MNB-V1
Figure-1 MNB-Vx Mounting Dimensions.
MNB-V2
MicroNet BACnet
VAV Controllers
Installation Instructions
Application
The TAC I/A Series® MicroNet™
BACnet™ VAV (Variable Air
Volume) Controllers are
interoperable controllers with native
BACnet MS/TP communications
support. All models incorporate: an
integral actuator with manual
override; an integral, patented,
pressure transducer; three
SW24H1
SW24H2
SW24H3
24H
24G
GND
STATUS
MSTP RCV
MSTP XM
AO
S-LK/COM
COM
UI
DI
S-LK
LON
LON
T
universal inputs; Sensor Link
(S-Link) support; LED status
indication; and over-the-shaft damper mounting. See the
model chart, below, for optional features.
Model Chart
Model
Number
MNB-V1 300
MNB-V2 313
Inputs and Outputs
UI UO DO (Triacs)
Installation
Inspection
Inspect carton for damage. If damaged, notify carrier
immediately. Inspect controllers for damage upon receipt.
Requirements
• Installer must be a qualified technician
The following items are not provided.
• Job wiring dia grams
• Tools:
– 1/8 inch allen wrench
– Screw drivers
– 1/4 inch hex driver for travel adjustment screws
– Pliers for turning damper shafts
– Digital Volt-ohm meter (DVM)
– Drill and bits for mounting screw
– Static protection wrist strap
– Torque wrench (capable of measuring at least
70 lb-in (8 N-m))
• MNA-FLO-1 enclosure for connecting to conduit (optional)
• AM-135, 3/8 in. (9.5 mm) to 1/2 in. (12.8 mm) shaft
adapter (optional)
• MS/TP trunk end-of-line termination resistor kit,
120 ±5%, part number 40-1758.
• Spacer or shim for anti-rotation bracket (if needed)
• One #10 sheet metal screw for anti-rotation bracket
• Class 2 power transformer supplying a nominal 24 Vac,
sized appropriately for the controller (15 VA) plus the
anticipated Digital Output (DO) loads. In European
Community, transformer must conform to EN 60742
• 0.170 in. (4.3 mm) I.D. FRPE polyethylene tubing or
0.125 in. (3.2 mm) I.D. Tygon
®
tubing for piping
connections. Not more than 5 ft (1.52 m) long.
Precautions
When installing the MNB-Vx controller, be sure to
follow the guidelines outlined in "Precautions" on
page 4.
Location
The MNB-Vx controllers are suitable for indoor use only.
Caution:
• Avoid locations where excessive moisture, corrosive
fumes, vibration, or explosive vapors are present.
• Avoid electrical noise interference. Do not install near
large contactors, electrical machinery, or welding
equipment.
• Locate where ambient temperatures do not exceed
131°F (55°C) or fall below 32°F (0°C) and relative
humidity does not exceed 85% or fall below 5%,
non-condensing.
Mounting location must clear the maximum dimensions of the
controller case and allow the controller to be mounted flush to
the surface of the terminal box and perpendicular to the
damper shaft.
Dimensions
Mounting dimensions are shown in Figure-1.
6-1/4 (159)
4-1/2
(114)
1-3/4
(44)
5-3/4
(146)
2-1/2 (63)
7-3/4
(197)
Dimensions shown
are in inches (mm).
Printed in U.S.A. 02-10 © 2010 Schneider Electric. All rights reserved. F-27346-4
Mounting Mount the controller to the damper according to the instructions in Figure-2.
SW24H1
SW24H2
SW24H3
24H
24G
GND
STATUS
STP RCV
PXMT
UO1
COM
UI1
COM
UI2
UI3
S-LK/C
OM
S-LK
MSTP +
MSTP -
SHLD
Figure-2 MNB-Vx Damper Mounting.
Warning: Electrical shock hazard! Disconnect power before installing or removing the
cover.
1 Slide the controller onto the damper
shaft and mount the controller as
shown, making sure it is on a plane
that is perpendicular to the damper
shaft. See notes through .
1 4
3 Press the manual override button and turn the
output shaft to the full CCW position. If necessary,
rotate the output shaft slightly to return the button
to the fully extended position.
For CW (closed) position, turn the output shaft
fully CW.
2 Turn the damper shaft to the
full CCW (closed) position.
For CW (closed) position,
4 Finish mounting the controller to
the damper as shown, referring
to notes and .
turn the damper shaft fully CW.
1 Check that the position selected for the mounting
hole does not interfere with the operation of the
damper.
2 Some terminal boxes have sheet metal screw
heads or other protrusions near the damper shaft.
In these cases, add a spacer or shim (not provided)
under the controller's anti-rotation bracket to make
the controller perpendicular to the shaft.
3 The anti-rotation bracket is pre-installed in the
controller slot when shipped.
4 Caution: Use the anti-rotation bracket when direct-
mounting the controller onto a damper shaft. Do not
rigidly mount the controller to the damper. Position
the anti-rotation bracket so that the controller can
float, to ensure that the controller's output shaft can
turn freely through its full stroke, without binding.
5
If necessary, loosen and slide the CW travel
adjustment screw to the desired position, and then
tighten the screw.
For CW (closed) position, reposition the CCW
travel adjustment screw.
6 If preloading the damper for closed position is
required, set the controller as follows:
a. Rotate the controller CW approximately 3/16"
(4 mm) off the centerline of the damper (see
view below) and then tighten the output shaft set
screws 60 - 70 lb-in. (6.8 - 7.9 N-m), using an
1/8" allen wrench.
For CW (closed) position
, rotate the controller
CCW (see view below).
b. Rotate the controller back into alignment with
the centerline of the damper. This should ensure
closure of the damper.
CCW Closed
CW Closed
5 6
MSTP XM
MSTP RCV
STATUS
GND
24G
T
SHLD
MSTP -
S-LK/COM
S-LK
Output
Shaft
CW Travel
Adjustment Screw
24H
SW24H3
SW24H2
SW24H1
UI3
COM
UI2
UI1
COM
UO1
Travel
Indicator
Pin
#8 (4 mm) Sheet
Metal Screw
(not provided)
1
5
Short Shaft
Set Screw
Locations
Manual Override
Slot
Damper
Damper
Shaft
Set Screws (2)
60 - 70 lb-in. (6.8 - 7.9 N-m).
CCW Travel
Adjustment Screw
5
Button
Anti-rotation
Bracket
432
5 When finished, verify free movement of the damper as follows:
Press and hold the manual override button.
a.
b. Verify that the damper can be freely positioned between full open and full
closed. There must be no binding between the controller and damper, and
3 3
3/16" (4 mm)
(approx.)
3/16" (4 mm)
(approx.)
the damper must be free of obstructions that may hinder its operation.
c. Release the manual override button. If the button does not fully extend, it
will do so automatically once power is applied to the controller. The button
may also be made to fully extend by rotating the output shaft slightly.
2 © 2010 Schneider Electric. All rights reserved. F-27346-4