The i2810 Series controllers are designed for control of Air Handling
Units, Roof Top Units, and other mechanical plant equipment.
Page 2
Andover Continuum Infi net II
i2810 Series Local Controllers
Features
PRODUCT AT A GLANCE
• Powerful , Flexib le Loca l Controlle r for th e
Most Demanding Applications
• Expandable I/O Meets Additional Point
Count Needs
• Non-Vola tile Fl ash Mem ory Prov ides U tmost
Reli ability — Stor es Both Applic ation P rogram
and Operating System
• Optional Display/Keypad Provides Easy
Operator Interface (Mounted Separately)
• Local, Extended Storage of Log Data
• View and Mo dify In formatio n with Optional
Smart Sensor Display
• Local, On-Board Service Port
02
Choose the i2810 model with the
confi guration that matches your application:
•
The i2810, designed for stand-alone equipment
control of Roof Top Units, Air Handling Units, or
other packaged mechanical equipment, features
eight universal inputs, one Smart Sensor/Room
Sensor input, plus eight program-controlled
digital outputs.
• The i2814, designed for stand-alone equipment
control of Roof Top or Air Handling Units, features
eight universal inputs, one Smart Sensor/Room
Sensor input, plus four program-controlled digital
outputs and four analog outputs for direct control
of devices requiring 0-10 volt control signals.
Note: The i2814 is only compatible with Andover
Continuum.
Both models feature an additional room sensor
input, which supports Andover Continuum Smart
Sensor, or any standard room temperature sensor.
The i2810 Series also features universal inputs, a
real-time clock, override switches on all outputs,
two-piece removable connectors, and the ability to
expand the I/O for additional points.
The i2810 Series features Flash memory, increased
user memory, and a fast (32-bit) processor for faster
scan times, with plenty of memory available for data
logging of your critical data.
The i2810 communicates with the entire Andover
Continuum Infi net RS-485 fi eld bus (i.e. both
Andover Continuum Infi net and Andover Continuum
Infi net II controllers) and is compatible with both
the Andover Continuum CyberStation and Infi nity
SX 8000 front-ends. The i2814 is only compatible
with Andover Continuum. Up to 254 Andover
Continuum Infi net devices can be networked to any
Andover Continuum network controller.
S
chneider Electric
SDS-I2810-A4.BU.N.EN.11.2007.0.00.CC
Page 3
Andover Continuum Infinet II
i2810 Series Local Controllers
03
Features
(continued)
Increased Reliability with Flash Memory
The i2810’s non-volatile Flash memory stores your
operating system and application programs, so that
in the event of a power loss, your application will
be restored when power is returned. In addition,
the Flash memory allows for easy upgrades of
your operating system via software downloads,
eliminating the need to swap out proms.
The i2810 controllers include an on-board battery to
safeguard your runtime data — protecting all point
data and log data from being lost if power
is removed.
Inputs
The input configuration on the i2810 Series consists
of eight full range, 12-bit universal inputs that accept
voltage (0-10VDC), digital (on/off), counter signals
(up to 4Hz), temperature signals, or supervised
alarm circuits for security applications or broken
wire detection. The i2810 Series offers an additional
input to support the Andover Continuum Smart
Sensor, or any standard room temperature sensor.
Dimensional Drawings
1
2
4
3
Outputs
The i2810 contains eight Form C relay outputs, each
rated for 24 VAC/30 VDC, 3 amp, while the i2814
contains four Form C relay outputs and four analog
outputs (0-10V). Both the relay and analog outputs
have manual override switches, with software
feedback of the switch position.
I/O Expansion
The i2810 contains an I/O expansion port for
the addition of up to two Andover Continuum xP
expansion modules directly on the bottom of the
controller. The xP family of modules includes the
xPUI4, xPDI8, xPDO2, xPDO4, xPAO2, and xPAO4.
In addition to two input/output modules, the I/O bus
supports the xP Local Display Module, which allows
the user to view and change point values.
Schneider Electric
SDS-I2810-A4.BU.N.EN.11.2007.0.00.CC
Page 4
Andover Continuum Infinet II
B
3
2
1
AC PO WER
24 VAC
30 VA
50/6 0 HZ
L
N
+
DC PO WER
12-28 V DC
20W
REV:
B
4
5
6
SHLD
+
-
RS-4 85
TD
3
2
1
AC POWER
24 VAC30 VA50/60 HZ
L
N
+
DC POWER
12-28 VDC20W
PLACARD, INPUT,
I2814 / I2810
05-1001-223
TITLE:
P/N:
REV:
DATE:
1OF1
DRAWNBY:
B
11/3/04M.ROGERS
SHEET:
FULL
ECO#11244
SCALE:
SOFTWARE:ECONUMBER:
ADOBEILLUSTRATOR10.0
21
19
20
7 RE T
8 IN 1
9 IN 2
10
RET
11 IN 3
12 IN 4
13 RET
14 IN 5
15 IN 6
16 RET
17 IN 7
18 IN 8
RET
IN 9
SPWR
SMART
SENSOR
UNIVERSAL
INPUTS
1
2
3
6
5
4
8
7
OFF
ON
SERVICEPORT
4
5
6
SHLD
+
-
RS-485
R
D
TD
RESTART
CPU
3
2
1
AC POWER
24 VAC30 VA50/60 HZ
L
N
+
DC POWER
12-28 VDC20W
40
36
45
44
43
42
41
39
38
37
35
34
1
2
28
24
33
32
31
30
29
27
26
25
23
22
3
4
I
V
GND
5
I
V
GND
6
I
V
GND
7
I
V
GND
8
40
36
45
44
43
42
41
39
38
37
35
34
1
2
3
4
28
24
33
32
31
30
29
27
26
25
23
22
5
6
7
8
i2810 Series Local Controllers
04
Features
(continued)
Software Capabilities
The dynamic memory of the i2810 can be allocated
for any combination of programs, scheduling,
alarming, and data logging using the powerful
Andover Continuum Plain English programming
language. Our object-oriented Plain English
language with intuitive keywords provides an
easy method to tailor the controller to meet your
exact requirements. Programs are entered into the
i2810 using the Andover Continuum CyberStation.
Programs are then stored and executed by the
i2810 controllers.
Programming multiple i2810 Series controllers is
inherently easy with Plain English. A complete copy
of one i2810 controller’s programs can be loaded
directly into other i2810 controllers without changing
any point names or programs.
Smart Sensor Interface
The i2810 provides a built-in connection for Andover
Continuum Smart Sensor. The Smart Sensor
provides a 2-character LED display and a 6-button
programmable keypad that enables operators and
occupants to change setpoints, balance VAV boxes,
monitor occupancy status, and turn equipment on
and off. An enhanced version of the Smart Sensor
is also available with a 4-digit custom LCD that
provides the following icons: PM, %, °, Setpoint,
Cool, Heat, CFM, Fan, OA, and SP.
Local Display
The local display with keypad (xP-Display) allows for
the addition of a fully programmable local display
module that can be mounted within 10 feet (3
meters) of the controller. Connected via a ribbon
cable, the xP-Display easily allows the Operator
Interface to be mounted on the door of an enclosure
or on a wall below or next to the controller.
Optional Wireless Andover Continuum Infinet
The i2810 Series Andover Continuum Infinet
controllers can also communicate using a wireless
mesh network. Simply plug Andover Continuum
Wireless Adapters into the service ports of these
controllers with wireless compatible firmware to
create a wireless mesh network that sends and
receives Andover Continuum Infinet messages.
Sc
SDS-I2810-A4.BU.N.EN.11.2007.0.00.CC
hneider Electric
Dimensional Drawings
1
Power Drawing
2
Communi cation
Drawing
Smart S ensor and
3
Inputs D rawing
i2810
Outputs D rawing
4
i2814
Page 5
Andover Continuum Infinet II
i2810 Series Local Controllers
Specifications
i2810 Series Local Controllers
05
Electrical
Power
24VAC, 12-24VDC - auto sensing,
+10% -15%, 50/60 Hz
Power Consumption
30 VA
Overload Protection
Fused with 3 amp fuse.
MOV protected
Real-Time Clock
Battery-backed real-time clock
Mechanical
Operating Environment
32°–120°F (0–49°C),
10–95% RH (non-condensing)
Size
9.51˝ H x 7.26˝ W x 2.14˝ D
(241 H x 184 W x 54 D) mm
Weight
1.65 lbs. (0.75 kg)
Enclosure Type
UL Open class, IP 10.
Flammability rating of UL94-5V
Mounting
Panel mount
Battery
Battery Backup
Replaceable, non-rechargeable,
lithium battery. Provides 5 years
typical accumulated power failure
backup of RAM memory
Communications
Communications Interface
Through Andover Andover Continuum
Infinet RS-485 field bus to network
controller
Communications Speed
1200 to 19.2K baud
Bus Length
4,000 ft. (1,220m) standard for
Andover Continuum Infinet, i2 Infilink
module allows extension to longer distances
and is required after every group of
32 units on the network.
Bus Media
Andover Continuum Infinet: twisted,
shielded pair, low capacitance cable
RS-485 port for implementing Wireless
Infinet II connection, including:
Standard service port, four-position
shrouded connector
Comm. Error Checking
International Standard CRC 16
Compatibility
Andover Continuum Cyberstation
and Infinity SX 8000 systems
Note: The i2814 is compatible with
Andover Continuum software version 1.5
(or later).
Inputs/Outputs
Inputs
8 Universal inputs: Voltage (0-10 VDC);
Temperature -30°F to 230°F (-34°C to 110°C),
Digital (on/off), Counter (up to 4Hz at 50%
duty cycle, 125 ms min. pulse width).
Supervised Alarm (single or double resistor).
Current input (0 - 20 mA) using external 500
ohm resistor
1 Smart Sensor Temperature Input (32°F to
105°F) (0°C to 41°C)
Input Voltage Range
0-10 volts DC
Input Impedance
30.1K ohm to 10V or 5M ohm with
pull-up resistor disabled
Input Resolution
2.5 mV
Input Accuracy
±7.5mV (±0.25°C from -23°C to
+54°C) or (±0.46°F from -10°F to +130°F)
Digital Outputs
8 single pole single throw (SPST) Form C
relays (4 Form C on i2814)
(Any two consecutive Form C outputs can
be configured as one Form K Tri-state)
Output Rating
Maximum 3A, 24VAC/30VDC,
±1500V transients (Tested according
to EN61000-4-4)
Output Accuracy
0.1 sec. for pulse width modulation
hneider Electric
Sc
SDS-I2810-A4.BU.N.EN.11.2007.0.00.CC
Page 6
Andover Continuum Infinet II
i2810 Series Local Controllers
06
Specifications
(continued)
i2810 Series Local Controllers
Analog Outputs
4 analog outputs (i2814 only)
Output Rating
For 0-10V: 5mA maximum,
2K ohm minimum impedance,
±1000V transients (Tested according to
EN61000-4-4). Fuse-protected
only on the i2814
Output Resolution
0.1V for 0-10V
Output Overrides
Each output is equipped with a manual
override switch. Software feedback
of the switch position is provided,
for display and alarming
Expansion Bus
Interfaces to optional xP I/O
Expansion Modules
Connections
Power
3-position fixed screw terminal connector
Inputs
Removable two-piece terminal strip
Outputs
Removable two-piece terminal strip
Smart Sensor
Removable two-piece terminal strip
Communications
Removable 3-position terminal
connector
Expansion Port
6-position shrouded connector
Service Port
4-position shrouded connector
User LEDs/Switches
Status Indicator LEDs
CPU CPU Active
TD Transmit Data
RD Receive Data
Output Output Status (per
output) (Digital only)
EXPANSION
PORT PWR Power Status
Switches
RESET
Input Pull-up Resistor Switch (per input)
Individual Output Override Switches
General
Memory
256K SRAM, 1MB FLASH
Processor
Motorola 32-Bit Coldfire
Agency Listings
UL/CUL 916, FCC CFR 47 Part 15,
ICES-003, EN55022, ASIN2S 3548,
Class A, CE
Models
i2810
Infinet II i2810 Local Controller
i2810-WL
Wireless Infinet II i2810 Local Controller
i2814
Infinet II i2814 Local Controller
i2814-WL
Wireless Infinet II i2814 Local Controller
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
On October 1st, 2009, TAC became the Buildings Business of its parent company Schneider Electric. This document reflects the visual identit y of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.