................................................................37
NAC1 Nonsilenceable ..........................................................................................................................37
NAC1 Disable ......................................................................................................................................37
NAC2 Nonsilenceable (SK-4 only)......................................................................................................37
NAC2 Disable (SK-4 only) ..................................................................................................................38
Strobe Synchronization ........................................................................................................................38
Nonsilenceable Waterflow for Combination Circuit............................................................................38
Spares ...................................................................................................................................................38
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 5
Table of Contents
Section 4: Operating Instructions ......................................................................................... 40
4.1: Switch Functions in Normal Mode ..............................................................................................................40
4.1.1: ACK - Acknowledge .........................................................................................................................40
4.1.2: Silence................................................................................................................................................40
4.1.3: Zone Enable/Disable..........................................................................................................................40
4.1.4: Reset/(Lamp Test) .............................................................................................................................40
4.1.5: Walktest .............................................................................................................................................41
4.2: Walktest........................................................................................................................................................41
4.3: Status LEDs..................................................................................................................................................42
4.4: Operation......................................................................................................................................................43
4.4.1: Fire Alarm Response .........................................................................................................................44
4.4.2: Fire Alarm Restoral ...........................................................................................................................44
4.4.3: System Supervisory Condition Response..........................................................................................44
4.4.4: System Supervisory Restoral Response.............................................................................................44
4.4.5: Trouble Condition Response .............................................................................................................44
4.4.6: Trouble Condition Restoral ...............................................................................................................45
Section 5: Power Supply Calculations ................................................................................. 46
5.1: Overview......................................................................................................................................................46
5.2: Calculating the AC Branch Circuit ..............................................................................................................46
5.3: Calculating the System Current Draw .........................................................................................................47
5.3.1: Overview............................................................................................................................................47
5.3.2: How to Use Table 5.3 on page 48 to Calculate System Current Draw .............................................47
5.4: Calculating the Battery Size.........................................................................................................................48
5.4.1: NFPA Battery Requirements .............................................................................................................49
5.4.2: Selecting and Locating Batteries .......................................................................................................49
Appendix A: NFPA Standard-Specific Requirements ......................................................... 50
A.1: Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts......................................50
Index ........................................................................................................................................ 51
6 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
It is imperative that the installer understand the requirements of the Authority Having Jurisdiction (AHJ) and be familiar with the standards set forth by the following regulatory agencies:
Underwriters Laboratories Standards
NFPA 72 National Fire Alarm Code
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards This Fire Alarm Control Panel complies with the following NFPA Standards:
NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module)
Underwriters Laboratories Documents for Reference:
UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ)
Silent Knight Documents
Silent Knight Device Compatibility DocumentDocument #52612 411 Digital Alarm Communicator/TransmitterDocument #50921 411UD Digital Alarm Communicator/TransmitterDocument #50759
This product has been certified to comply with the requirements in the Standard for Control Units and Accessories for Fire
Alarm Systems, UL 864, 9th Edition. Operation of this product with products not tested for UL 864, 9th Edition has not
been evaluated. Such operation requires the approval of the local Authority Having Jurisdiction (AHJ).
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 7
J7 Transformer Connector
120 VAC, 2.3A or 220/240 VAC, 1.15A
Earth Neutral Hot
(supervised, nonpower-limited)
J8 Battery Connector (supervised, nonpower-limited) 18 Amp Hour max.
Charger Fault LED Battery Fault LED Earth Fault LED
SW1, SW2 and SW3 Programming DIP Switches
Note: Factory-installed cover removed for illustration purposes only!
24 VDC Special Application
Resettable Power
500 mA max. (nonsupervised,
power-limited)
- 24 VDC
+ 24 VDC
NAC (4.7KW, ½ watt ELR)
2.5A max.
(supervised, power-limited)
B-
B+
IDC (4.7 K, ½ watt ELR)
(supervised, power-limited)
Zone 2 B-
Zone 2 B+
Zone 1 B-
Zone 1 B+
Trouble Relay (fail-safe) 2 amps @ 30 VAC (nonsupervised)
Common Trouble (Normally Open) Normal (Normally Closed)
Alarm Relay 2 amps @ 30 VAC (nonsupervised)
Common Normally Closed Normally Open
ms2bord.wmf
JP3 - Cut to disable Ground Fault detection (only with approval of AHJ)
J3 and J5
4XTMF Option
Module
Connectors
Module Placement Supervision (if installed) JP1 - cut to supervise module on J3 & J5
Two Zone Main Circuit Board
8 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
4 Zone Main Circuit Board
O N
1 2 3 4 5 6 7 8
O N
1 2 3 4 5 6 7 8
O N
1 2 3 4 5 6 7 8
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
TROUBLE
TROUBLE
TROUBLE
TROUBLE
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
FIRE ALARM
FIRE ALARM
AC
POWER
NAC
DISABLE
NAC
FAULT
SYSTEM
TROUBLE
POWER
TROUBLE
WALK
TEST
ALARM
SILENCE
ZONE
DISABLE
FIRE ALARM
FIRE ALARM
RESET
WAL K TEST
ALARM
SILENCE
ACK
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE
ENABLE/DISABLE
3
4
2
1
TB1
TB2
TB3
TB5
TB6
TB7
J1
B+ B- B+ B­ NAC 1 NAC 2
+ - + -
Nonreset Reset
B+ B- B+ B­ ZONE 1 ZONE 2
B+ B- B+ B­ ZONE 3 ZONE 4
C TRBL NORM TROUBLE
C NC NO
ALARM SUPV
C NC NO
J3
J5
J4
J8
J7
J9
TB8
J6
JP1
JP3
SW1
BATTERY
HOT NEUT EARTH
TRANSFORMER 1TRANSFORMER 2
SW2 SW3
JP2
EARTH BATT CHG
CLASS A CONVERTER
J7 Transformer
Connector
120 VAC, 2.3A or
220/240 VAC, 1.15A
Hot
Neutral
Earth
(supervised,
nonpower-limited)
J8 Battery
Connector
(supervised, nonpower-limited)
18 Amp Hour max.
Charger Fault LED Battery Fault LED Earth Fault LED
SW1, SW2 and SW3 Programming DIP Switches
Note: Factory-installed cover removed for illustration purposes only!!
24 VDC Special Application
Power TB1
500 mA per circuit
(nonsupervised, power-
limited)
- Reset + Reset
- Nonreset +Nonreset
NAC (4.7K, ½ watt ELR)
TB2 2.5A max. per NAC
(supervised, power-limited)
NAC 2 B-
NAC 2 B+
NAC 1 B-
NAC 1 B+
Zone 4 B-
Zone 4 B+
Zone 3 B-
Zone 3 B+
Zone 2 B-
Zone 2 B+
Zone 1 B-
Zone 1 B+
Trouble Relay TB5 (fail-safe) 2A @ 30 VAC (nonsupervised)
Common Trouble (Normally Open) Normal (Normally Closed)
Alarm Relay TB6 2A @ 30 VAC (nonsupervised)
Common Normally Closed Normally Open
Supv. Relay TB7 2A @ 30 VAC (nonsupervised)
Common Normally Closed Normally Open
J3 and J5 Option Module Connectors
J4 and J6
Option Module
Connectors
Module Placement Supervision (if installed)
JP1 - cut to supervise module on J3 & J5 JP2 - cut to supervise module on J4 and J6
Class A
Converter Module
J9 Transformer
(optional)
ms4bord.wmf
JP3 - Cut to disable Ground Fault detection (only with approval of AHJ)
IDC (4.7 K, ½ watt ELR) TB3 (supervised, power-limited)
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 9

Section 1: Product Description

The SK-2 is a two zone FACP (Fire Alarm Control Panel) and the SK-4 is a four zone FACP. The information in this manual refers to both the SK-2 and SK-4 unless otherwise specified. These control panels provide reliable fire signaling protection for small to medium sized commercial, industrial and institutional buildings. The FACP is compatible with System Sensor’s i which are microprocessor-based conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory ‘freeze’ signal when the ambient temperature falls below the detector rating (refer to System Sensor’s i Maintenance Instructions document I56-1800-00 for device specifications). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches and other normally-open contact devices. Refer to the Silent Knight Device Compatibility Document for a complete listing of compatible devices.
Outputs include one NAC (Notification Appliance Circuit) on the SK-2 and two NACs on the SK-
4. Each FACP has a Form-C Alarm and Trouble relay and 24 VDC special application resettable power. In addition, the SK-4 has a Form-C Supervisory relay and a nonresettable special application power output. The FACP supervises wiring, AC voltage and battery level.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicating LED, sound the piezo sounder at the FACP, activate the FACP alarm relay and operate an optional module used to notify a remote station or initiate a auxiliary control function. The SK-2E and SK-4E offer the same features as the SK-2 and SK-4 but allows connection to 220/240 VAC.
3
detectors
3
Installation and
NOTE: Unless otherwise specified, the terms SK-2 and SK-4 are used in this manual to refer to the SK-2 and SK-2E as well as the SK-4 and SK-4E FACPs respectively.

1.1 Product Features

Style B (Class B) IDC (Initiating Device Circuit)
one zone programmable for combination supervisory and
waterflow
SK-2 - two IDCs
SK-4 - four IDCs
Style Y (Class B) NAC (Notification Appliance Circuit)
SK-2- one NAC
SK-4 - two NACs
Form-C Alarm Relay
Form-C Trouble Relay
Form-C Supervisory Relay (SK-4 only)
3.0 amps total system current standard for SK-2 and SK-4
6.0 amps total system current available for SK-4 with optional second transformer
Dress Panel DP-MS2/4
Optional Trim Ring P/N: TR-1-R for semi-flush mounting the cabinet
Control Buttons
ACK (Acknowledge)
Alarm Silence
Reset
Walktest
10 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Specifications Product Description
Zone Enable/Disable (one per zone)
LED Indicators
Fire Alarm (one per zone)
Supervisory (one per zone)
Trouble (one per zone)
Maintenance (one per zone)
AC Power
NAC Disable
Zone Disable
NAC Fault
System Trouble
Power Trouble
Walktest
Alarm Silence
Earth Fault LED (on circuit board) lights if zero impedance between FACP and ground exist
Battery Fault (on circuit board)
Charger Fault (on circuit board)
Piezo sounder for alarm, trouble and supervisory
24 volt operation
Low AC voltage sense
Alarm Verification
NACs Programmable for:
Silence Inhibit
Auto-Silence
Strobe Synchronization
Selective Silence (horn-strobe mute)
Temporal or Steady Signal
Silenceable or Nonsilenceable
Automatic battery trickle charger
Silent or audible walktest capabilities
Optional NAC Class A converter module (SK-4 only)
Optional 4XTMF Transmitter Module (SK-2 and SK-4)
Optional 4XZMF Zone Relay Module (SK-4 only)
Optional 4XLMF Module for RZA-4XF Remote LED Annunciator (SK-4 only)

1.2 Specifications

AC Power - TB8
SK-2/SK-4: 120 VAC, 50/60 Hz, 2.3 amps SK-2E/SK-4E: 240 VAC, 50 Hz, 1.15 amps Wire size: minimum #14 AWG (2.0 mm
Battery (sealed lead acid only) - J8
Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 0.8 amp Maximum Charger Capacity: 18 Amp Hour battery (two 7 Amp Hour batteries can be housed in the FACP cabinet. Larger batteries require a separate battery box such as the BB-17F.)
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 11
2
) with 600V insulation
Product Description Controls and Indicators
Initiating Device Circuits - TB3
Alarm Zones 1 & 2 (SK-2 and SK-4) Alarm Zones 3 & 4 (SK-4 only) Power-limited circuitry Operation: All zones Style B (Class B) Normal Operating Voltage: Nominal 20 VDC, Maximum 27 VDC Alarm Current: 15 mA minimum Short Circuit Current: 40 mA maximum Maximum Loop Resistance: 100 ohms End-of-Line Resistor: 4.7K, 1/2 watt (Part #71252) Standby Current: 4 mA Refer to the Silent Knight Device Compatibility Document for listed compatible devices
Notification Appliance Circuit(s) - TB2
One NAC on SK-2, two NACs on SK-4 Operation: Style Y (Class B) Power-limited Circuitry Normal Operating Voltage: Nominal 24 VDC, Maximum 27 VDC Maximum Signaling Current: 2.5 amps total with standard transformer. 5.0 amps total (2.5 amp maximum per NAC) with optional transformer on SK-4 only Maximum Line Impedance: 1.5 volt drop end-of-line End-of-Line Resistor: 4.7K, 1/2 watt (Part #71252) Refer to the Silent Knight Device Compatibility Document for compatible listed devices
1
Form-C Relays
Trouble Relay TB5 (fail-safe) Alarm Relay TB6 Supervisory Relay TB7 (SK-4 only) Relay Contact Ratings: 2 amps @ 30 VAC (resistive)
Resettable Special Application Power - TB1
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA - appropriate for powering 4-wire smoke detectors (see Footnote 1.) Power-limited Circuitry Refer to the Silent Knight Device Compatibility Document for compatible listed devices
Nonresettable Special Application Power - TB1 (SK-4 only)
Operating Voltage: Nominal 24 VDC Maximum Available Current: 500 mA (see footnote 1 on page 12.) Power-limited Circuitry Refer to the Silent Knight Device Compatibility Document for compatible listed devices

1.3 Controls and Indicators

Front Panel Membrane Buttons
Acknowledge
Alarm Silence
Reset
1. Total current for resettable power and one Notification Appliance Circuit must not exceed
3.0 amps for the SK-2. Total current for nonresettable power, resettable power and two Notification Appliance Circuits must not exceed 6.0 amps for the SK-4 (requires optional second transformer).
12 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Controls and Indicators Product Description
Walktest
Zone Enable/Disable - Zone 1
Zone Enable/Disable - Zone 2
Zone Enable/Disable - Zone 3 (SK-4 only)
Zone Enable/Disable - Zone 4 (SK-4 only)
LED Indicators
Fire Alarm Zone 1 - red LED
Fire Alarm Zone 2 - red LED
Fire Alarm Zone 3 - red LED (SK-4 only)
Fire Alarm Zone 4 - red LED (SK-4 only)
Supervisory Zone 1 - yellow LED
Supervisory Zone 2 - yellow LED
Supervisory Zone 3 - yellow LED (SK-4 only)
Supervisory Zone 4 - yellow LED (SK-4 only)
Trouble Zone 1 - yellow LED
Trouble Zone 2 - yellow LED
Trouble Zone 3 - yellow LED (SK-4 only)
Trouble Zone 4 - yellow LED (SK-4 only)
Maintenance Zone 1 - yellow LED
Maintenance Zone 2 - yellow LED
Maintenance Zone 3 - yellow LED (SK-4 only)
Maintenance Zone 4 - yellow LED (SK-4 only)
AC Power - green LED
NAC Disable - yellow LED
Zone Disable - yellow LED
NAC Fault - yellow LED
System Trouble - yellow LED
Power Trouble - yellow LED
Walktest - yellow LED
Alarm Silence - yellow LED
Earth Fault - yellow LED (on main circuit board) lights if zero impedance between FACP and ground exists
Battery Fault - yellow LED (on main circuit board)
Charger Fault - yellow LED (on main circuit board)
Local Piezo Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble, maintenance and supervisory conditions as follows:
Alarm - on steady
Trouble - pulse 1 second on and 1 second off
Maintenance - pulse ½ second on and ½ second off
Supervisory - pulse ½ second on and ½ second off
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 13
Product Description Circuits

1.4 Circuits

Input Circuits
Two input IDCs (Initiating Device Circuits) on the SK-2 and four IDCs on the SK-4 provide Style B (Class B) configurations. All IDCs accept i detectors, four-wire smoke detectors and normally-open contact devices.
Output Circuits
24 VDC resettable special application power output - 500 mA
24 VDC nonresettable special application power output (SK-4 only) - 500 mA
24 volt battery charger (up to 18 Amp Hour batteries)
Notification Appliance Circuits
One NAC (Notification Appliance Circuit) Style Y (Class B) on the SK-2 Two NACs Style Y (Class B) on the SK-4
Relays
Alarm Relay Trouble Relay (fail-safe) Supervisory Relay (SK-4 only) Form-C contacts rated 2.0 amps @ 30 VAC (resistive)

1.5 Components

Main Circuit Board
The main circuit board contains the system’s CPU, power supply, other primary components and wiring interface connectors. Optional modules plug in and are mounted to the main circuit board.
3
detectors as well as conventional two-wire smoke
Cabinet
The backbox measures 14.5” (36.8 cm) x 15.218” (38.65 cm) x 2.875” (7.3 cm) and provides space for two batteries (up to 7 Amp Hours). Also included is a dress panel which mounts inside the cabinet.
Transformer Assembly
One 100VA transformer is provided standard with the FACP. An optional second 100VA transformer is available for the SK-4 to provide maximum accessory power.
Batteries
The cabinet provides space for two 7 Amp Hour batteries (larger batteries up to 18 Amp Hour, require use of a UL listed battery box such as the BB-17F). Batteries must be ordered separately.

1.6 Optional Modules and Accessories

CAC-4 Class A Converter Module (SK-4 only)
The CAC-4 Module can be used to convert the Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The module connects to J1 on the SK-4 main circuit board.
4XTMF Transmitter Module (SK-2 and SK-4)
The 4XTMF provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity. It includes a disable switch and disable trouble LED. A module jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm
14 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Optional Modules and Accessories Product Description
condition exists. The 4XTMF mounts to the SK-2 main circuit board option module connectors J3 & J5 or the SK-4 main circuit board, occupying one of the two sets of option module connectors J3 & J5 or J4 & J6.
4XLMF LED Interface Module (SK-4 only)
The LED Interface Module supports the RZA-4XF Remote Annunciator module. Annunciator wiring is supervised for open conditions by this module. The 4XLMF mounts to the SK-4 main circuit board option module connectors J3 and J5 only
.
RZA-4XF Remote Annunciator (SK-4 only)
The Remote Annunciator mounts on a standard single-gang electrical box and provides LED indication of the following:
Alarm Zone 1 (red LED)
Alarm Zone 2 (red LED)
Alarm Zone 3 (red LED)
Alarm Zone 4 (red LED)
System Trouble (yellow LED)
A Local Trouble Sounder and Silence Switch are also provided. All LED wiring is supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in paper labels permit an easy change of zone information.
NOTE: The RZA-4XF Remote Annunciator requires the use of the LED Interface Module (4XLMF).
4XZMF Zone Relay Module (SK-4 only)
The Zone Relay Module provides Form-C relay contacts for the following:
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 4
System Alarm
System Trouble
As a jumper option, the first four relays described above can be made silenceable. The 4XZMF mounts to the SK-4 main circuit board, occupying one of the two sets of option module connectors.
Dress Panel DP-MS2/4
A dress panel DP-MS2/4 is optional. The dress panel restricts access to the system wiring while allowing access to the membrane switch panel.
Battery Box
The BB-17F battery box may be used to house two batteries greater than 7 Amp Hour to a maximum of 18 Amp Hour. The battery box mounts directly below the control panel cabinet, centered to the main circuit board. The BB-17F is red and is provided with knockouts.
411 and 411UD Digital Alarm Communicator/Transmitter
The three input/channel 411 and the four input/channel 411UD are dual line, digital alarm communicator/transmitters which can be used as slave communicators with the SK-4 FACP. The inputs/channels are compatible with normally open relay contacts, require ELRs (End-of-Line Resistors), are supervised and are fully programmable. The communicators interface with the public switched telephone network and are compatible with most central station receivers. Power supplied must be 12 or 24 volts, filtered and nonresettable. The communicators are mounted in a small metal enclosure, providing a variety of mounting options. Refer to the 411 or 411UD manual for additional information.
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 15
Notes
16 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010

Section 2: Installation

Figure 2.1 Backbox Mounting Dimensions
Bottom
Height=15.000”
(38.10 cm)
10.375”
(26.35 cm)
0.75”(1.9 cm)
2.875” (7.3 cm)
Backbox = 14.5”
(36.8 cm)
Depth = 3.000”
(7.62 cm)
Top
9.1” (23.1 cm)
2.7”
(6.86cm)
1.125” (2.868 cm)
Pem Studs
Backbox Mounting Holes
ms2-4cab.wmf
The cabinet can be surface mounted or semi-flush mounted using the optional Trim Ring P/N: TR­1-R. The door is removable during the installation period by opening and lifting if off the hinges.
The cabinet mounts using two key slots at the top of the backbox and two additional 0.250” diameter holes located at the bottom.
Carefully unpack the system and check for shipping damage. Select a location for the cabinet that is in a clean, dry, vibration-free area where extreme temperatures are not encountered. The area should be readily accessible with sufficient room to easily install and maintain the control panel. Locate the top of the cabinet approximately five feet above the floor with the hinge mounting on the left.
Determine the number of conductors required for the devices to be installed and determine the appropriate knockouts. All wiring must be in accordance with the National and/or Local codes for fire alarm systems and power supplies.

2.1 Backbox Mounting

1. Mark and predrill holes for the top two keyhole mounting bolts
2. Install two upper fasteners in the wall with the screw heads protruding approximately Ľ”
3. Using the upper keyholes, mount the backbox over the two screws
4. Mark the lower two holes, remove the backbox from the wall and drill the mounting holes
5. Mount the backbox, install the remaining fasteners and tighten all screws
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 17
Installation Backbox Mounting
Top
Depth = 2.875” (7.3 cm)
Door = 14.677” (37.28 cm)
Depth = 3.05”
(7.75cm)
Door = 15.342”
(38.97 cm)
Bottom
Battery Box = 8.5”
(21.59 cm)
Battery Box = 14.5”
(37.384 cm)
Depth = 4.75”
(12.065 cm)
Figure 2.2 Backbox and Battery Box
ms-4cabb.wmf
18 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
When using batteries larger than 7 Amp Hour (up to 18 Amp Hour), the BB-17F battery box (or UL-listed equivalent) must be installed. To install the BB-17F:
1. Mount the FACP cabinet to the wall.
2. Remove knockouts on the bottom of the FACP cabinet and top of the BB-17F.
3. Using conduit, hang the BB-17F from the FACP cabinet making sure there is at least 1/2” of clearance between the two cabinets.
4. Anchor the BB-17F to the wall.
Operating Power Installation
!
!
Figure 2.3 Operating Power Connections
Optional second transformer shown installed
Standard transformer
Earth ground wire shown connected to transformer mounting stud
ms4powr2.wmf

2.2 Operating Power

WARNING: DISCONNECT POWER
SEVERAL DIFFERENT SOURCES OF POWER CAN BE CONNECTED TO THIS PANEL. DISCONNECT ALL SOURCES OF POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The primary power source for the panel is 120 VAC, 50/60 Hz, 2.3 amps for the SK-2/SK-4 or 240 VAC, 50 HZ, 1.15 amps for the SK-2E/SK-4E. Run a pair of wires (with ground conductor) from the protected premises main breaker box to TB8 of the main circuit board. As per the National Electrical Code, use 14 AWG (2.00 mm connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect devices. A separate Earth Ground connection must be made to ensure proper panel operation and lightning and transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm
Earth Ground connection since this does not provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to J8 on the main circuit board using the plug-in connector and cable provided. The battery charger is current-limited and capable of charging sealed lead acid batteries. The charger shuts off when the system is in alarm.
2
, 1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other equipment may be
2
)] to the transformer mounting stud. Do not use conduit for the
WARNING: BATTERIES CONTAIN SULFURIC ACID
BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID, IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK IMMEDIATE MEDICAL ATTENTION.
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 19
Installation Input Circuits
Figure 2.4 IDC Connections
Class B Initiating Device Circuits (supervised and power-limited)
4.7 K, ½ watt resistor P/N:71252
UL listed compatible 2-wire smoke detectors
manual pull stations
heat detectors
Dummy load all unused circuits - 4.7 K, ½ watt resistor (P/N: 71245)
Note: Zones 3 & 4 on SK-4 only
ms-4idc.wmf
UL listed Power Supervision Relay
(refer to Device Compatibility Document for list of compatible relays)
Resettable 24 VDC 4-wire smoke detector power (500 mA maximum)
UL listed compatible 4-wire smoke detector

2.3 Input Circuits

The SK-2 has two IDCs (Initiating Device Circuits) and the SK-4 has four IDCs. Each circuit is
3
compatible with System Sensor’s i
smoke detectors which generate a maintenance signal when the detector becomes dirty and a separate supervisory ‘freeze’ signal when ambient temperature falls below the detector rating. The maximum loop resistance limit for each IDC is 100 ohms. The field wiring for each zone is supervised for opens, shorts and ground faults (zero impedance to ground). All conditions are visually and audibly annunciated.
3
Each circuit is configured for Style B (Class B) operation and will accept I
smoke detectors, any normally-open contact devices as well as conventional 2-wire or 4-wire, 24 VDC smoke detectors. In addition, Zone 1 (IDC 1) on the SK-2 and Zone 2 (IDC2) on the SK-4 can be programmed as combination supervisory and waterflow zones. Refer to the Silent Knight Device Compatibility Document for a list of compatible devices.
SK-4 Initiating Device Circuits can be converted to Style D (Class A) by installing the optional Class A Converter module. Refer to “CAC-4 Class A Converter Module (SK-4 only)” on page 25.
20 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Input Circuits Installation
Class B Initiating Device Circuits (supervised and power-limited)
4.7 K, ½ watt resistor P/N:71252
In-Line-Resistor
1.2 K, ½ watt resistor P/N: 75579
Alarm Switch (waterflow)
Dummy load all unused circuits - 4.7 K, ½ watt resistor (P/N: 71245)
Figure 2.5 Style B Combination Circuit on Zone 2 of the SK-4
Supervisory Switch (tamper)
Supervisory Switch (tamper)
Note: Zones 3 & 4 on SK-4 only
ms-4zon1.wmf
Combination Waterflow/Supervisory Zone
A combination Waterflow/Supervisory circuit allows an FACP to distinguish between an Alarm switch (waterflow device) and a Supervisory switch (tamper) installed on the same circuit. The following figure illustrates the wiring of Zone 2 as a Style B (Class B) Waterflow/Supervisory circuit. Note that only
Zone 1 on the SK-2 and Zone 2 on the SK-4 can be configured in this
manner.
Requirements for the Combination Waterflow/Supervisory circuit are as follows:
The Waterflow Alarm Switch(es) must connect to the FACP Initiating Device Circuit before
the In-Line Resistor as shown in Figure 2.5
The Waterflow Supervisory Switch(es) must connect to the FACP Initiating Device Circuit
after the In-Line Resistor as shown in Figure 2.5
Program the FACP Initiating Device Circuit #1 on the SK-2 or Circuit #2 on the SK-4 as a
Combination circuit by placing SW1 DIP switch 8 to the ON position as described in “SW1 DIP Switch Settings” on page 35
Waterflow Alarm Switch activation causes the panel to latch into alarm until the alarm
condition is cleared and the FACP is reset
Supervisory Switch activation causes the panel to track the supervisory condition, that is,
the panel will clear when the supervisory condition is cleared (if FACP is programmed for Autoresettable Supervisory)
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 21
Installation Output Circuits
TB2
B+ B- B+ B­ NAC 1 NAC 2
Figure 2.6 NAC Connections
Class B Notification Appliance Circuits (supervised and power-limited)
4.7 K, ½ watt resistor P/N:71252
Dummy load any unused circuits (P/N: 71245)
Polarized Bell
Polarized Strobe
Polarized Horn
Polarized Horn
Polarized Horn-Strobe
Polarized Bell
Notification Appliance Circuit polarity shown in alarm condition
ms-4nac.wmf

2.4 Output Circuits

2.4.1 Notification Appliance Circuits

The SK-2 provides one Style Y (Class B) NAC (Notification Appliance Circuit) while the SK-4 provides two Style Y (Class B) NACs. Each circuit is capable of providing a maximum of 2.5 amps of current. Total current drawn from these as well as other DC power outputs cannot exceed
3.0 amps for the SK-2 or 6.0 amps for the SK-4 with the optional second transformer installed (refer to battery calculations section). Each circuit is supervised and power-limited. Refer to the Silent Knight Device Compatibility Document for a listing of compatible notification appliances.
The SK-4 NACs can be converted to Style Z (Class A) by installing the optional Class A Converter module. Refer to “CAC-4 Class A Converter Module (SK-4 only)” on page 25.
22 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Output Circuits Installation
TB1
Figure 2.7 Special Application Power
4-Wire Smoke Detector Power (500 mA)
24 VDC filtered, resettable special application power for 4-wire smoke detectors can be obtained from these terminals (power-limited)
Nonresettable Power (500 mA) -SK-4Only
24 VDC filtered, nonresettable special application power can be obtained from these terminals (power-limited)
+ - + -
ms-4tb1.wmf
TB5
TB6
TB7
TROUBLE C TRBL NORM
C NC NO
ALARM
SUPV
C NC NO
Figure 2.8 Relay Terminals
Note: Relay contacts are shown with
power applied to the panel and no active troubles, alarms or supervisories. The Trouble Relay is a fail-safe relay which will transfer on any trouble or total power failure.
ms4relay.wmf

2.4.2 Special Application DC Power Output Connections

Resettable 24 VDC special application power is available on both the SK-2 and SK-4 control panels. Nonresettable 24 VDC special application power is available only on the SK-4.

2.4.3 Relays

The SK-2 and SK-4 control panels provide an alarm and fail-safe trouble relay and the SK-4 also provides a supervisory relay. Each Form-C relay is rated for 2 amps @ 30VAC (resistive).
Note that relay connections may be power-limited or nonpower-limited, provided that 0.25” minimum spacing is maintained between conductors of power-limited and nonpower-limited circuits.
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 23
Installation Power-limited Wiring Requirements
ON
1 2
3 4 5 6 7 8
ON
1 2 3 4 5 6 7
8
ON
1 2 3 4 5 6 7 8
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
TROUBLE
TROUBLE
TROUBLE
TROUBLE
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
FIRE ALARM
FIRE ALARM
AC
POWER
NAC
DISABLE
NAC
FAULT
SYSTEM
TROUBLE
POWER
TROUBLE
WALK TEST
ALARM
SILENCE
ZONE
DISABLE
FIRE ALARM
FIRE ALARM
RESET
WALK TEST
ALARM
SILENCE
ACK
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE
ENABLE/DISABLE
3
4
2
1
TB1
TB2
TB3
TB5
TB6
TB7
+ - + -
Nonreset Resettable
C NC NO
ALARM SUPV
C NC NO
J8
J7
J9
TB8
JP1
SW1
BATTERY
HOT NEUT EARTH
TRANSFORMER 1TRANSFORMER 2
SW2 SW3
JP2
EARTH BATT CHG
4XLB
TB1
A+ A- A+ A-
NAC 1 NAC 2
CLASS A CLASS A
A+ A- A+ A-
ZONE 1 ZONE 2
CLASS A CLASS A
A+ A- A+ A-
ZONE 3 ZONE 4
CLASS A CLASS A
SIGNAL TRANSFORMER
XX-XXX-XXXXXX Rev X
SIGNAL TRANSFORMER
XX-XXX-XXXXXX Rev X
Figure 2.9 Typical UL Power-limited Wiring Requirements
Power-limited Circuits
Nonpower-limited Circuits
Power-limited Circuits
Nonpower-limited Circuit
AC Power
4XTMF
4XLMF
CAC-4
ms4ulpwr2.wmf

2.5 Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower­limited circuit wiring. Furthermore, all power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring diagram for the SK-4 is illustrated below.
24 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Installation of Optional Modules Installation
!
Figure 2.10 CAC-4 Module Installation
J1 Connector
SK-4 Main Circuit Board
Secure to Standoffs
Secure to Standoff
CAC-4 Module
ms4tocac.wmf

2.6 Installation of Optional Modules

CAUTION: DISCONNECT POWER
REMOVE ALL POWER (AC AND DC) BEFORE INSTALLING OR REMOVING MODULES OR WIRING.

2.6.1 CAC-4 Class A Converter Module (SK-4 only)

Installation
The CAC-4 Module can be used to convert the four Style B (Class B) Initiating Device Circuits to Style D (Class A) and the two Style Y (Class B) Notification Appliance Circuits to Style Z (Class A). The module plugs into connector J1 which is located at the top right of the SK-4 main circuit board.
Install the three supplied standoffs in the holes on the main circuit board as indicated in the following figure. Carefully align the connector on the CAC-4 with J1 on the FACP main circuit board and press the module securely into place. Make certain the pins are properly aligned to prevent bending or breaking of any connector pins.
Wiring NACs and IDCs for Class A
Wire the Style Z (Class A) Notification Appliance Circuits using TB2 of the SK-4 and TB1 of the CAC-4 module. Wire the Style D (Class A) Initiating Device Circuits using TB3 of the SK-4 and TB1 of the CAC-4. Make certain to observe polarity when connecting the devices to the circuits. The B+ and A+ terminals must comprise the feed and return for the positive side of a device and the B- and A- terminals must comprise the feed and return for the negative side of a device. To configure any of the zones for Class B when the CAC-4 is installed, simply wire to the B+ and B­input on the FACP terminal(s) and install the End-of-Line Resistor after the last device on the
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 25
Installation Installation of Optional Modules
Figure 2.11 Wiring NACs and IDCs for Class A Operation
CAC-4 Class A Converter Module
SK-4 Circuit Board
Class B (Style B)
IDC - 4.7 K
½ watt ELR
resistor
P/N:71252
(supervised and
power-limited)
Dummy load all unused circuits - 4.7 K ½ watt ELR resistor (P/N: 71245)
Polarized
Bell
Circuit polarities shown in alarm condition
Class A (Style Z) NAC
(supervised and power-limited)
Class A
(Style D) IDC
(supervised and
power-limited)
Class A
(Style D) IDC
Combo Waterflow &
Supervisory 20K, ½ watt ELR resistor P/N:75477
(supervised and
power-limited)
1.2 K ½ watt In-Line
resistor
P/N:75579
Polarized
Strobe
Polarized
Horn
Tamper
Tamper
Waterflow
Smoke
Smoke
Pull
Station
Pull
Station
Heat
Heat
IMPORTANT! All
devices must be
within 20 feet of the
Class A portion of
the circuit and
wiring must be in
conduit.
ms4comba.wmf
circuit. Do not wire to the corresponding A+ and A- terminals on the CAC-4 module. Note that Zone 1 IDC on the SK-2 and Zone 2 IDC on the SK-4 can be configured as a combination waterflow/supervisory circuit as illustrated in the following figure.

2.6.2 4XTMF, 4XLMF and 4XZMF Option Modules

SK-4: The 4XLMF LED Interface Module can only be plugged into connectors J3 and J5 on the SK-4 main circuit board. The 4XTMF and 4XZMF modules can be plugged into connectors J3 and J5 or can be installed.
SK-2: Only the 4XTMF module can be plugged into connectors J3 & J5 on the SK-2 main circuit board. (No other option modules can be installed on the SK-2).
26 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
J4 and J6 on the SK-4 main circuit board. A combination of any two of the three modules
Installation of Optional Modules Installation
ON
1 2 3 4 5 6 7 8ON1 2 3 4 5 6 7 8ON1 2 3 4 5 6 7 8
SUPERVISORY
SUPERVISORY
SUPERVISORY
SUPERVISORY
TROUBLE
TROUBLE
TROUBLE
TROUBLE
MAINTENANCE
MAINTENANCE
MAINTENANCE
MAINTENANCE
FIRE ALARM
FIRE ALARM
AC
POWER
NAC
DISABLE
NAC
FAULT
SYSTEM
TROUBLE
POWER
TROUBLE
WALK TEST
ALARM
SILENCE
ZONE
DISABLE
FIRE ALARM
FIRE ALARM
RESET
WALK TEST
ALARM
SILENCE
ACK
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE
ENABLE/DISABLE
3
4
2
1
TB1
TB2
TB3
TB5
TB6
TB7
J1
B+ B- B+ B­ NAC 1 NAC 2
+ - + -
Nonreset Reset
B+ B- B+ B­ ZONE 1 ZONE 2
B+ B- B+ B­ ZONE 3 ZONE 4
C TRBL NORM TROUBLE
C NC NO
ALARM SUPV
C NC NO
J3
J5
J4
J8
J7
J9
TB8
J6
JP1
JP3
SW1
BATTERY
HOT NEUT EARTH
TRANSFORMER 1TRANSFORMER 2
SW2 SW3
JP2
EARTH BATT CHG
CLASS A CONVERTER
Figure 2.12 4X Option Module Connection to SK-4
J3
J5
J4
J6
JP1 Jumper
Cut to install module on J3 & J5
JP2 Jumper
Cut to install module on J4 & J6
Standoffs
(when using
J3 & J5
ms4bord2.wmf
Standoffs
(when using
J4 & J6
The following steps must be followed when installing each of these modules:
1. Remove all power (AC and DC) from the FACP before installing the modules.
2. Cut jumper JP1 (for connectors J3 and J5) and/or JP2 (for connectors J4 and J6) on the main circuit board to allow the control panel to supervise the placement of any installed option module.
3. Install the two supplied metal standoffs in the locations indicated. These standoffs provide the required earth ground protection.
4. Carefully plug the connectors on the option module into connectors J3 and J5 or
J4 and J6 on
the FACP main circuit board, being careful not to bend any pins.
5. Secure the option module to the standoff on the main circuit board with the supplied screws.
6. When the installation has been completed, connect the wiring to the modules as indicated in the following sections.
7. Test system for proper operation.
4XTMF Transmitter Module Installation
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 27
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition to alarm and trouble reverse polarity. A jumper option allows the reverse polarity circuit to open with a system trouble condition if no alarm condition exists. A disable switch allows disabling of the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA Trip Current: 350 mA (subtracted from notification appliance power) Coil Voltage: 3.65 VDC
Installation Installation of Optional Modules
Figure 2.13 4XTMF Transmitter Module
Connect to:
• SK-4 Connectors J3 & J5 or J4 & J6
• SK-4 Connectors J3 & J5.
Disconnect Switch shown in disconnect position
TBL Jumper
Remote Alarm (power-limited)*Remote Trouble (power-limited)*
No connection
Municipal Box (nonpower-
limited)*
1+ 2­3+ 4­5 6+ 7-
Polarities are shown for module activation
Note: 4XTMF Module is not suitable for transmitting reverse polarity supervisory signal.
* Wiring from these terminals can exit the protected premises. Dummy load terminals 6 and 7 (4.7k, ¼ watt resistor) if Municipal Box is not connected.
Disconnect LED
4xtmf.wmf
Maximum Coil Resistance: 14.6 ohms Maximum allowable wire resistance between panel and trip coil: 3 ohms Municipal Box wiring can leave the building
Remote Station Service (NFPA 72 Remote Station Fire Alarm Systems) - Intended for connection to a polarity reversal circuit or a Remote Station receiving unit having compatible ratings:
Maximum load for each circuit: 10 mA Reverse polarity output voltage: 24 VDC Remote Alarm and Remote Trouble wiring can leave the building
Before installing the module, place the disconnect switch to the down (disconnect) position to prevent accidental activation of the municipal box. Note that a Disconnect LED will illuminate after the module is installed in the FACP. In addition, the System Trouble LED will turn on to indicate the Disconnect condition.
28 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Installation of Optional Modules Installation
Relay #1 through #4 will activate with Output #1 through #4 and remain latched unless ‘LATCH’ jumper is cut.
Use Disable Switch to disconnect the relays
Cut jumper for nonlatching (silenceable) relay operation
NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C
Relay #1
Relay #2
Relay #3
Relay #4
Alarm
Trouble
}
}
}
}
}
}
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
4xzma.wmf
power-limited circuit
power-limited circuit
}
}
}
}
NO NC
C NO NC
C NO NC
C NO NC
C
Relay #1
Relay #2
Relay #3
Relay #4
{
{
{
{
no connection
Figure 2.14 4XZMF Zone Relay Module
4xzma.wmf
nonpower-limited circuit
nonpower-limited circuit
4XZMF Zone Relay Module (SK-4 only)
The 4XZMF provides four zone alarm, one system alarm and one system trouble Form-C relays. Nonpower-limited and power-limited wiring must have a minimum distance of 0.25”, wire to wire. If this module is used to drive nonpower-limited and power-limited circuits, follow the instructions below:
1. Skip a set of dry contacts to maintain the 0.25” required space between power-limited and nonpower-limited circuits. The wiring of this module must follow the requirements as specified in “Power-limited Wiring Requirements” on page 24.
OR
2. If this module is needed to drive power-limited and nonpower-limited relays that are next to each other, refer to the following illustration which shows a typical connection:
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 29
Installation Installation of Optional Modules
4XLB
Figure 2.15 4XLMF LED Interface Module
Front View of RZA-4XF
Side View
Single-gang Box
4XLMF Module
Note: Make wiring connections with system
power off. Maximum wire impedance is 50 ohms per wiring connection.
+24 VDC Out #1 Out #2 Out #3 Out #4 System Trouble Sound Resound
1 2 3 4 5 6 7 8
Connect to corresponding terminals of
RZA-4XF Remote Annunciator
4xlma.wmf
rza-4xf.wmf
rza-4xbx.wmf
4XLMF LED Interface Module (SK-4 only)
The 4XLMF supports the RZA-4XF Remote Annunciator module. The wiring of this module must follow the requirements as specified in “Power-limited Wiring Requirements” on page 24.
Important: The 4XLMF module can only circuit board.
be installed on connectors J3 and J5 of the SK-4 main
30 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Notes
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 31

Section 3: Program Options via DIP Switch

Figure 3.1 Field Programming DIP Switches
Switches 1 through 7 shown in OFF position
Switch 8 shown in ON position
ms4switc.wmf
To remove dip switch cover, remove the two screws, pull upper arm (A) partially from hole, then unhook the bottom side of cover (B) from circuit board edge. Replace when programming is complete.
cover2.wmf
screws
(B)
(A)
This section describes the programming options available via DIP switch settings. The FACP can be field programmed using option DIP switches SW1, SW2, and SW3 which are located in the bot­tom right side of the main circuit board. A factory-installed dip switch cover, which prevents acci­dental programming, must first be removed. Once programming is complete, the cover must be reinstalled. Refer to the following illustration for switch locations and DIP switch placement in the ON and OFF positions.
32 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
DIP Switch Settings Program Options via DIP Switch

3.1 DIP Switch Settings

The following tables list the programmable features for the SK-2 and SK-4. Placing a DIP switch in the ON position will select the feature while placing the DIP switch in the OFF position will deselect the feature. The exceptions to this rule are SW3 DIP switches 5 & 6. These two switches are used to select the Notification Appliance Circuit synchronization feature. A detailed description of each feature is presented in the following pages.
Important: When any programmable feature is changed by repositioning a DIP switch, the FACP Reset button must be pressed to ensure that the control panel can read the new switch position.
Switch Number DIP Switch Number DIP Switch ON
1 Silence Inhibit
2 Auto-silence
3 Temporal Coding
4 Selective Silence (if sync. enabled)
SW1
5 Trouble Reminder
6 AC Trouble Delay
7 Autoresettable Supervisory
8 IDC Combination
Waterflow/Supervisory Circuit
SW2
SW3
1 not used
2 not used
3 IDC1 Verification
4 IDC1 Supervisory
5 IDC2 Verification
6 IDC2 Supervisory
7 not used
8 not used
1 NAC1 Nonsilenceable
2 NAC1 Disable
3 not used
4 not used
5 & 6
used to select strobe
synchronization feature as
shown to the right
7 Nonsilenceable Waterflow for
8spare
Switch 5 Switch 6
No Synchronization OFF OFF
System Sensor Synchronization ON OFF
Gentex Synchronization OFF ON
Wheelock Synchronization ON ON
Combination Circuit (only if SW1 switch 8 is ON)
Table 3.1 SK-2 DIP Switch Settings
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 33
Program Options via DIP Switch DIP Switch Settings
Switch Number DIP Switch Number DIP Switch ON
1 Silence Inhibit
2 Auto-silence
3 Temporal Coding
4 Selective Silence (if sync. enabled)
SW1
5 Trouble Reminder
6 AC Trouble Delay
7 Autoresettable Supervisory
SW2
SW3
8 IDC Combination
1 IDC1 Verification
2 IDC1 Supervisory
3 IDC2 Verification
4 IDC2 Supervisory
5 IDC3 Verification
6 IDC3 Supervisory
7 IDC4 Verification
8 IDC4 Supervisory
1 NAC1 Nonsilenceable
2 NAC1 Disable
3 NAC2 Nonsilenceable
4 NAC2 Disable
5 & 6
used to select strobe
synchronization feature as
shown to the right
Waterflow/Supervisory Circuit
Switch 5 Switch 6
No Synchronization OFF OFF
System Sensor Synchronization ON OFF
Gentex Synchronization OFF ON
Wheelock Synchronization ON ON
7
8spare
Nonsilenceable Waterflow for Combination Circuit (only if SW1 switch 8 is ON)
Table 3.2 SK-4 DIP Switch Settings
34 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
DIP Switch Settings Program Options via DIP Switch

3.1.1 SW1 DIP Switch Settings

Silence Inhibit
Switch 1, placed in the ON position, selects the Silence Inhibit feature. This feature prevents the silencing or resetting of the NACs (Notification Appliance Circuits) for a period of one minute after initiation of an alarm. Placing switch 1 to the OFF position deselects the Silence Inhibit fea­ture. The factory default setting is switch 1 OFF for no Silence Inhibit.
Auto-silence
Switch 2, placed in the ON position, selects the Auto-silence feature. This feature automatically silences all NACs, programmed for silenceable operation, ten minutes after alarm activation. A new activation on another zone will resound the NACs. The factory default setting is switch 2 OFF for no Auto-silence.
Temporal Coding
Switch 3, placed in the ON position, selects the Temporal Coding feature. This feature causes the NACs to pulse, off, continually repeating this pattern while activated. The factory default setting is switch 3 OFF for no Temporal Coding, which will cause the NACs to sound a steady signal when activated.
Note that Temporal Coding is disabled if Strobe Synchronization is enabled.
Selective Silence
½ second on, ½ second off, ½ second on, ½ second off, ½ second on, 1½ seconds
Switch 4, placed in the ON position, selects the Selective Silence feature. This feature allows the use of various manufacturer’s horn strobe mute protocols. When Selective Silence is enabled and the Synchronization feature is selected (refer to“Strobe Synchronization” on page 38), pressing the Silence button will turn off all silenceable audible devices while leaving on the visual devices, such as strobes. The factory default setting is switch 4 OFF for no Selective Silence.
NOTE: Enabling Selective Silence but not Synchronization will cause audible and visual devices to be turned off when the Silence button is pressed.
Trouble Reminder
Switch 5, placed in the ON position, selects the Trouble Reminder feature. This feature causes the FACP piezo to sound every 15 seconds for alarms and every two minutes for troubles after the alarms or troubles have been silenced. In addition, the piezo will resound 24 hours after a trouble has been silenced but not cleared. The factory default setting is switch 5 OFF for Trouble Reminder disabled.
AC Trouble Delay
Switch 6, placed in the ON position, selects the AC Trouble Delay feature. This feature allows the FACP to delay trouble activation for six hours following an AC loss or brownout condition. The factory default setting is switch 6 OFF for no AC Trouble Delay.
Autoresettable Supervisory
Switch 7, placed in the ON position, selects the Autoresettable Supervisory feature. This feature causes the IDCs (Initiating Device Circuits), programmed as supervisory circuits, to automatically reset (nonlatching) after the alarm condition has been cleared. The factory default setting is switch 7 OFF for no Autoresettable Supervisory.
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 35
Program Options via DIP Switch DIP Switch Settings
78 sec.
18 sec.
0 sec.
CONFIRMATION
RETARD
Alarm Ignored
Control Panel Processes Alarm if Same Detector is Still in Alarm
Control Panel Immediately Processes Alarm
Detector Alarm Verification (Reset/Retard + Confirmation)
Detector Goes Into Alarm
Detector Alarms on Different Zone During First Detector's Verification Period
6 sec.
RESET
IDC Combination Circuit
Switch 8, placed in the ON position, sets IDC #1 on the SK-2 or IDC #2 on the SK-4 as a combina­tion circuit. A combination zone can be used for monitoring supervisory devices such as valve tamper switches and alarm devices such as waterflow switches. Supervisory conditions, which latch via software, can be silenced by pressing the Acknowledge and then Silence buttons. The fac­tory default setting is switch 8 OFF for no Combination circuit.

3.1.2 SW2 DIP Switch Settings

IDC1 Verification (SK-4 only)
Switch 1 only on the SK-4, placed in the ON position, selects the Verification feature for IDC (Ini­tiating Device Circuit) #1. When Verification is selected the following events will occur when a smoke detector activates:
1. FACP removes power from all zones for 6 seconds, resetting all smoke detectors
2. Power is reapplied and a 12 second retard period begins, allowing detectors to stabilize
3. During the 18 second reset/retard periods of steps 1 & 2, subsequent alarms by the same zone are ignored
4. Alarms detected on any other zone during the retard period will cause the FACP to immediately process the alarm
5. A 60 second confirmation period follows the reset/retard period. If an alarm occurs during the confirmation period, on the zone which initiated verification, the FACP will immediately process the alarm. If no alarm is detected during this confirmation period, the FACP returns to normal condition
Important! Circuits selected for verification must have only smoke detectors installed
The factory default setting is switch 1 OFF for no IDC1 Verification.
IDC1 Supervisory (SK-4 only)
Switch 2 only on the SK-4, placed in the ON position, programs IDC #1 as a Supervisory circuit. A supervisory zone can be used for monitoring supervisory devices such as sprinkler tamper switches. A supervisory activation will pulse the piezo sounder at a ½ second rate and flash the zone supervi­sory LED at the same rate. The factory default setting is switch 2 OFF for no IDC1 Supervisory.
IDC1 Verification for SK-2 or IDC2 Verification for SK-4
Switch 3, placed in the ON position, selects the Verification feature for IDC #1 on the SK-2 or IDC #2 on the SK-4. The factory default setting is switch 3 OFF for no Verification. Refer to IDC1 Ver­ification (SK-4 only) for a description of this feature.
36 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
DIP Switch Settings Program Options via DIP Switch
IDC1 Supervisory for SK-2 or IDC2 Supervisory for SK-4
Switch 4, placed in the ON position, programs IDC #1 on the SK-2 or IDC #2 on the SK-4 as a Supervisory circuit. A supervisory zone can be used for monitoring supervisory devices such as sprinkler tamper switches. A supervisory activation will pulse the piezo sounder at a ½ second rate and flash the zone supervisory LED at the same rate. The factory default setting is switch 2 OFF for no Supervisory.
IDC2 Verification for SK-2 or IDC3 Verification for SK-4
Switch 5, placed in the ON position, selects the Verification feature for IDC #2 on the SK-2 or IDC #3 on the SK-4. The factory default setting is switch 5 OFF for no Verification. Refer to “IDC1 Verification (SK-4 only)” on page 36 for a description of this feature.
IDC2 Supervisory for SK-2 or IDC3 Supervisory for SK-4
Switch 6, placed in the ON position, programs IDC #2 on the SK-2 or IDC #3 on the SK-4 as a Supervisory circuit. A supervisory zone can be used for monitoring supervisory devices such as sprinkler tamper switches. A supervisory activation will pulse the piezo sounder at a ½ second rate and flash the zone supervisory LED at the same rate. The factory default setting is switch 6 OFF for no Supervisory.
IDC4 Verification (SK-4 only)
Switch 7 only on the SK-4, placed in the ON position, selects the Verification feature for IDC #4. The factory default setting is switch 7 OFF for no IDC4 Verification. Refer to “IDC1 Verification (SK-4 only)” on page 36 for a description of this feature.
IDC4 Supervisory (SK-4 only)
Switch 8 only on the SK-4, placed in the ON position, programs IDC #4 as a Supervisory circuit. A supervisory zone can be used for monitoring supervisory devices such as sprinkler tamper switches. A supervisory activation will pulse the piezo sounder at a ½ second rate and flash the zone supervi­sory LED at the same rate. The factory default setting is switch 8 OFF for no IDC4 Supervisory.

3.1.3 SW3 DIP Switch Settings

NAC1 Nonsilenceable
Switch 1, placed in the ON position, programs NAC #1 as a nonsilenceable circuit. Selecting this feature will prevent the notification appliances on NAC #1 from being silenced by the Autosilence feature or by pressing the Alarm Silence button. The factory default setting is switch 1 OFF for silenceable circuit.
NAC1 Disable
Switch 2, placed in the ON position, will disable NAC #1, preventing the notification appliances from activating. This feature may be used during maintenance or while testing the system to pre­vent building evacuation. The FACP will indicate an NAC disabled fault and system trouble while this feature is selected. The factory default setting is switch 2 OFF for NAC1 enabled.
NAC2 Nonsilenceable (SK-4 only)
Switch 3 only on the SK-4, placed in the ON position, programs NAC #2 as a nonsilenceable cir­cuit. Selecting this feature will prevent the notification appliances on NAC #2 from being silenced by the Autosilence feature or by pressing the Alarm Silence button. The factory default setting is switch 3 OFF for silenceable circuit.
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 37
Program Options via DIP Switch DIP Switch Settings
NAC2 Disable (SK-4 only)
Switch 4 only on the SK-4, placed in the ON position, will disable NAC #2, preventing the notifi­cation appliances from activating. This feature may be used during maintenance or while testing the system to prevent building evacuation. The FACP will indicate an NAC disabled fault and sys­tem trouble while this feature is selected. The factory default setting is switch 4 OFF for NAC2 enabled.
Strobe Synchronization
Switches 5 and 6 are used to program the Synchronization feature. This feature controls the activa­tion of notification appliances in such a way that all devices will turn on and off at exactly the same time, This is particularly critical when activating strobes which must be synchronized to avoid ran­dom activation and a potential hazard or confusion. The FACP can be programmed to operate with a variety of manufacturer’s devices. The following table lists the required switch settings to accomplish synchronization:
Synchronization Feature Switch 5 Switch 6
No Synchronization OFF OFF
System Sensor Synchronization ON OFF
Gentex Synchronization OFF ON
Wheelock Synchronization ON ON
The factory default setting is switches 5 and 6 OFF for No Synchronization.
Maximum Number of Strobes for Synchronization
The total current draw for each Notification Appliance Circuit cannot exceed 2.5 amps. Refer to the manufacturer’s documentation supplied with the strobes to determine the maximum current draw for each strobe and ensure that the circuit maximum is not exceeded.
To ensure proper strobe and circuit operation, there is also a limit to the number of strobes that can be attached to each circuit. Following is a list of the strobes that have been tested with this FACP and the maximum number that can be connected to each NAC. Make sure that the NAC maximum
current is not exceeded:
System Sensor: 40 Strobes
Wheelock: 25 Strobes
Gentex: 23 Strobes
Nonsilenceable Waterflow for Combination Circuit
If SW1 switch 8 is set to the ON position to select a Combination Waterflow/Supervisory Circuit (refer to“IDC Combination Circuit” on page 36) and SW3 switch 7 is set to the ON position to select the Nonsilenceable Waterflow for the Combination Circuit option, the following conditions will occur:
SK-2 - NACs become nonsilenceable upon acitvation of IDC #1 (Combination Circuit)
SK-4 - NACs become nonsilenceable upon activation of IDC #2 (Combination Circuit)
Notes:
1. If initial alarm activations are from IDCs other than the Combination Circuit, the NACs will be either silenceable or nonsilenceable, depending on the setting of SW3 switches 1 and 3 (refer to “NAC1 Nonsilenceable” on page 37 and “NAC2 Nonsilenceable (SK-4 only)” on page 37).
2. If alarm activation is from the Combination Circuit programmed for nonsilenceable, all NACs will be nonsilenceable regardless of subsequent IDC activations.
Spares
Switch 8 is a spare switch and has no function at this time. The switch should therefore be left in the factory default setting of OFF.
38 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Notes
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 39

Section 4: Operating Instructions

The SK-2 and SK-4 have two modes of operation which are Normal and Walktest modes. Upon initial power-up, the system will be in Normal Mode. This section discusses operation of the control panel in the Normal Mode.

4.1 Switch Functions in Normal Mode

4.1.1 ACK - Acknowledge

The Acknowledge button, which is located on the FACP membrane switch panel, silences the system piezo sounder and changes all flashing system LEDs to on steady. Pressing the Acknowledge button will have no effect on the Notification Appliance Circuits. To activate, press and hold the Acknowledge button for a minimum of one second.

4.1.2 Silence

Pressing the Silence button, which is located on the FACP membrane switch panel, silences the system piezo sounder, turns off the silenceable Notification Appliance Circuits and turns on the Alarm Silence LED. The Silence button will be ignored for nonsilenceable waterflows and NACs. Upon the occurrence of a subsequent event (alarm or trouble), Silence is overridden and the control panel will respond to the new event. To activate, press the Silence button for a minimum of one second.
NOTE: If Silence Inhibit has been enabled, NACs cannot be silenced for one minute following initiation of an alarm.

4.1.3 Zone Enable/Disable

To disable a zone, press the corresponding Zone Enable/Disable button. The Zone Disable and system Trouble LEDs will blink, as well as the Trouble LED for the disabled zone. To enable the zone, press the Zone Enable/Disable button a second time.

4.1.4 Reset/(Lamp Test)

The system Reset button, which is located on the FACP membrane switch panel, resets the system and any smoke detectors. Each press of the Reset button will cause the following:
Clear all status LEDs
Turn off the Notification Appliance Circuits
Reset all zones by temporarily removing power
Silence the onboard piezo sounder
Restore all system relays to normal
Temporarily remove power from the resettable power output
NOTE: If Silence Inhibit is active, a panel reset cannot occur for one minute.
Any alarm, supervisory or trouble condition that exists after a system reset will resound the system, reactivating appropriate system activity. Any zones that were disabled before the reset will be disabled after the reset.
Lamp Test When the Reset button is pressed and then released, the FACP will perform a Lamp Test. All panel LEDs will be turned on and the piezo will sound for approximately two seconds.
40 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Walktest Operating Instructions
!

4.1.5 Walktest

The Walktest button, which is located on the FACP membrane switch panel, allows a panel walktest to be performed. Pressing and holding the Walktest button for a minimum of two seconds causes the FACP to enter audible walktest. Pressing the Walktest button and then the Silence button and holding both for a minimum of two seconds will cause the panel to enter silent walktest. Walktest can be exited by pressing and holding the Walktest button for a minimum of three seconds or by pressing the Reset button. Refer to “Walktest” for a complete description of this feature.

4.2 Walktest

Walktest allows the testing of all control panel IDCs (input zones). An audible or silent walktest may be performed.
WARNING: NO FIRE PROTECTION
IT IS IMPORTANT TO NOTE THAT WHILE THE FACP IS IN WALKTEST MODE, THE CONTROL PANEL IS IN AN OFF-NORMAL CONDITION AND DOES NOT PROVIDE FIRE PROTECTION.
It should also be noted that the trouble relay will be activated while the control panel is in Walktest mode. Placing the control panel into Walktest mode will only be possible if the system has no active alarms.
Prior to initiating a walktest, check to make certain that all system faults have been cleared. Upon entering Walktest mode, the following conditions should occur:
Trouble relay will activate
Alarm relay will be disabled
Supervision relay will be disabled (SK-4 only)
Piezo sounder will be disabled
3
•I
smoke detectors will enter their own test mode causing their LEDs to flash twice every five
seconds (refer to the i
3
specification document)
All alarm conditions will be displayed as they occur by blinking zone alarm LED
All zone troubles will be displayed as they occur by blinking zone trouble LED
During walktest, the FACP zone LEDs will blink for the first activation on a zone. Subsequent activations on the same zone will cause the corresponding zone LED to blink the number of alarms on the zone since the start of the test, followed by a two second pause and then a repeat of the sequence.
Note that following a zone activation, a 6 second reset for conventional and 60 second reset for I
3
detectors is initiated. No new alarms or troubles will be detected during this reset period.
Disabled zones will not respond during Walktest. A zone may be disabled while in Walktest mode, should a faulty device be detected. This allows the user to return the system to Normal mode, enabling all other zones while preventing the faulty zone from triggering a false alarm.
Audible Walktest
To perform an audible Walktest, press and hold the Walktest button for a minimum of two seconds. The Trouble and Walktest LEDs will blink at a ¼ second rate.
While testing input devices, the first initiating device activated on a zone will cause the NACs to sound for four seconds. Subsequent device activations on the same zone will cause the NACs to turn on for one second. Any smoke detectors that are activated will automatically be reset by the panel. Zone faults (open circuits) will cause the NACs to remain on steadily until the fault is cleared.
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 41
Operating Instructions Status LEDs
During an audible walktest, if a device remains latched in alarm (such as a Pull Station that is not reset after activation), subsequent testing of devices on the same zone will not Be certain to reset or clear each device after testing.
Silent Walktest
To perform a silent Walktest, press the Walktest button, then press the Alarm Silence button and hold both for a minimum of two seconds. The Trouble, Walktest and Alarm Silence LEDs will blink at a ¼ second rate.
A silent walktest will not activate the control panel Notification Appliance Circuits. All alarm and trouble conditions must be observed using the LEDs at the control panel as described in the previous sections.
Exiting Walktest Mode
Walktest mode can be exited by pressing and holding the Walktest button for a minimum of three seconds or by pressing the Reset button. The time-out feature will cause the control panel to
automatically exit Walktest mode if no button presses have occurred for one hour.
trigger the NACs.

4.3 Status LEDs

AC Power LED
A green LED that remains on while the AC power supply is within correct limits. If this indicator fails to light under normal conditions, service the system immediately.
NAC Disable LED
A yellow LED that blinks to indicate that a Notification Appliance Circuit has been disabled using the main circuit board DIP switches. The LED will turn on steady when the Acknowledge or Alarm Silence button is pressed.
Zone Disable LED
A yellow LED that blinks to indicate that one or more alarm zones have been disabled using the Zone Enable/Disable buttons. The disabled zone’s trouble LED will also be on. The Acknowledge or Alarm Silence button does not affect the Zone Disable LED.
NAC Fault LED
A yellow LED that blinks to indicate that an NAC trouble condition exists in the system. The LED turns on steady when the Acknowledge or Alarm Silence button is pressed.
System Trouble LED
A yellow LED that blinks to indicate that a system fault or abnormal condition exists and that the fire alarm system may be inoperative. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Power Trouble LED
A yellow LED that blinks to indicate an AC power, battery or charger trouble condition. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Walktest LED
A yellow LED that blinks to indicate that the control panel is in Walktest mode. The Acknowledge and Alarm Silence buttons do not affect the Walktest LED.
Alarm Silence LED
A yellow LED that turns on to indicate that an Alarm condition exists in the system but the Notification Appliance Circuits and the local piezo sounder have been silenced.
42 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Operation Operating Instructions
Zone Fire Alarm LED
A red LED for each zone that blinks to indicate that an alarm exists on the corresponding zone. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Zone Supervisory LED
A yellow LED for each zone that blinks if the zone has been programmed for supervisory and a supervisory condition exists on the corresponding zone. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Note that an i
3
smoke detector freeze condition is displayed as a supervisory condition. The zone
does not have to be programmed as a supervisory for this to occur.
Zone Trouble LED
A yellow LED for each zone that blinks to indicate that a trouble exists on the corresponding zone. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Zone Maintenance LED
A yellow LED for each zone that blinks to indicate that a I
3
smoke detector on the corresponding zone is dirty or in need of maintenance. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Earth Fault LED (on main circuit board)
A yellow LED that blinks to indicate a ground fault condition on the system. A ground fault occurs when zero impedance between the FACP and earth ground exists. The LED turns on steady when the Acknowledge or Alarm Silence button is pressed.
Battery Fault LED (on main circuit board)
A yellow LED that blinks to indicate a low battery or no battery condition on the FACP. It turns on steady when the Acknowledge or Alarm Silence button is pressed.
Charger Fault LED (on main circuit board)
A yellow LED that blinks to indicate a battery charger fault. It turns on steady when the Acknowledge or Alarm Silence button is pressed.

4.4 Operation

Normal mode is the standard mode of operation. In this mode, the panel continuously monitors system status. When no alarm or trouble conditions exist, the control panel will be in the following state:
all LEDs will be off (except the AC Power LED)
the Notification Appliance Circuits will be off
all relays are in their normal state
the onboard piezo sounder will be off
3
smoke detectors will be polled for maintenance and freeze conditions on initial entry into
•i
Normal mode. Thereafter, each device will be polled every hour for freeze and every four hours for maintenance conditions
All alarm and system trouble conditions are annunciated on the control panel’s LEDs.
NOTE: To ensure that the system is functioning properly, the FACP will perform a freeze check
five minutes after the panel is reset, followed by a maintenance check. If there is no freeze or maintenance condition, the panel will continue to monitor for freeze conditions every hour and maintenance conditions every four hours.
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 43
Operating Instructions Operation

4.4.1 Fire Alarm Response

The control panel will, upon detection of an alarm condition, cause the following:
Latch the alarm condition - requires panel reset to clear alarm condition
Blink the Zone Alarm LED one second On and one second Off
Turn on remote annunciator alarm LED and piezo sounder
Turn the Notification Appliance Circuit(s) on
Turn the FACP piezo sounder on steady
Turn on the alarm relay
Start the Silence Inhibit, Auto-silence and Trouble Reminder functions if enabled

4.4.2 Fire Alarm Restoral

The control panel returns to normal after all alarms have been cleared and a system reset button has been pressed (pull stations have been reset, smoke detectors have reset and no smoke is present, waterflow has stopped). The control panel will perform the following upon restoral of all active alarms:
Turn off the FACP Zone Alarm LED
Turn off remote annunciator alarm LED and piezo sounder
Turn off the Notification Appliance Circuit(s)
Turn off the FACP piezo sounder
Turn off the alarm relay
3
smoke detectors will be polled for maintenance and freeze conditions on initial entry into
•i
Normal mode. Thereafter, each device will be polled every hour for freeze and every four hours for maintenance conditions

4.4.3 System Supervisory Condition Response

Zones can be programmed for supervisory in applications where a waterflow sensing device has been employed and a sprinkler tamper switch is to be monitored. An I condition (detected abnormally low ambient temperature) will also generate a supervisory condition on its alarm zone (refer to the I supervisory condition will cause the control panel to perform the following functions:
Blink the FACP Zone Supervisory LED ½ second On and ½ second Off
Pulse the piezo sounder ½ second On and ½ second Off
Turn on the supervisory relay (SK-4 only)
3
specification sheet for temperature threshold). Any

4.4.4 System Supervisory Restoral Response

When the supervisory condition has been cleared, the control panel will perform the following:
Turn off the FACP Zone Supervisory LED
Turn off the piezo sounder
Turn off the supervisory relay (SK-4 only)

4.4.5 Trouble Condition Response

The control panel, upon detection of one or more trouble conditions, well perform the following:
Blink the FACP System Trouble LED one second On and one second Off
Blink the FACP Zone Trouble LED one second On and one second Off
Turn on remote annunciator Trouble LED and pulse the piezo sounder
3
detector in a ‘freeze’
44 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Operation Operating Instructions
Pulse the FACP piezo sounder one second On and one second Off
Transfer fail-safe Trouble relay
Additional LEDs will turn on or blink according to the specific trouble
NAC Disable LED if NAC has been disabled
Zone Disable LED if a zone has been disabled
NAC Fault LED if a fault is detected on an NAC
Power Trouble LED if an AC, battery or charger fault is detected
AC Power LED will turn off if AC fail or brownout occurs
Alarm Silence LED if Silence button is pressed after an alarm or trouble
Walktest LED if Walktest mode is entered
Zone Maintenance LED if a I
Earth Fault LED if a ground fault occurs (zero impedance to ground)
Battery Fault LED if low or no battery condition occurs
Charger Fault LED if a charger trouble occurs
3
smoke detector needs servicing

4.4.6 Trouble Condition Restoral

The control panel performs the following upon restoral of all trouble conditions:
Turn off the FACP System Trouble LED
Turn off the FACP Zone Trouble LED
Turn off the remote annunciator Trouble LED and piezo sounder
Turn off the piezo sounder
Transfer the fail-safe Trouble relay
Turn off additional LEDs corresponding to specific troubles
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 45

Section 5: Power Supply Calculations

5.1 Overview

This section contains instructions and tables for calculating power supply currents in alarm and standby conditions. This is a four-step process, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the system
2. Calculating the power supply load current for non-fire and fire alarm conditions and
calculating the secondary (battery) load
3. Calculating the size of batteries required to support the system if an AC power loss occurs
4. Selecting the proper batteries for your system

5.2 Calculating the AC Branch Circuit

The control panel requires connection to a separate, dedicated AC branch circuit, which must be labeled FIRE ALARM. This branch circuit must connect to the line side of the main power feed of the protected premises. No other non-fire alarm equipment may be powered from the fire alarm branch circuit. The branch circuit wire must run continuously, without any disconnect devices, from the power source to the control panel. Overcurrent protection for this circuit must comply with Article 760 of the National Electrical Codes as well as local codes. Use 14 AWG (2.00 mm wire with 600 volt insulation for this branch circuit.
Use Table 5.1 , to determine the total amount of current, in AC amperes (A), that must be supplied to the system.
2
)
Device Type
SK-2/SK-4
or
SK-2E/SK-4E
Number of
Devices
1X
[ ] X =
[ ] X [ ] =
Sum Column for AC Branch Current Required =
Current Draw
(AC amps)
2.3 or
1.15
=
Table 5.1 120/240 VAC Branch Circuit Requirements
Total Current per
Device
46 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Calculating the System Current Draw Power Supply Calculations

5.3 Calculating the System Current Draw

5.3.1 Overview

The control panel must be able to power all internal and external devices continuously during the non-fire alarm condition. To calculate the non-fire alarm load on the system power supply when primary power is applied, use Calculation Column 1 in Table 5.3 on page 48. The control panel must support a larger load current during a fire alarm condition. To calculate the fire alarm load on the power supply, use Calculation Column 2 in Table 5.3 on page 48. The secondary power source (batteries) must be able to power the system during a primary power loss. To calculate the non-fire alarm load on the secondary power source, use Calculation Column 3 in Table 5.3 on page 48.
When calculating current draw and the battery size, note the following:
‘Primary’ refers to the main power source for the control panel
‘Secondary’ refers to the control panel’s backup batteries
All currents are given in amperes (A). Table 5.2 shows how to convert milliamperes and microamperes to full amperes.
To convert... Multiply Example
Milliamperes (mA) to amperes (A)
Microamperes ( amperes (A)
µA) to
Table 5.2 Converting to Full Amperes
mA x 0.001 3 mA x 0.001 = 0.003A
µA x 0.000001 300 µA x 0.000001 = 0.0003 A

5.3.2 How to Use Table 5.3 on page 48 to Calculate System Current Draw

Use Table 5.3 on page 48 to calculate current draws as follows:
1. Enter the quantity of devices in all three columns.
2. Enter the current draw where required. Refer to the Silent Knight Device Compatibility Document for compatible devices and their current draw.
3. Calculate the current draws for each in all columns.
4. Sum the total current for each column.
5. Copy the totals from Column 2 and Column 3 to Table 5.4 on page 49.
Following are the types of current that can be entered into Table 5.3 on page 48:
Calculation Column 1 - The primary supply current load that the control panel must
support during a non-fire alarm condition, with AC power applied.
Calculation Column 2 - The primary supply current load that the control panel must
support during a fire alarm condition, with AC power applied.
Calculation Column 3 - The standby current drawn from the batteries in a non-fire alarm
condition during a loss of AC power.
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 47
Power Supply Calculations Calculating the Battery Size
Table 5.3 contains three columns for calculating current draws. For each column, calculate the current and enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation Column 2 and Calculation Column 3 to Table 5.4 on page 49.
Calculation Column 1
Device Type
Main Circuit Board
SK-2
or
SK-4
CAC-4 [ ] X[0.001]= [ ] X[0.001]= X[0.001]=
4XTMF [ ] X[0.005]= [ ] X[0.011]
4XZMF [ ] X[0.004]= [ ] X[0.008]= X[0.004]=
4XLMF/RZA-4XF
pair
2-wire Detector
Heads
4-wire Detector
Heads
Power Supervision
Current Draw from
TB1 (nonalarm
column
**
Relays
††
NAC #1
NAC #2 [ ] X[ ]=
Sum each
***
for totals
Primary, Non-Fire Alarm Current
Qty
1
[ ]
1 pair max.
[ ] X[ ]
[ ] X[ ]
[ ] X[0.025]= [ ] X[0.025]= X[0.025]=
‡‡
)
(amps)
X[current
draw]=
X[0.080]=
X[0.085]=
X[0.004]= [ ] X[0.019]= X[0.004]=
[ ]= [ ]= [ ]=
Primary Non-Alarm = Primary Alarm = Secondary Alarm =
Total Qt y
0. 1
= [ ] X[ ]= X[ ]=
= [ ] X[ ]= X[ ]=
Calculation Column 2
Primary, Fire Alarm Current
[ ] X[ ]=
(amps)
X [current draw]
=
*
X[0.112]
X[0.175]
=
*
=
*
= X[0.005]=
Total Qt y
0. 1
Calculation Column 3
Secondary, Non-Fire Alarm
Current
(amps)
X[current
draw]=
X[0.080]=
X[0.085]=
Total
0.
Table 5.3 System Current Draw Calculations
* If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add
another 0.005 amps. † Refer to the Device Compatibility Document for standby current. ‡ Refer to the Device Compatibility Document for standby current. ** Must use compatible listed Power Supervision Relay. †† Current limitation of Terminal TB2 circuits is 2.50 amps per NAC (SK-4 requires optional transformer for max.
current) ‡‡ The total standby current must include both the resettable (TB1 Terminals 3 & 4) and nonresettable for SK-4
only (TB1 Terminals 1 & 2) power. Caution must be taken to ensure that current drawn from these outputs
during alarm does not exceed maximum ratings specified. Current limitations of TB1, Terminals 1 & 2 = 0.500
amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10 mV
0.500 amps, filtered, 24 VDC +/-5%, 120 Hz ripple @ 10mV
, nonresettable power and TB1, Terminals 3 & 4 =
RMS
, resettable power.
RMS
*** Total current draw listed above cannot exceed 3.0 amps with only standard transformer installed or, for the SK-
4, 6.0 amps with both the standard and optional transformers installed.

5.4 Calculating the Battery Size

Use Table 5.4 to calculate the total Standby and Alarm load in ampere hours (AH). This total load determines the battery size (in AH), required to support the control panel under the loss of AC power. Complete Table 5.4 as follows:
48 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Calculating the Battery Size Power Supply Calculations
1. Enter the totals from Table 5.3 on page 48, Calculation Columns 2 and 3 where shown.
2. Enter the NFPA Standby and Alarm times (refer to ‘NFPA Requirements’ below).
3. Calculate the ampere hours for Standby and Alarm, then sum the Standby and Alarm ampere hours.
4. Multiply the sum by the derating factor of 1.2 to calculate the proper battery size (in AH).
5. Write the ampere hour requirements on the Protected Premises label located inside the cabinet door.
Secondary Standby Load (total from Table 5.3 Calculation Column 3) [ ]
Primary Alarm Load (total from Table 5.3 Calculation Column 2) [ ]
Sum of Standby and Alarm Ampere Hours = AH
Multiply by the Derating Factor X 1.2
Battery Size, Total Ampere Hours Required = AH
Required Standby Time (24 or 60 hours)
X[ ] = AH
Required Alarm Time (for 5 min., enter 0.084, for 10 min., enter 0.168) X[ ] = AH
Table 5.4 Total Secondary Power Requirements at 24 VDC

5.4.1 NFPA Battery Requirements

NFPA 72 Local, Central and Proprietary Fire Alarm Systems require 24 hours of standby power followed by 5 minutes in alarm
NFPA 72 Auxiliary and Remote Station require 60 hours of standby followed by 5 minutes in alarm. Batteries installed in a system powered by a generator need to provide at least 4 hours of standby power

5.4.2 Selecting and Locating Batteries

Select batteries that meet or exceed the total ampere hours calculated in Table 5.4 . The control panel can charge batteries in the 7 AH to 18 AH range. The control panel cabinet is capable of housing batteries up to 7 AH. Batteries larger than 7 AH require the BB-17F or other UL listed external battery cabinet.
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 49

Appendix A: NFPA Standard-Specific Requirements

T B 3
T B 5
T B 6
T B 7
B+ B- B+ B­ ZONE 1 ZONE 2
B+ B- B+ B­ ZONE 3 ZONE 4
C TRBL NORM TROUBLE
C NC NO
ALARM SUPV
C NC NO
JP3
Figure A.1 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter
Typical Central Station/Remote Station Transmitter Module
Typical Input Zone Triggers
FACP Main Circuit Board
Alarm
Trouble*
Supervisory
*Note: The Trouble Relay is a fail-safe relay. With power applied to the FACP and no troubles in the panel, the wiring should be connected to the C and TRBL contacts as indicated in the illustration.
ms4cdryxmit.wmf
The SK-2 and SK-4 have been designed for use in commercial, industrial, and institutional applications and meet the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this Appendix. The minimum system components required for compliance with the appropriate NFPA standard are listed below:
SK-2/SK-4 Control Panel
Contains the main control board, cabinet (backbox and door), main power supply transformer, and power supply.
Batteries
Refer to “Power Supply Calculations” on page 46, for Standby Power Requirements.
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to the control panel's Notification Appliance Circuits via a control module.
A.1 Central Station/Remote Station Transmitter: Connection
to FACP Dry Contacts
The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value determined by the Transmitter manufacturer. Power is also provided by the Central Station/Remote Station Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter manufacturer’s manual for details.
50 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010

Index

Numerics
2 Zone Main Circuit Board 8 4 Zone Main Circuit Board
15
411
15
411UD 4XLMF
installation see also LED Interface Module see also LED interface module specifications wiring to RZA-4XF
4XTMF
installation operation see also Transmitter Module see also transmitter module specifications
4XZMF
installation see also Zone Relay Module see also zone relay module specifications
26, 30
30
30
26, 27
27
27
26, 29
29
A
AC power 19 AC Power LED AC power rating AC power requirements AC trouble delay accessories ACK
see also Acknowledge
Acknowledge Acknowledge button alarm
piezo pulse rate
alarm relay
contact rating
Alarm Silence Alarm Silence LED alarm verification
timing graph
annunciator, remote
see also RZA-4XF
applications audible Walktest autoresettable supervisory auto-silence auxiliary power
42
11
46
35
14
10, 12
40
13
8, 9, 10, 14, 23
12
10, 12
42
36, 37
36
30
10
41
35
35
23
9
10
27
29
14
15
15
30
B
backbox
dimensions mounting
14, 19
battery
precautions rating
battery box
mounting battery calculations battery connector Battery Fault LED BB-17F
buttons
18
see also battery box
12
see also control buttons
14, 17
17
19
11
15
18
48
8, 9
43
15
10
C
cabinet
dimensions
mounting
see also backbox
20
CAC-4
installation
see also Class A Converter Module
14
charger charger capacity Charger Fault LED
10
circuits Class A Class A Converter Module
Class B coding
combination circuit
combination waterflow/supervisory
compatibility
control buttons controls cover current
current requirements for system
14, 20, 25
installation
10, 12, 14, 20
NACs
see also waterflow/tamper
requirements
wiring
see also device compatibility
12
32
maximum system
nonresettable power
resettable power
see also system current
total output
17, 18
17
14
25
11
43
9, 14
25
35
10, 21
36
21
21
10
12
23
23
10
22
47, 48
9, 14
10, 20, 21
10
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 51
D–L Index
D
description 10 device compatibility Digital Alarm Communicator/Transmitter
see also 411 & 411UD
dimensions
backbox dip switch cover DIP switch options
see also programming DIP switch settings
see also programming disable
see also zone enable/disable disable NAC dress panel
10, 15
10
15
14, 17
32
32
33
32
11
37
E
Earth Fault LED 43 earth ground enable
see also zone enable/disable End-of-Line resistor
IDC
NAC
19
11
12, 20, 21
12, 22
short circuit current standby current
20
wiring
indicators
Initiating Device Circuit
In-Line resistor
installation
12
see also LED
Class A
IDC combination circuit
25
17
4XLMF 4XTMF 4XZMF
25
CAC-4 Class A Converter Module option modules
12
11
26 26, 27 26
25, 26
J
J3 and J5
option module connectors
J4 and J6
option module connectors
JP1 jumper
placement supervision
JP2
placement supervision
12
8, 9, 10, 12, 14, 20
21
25
26
26
27
27
F
fail-safe
trouble relay fail-safe relay
see also trouble relay
10
features fire alarm response fire alarm restoral
15, 29
Form-C
see also relay
20
freeze freeze signal
see also smoke detector monitoring
23
14
44
44
10, 14
G
Gentex synchronization 38
disable
20, 43, 45 8, 9
ground fault
I
i3 detectors 14, 20
9, 10, 12, 14, 20
IDC
alarm current
compatibility
End-of_Line resistor
End-of-Line resistor
maximum loop resistance
see also Initiating Device Circuit
12 20
21
12, 20
12, 20
L
Lamp Test 40
11, 13
LED
AC Power Alarm Silence Battery Fault Charger Fault Earth Fault Fire Alarm main circuit board Maintenance
10
NAC Disable NAC Fault Power Trouble Supervisory System Trouble Trouble Walktest Zone Disable Zone Fire Alarm Zone Maintenance Zone Supervisory Zone Trouble
LED Interface Module
installation see also 4XLMF
8
11, 13, 42
11, 13, 42
11, 13, 43
11, 13, 43 11, 13, 43 11, 13
8, 9
11, 13
11, 13, 42
11, 13, 42
11, 13, 42
11, 13
11, 13, 42
11, 13
11, 13, 42
11, 13, 42
43
43
43
43
15
26
30
52 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
Index M–S
M
main circuit board
see also 2 Zone see also 4 Zone
maintenance
piezo pulse rate
maintenance signal
see also smoke detector monitoring
modes of operation
see also normal and walktest
mounting
cabinet municipal box municipal box transmitter
see also 4XTMF
20
17
8 9
13
27
14
N
NAC 9, 10, 12, 14, 22
35
coding
22
current
37
disable
End-of-Line resistor
maximum current
nonsilenceable
see also Notification Appliance Circuit
22
wiring NAC Disable LED NAC Fault LED nonpower-limited wiring nonresettable power
current
maximum current nonsilenceable NAC normal mode Notification Appliance Circuit
22
Class A
42
23
40
25
12, 22
12
37
42
24
9, 10, 12, 14, 23
12
37
8, 9, 10, 12, 14,
O
operating instructions 40 operation option modules
43
14
connector
connectors
installation
placement supervision
8, 9
26
25, 26
27
P
piezo 13
13
alarm
maintenance
see also sounder
supervisory
trouble polarity reversal circuit
13
11
13
13
40
10
see also 4XTMF
12, 19, 23
power
maximum system primary secondary
see also resettable and nonresettable power
power supply calculations Power Trouble LED power-limited wiring programming
chart DIP switches feature chart supervisory
programming DIP switches
19
see also battery
9
32, 33
33
28
12
19
46
42
24
32
33
36
32
R
relay 8, 9, 10, 14, 15, 23, 29
contact rating
Remote Annunciator
see also RZA-4XF
remote station service
10
8
Reset Reset button resettable power
current maximum current
reverse polarity circuit
see also 4XTMF
RZA-4XF
see also Remote Annunciator see also remote annunciator wiring to RXLMF
12, 23
15
28
40
8, 9, 10, 12, 14, 23
23
12
14
15
30
30
S
selective silence 35 silence
selective Silence button silence inhibit silent walktest sounder status LEDs strobe synchronization
see also synchronization strobes
maximum quantity Style B
see also Class B Style D Style Y
see also Class B Style Z supervision
35
40
35
42
11, 13
42
38
38
12, 14, 20
10 14, 20, 25 12, 14
10
14, 25
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 53
T–Z Index
option module placement 27
supervisory
piezo pulse rate see also programming supervisory
supervisory relay
contact rating supervisory response supervisory restoral switch functions synchronization
38
Gentex
see also strobe synchronization
System Sensor
Wheelock system current system current calculations System Sensor synchronization System Trouble LED
13
9, 10, 14, 23
12
44
44
40
38
38
10
47
42
T
temporal coding 35 transformer assembly
14
rating Transmitter Module transmitter module
see also 4XTMF trouble
piezo pulse rate trouble relay
contact rating
fail-safe trouble reminder trouble response trouble restoral
8, 9, 10, 14, 23
23
14
14
27
13
12
35
44
45
38
38
36, 37
CAC-4
25
Class A Converter Module Class A IDC Class A NAC combination waterflow/supervisory
20
IDC NAC nonpower-limited power-limited UL requirements
26
26
22
24
24
24
Z
Zone 1 20 Zone Disable LED Zone Enable/Disable Zone Fire Alarm LED Zone Maintenance LED zone relay module
see also 4XZMF Zone Supervisory LED Zone Trouble LED
42
11, 13
43
43
15
29
43
43
25
21
U
UL
wiring requirements
24
V
verification
alarm timing graph see also alarm verification
36
36
W
Walktest 10, 13 Walktest LED Walktest mode
audible exiting
silent waterflow/tamper circuit Wheelock synchronization wiring
54 SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010
42
40, 41
41
42
42
36
38
Manufacturer Warranties and Limitation of Liability
Manufacturer Warranties. Subject to the limitations set forth herein,
Manufacturer warrants that the Products manufactured by it in its Northford, Connecticut facility and sold by it to its authorized Distributors shall be free, under normal use and service, from defects in material and workmanship for a period of thirty six months (36) months from the date of manufacture (effective Jan. 1, 2009). The Products manufactured and sold by Manufacturer are date stamped at the time of production. Manufacturer does not warrant Products that are not manufactured by it in its Northford, Connecticut facility but assigns to its Distributor, to the extent possible, any warranty offered by the manufacturer of such product. This warranty shall be void if a Product is altered, serviced or repaired by anyone other than Manufacturer or its authorized Distributors. This warranty shall also be void if there is a failure to maintain the Products and the systems in which they operate in proper working conditions.
MANUFACTURER MAKES NO FURTHER WARRANTIES, AND DISCLAIMS ANY AND ALL OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, WITH RESPECT TO THE PRODUCTS, TRADEMARKS, PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION, INFRINGEMENT, TITLE, MERCHANTABILITY, OR FITNESS FOR ANY PARTICULAR PURPOSE. MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS.
This document constitutes the only warranty made by Manufacturer with respect to its products and replaces all previous warranties and is the only warranty made by Manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. Manufacturer does not represent that its products will prevent any loss by fire or otherwise.
Warranty Claims. Manufacturer shall replace or repair, at Manufacturer's discretion, each part returned by its authorized Distributor and acknowledged by Manufacturer to be defective, provided that such part shall have been returned to Manufacturer with all charges prepaid and the authorized Distributor has completed Manufacturer's Return Material Authorization form. The replacement part shall come from Manufacturer's stock and may be new or refurbished. THE FOREGOING IS DISTRIBUTOR'S SOLE AND EXCLUSIVE REMEDY IN THE EVENT OF A WARRANTY CLAIM.
Warn-HL-08-2009.fm
SK-2 & SK-4 Series Manual — P/N 52604:B 9/14/2010 55
12 Clintonville Road Northford, CT 06472-1610 USA 203-484-7161 Fax: 203-484-7118 www.silentknight.com
© 2010 Honeywell International Inc.
Loading...