Specification Sheet
Electrical Connections
Power input, running with full
load
MGF350V-24FP, MG350V-24M,
MGF350V-24MP
MG350V-24F 24 Vac, ±20% (Class 2 power
Power input, holding
MGF350V-24FP, MG350V-24M,
MGF350V-24MP
MG350V-24F Actuator is unpowered
Internal power supply type
MGF350V-24FP, MG350V-24M,
MGF350V-24MP half wave
MG350V-24F full wave
Input signal impedance
MG350V-24M and MGF350V24MP
MGF350V-24MP
Input Signal Auto Calibration
(MGF350V-24FP, MG350V-24M,
MGF350V-24MP)
Floating Control Signal
(MG350V-24F, MGF350V-24FP)
Floating Input Signal Minimum
Pulse Width (MG350V-24F) 100 msec
Position Feedback Output
Signal
(MGF350V-24FP, MGF350V24MP)
Conduit Connection Removable 1/2” conduit
Electrical Connections Removable terminal block,
24 Vac, ±20% (Class 2 power
supply), 50/60 Hz, 7.2VA,
20 … 29 Vdc, 3.5 W
supply), 50/60 Hz, 5VA,
20 … 29 Vdc, 3.5 W
24 Vac, ±20% (Class 2 power
supply), 50/60 Hz, 1.2 VA
(24FP 0.7W, 24M 0.4W,
24MP 0.5W)
when it is holding
2 … 10 Vdc and 0 … 10 Vdc
>100 kOhms
4 … 20 mA, 500 Ohms
Automatic span calibration
to precisely match the stroke
length of the valve (with a
minimum stroke of 1/8” (3.2
mm) and a maximum stroke of
21/32” (16.5 mm).
SPST center off (floating)
control contacts or one or
two SPST control contacts,
minimum rating of 250 mA at
24 V or one or two triacs must
be able to switch 250 mA at
24 Vac,
1,100 Ohms input impedance
2 … 10 Vdc and 0 … 5 Vdc,
0.5 mA (field selectable)
opening plate
AWG 12 … 24, meets the
requirements of cUL without
the need of an electrical earth
ground connection
Mechanical
Linkage Linkage for 1/2” … 2” VB-7000 and
1/2” … 1-1/4” obsolete VB-9000 Globe
Valves included with actuator
Manual Override 3 mm hex wrench (not included
with actuator), “tee”
handle style recommended
Mechanical Valve Position Indicator
Electrical Valve Status
Indication
Speed
MG350V-24 and
MG350V-24M
MG350-24FP and
MGF350V-24MP
Force
MG350V-24F and
MG350V-24M
MG350-24FP and
MGF350V-24MP
Enclosure Plenum rated per UL 2043
Yoke Rugged die cast aluminum
Weight 0. 8 lbs. (0.36 kg)
Graduated position indicator showing
open to close with end point indicators
Bi-color LED status indication for
motion indication, calibration, and
alarm notification. MG350V-24F does
not include the calibration and alarm
indication
0.295” (7.5 mm) per minute
0.59” (15 mm) per minute
78 lbf (350 N) force
67 lbf (300 N) force
Environmental
Operating Temperature Range
For fluid up to 266 °F (130 °C):
For fluid up to 281 °F (138 °C):
For fluid up to 340 °F (171 °C):
For fluid up to 400 °F (204 °C):
Shipping / Storage Temp. -40 … 158 ˚F (-40 … 70 ˚C)
Operating Humidity Range 5 … 95% non condensing
Location NEMA 2 (IP 53) with proper
Noise Level ≤30 dB (A) @ 1 meter
23 … 131 °F (-5 … 55 °C)
23 … 127 °F (-5 … 53 °C)
23 … 115 °F (-5 … 46 °C)
23 … 102 °F (-5 … 39 °C)
mounting orientation
Agency Listings
North
America
European
Community
Australia,
New Zealand
Russia,
Kazakhstan,
Belarus
cUL-us LISTED mark (xapx & xapx7), per UL
60730-1 and -2-14 and CAN/CSA E60730-1 and
-2-14 Automatic Electric Controls, NEMA 2, NEC
class 2 FCC part-15 class B, Canadian ICES-
003, and ESA registered. Plenum rated per UL
2043.
CE mark, LVD directive [2014/35/EU) per EN
IEC 60730-1 and -2-14 Automatic Electric
Controls, protection class III SELV, EMC directive
[2014/30/EU] per EN IEC 61000-6-2 and -6-3,
IP53 Ingress Protection per EN IEC 60529 (prop-
erly mounted), RoHS2 directive [2011/65/EC]
and REACH directive [2006/1907/EC].
RCM, Regulatory Conformance Mark, per ACMA
(Australia) and RSM (New Zealand)..
EAC, EurAsian Conformity Mark.
Accessories
AM-708 500 Ohm resistor for connection to 4 … 20 mA input
signals for MG350V-24M (not required for MGF350V-24MP)