Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this control
equipment must satisfy themselves that all necessary steps have been
taken to assure that each application and use meets all performance and
safety requirements, including any applicable laws, regulations, codes,
and standards.
The illustrations, charts, sample programs, and layout examples shown in
this guide are intended solely for purposes of example. Since there are
many variables and requirements associated with any particular
installation, Allen-Bradley does not assume responsibility or liability
(to include intellectual property liability) for actual use based on the
examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application,
Installation, and Maintenance of Solid State Control (available from your
local Allen-Bradley office), describes some important differences between
solid-state equipment and electromechanical devices that should be taken
into consideration when applying products such as those described in
this publication.
Reproduction of the contents of this copyrighted publication, in whole
or in part, without written permission of Allen-Bradley Company, Inc.,
is prohibited.
Throughout this manual we use notes to make you aware of
safety considerations:
ATTENTION: Identifies information about practices or
circumstances that can lead to personal injury or death,
property damage, or economic loss.
Attention statements help you to:
identify a hazard
avoid the hazard
recognize the consequences
Important: Identifies information that is critical for successful application
and understanding of the product.
Summary of Changes
Summary of Changes
This manual has been revised to cover only Classic PLC-5 programmable
controllers: PLC-5/10, -5/12, -5/15, and -5/25.
It has also been revised to include the accompanying design worksheets
that were formerly available as a separate publication: 1785-5.2. This
separate publication is no longer available; see Appendix B for these
worksheets.
For information about Enhanced and Ethernet PLC-5 processors, see the
Enhanced and Ethernet PLC-5 Programmable Controllers User Manual,
publication 1785-6.5.12.
i
Table of Contents
Summary of Changes
Classic PLC5 Programmable Controllers
Purpose
Manual Organization
How to Use this Manual
Understanding the Terms Used in this Chapter 11
Designing Systems 12
Preparing Your Functional Specification 13
Introducing Classic PLC5 Processor Modules 15
Using the Classic PLC5 Processor as a Remote I/O Scanner 18
Using the Classic PLC5 Processor as a Remote I/O Adapter 19
Chapter
Selecting
Selecting I/O Adapter Modules 24
Selecting
Selecting an Operator Interface 26
Choosing a Classic PLC5 Processor for Your Application 29
Selecting Power Supplies 29
Selecting Memory Modules 213
Selecting a Replacement Battery 213
Selecting
Selecting a PLC5 Processor Backup System 214
Selecting Link Terminators 215
Connecting a Programming Terminal to a Processor Module 215
Choosing Cables 215
Assigning Addressing Modes, Racks, and Groups 41. . . . . .
Chapter
Placing
Understanding the Terms Used in this Chapter 42
Choosing the Addressing Mode 43
Assigning Racks 49
Addressing
Choosing
Chapter
Identifying Classic PLC5 Processor Channels/Connectors 51
Configuring
Configuring a DH+ Link 53
Connecting a DH+ Link to Data Highway 510
Choosing Programming Terminal Connection 510
Chapter
Planning Application Programs 61
Using SFCs with PLC5 Processors 61
Preparing the Programs for Your Application 63
Addressing Data T
Using the Processor Status File 69
Transferring Discrete and BlockTransfer Data 81. . . . . . . . .
Chapter
Transferring Data Using Adapter Mode 81
Programming Discrete Transfer in Adapter Mode 84
Programming Block Transfer in Adapter Mode 87
Transferring Data Using Scanner Mode 816
Programming Discrete Transfer in Scanner Mode 816
Programming Block Transfer in Scanner Mode 817
Programming Considerations 821
Chapter
Introduction to Classic PLC5 Processor Scanning 91
I/O ScanningDiscrete and Block Transfer 95
Instruction Timing and Memory Requirements 97
Program Constants 913
Direct and Indirect Elements 913
Conventions Used in These Worksheets B1. . . . . . . . . . . . . . . . . . .
Prepare
Determine Control Strategy B4
Identify Chassis Locations B6
Select Module T
Total
Assign I/O Modules to Chassis and Assign Addresses B10
Select Adapter Modules B12
Place System Hardware B14
Your Classic PLC-5 Programmable Controllers documentation is organized
into manuals according to the tasks you perform. This organization lets
you easily find the information you want without reading through
information that is not related to your current task. The arrow in Figure 1
points to the book you are currently using.
For more information on 1785 PLC-5 programmable controllers or the
above publications, contact your local Allen-Bradley sales office,
distributor, or system integrator.
This manual is intended to help you design a Classic PLC-5 programmable
controller system. Use this manual to assist you in:
selecting the proper hardware components for your system
determining the important features of classic PLC-5 processors and how
to use those features
planning your classic PLC-5 system layout
iii
Preface
Manual Organization
Chapter
/
Appendix
1Understanding Your SystemProvides an overview of Classic PLC5 processors in different system configurations. Provides
2Choosing HardwareProvides information on your hardware choices when you design a Classic PLC5 processor
3Placing System HardwareDescribes proper environment, Classic PLC5 processor protection, and prevention of
4Assigning Addressing Mode,
Rack, and Groups
5Choosing CommunicationIdentifies each Classic 5 processor channel/connector, and explains how to configure your
6Planning Your System ProgramsExplains the use of sequential function charts (SFCs). Provides guidelines and examples for
This manual has ten chapters and two appendices. The following table
lists each chapter or appendix with its corresponding title and a brief
overview of the topics covered in it.
TitleTopics Covered
an introduction to Classic PLC5 processors and their primary features and configurations. Also
provides information on using a Classic PLC5 processor as a remote I/O scanner or a remote
I/O adapter.
system.
electrostatic damage for your Classic PLC5 programmable controller system. Also covers
raceway and cable layout, backpanel spacing, and grounding configurations.
Describes the I/O addressing modes that you can choose for your chassis. Explains how you
assign group and rack numbers to your I/O chassis. Also covers how you configure
complementary I/O by assigning rack and group addresses.
Classic PLC5 processor. Provides additional information about the Data Highway Plust
(DH+t) link, programming software, and programmingterminal connections.
preparing system programs. Provides a map of data table files and methods to address the
data table files. Explains how to use the processor status file.
7Selecting Interrupt RoutinesSummarizes the conditions for which you would choose fault routines for your application.
Provides a definition of fault routines.
8Transferring Discrete and
BlockTransfer Data
9Calculating Program TimingProvides an overview of processor scan timing. Lists execution times and memory
10Maximizing System PerformanceExplains how to calculate throughput, and provides methods for optimizing I/O scan time.
ASelecting Switch SettingsDescribes the switch settings for configuring a Classic PLC5 programmable controller system.
BDesign WorksheetsProvides worksheets to help the designer plan the system and the installer to install the system.
How to Use this Manual
Explains how your CLassic PLC5 processor transfers discrete and blocktransfer data in both
scanner and adapter modes.
requirements for bit and word instructions as well as file instructions.
The following flow chart demonstrates a thought process that you can use
when you plan your Classic PLC-5 programmable controller system.
iv
System Design
Determined
Select I/O
modules, terminals
Place
hardware
Preface
Assign
addressing
Configure processor
communication
Assigning
Addressing Mode,
Racks, and Groups
Select adapter modules
Select I/O chassis
Select power supply
Select PLC5 processor
Select batteries and
memory modules
Complementary I/O
selected?
Backup system
selected?
Choosing
Hardware
and
Placing
System
Hardware
Configure Data
Highway Plus
Select programming
software
Design SFCs
Data table layout and
processor status
Use fault routines
Transfer data in adapter
and scanner modes
I/O update and ladder
program scan times
Choosing
Communication
Planning Your
System Programs
Transferring
Discrete and
Block Data
Calculating
Program Timing
and Maximizing
System
Performance
Since your decisions cannot always be made as a part of a strictly linear
process, you can choose to complete tasks in parallel. When you select
your I/O modules, for example, you can also begin to lay out and address
your modules. Consult chapter 3, “Placing System Hardware,” to
determine environmental requirements, enclosures needed, cable layout,
and grounding requirements for your chassis and I/O links. Also, you can
choose to assess block-transfer timing when you determine where you will
place your block-transfer modules (in the processor-resident local I/O
chassis, extended-local I/O chassis, or remote I/O chassis).
v
Chapter
Understanding Your System
1
Using this Chapter
Understanding the Terms
Used in this Chapter
If you want to read about:Go to page:
Terms used in this chapter11
Designing systems12
Preparing your functional specification13
Identifying Classic PLC5 processor features15
Using the Classic PLC5 processor as a remote I/O scanner18
Using the Classic PLC5 processor as a remote I/O adapter19
Become familiar with the following terms and their definitions.
TermDefinition
Processorresident
local I/O chassis
Processorresident
local I/O
Remote I/O linka serial communication link between a PLC5 processor port in scanner
the I/O chassis in which the PLC5 processor is installed
I/O modules located in the same chassis as the PLC5 processor
mode and an adapter as well as I/O modules that are located remotely
from the PLC5 processor
Remote I/O chassisthe hardware enclosure that contains an adapter and I/O modules that
are located remotely on a serial communication link to a PLC5
processor in scanner mode
Discretetransfer datadata (words) transferred to/from a discrete I/O module
Blocktransfer datadata transferred, in blocks of data up to 64 words, to/from a block
transfer I/O module (for example, an analog module)
1-1
Chapter 1
Understanding Your System
Designing
Centralized
Systems
control
is a
hierarchical system where control
over an entire process is
concentrated in one processor
Distributed
control
is a system in
which control and management
functions are spread throughout a
plant. Multiple processors handle
the control and management
functions and use a Data
Highway
or a bus system
for communication.
You can use Classic PLC-5 processors in a system that is designed for
centralized control or in a system that is designed for distributed control.
HP 9000
or VAX
Host
.
Programming
Terminal with
ControlView
Software
Remote I/O Link
Chassis withChassis with
1771ASB
Remote I/O
Adapter
r
6200 VMS
INTERCHANGE
Software
Pyramid
Integrator
To DECnet
DH+ Link
Classic PLC5
Processor
1771ASB
Remote I/O
Adapter
Programming
Terminal
Programming Terminal
ControlView
INTERCHANGE
Software
DH+ Link
PanelView
Operator
Terminal
SLC 5/01 Processor
7slot Modular System
with 1747DCM Module
Remote I/O Link
Series 8600
CNC with
Remote I/O
Consider the following items as general guidelines when designing
your system.
Will your processor(s) be used in a centralized or distributed system?
What type of process(es) will be controlled by the PLC-5 system?
What processes will be controlled together?
What are the environmental and safety concerns?
What is the flow and functionality of your system?
18084
1-2
System Design
Determined
Select I/O
modules, terminals
Place
hardware
Chapter 1
Understanding Your System
Determine the general criteria for your system. Use the chapters that
follow to guide you through the criteria and choices for selecting the major
Classic PLC-5 programmable controller system elements, as shown in
Figure 1.1.
Figure 1.1
Processor System Design Flow
PLC5
Assign
addressing
Configure processor
communication
Assigning
Addressing Mode,
Racks, and Groups
Select adapter modules
Select I/O chassis
Select power supply
Select Classic PLC5
processor
Select batteries and
memory modules
Complementary I/O
selected?
Backup system
selected?
Preparing Your
Functional Specification
Choosing
Hardware
and
Placing
System
Hardware
Configure Data
Highway Plus
Select programming
software
Design SFCs
Data table layout and
processor status
Use fault routines
Transfer data in adapter
and scanner modes
I/O update and ladder
program scan times
Choosing
Communication
Planning Your
System Programs
Transferring
Discrete and
Block Data
Calculating
Program Timing
and Maximizing
System
Performance
We recommend that you first develop a specification that defines your
hardware selection and your programming application. The specification
is a conceptual view of your system. Use it to determine your:
control strategy
hardware selection, layout, and addressing
sequential function chart (SFC)
special programming features
ladder-logic requirements
1-3
Chapter 1
Understanding Your System
Figure 1.2 illustrates a program-development model that you can use.
Figure 1.2
ProgramDevelopment
Functional
Specification
(General Conception)
Model
Acceptance
Signoff
Detailed
Anaylsis
Program
Development
Testing
This model allows for the interaction of activities at the different levels.
Each section represents an activity that you perform. Prepare a functional
specification to start; then, prepare the detailed analysis.
Based on the detailed analysis, you can also develop your programs, enter
your programs, and test them. When testing is complete, you are ready to
implement the programs in your application. The detailed analysis can be
used as the basis for developing your testing procedures and requirements.
Because the functional specification is well thought out, it can be used as
the program sign-off document.
Functional Specification Content
1-4
The functional specification represents a very general view of your process
or a description of operation. Identify the events and the overall order in
which they must occur. Identify the equipment that you will need for your
process/operation. Generally indicate the layout of your system. If your
application requires a distributed control system, for example, indicate
where you will need remote I/O links. Also, you can have a process that is
located close to your processor. The process can require faster update time
than that provided by a remote I/O link, so you can select an extendedlocal I/O link for that process.
Important: Choose a communication rate for your remote I/O link at
which every device on the link can communicate.
Chapter 1
Understanding Your System
The program-development portion of your functional specification can be
in any form: written statement; flowchart; or rough-draft MCPs, SFCs,
and subroutines. Use the form that is most familiar to you. We
recommend, however, that you generate rough-draft SFCs and subroutines
so that you have a better correspondence between your beginning diagrams
and your finished program.
Detailed Analysis
In this phase, you identify the logic needed to plan your programs. This
includes inputs, outputs, specific actions, and transitions between actions
(i.e., the bit-level details needed to write your program).
Program Development
Introducing
Classic PLC5
Processor Modules
You enter the programs either offline into your computer or online into a
processor. In the next phase, you test the programs that you have entered.
Once testing is complete, your resulting programs should match your
functional specification.
Checking for Completeness
When you complete the functional specification and the detailed analysis,
review them and check for missing or incomplete information such as:
input conditions
safety conditions
startup or emergency shutdown routines
alarms and alarm handling
fault detection and fault handling
message display of fault conditions
abnormal operating conditions
The following is a list of the PLC-5 processors and their catalog numbers.
ProcessorCatalog Number
PLC5/10t
PLC5/12t
PLC5/15t
PLC5/25t
1785LT4
1785LT3
1785LT
1785LT2
For information on other PLC-5 processors (Enhanced, Ethernet, or
ControlNet), see your Allen-Bradley representative.
1-5
Chapter 1
Understanding Your System
Classic PLC5 Family Processor Features
From the family of PLC-5 processors, you can choose the processor(s)
that you need for your application. Features common to all Classic PLC-5
processors are:
same physical dimensions
use of the left-most slot in the 1771 I/O chassis
can use any 1771 I/O module in the processor-resident local I/O chassis
with up to 32 points per module
same programming software and programming terminals
same base set of instructions
ladder programs and SFCs can be used by any of the PLC-5 processors
Check with your Allen-Bradley sales office or distributor if you have
questions regarding any of the features of your PLC-5 processor.
Subprogram Calls
Use a subroutine to store recurring sections of program logic that can be
accessed from multiple program files. A subroutine saves memory
because you program repetitive logic only once. The JSR instruction
directs the processor to go to a separate subroutine file within the logic
processor, scan that subroutine file once, and return to the point
of departure.
For detailed information about how you generate and use subroutines, see
your programming software documentation set.
Sequential Function Charts
Use SFCs as a sequence-control language to control and display the state
of a control process. Instead of one long ladder program for your
application, divide the logic into steps and transitions. A step corresponds
to a control task; a transition corresponds to a condition that must occur
before the programmable controller can perform the next control task. The
display of these steps and transitions lets you see what state the machine
process is in at a given time.
1-6
For detailed information about how you generate and use SFCs, see you
programming software.
Ladder Logic Programs
A main program file can be an SFC file numbered 1-999; it can also be a
ladder-logic file program numbered 2-999 in any program file.
Chapter 1
Understanding Your System
Consider using this technique:
SFC
Ladder Logic
If you are:
• defining the order of events in a sequential process
• more familiar with ladder logic than with programming
languages such as BASIC
• performing diagnostics
• programming discrete control
For detailed information about how you use ladder logic, see your
programming software documentation.
Backup System
The following diagram shows a typical PLC-5 backup system:
Local I/O Chassis
1785BCM Module
PLC5
Processor
1771P4S
Power Supply
HSSL
DH+ Link
Remote I/O Link
Local I/O Chassis
1785BCM Module
PLC5
Processor
1771P4S
Power Supply
DH+ LInk
Remote I/O ChassisRemote I/O Chassis
Remote I/O Link
18691
In a PLC-5 backup system configuration, one system controls the operation
of remote I/O and DH+ communications. This system is referred to as the
“primary system.” The other system is ready to take control of the remote
I/O and DH+ communications in the event of a fault in the primary system.
This is referred to as the “secondary system.”
See chapter 2, “Choosing Hardware,” to select backup system hardware.
See the PLC-5 Backup Communication Module User Manual, publication
1785-6.5.4, for more information on configuring a PLC-5 backup system.
1-7
Chapter 1
Understanding Your System
Using the Classic PLC5
Processor as a Remote I/O
Scanner
Use scanner mode whenever you want a Classic PLC-5 processor to scan
and control remote I/O link(s). The scanner-mode processor also acts as a
supervisory processor for other processors that are in adapter mode.
The scanner-mode processor scans the processor memory file to read
inputs and control outputs. The scanner-mode processor transfers
discrete-transfer data and block-transfer data to/from the processor-resident
local rack as well as to/from modules in remote I/O racks.
A PLC-5 processor scans processor-resident local I/O synchronously to the
program scan. A PLC-5 processor scans remote I/O asynchronously to the
program scan, but the processor updates the input/output image data table
from the remote I/O buffer(s) synchronously to the program scan. This
occurs at the end of each program scan.
ProcessorResident
Local I/O Scan
Synchronous to
Program Scan
ScannerMode
PLC5
Processor
Input
Output
Remote
I/O
Buffer
Input
Output
Processor
Resident
I/O
Remote I/O
Scan
Asynchronous to
Program Scan
OutputInput
Remote I/O
Link
The scanner-mode PLC-5 processor can also:
gather data from node adapter devices in remote I/O racks
process I/O data from 8-, 16-, or 32-point I/O modules
address I/O in 2-, 1-, or 1/2-slot I/O groups
support a complementary I/O configuration
support block transfer in any I/O chassis
Configure the PLC-5/15 or -5/25 processor for scanner mode by setting
switch assembly SW1.
1-8
Chapter 1
Understanding Your System
Using the Classic PLC5
Processor
as a Remote I/O Adapter
Use a Classic PLC-5 processor (except the PLC-5/10 processor) in adapter
mode when you need predictable, real-time exchange of data between a
distributed control PLC-5 processor and a supervisory processor. You
connect the processors via the remote I/O link (see Figure 1.3). You can
monitor status between the supervisory processor and the adapter-mode
PLC-5 processor at a consistent rate (i.e., the transmission rate of the
remote I/O link is unaffected by programming terminals and other
non-control-related communications).
Figure 1.3
AdapterMode
Supervisory
Processor
1
The following programmable controllers can operate as supervisory processors:
PLC2/20t and PLC2/30t processors
PLC3t and PLC3/10t processors
PLC5/11, 5/15, 5/20, 5/25, and 5/30 processors as well as PLC5/VMEt processors
PLC5/40, 5/40L, 5/60, 5/60L, and 5/80 processors as well as PLC5/40BVt and
PLC5/40LVt processors
PLC5/20Et, 5/40Et
PLC5/250t
2
All PLC5 family processors, except the PLC5/10, can operate as remote I/O adapter modules.
Communication
1
Remote I/O Link
PLC5
Processor
in Adapter
2
Mode
1771
I/O
Remote I/O Link
DL40
Message
Display
The PLC-5 processor in adapter mode acts as a remote station to the
supervisory processor. The adapter-mode PLC-5 processor can monitor
and control its processor-resident local I/O while communicating with the
supervisory processor via a remote I/O link.
The supervisory processor communicates with the PLC-5/12, -5/15, or
-5/25 adapter with either eight or four I/O image table words.
A PLC-5 processor transfers I/O data and status data using discrete
transfers and block transfers. You can also use block-transfer instructions
to communicate information between a supervisory processor and an
adapter-mode processor. The maximum capacity per block transfer is
64 words.
1-9
Choosing Hardware
Chapter
2
Chapter
Objectives
Selecting I/O Modules
Use this chapter to guide you in the selection of system hardware for
your application.
To select:Go to page:
I/O modules21
I/O adapters24
Chassis26
Operator interface26
PLC5 processor29
Power supplies29
Memory modules213
Batteries213
Complementary I/O213
Backup system214
Termination resistor215
Cables215
System Design
Determined
Choosing Hardware
Placing System
Hardware
Assigning Addressing
Mode, Racks,
and Groups
Choosing
Communication
Planning Your
System Programs
Selecting Interrupt
Routines
Transferring Discrete
and Block Data
Calculating Program
Timing
You select I/O modules to interface your PLC-5 processor with machines
or processes that you have previously determined.
Use the following list and Table 2.A as guidelines for selecting I/O
modules and/or operator control interface(s).
How much I/O is required to control the process(es)?
Where will you concentrate I/O points for portions of an entire process
(when an entire process is distributed over a large physical area)?
What type of I/O is required to control the process(es)?
What is the required voltage range for each I/O module?
What is the backplane current required for each I/O module?
What are the noise and distance limitations for each I/O module?
What isolation is required for each I/O module?
2-1
Chapter 2
Choosing Hardware
Table 2.A
Guidelines
Choose this type of
I/O module:
Discrete input module
and block I/O module
Discrete output module
and block I/O module
Analog input moduleTemperature transducers, pressure transducers, load cell transducers,
Analog output moduleAnalog valves, actuators, chart recorders, electric motor drives,
A 1791 block I/O module is a remote I/O device that has a power supply, remote I/O adapter, signal conditioning circuitry, and I/O
connections. A block I/O module does not require a chassis mount. It is used to control concentrated discrete remote I/O such as control
panels, pilot lights, and status indications.
For these types of field devices or operations (examples):Explanation:
weigh scales, barcode readers, tag readers, display devices
for Selecting I/O Modules
Important: Determine addressing in conjunction with I/O module
selection. The selection of addressing and the selection of I/O module
density are mutually dependent.
Input modules sense ON/OFF or OPENED/
CLOSED signals. Discrete signals can be either
ac or dc.
Output module signals interface with ON/OFF or
OPENED/CLOSED devices. Discrete signals can
be either ac or dc.
Convert continuous analog signals into input
values for PLC processor.
Interpret PLC processor output to analog signals
(generally through transducers) for field devices.
Are generally used for specific applications such
as position control, PID, and external device
communication.
Selecting I/O Module Density
The density of an I/O module is the number of processor input or output
image table bits to which it corresponds. A bidirectional module with 8
input bits and 8 output bits has a density of 8. Table 2.B provides
guidelines for selecting I/O module density.
Table 2.B
Guidelines
Choose this I/O density:If you:
8point I/O module
16point I/O module
32point I/O module
for Selecting I/O Module Density
• currently use 8point modules
• need integral, separatelyfused outputs
• want to minimize cost per module
• currently use 16point modules
• need separately fused outputs with a special wiring arm
• currently use 32point modules
• want to minimize number of modules
• want to minimize the space required for I/O chassis
• want to minimize cost per I/O point
2-2
Chapter 2
Choosing Hardware
Master/Expander I/O Modules
Some I/O modules (called “masters”) communicate with their expanders
over the backplane. These master/expander combinations either:
can time-share the backplane, or
cannot time-share the backplane
For masters that can time-share the backplane, you can use two masters in
the same chassis. For a master/expander combination that cannot
time-share the backplane, you cannot put another master/expander
combination in the same I/O chassis.
Example: The stepper-controller module (cat. no. 1771-M1, part of a
1771-QA assembly) and the servo-controller module (cat. no. 1771-M3,
part of a 1771-QC assembly) always act as masters and cannot time-share
the backplane. Therefore, you cannot put a second master module in the
same chassis with either of these modules.
Table 2.C summarizes the compatibility of master modules within a single
I/O chassis.
Table 2.C
Compatibility
1st Master
Module
1771IX
1771IF
1771OF
1771M1
1771M3
1
2
of Master Modules within a Single I/O Chassis
2nd Master Module
1
1771IX
1
1
1
1771IF1 1771OF1 1771M1 1771M3
2
Valid
2
Valid
2
Valid
These
modules have been superseded by 1771IXE, IFE, and OFE master modules that
do not exhibit the master/expander conflict in a chassis as 1771IX, IF
modules shown in this table.
These are the only master combinations that you can use in a single I/O chassis. These
combinations are valid with or without the module'
M3 have expander modules). Y
chassis; you can use any other intelligent I/O modules not shown here with these masters.
2
Valid
2
Valid
ou can use a maximum of two masters in the same
2
Valid
2
Valid
2
Valid
s associated expanders (1771M1 and
, and OF master
Important: Density is not relevant to an expander module because it
communicates only with its master; an expander module does not
communicate directly with an adapter.
2-3
Chapter 2
Remote I/O Adapter
I/O Density
Choosing Hardware
Selecting I/O Adapter
Modules
ASB
ALX
Select I/O adapter modules to interface your PLC-5 processor with I/O
modules. Use Table 2.D as a guide when you select I/O adapter modules.
Table 2.D
Guidelines
Choose:When your requirements are:
1771AS or 1771ASB
Remote I/O Adapter Module
(or 1771AM1, AM2 chassis
with integral power supply and
adapter module)
1771ALX ExtendedLocal I/O
Adapter Module
1
1771ASB
series C and later have 230.4 kbps communication rate in addition to 57.6 kbps and 1
for Selecting Adapter Modules
1
a remote I/O link with:
• 57.6 kbps with a distance of up to 10,000 cable feet or
• timing that isn't critical enough to place I/O modules in a processor local
I/O chassis or an extendedlocal I/O chassis
an extendedlocal I/O link with timing that is critical and all extendedlocal
I/O chassis are located within 100 ft of the processor.
17 71AS/ASB Remote I/O Adapter Modules
Table 2.E shows the I/O density per module and addressing modes you can
use with I/O chassis and remote I/O adapter modules.
Table 2.E
Chassis/Adapter Module Combinations
I/O
15.2 kbps.
Remote I/O AdapterI/O Density
Module Cat. No.
1771AS8
1771ASB
Series A
1771ASB
Series B, C, and D
1771AM28
1
Conditional
adjacent slots (even/odd pair) of the I/O chassis beginning with slot 0. If you cannot pair the
modules this way
module placement; you must use an input module and an output module in two
, leave the adjacent slot empty
per Module
16
32
8
16
32
8
16
32
16
32
.
2Slot1Slot1/2Slot
Yes
1
No
Yes
1
No
Yes
1
No
Addressing
No
No
No
Yes
Yes
1
Yes
Yes
1
Yes
Yes
1
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Using the 1771-ASB Series C or D adapter module, you can choose one of
three communication rates: 57.6 kbps, 115.2 kbps, or 230.4 kbps.
2-4
Chapter 2
Module C
I/ODensity
Choosing Hardware
1771ALX ExtendedLocal I/O Adapter Module
Table 2.F shows the I/O density per module and addressing modes you can
use with I/O chassis and extended-local I/O adapter modules.
module placement; you must use an input module and an output module in two adjacent slots (even/
odd pair) of the I/O chassis beginning with slot 0. If you cannot pair the modules this way
empty.
I/O Density
per Module
8
16
32
2Slot1Slot1/2Slot
Yes
1
No
Addressing
Yes
Yes
1
, leave the adjacent slot
Other Devices on an I/O Link
Other devices that you can use on a remote I/O link are:
PLC-5 processor in adapter mode
PLC-5/250 remote scanner in adapter mode
PLC interface module for digital ac and dc drives
remote I/O adapter for Bulletin 1336 drives
RediPANELt pushbutton and keypad modules
Datalinert
PanelView (see operator interface)
F30D option module (for T30 plant-floor terminal)
8600 or 9/SERIES CNC with remote I/O adapter option
CVIMt in adapter mode
Pro-Spect 6000 Fastening System with remote I/O adapter option
1747-DCM module (to SLC-500 rack)
1771-DCM module
1771-GMF robot (remote I/O interface module)
Yes
Yes
Yes
See the appropriate Allen-Bradley product catalog for more information on
these devices.
2-5
Chapter 2
Choosing Hardware
Selecting
I/O Chassis
4-Slot
1771A1B
An I/O chassis is a single, compact enclosure for the processor,
power-supply modules, remote and extended-local I/O adapter modules,
and I/O modules. The left-most slot of the I/O chassis is reserved for the
processor or adapter module. Consider the following when selecting
a chassis:
When you determine the maximum number of I/O in your application,
allow space for the I/O slots dedicated to power-supply modules,
communication modules, and other intelligent I/O modules.
You must use series B or later chassis with 16- and 32-point
I/O modules.
Allow space for future addition of I/O modules to chassis.
I/O chassis available are:
4-slot (1771-A1B)
8-slot (1771-A2B)
12-slot—rack mount (1771-A3B), panel mount (1771-A3B1)
16-slot (1771-A4B)
You can also choose a chassis with an integral power supply and remote
I/O adapter (show at left). The two types are:
1771AM1
1771AM2
Selecting an Operator
Interface
1-slot (1771-AM1)
2-slot (1771-AM2)
PanelView and ControlView are operator interface products or packages
that communicate with a PLC-5 processor. Use Table 2.G as a guideline
when selecting either PanelView or ControlView for your PLC-5
programmable controller system. Use Table 2.H for a comparison of
PanelView and ControlView features.
Used as an operator window to enter commands that make process adjustments such
as starts/stops and loop changes. Can also be used for alarming operations. Can
communicate with a single PLC5 processor on a remote I/O link. Has a fixed number
of devices and amount of data that it can handle. Has builtin error checking. Is an
industrialhardened CRT with pushbuttons, solid state memory and processor, and no
moving parts (i.e., disk drive).
Utilizes pass through, which is the ability to download/upload via DH+/remote I/O links.
ControlView
1
Refer
1
Store, display, and manipulate data
on process performance (i.e., trends,
process graphics, formulas, reports,
and journals)
to your local AllenBradley sales of
Used as an operator window that communicates with a PLC5 processor on Data
Highway Plus (DH+) link. Designed for use as an information link. Can communicate
to multiple PLC processors. ControlView is a software package that runs on an IBMr
DOSbased personal computer.
fice or AllenBradley distributor for more information on PanelV
iew and ControlV
iew.
Table 2.H
Comparison
of PanelV
CategoryPanelViewControlView
Communication with
PLC processor
Remote I/O
5 block transfers per terminal maximum (32 words per transfer)
1 discrete transfer per terminal (64 words maximum, one way)
This is 8 racks of transfer
GraphicsCharacter graphics
Create screens with PanelBuilder software
Monochrome or color (8 of 16 colors displayed at a time)
Number of
Screens per
Terminal/Workstation
8 to 12 screens of medium complexity typical
200 objects maximum per screen
Limited by terminal memory size: 128 Kbytes
Data Capacity200 objects maximum per screen10,000 points maximum in database
Communication
Limited by blocktransfer and discretetransfer timing
Rate
Depends on PLC processor and remote I/O link size
HardwareKeypad or Touchscreen terminals, color or monochrome
AllenBradley, IBM, or compatible computer required for
PanelBuilder software
ProgrammingPanelBuilder software
Menudriven with fillintheblank information entry
Use PanelBuilder to create application file that defines
screens, messages, alarms, then download application file to
PanelView terminal
Messages496 maximum per terminalNot Applicable
Alarms496 maximum per terminal2000 points with Alarming option
Security8 levels16 levels with individual operator login capability
OptionsRemote serial port
EEPROM or EPROM memory
iew and ControlV
DH+ link
Data Highway
Data Highway II Native Mode
Pixel Graphics
Create screens with Mouse Grafix editor option or C Toolkit
EGA, VGA, or equivalent with 256K RAM
Monochrome or color monitor
Limited only by hard disk capacity
50 data entry locations per screen
50 tags per command list per screen
300 tags/points maximum per screen
8 scan classes, each with userconfigurable foreground and
background update times; limited by performance of Data
Highway, DH+, or Data Highway II link
AB, IBM, or compatible computer with 286 or 386
processor, math coprocessor, hard disk required at each
operator station
Create data base online via the menu. Menudriven,
fillintheblank information entry, or import data via the ASCII
import capability
Create screens with the mouse GRAFIX editor option or C
toolkit option
Individual objects with security
Screen lockout
Lots of software options
iew Features
2-7
Chapter 2
Choosing Hardware
For more information on selecting and configuring PanelView, see:
PanelView Operator Terminal and PanelBuilder Development Software
User Manual, cat. no. 2711-ND002 version C, PN40061-139-01—
request latest revision
Replacing Node Adapter Firmware for PanelView Terminals Installation
Data, PN40062-236-01—request latest revision
For more information on selecting and configuring ControlView, see:
ControlView Core User Manual, publication 6190-6.5.1
ControlView Allen-Bradley Drivers User Manual,
publication 6190-6.5.5
ControlView Networking User Manual, publication 6190-6.5.9
Other Operator Interfaces
You can use the following as operator interfaces in your PLC-5
processor system:
RediPANEL pushbutton and keypad modules
Dataliner
1784-T47 and 1784-T53 programming terminals
See the appropriate Allen-Bradley product catalog for more information on
these operator interfaces.
2-8
Chapter 2
Choosing Hardware
Choosing
a Classic PLC5
Processor for Your
Application
Processor/
No.
Cat.
PLC5/10
(1785LT4)
PLC5/12
(1785LT3)
PLC5/15
(1785LT)
PLC5/25
(1785LT2)
Processor/
Cat. No.
PLC5/10
(1785LT4)
PLC5/12
(1785LT3)
PLC5/15
(1785LT)
PLC5/25
(1785LT2)
Maximum User
Memory Words
6 K
6 K
6 K expandable
to 10 K or 14 K
13 K
expandable to
17 K or 21 K
Number of Remote I/O, ExtendedLocal
I/O, and DH+ Ports
•
1 DH+
•
1 DH+
•
1 Remote I/O (Adapter Only)
•1
DH+
•
1 Remote I/O (Adapter or Scanner)
•1
DH+
•
1 Remote I/O (Adapter or Scanner)
EEPROM Module
Memory (W
Module Number
8 K (1785MJ)
8 K (1785MJ)
8 K (1785MJ)
8 K (1785MJ) or
16 K (1785MK)
ords) &
Choose from the following PLC-5 processors.
Table 2.I
PLC5 Processor Selection ChartPart 1
Classic
Total I/O Maximum
(any mix)
•
512 (32I/O modules)
•
256 (16I/O modules)
•
128 (8I/O modules)
•
512 (32I/O modules)
•
256 (16I/O modules)
•
128 (8I/O modules)
•
512 (any mix) or
•
512 in + 512 out
(complementary)
•
1024 (any mix) or
•
1024 in + 1024 out
(complementary)
Table 2.J
PLC5 Processor Selection ChartPart 2
Classic
Maximum
Number of
I/O Racks
110002.5A
41000
4130120
8170160
Analog
I/O Max
256
256
512
1024
Maximum Number of I/O
Chassis
Total
Program Scan T
K W
2 ms (discrete logic)
8 ms (typical)
2 ms (discrete logic)
8 ms (typical)
2 ms (discrete logic)
8 ms (typical)
2 ms (discrete logic)
8 ms (typical)
Ext Local
ord
Remote
ime /
Number of
RS232/
422/ 423
ports
I/O Scan time/Rack
(in a single Chassis,
extlocal or remote)
N/A
•
10 ms @ 57.6 kbps
(remote)
•
10 ms @ 57.6 kbps
(remote)
•
10 ms @ 57.6 kbps
(remote)
Remote I/O
Transmission
1
Rates
57.6 kbps
57.6 kbps
57.6 kbps
Multiple
MCPs /
Quantity
No / 1
No / 1
No / 1
No / 1
Backplane
Current
Load
2.5A
2.5A
2.5A
Selecting Power Supplies
1771P7
Use the following steps as guidelines for selecting a power supply for a
chassis that contains a PLC-5 processor, a 1771-AS or -ASB remote I/O
adapter module, or a 1771-ALX extended-local I/O adapter module.
1.Determine the input voltage for the power supply.
2.Calculate the total backplane current draw for I/O modules by
adding together the backplane current draw for each I/O module in
that chassis.
2-9
Chapter 2
Choosing Hardware
3. Add to the total of the I/O module backplane current draw either:
a. 3.3 Amps when the chassis will contain a PLC-5 processor
(maximum current draw for any PLC-5 processor) or
b. 1.2 Amps when the chassis will contain either a remote I/O
1771-AS or -ASB module or a 1771-ALX extended-local I/O
adapter module
4. If you leave slots available in your chassis for future expansion:
a. list backplane current draw for future I/O modules
b. add the total current draw for all expansion I/O modules to the
total calculated in step 3.
5. Determine whether the available space for the power supply is in the
chassis or mounted external to the chassis.
Choose your power supply from Table 2.K or Table 2.L using the input
voltage requirement and the total backplane current draw as determined in
the previous steps, 1 through 5.
See the Automation Products Catalog, publication AP100, for more
information on power supplies.
Powering a Chassis Containing a PLC5 Processor
Table 2.K lists the power-supply modules that you can use with a Classic
PLC-5 processor.
2-10
Chapter 2
Power
Input
Output Current
Power Supply
Choosing Hardware
Table 2.K
Powering
Power
Input Output Current
Supply
1771P3120V ac361111chassis, 1slot
1771P4120V ac8111616chassis, 2slot
1771P4S120V ac8111616
1771P4S1100V ac816
1771P4R120V ac8/16/24
1771P524V dc816chassis, 2slot
1771P6S220V ac816
1771P6S1200V ac816
1771P6R220V ac8/16/24
1771P7120/220V ac16
1771PS7120/220V ac16
1
See
publication 17712.136 for more information.
2
Y
ou cannot use an external power supply and a slotbased power supply module to power the same chassis;
they are not compatible.
Power
a Chassis Containing a Classic PLC5 processor
Output Current (in Amps) When Parallel with:
(in Amps)
P3P4P4SP4S1 P5P6SP6S1
1
1
Power Supply
Location
chassis, 1slot
chassis, 1slot
2
external
2-11
Loading...
+ 156 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.