Rockwell Automation 1769-SDN Installation Instructions

Installation Instructions
Compact I/O DeviceNet Scanner Module
(Cat. No. 1769-SDN)
Inside...
For More Information.............................................................................. 2
European Communities (EC) Directive Compliance ................................ 3
Hazardous Location Considerations ....................................................... 4
Module Description ................................................................................ 5
Module Installation................................................................................. 6
System Planning ..................................................................................... 8
System Assembly.................................................................................... 9
System Mounting.................................................................................. 10
Replacing the Scanner Module within a System ................................. 13
Field Wiring Connections ...................................................................... 14
Scanner Module Power-Up ................................................................... 15
Configuring the 1769-SDN on DeviceNet............................................. 16
Data Organization................................................................................. 17
Diagnostic Indicators ............................................................................ 18
Error Codes............................................................................................ 19
Specifications ....................................................................................... 21
Publication 1769-IN060C-EN-P - May 2002
2 Compact I/O DeviceNet Scanner Module
TIP

For More Information

For Refer to this Document Pub. No.
A more detailed description of how to use your DeviceNet Scanner Module
Detailed information on planning, mounting, wiring, and troubleshooting your CompactLogix System.
Detailed information on planning, mounting, wiring, and troubleshooting your MicroLogix 1500 System.
DeviceNet network planning information. DeviceNet Cable System Planning and
More information on proper wiring and grounding techniques.
If you would like a manual, you can:
download a free electronic version from the internet:
www.theautomationbookstore.com
purchase a printed manual by:
contacting your local distributor or Rockwell Automation representativevisiting www.theautomationbookstore.com and placing your ordercalling 1.800.963.9548 (USA/Canada)
or 001.330.725.1574 (Outside USA/Canada)
Compact I/O DeviceNet Scanner Module User Manual
CompactLogix System User Manual 1769-UM007C-EN-P
MicroLogix 1500 Programmable Controllers User Manual
Installation Manual
Industrial Automation Wiring and Grounding Guidelines
1769-UM009A-EN-P
1764-UM001A-US-P
DN-6.7.2
1770-4.1
Translated versions of these Installation Instructions are available electronically. Obtain a translated version of this publication at www.theautomationbookstore.com.
Publication 1769-IN060C-EN-P - May 2002
Compact I/O DeviceNet Scanner Module 3

European Communities (EC) Directive Compliance

This product carries the CE mark and is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
This product is tested to meet the Council Directive 89/336/EC Electromagnetic Compatibility (EMC) by applying the following standards, in whole or in part, documented in a technical construction file:
EN 50081-2 EMC — Generic Emission Standard, Part 2 — Industrial
Environment
EN 50082-2 EMC — Generic Immunity Standard, Part 2 — Industrial
Environment
This product is intended for use in an industrial environment.
Low Voltage Directive
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 ­Equipment Requirements and Tests. For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the Allen-Bradley publication Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1. and the Automation Systems Catalog, B111.
This equipment is classified as open equipment and must be mounted in an enclosure during operation to provide safety protection.
Publication 1769-IN060C-EN-P - May 2002
4 Compact I/O DeviceNet Scanner Module
WARNING
!
AVERTISSEMENT
!

Hazardous Location Considerations

This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.
EXPLOSION HAZARD
Substitution of components may impair suitability for Class
I, Division 2.
Do not replace components or disconnect equipment
unless power has been switched off or the area is known to be non-hazardous.
Do not connect or disconnect components unless power
has been switched off or the area is known to be non-hazardous.
This product must be installed in an enclosure. All cables
connected to the product must remain in the enclosure or be protected by conduit or other means.
All wiring must comply with N.E.C. article 501-4(b).

Environnements dangereux

Cet équipement est conçu pour être utilisé dans des environnements de Classe 1, Division 2, Groupes A, B, C, D ou non dangereux. La mise en garde suivante sapplique à une utilisation dans des environnements dangereux.
Publication 1769-IN060C-EN-P - May 2002
DANGER DEXPLOSION
La substitution de composants peut rendre cet équipement
impropre à une utilisation en environnement de Classe 1, Division 2.
Ne pas remplacer de composants ou déconnecter
l'équipement sans s'être assuré que l'alimentation est coupée et que l'environnement est classé non dangereux.
Ne pas connecter ou déconnecter des composants sans
s'être assuré que l'alimentation est coupée ou que l'environnement est classé non dangereux.
Ce produit doit être installé dans une armoire.

Module Description

2A
Compact I/O DeviceNet Scanner Module 5
1
8A
3A
4
8B
5
7A
6
3B
2B
7B
Table A
1 bus lever (with locking function) 6 grounding screw
2A upper DIN rail latch 7A DeviceNet mating male receptacle
2B lower DIN rail latch 7B removable DeviceNet female connector
3A upper panel mounting tab 8A movable bus connector with female pins
3B lower panel mounting tab 8B bus connector with male pins
4 Module and Network status LEDs 9 nameplate label
5 Address and Error numeric displays
8B
9
Publication 1769-IN060C-EN-P - May 2002
6 Compact I/O DeviceNet Scanner Module
ATTENTION
!

Module Installation

The 1769-SDN module is suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is
intended for use in clean, dry environments (Pollution Degree 2 circuits not exceeding Over Voltage Category II
(2)
(IEC 60664-1).
Prevent Electrostatic Discharge
Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. Follow these guidelines when you handle the module:
Touch a grounded object to discharge static potential.
Wear an approved wrist-strap grounding device.
Do not touch the bus connector or connector pins.
Do not touch circuit components inside the module.
If available, use a static-safe work station.
When not in use, keep the module in its static-shield box.
(1)
) and with
(3)
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Publication 1769-IN060C-EN-P - May 2002
Remove Power
ATTENTION
!
Compact I/O DeviceNet Scanner Module 7
Remove power before removing or inserting this module. When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
sending an erroneous signal to your systems field devices,
causing unintended machine motion
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance.
Publication 1769-IN060C-EN-P - May 2002
8 Compact I/O DeviceNet Scanner Module

System Planning

Consider the following when planning your system:
The scanner can communicate with up to 63 DeviceNet devices.
The scanner, as a master, can own up to 63 slave I/O nodes.
The scanner can simultaneously be a master and be a slave owned by
another DeviceNet master.
A 1769-ECR (right end cap) or 1769-ECL (left end cap) is required to
terminate the end of the Compact I/O bus.
Each bank of Compact I/O must have its own power supply (a MicroLogix
1500 acts as the power supply for modules directly connected to it).
A Compact I/O power supply, or MicroLogix 1500 Base Unit, has limits in
the amount of +5V dc and +24V dc current it can supply to modules in its I/O bank. These limits depend on the catalog number (e.g. 1769-PA2) of the supply. A bank of modules must not exceed the current limits of the I/O bank power supply or MicroLogix 1500 Base Unit.
Refer to the Compact 1769 Expansion I/O Power Supplies Installation Instructions, publication 1769-5.14 or the MicroLogix 1500 User Manual, publication 1764-UM001A-EN-P.
The scanner has a distance rating of four, therefore the scanner must be
within four modules of the I/O banks power supply.
Determine the DeviceNet baud rate based on standard DeviceNet
considerations.
Consider the number of words of I/O data the host controller supports.
For more information on planning your DeviceNet network, refer to the DeviceNet Cable System Planning and Installation Manual, publication DN-6.7.2.
Publication 1769-IN060C-EN-P - May 2002
Compact I/O DeviceNet Scanner Module 9
ATTENTION
!

System Assembly

The module can be attached to an adjacent controller, power supply, or I/O module. For mounting instructions, see Panel Mounting on page 10, or “DIN Rail Mounting on page 12. To work with a system that is already mounted, see Replacing a Single Module within a System on page 13.
The following procedure shows you how to assemble the Compact I/O system.
A
C
1. Disconnect power.
2. Check that the bus lever of the module (A) is in the unlocked (fully right)
position.
3. Use the upper and lower tongue-and-groove slots (B) to secure the modules
together.
4. Move the module back along the tongue-and-groove slots until the bus
connectors (C) line up with each other.
5. Use your fingers or a small screw driver to push the bus lever back slightly
to clear the positioning tab (D).
6. Move the module’s bus lever fully to the left (E) until it clicks. Ensure it is
locked firmly in place.
B
B
D
E
G
F
When attaching I/O modules, it is very important that the bus connectors are securely locked together to ensure proper electrical connection.
Publication 1769-IN060C-EN-P - May 2002
10 Compact I/O DeviceNet Scanner Module
ATTENTION
!
7. Attach an end cap terminator (F) to the last module in the system by using
the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (G).
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap must be used to terminate the end of the serial communication bus.

System Mounting

During panel or DIN rail mounting of all devices, be sure that all debris (metal chips, wire strands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage on power up.
Minimum Spacing
Compact I/O
Top
Compact I/O
Bottom
Compact I/O
Compact I/O
Maintain spacing from enclosure walls, wireways, adjacent equipment, etc. Allow 50 mm (2 in.) of space on all sides for adequate ventilation, as shown:
Allow at least 110 mm (4.33 in.) of enclosure depth to accommodate the module and the DeviceNet connector.
Side
Controller
Panel Mounting
Mount the module to a panel using two screws per module. Use M4 or #8 panhead screws. Mounting screws are required on every module.
Publication 1769-IN060C-EN-P - May 2002
Side
Compact I/O
End Cap or Cable
Compact I/O DeviceNet Scanner Module 11
Panel Mounting Using the Dimensional Drawing
NOTE: All dimensions are in mm (inches). Hole spacing tolerance: ±0.04 mm (0.016 in.).
Compact I/O with CompactLogix Controller and Power Supply
Mounting Hole Dimension
132 mm (5.19 in)
122.6 mm (4.83 in)
59 mm
59 mm
(2.32 in)
(2.32 in)
(1.97 in)
40 mm
(1.58 in)
118 mm (4.65 in)
35 mm
(1.38 in)
35 mm
50 mm
(1.38 in)
DIN Rail Center Line
Compact I/O with MicroLogix 1500 Base Unit and Processor
168 mm
Mounting Hole Dimension
59 mm
(2.32 in)
(6.62 in)
147 mm (5.79 in)
35 mm
(1.38 in)
70 mm
(2.76 in)
(1.38 in)
14.7 mm (0.58 in)
35 mm
35 mm
(1.38 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
28.5 mm (1.12 in)
147.4 mm (5.81 in)
28.5 mm (1.12 in)
132 mm (5.19 in)
122.6 mm (4.83 in) 59 mm
(2.32 in)
118 mm (4.65 in)
DIN Rail Center Line
13.5 mm (0.53 in)
14.7 mm (0.58 in)
Publication 1769-IN060C-EN-P - May 2002
147.4 mm (5.81 in)
12 Compact I/O DeviceNet Scanner Module
Panel Mounting Procedure Using Modules as a Template
The following procedure allows you to use the assembled modules as a template for drilling holes in the panel. Due to module mounting hole tolerance, it is important to follow these procedures:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the center of all
module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including any
previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8 screw.
5. Place the modules back on the panel, and check for proper hole alignment.
6. Attach the modules to the panel using the mounting screws.
7. Repeat steps 1 to 6 for any remaining modules.
DIN Rail Mounting
The module can be mounted using the following DIN rails: 35 x 7.5 mm (EN 50 022
- 35 x 7.5) or 35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latches. Press the DIN rail mounting area of the module against the DIN rail. The latches will momentarily open and lock into place. DIN rail mounting dimensions are shown below.
Dimension Height
B
A
C
Publication 1769-IN060C-EN-P - May 2002
A 118 mm
B 59 mm
C 59 mm
(4.65 in.)
(2.325 in.)
(2.325 in.)
Compact I/O DeviceNet Scanner Module 13
TIP

Replacing the Scanner Module within a System

The scanner can be replaced while the system is mounted to a panel (or DIN rail).
1. Remove power. See important note on page 7.
2. Remove the DeviceNet cable from the scanner by removing the DeviceNet
connector.
3. Remove the upper and lower mounting screws from the scanner (or open
the DIN latches using a flat-blade screwdriver).
4. On the scanner to be replaced and the right-side adjacent module (or end
cap if the scanner is the last module in the bank), move the bus levers to the right (unlock) to disconnect the scanner from the adjacent modules.
5. Gently slide the disconnected scanner module forward.
If you feel excessive resistance, make sure that you disconnected the scanner from the bus and that you removed both mounting screws (or opened the DIN latches).
.
It may be necessary to rock the scanner slightly from front to back to remove it, or, in a panel-mounted system, to loosen the screws of adjacent modules.
6. Before installing the replacement scanner, be sure that the bus lever on the
right-side adjacent module is in the unlocked (fully right) position.
7. Slide the replacement scanner into the open slot.
8. Connect the scanner and modules together by locking (fully left) the bus
levers on the replacement scanner and the right-side adjacent module or end cap.
9. Replace the mounting screws (or snap the scanner onto the DIN rail).
10. Replace the DeviceNet cable on the scanner by attaching the connector to
the scanner.
Publication 1769-IN060C-EN-P - May 2002
14 Compact I/O DeviceNet Scanner Module
ATTENTION
!
11. Restore scanner configuration using RSNetWorx for DeviceNet.
IMPORTANT
Be sure that the new module has the same node address and baud rate as the module that was replaced.

Field Wiring Connections

Grounding the Scanner Module
This product is intended to be mounted to a well-grounded mounting surface such as a metal panel. Additional grounding connections from the scanners mounting tabs or DIN rail (if used), are not required unless the mounting surface cannot be grounded.
The grounding screw on the front of the scanner must be connected to a suitable ground source when operating in electrically noisy environments. Use a #14 AWG wire to make this connection.
Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley publication 1770-4.1, for additional information.
Publication 1769-IN060C-EN-P - May 2002
DeviceNet Wiring
Compact I/O DeviceNet Scanner Module 15
DeviceNet Connector
Grounding Screw Use #14 AWG wire to connect to panel ground.
(1)
Connect
Red Wire V+
White Wire CAN High
Bare Wire Shield
Blue Wire CAN Low
Black Wire V-
To
1. Connect the DeviceNet cable to the removable connector as shown.
2. Insert the removable female connector into the mating male connector on
the DeviceNet scanner module.
3. Screw the removable connector to the scanner case with the upper and
lower mounting screws. Screw torque is 0.6 to 0.7 Nm (5 to 6 in-lbs).
IMPORTANT
If the 1769-SDN is the first or last device connected to the DeviceNet network trunkline, be sure to add a termination resistor
(120 1% ¼W resistor, Allen-Bradley part number 1485A-C2)
across the Blue (CAN Low) and White (CAN High) wires.

Scanner Module Power-Up

When power is applied via the Compact I/O bus, the scanner module goes through a self test sequence. Upon successful completion of the self test, the scanner is ready to communicate.
The default scanner settings are:
baud rate = 125K
node address = 63
Use your configuration software to change the baud rate and node address.
Publication 1769-IN060C-EN-P - May 2002
16 Compact I/O DeviceNet Scanner Module
TIP
TIP

Configuring the 1769-SDN on DeviceNet

The 1769-SDN must be configured using a DeviceNet configuration tool. The recommended configuration software is RSNetWorx for DeviceNet (version 3.00 or higher).
If your RSNetWorx configuration software does not include the required EDS (Electronic Data Sheet) file, it is available via http://www.ab.com/networks/eds.
This configuration tool allows you to identify all of the devices (I/O modules, power supplies, expansion cables, end caps) and their locations in your system.
The controller must be in the Run mode, or the scanner in the Idle mode (bit 0 of the Module Command Array = 0), for the scanner to accept the configuration information.
For more information, refer to the Manual, publication 1769-UM009A-EN-P.
Publication 1769-IN060C-EN-P - May 2002
Compact I/O DeviceNet Scanner Module
User
Compact I/O DeviceNet Scanner Module 17

Data Organization

The scanner uses the input and output data images to transfer data, status and command information between the scanner and the controller. The basic structure is shown below. Refer to the
Compact I/O DeviceNet Scanner Module
publication 1769-UM009A-EN-P, for more detailed information.
Input Data Image
The input data image is transferred from the scanner module to the controller.
Word Description Data Type
0 to 63 Status Structure 64-word array
64 and 65 Module Status Register 2 words
66 to 245 Input Data Image 180-word array
Output Data Image
The output data image is transferred from the controller to the scanner module.
User Manual,
Word Description Data Type
0 and 1 Module Command Array 2-word array
2 to 181 Output Data Image 180-word array
The following table shows the bit descriptions for the Module Command Array.
Word Bit Operating Mode
0 0 1 = Run, 0 = Idle
1 1 = Fault
2 1 = Disable Network
3
4 1 = Reset
5 to 15
10 to 15
(1)
DO NOT manipulate Reserved Bits. Doing so may interfere with future compatibility.
Reserved
Reserved
Reserved
(1)
(1)
(1)
Publication 1769-IN060C-EN-P - May 2002
18 Compact I/O DeviceNet Scanner Module

Diagnostic Indicators

Indicator Color/
Module Off No power applied to module. Apply power.
Network Off No module power, no network power, or
7-Segment Numeric Display
Status
Flashing Green
Solid Green Normal operation. No action required.
Flashing Red
Solid Red Unrecoverable fault Verify module connectors are properly
Flashing Green
Solid Green Normal operation. Scan list is
Flashing Red
Solid Red Critical network failure. Duplicate
Node Address and Status Display
Indicates Recommended Action
No Bus Master (MicroLogix or CompactLogix controller) present.
Recoverable Fault - Memory has been erased or is being programmed.
communications are not occurring between the module and the DeviceNet network. (This may be an acceptable condition.)
Device is operational. There are no connections established with any of the network devices.
configured. Module is not in Idle mode.
One or more of the devices that the scanner is communicating with is in a timed out state.
DeviceNet node address detected.
Indicates diagnostic information about the status of the module. When the numeric display is showing 0 to 63, it is indicating the 1769-SDN module’s DeviceNet node address. When it shows 70 to 99, it indicates an Error Code for the displayed node address. When it flashes alternating numbers, one is the Error Code (70 to 99), and the other is the Node Number (0 to 63) that has generated the error. See the list of Error Codes on page 19 for more information.
Verify module connectors are properly seated. If they are, cycle power to the controller. If this does not correct the problem, replace the controller. If replacing the controller does not correct the problem, replace the 1769-SDN.
Complete flash update or start a new update.
seated. If they are, verify that bus terminator/end cap is installed. Cycle power. If still faulted, replace the module.
Verify module has power. Check that the DeviceNet cable is securely connected and the DeviceNet network is powered. Verify that network power is adequate (11 to 25V dc).
If the module is supposed to be controlling DeviceNet slaves, configure the modules scan list.
No action required.
Monitor the status display, or the module’s status field to determine which slave device is offline.
Reset module. Change modules node address or change conflicting device’s node address. If failure continues, replace module.
Publication 1769-IN060C-EN-P - May 2002
Compact I/O DeviceNet Scanner Module 19

Error Codes

The following table describes the Error Codes indicated by the 7-segment numeric display.
Code (decimal)
70 Duplicate Node Controller has Failed Duplicate
71 Illegal Scan
72 Slave Timeout One of the module’s slave devices
73 Electronic Key
75 No Messages
76 No Message
77 Slave Data Size
78 No Such
79 Transmit
80 In Idle Mode Module is in Idle mode. Put the controller into Run mode and
81 Scanner
Name Description Recommended Action
Change the module’s or conflicting device’s network address (node number) to an available one.
remove any illegal data.
Inspect the module’s slave devices and verify the DeviceNet connections.
Make sure that the device at the flashing node address matches the desired electronic key (vendor, product code, product type)
Verify the scan list is correctly configured to scan slave devices. Verify DeviceNet network connections.
None. There are other active devices on the network, initiating messages, but none of the messages are for the module.
Either reconfigure the slave device, or change the modules scan list to match the slave device.
Either add the device to the DeviceNet network, or delete the devices entry in the scan list.
Make sure that the module is connected to a valid network. Check for disconnected cables.
enable the scanner Run bit (bit 0 of the Module Command Array = 1). See page
17.
Check the FAULT value in the module command array.
List Data
Mismatch
Received
For Scanner
Mismatch
Device
Failure
Faulted
Node Address Check. The node address selected is already in use.
Illegal data in Scan List. Reconfigure the scan list table and
has stopped communicating.
The slave device Vendor ID key parameter does not match the slave’s configuration in the module’s scan list.
No network traffic received by the scanner. 10 seconds have elapsed and no network traffic for the module or for any other device have been received by the module.
No direct network traffic for the scanner detected. 10 seconds elapsed and no DeviceNet input being screened by the module has been received.
The data being received from the slave device does not match the configuration in the scan list.
Slave device in scan list does not exist.
The module has failed to transmit a message.
The Scanner has stopped producing and consuming I/O data. This condition does not affect the scanners system or messaging modes.
Publication 1769-IN060C-EN-P - May 2002
20 Compact I/O DeviceNet Scanner Module
Code (decimal)
82 Fragmentation
83 Slave Init Error Slave device is returning error
84 Not Yet
85 Receive Buffer
86 Device Went
89 Auto Device
90 Disabled
91 Bus Off Bus off condition detected on
92 No DeviceNet
95 FLASH Update Flash Update In Progress None. DO NOT disconnect the module
98 Firmware
99 Hard Fault Cycle Power. Reflash module firmware.
Name Description Recommended Action
Error
Initialized
Overflow
Idle
Replacement (ADR) Error
Network
Power
Corrupted
Error detected in sequence of fragmented I/O messages from device.
responses when the module attempts to communicate with it.
Module has not completed its initial attempt to establish communications with its slaves.
Data size returned is larger than expected.
Device is producing Idle state. Check the device configuration and
Slave device responded with an error to the initialization data sent to it by the scanner; or the configuration table in the scanner’s flash memory is not valid for a slave node.
DeviceNet Port is Disabled Check for the disable being set in the
integral DeviceNet port.
No network power detected on DeviceNet port.
Firmware is corrupted. Reflash module firmware. DO NOT
Check scan list table entry for slave device to make sure that input and output data lengths are correct. Check slave device configuration.
Check slave device’s configuration. Reboot slave device.
None. This code clears itself once the module properly initializes all slave devices on the network.
Configure the slave device for a smaller data size.
slave node status.
Try the ADR download again. If it still fails, try clearing the ADR flash by downloading an empty ADR configuration to the scanner and then try the ADR configuration again.
module command array.
Check the DeviceNet connections and physical media integrity. Check system for failed slave devices or other possible sources of network interference. Check the Baud Rate.
Provide network power. Make sure the module drop cable is providing the proper power to the DeviceNet port.
from the network while a flash update is in progress.
power cycle the module. Doing so may cause the module to become inoperable If the problem persists contact Rockwell Automation Technical Support.
Contact Rockwell Automation Technical Support.
Publication 1769-IN060C-EN-P - May 2002
Compact I/O DeviceNet Scanner Module 21

Specifications

General Specifications
Specification Value
Module Dimensions 118 mm (height) x 87 mm (depth) x 35 mm (width)
Approximate Shipping Weight (with carton)
Storage Temperature -40°C to +85°C (-40°F to +185°F)
Operating Temperature 0°C to +60°C (32°F to +140°F)
Operating Humidity 5% to 95% non-condensing
Operating Altitude
Vibration Operating: 10 to 500 Hz, 5G, 0.030 inches maximum peak-to-peak
Shock Operating: 30G panel mounted (20G DIN rail mounted)
Agency Certification
Hazardous Environment Class Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604,
Radiated and Conducted Emissions EN50081-2 Class A
Electrical /EMC: The module has passed testing at the following levels:
ESD Immunity (IEC61000-4-2)
Radiated Immunity (IEC61000-4-3)
Fast Transient Burst (IEC61000-4-4)
Surge Immunity (IEC61000-4-5)
Conducted Immunity (IEC61000-4-6)
(1)
For operation above 2000 meters, consult the factory.
(2)
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 1000 MHz.
height including mounting tabs is 138 mm
4.65 in. (height) x 3.43 in (depth) x 1.38 in (width) height including mounting tabs is 5.43 in.
280g (0.61 lbs.)
2000 meters (6561 feet)
Non-Operating: 40G panel mounted (30G DIN rail mounted)
C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE and C-Tick compliant for all applicable directives
ODVA DeviceNet conformance tested
C-UL under CSA C22.2 No. 213)
4kV contact, 8kV air, 4kV indirect
10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed carrier
2 kV, 5 kHz
2 kV galvanic gun
10V, 0.15 to 80 MHz
(1)
(2)
Publication 1769-IN060C-EN-P - May 2002
22 Compact I/O DeviceNet Scanner Module
Electrical and DeviceNet Specifications
Specification Value
Bus Current Draw (maximum) 440 mA at 5V dc (2.2 Watts)
DeviceNet Power Requirements N.E.C. Class 2
Heat Dissipation (maximum) 3.8 Watts (assumes typical network traffic)
Baud Rates 125K bits/second (default)
Maximum Cable Length 500 meters at 125K baud
DeviceNet Cable Allen-Bradley catalog number 1485C-P1-Cxxx. Refer to publication
Power Supply Distance Rating 4 (The module may not be more than 4 modules away from the
DeviceNet to Compact Bus Isolation Verified by one of the following dielectric tests: 500V ac for 1
Vendor I.D. code 1
Product Type Code 12
Product Code 105
90 mA at 11V dc (maximum) 110 mA at 25V dc (maximum) 200 mA for 1.5 ms (inrush)
250K bits/second 500K bits/second
100 meters at 500K baud
DN-2.5 for more information.
power supply).
minute or 707V dc for 1 minute. 30V dc working voltage (IEC Class 2 reinforced insulation)
Compact, CompactLogix, MicroLogix and RSNetWorx are trademarks of Rockwell Automation. DeviceNet is a trademark of Open DeviceNet Vendors Association (ODVA).
Publication 1769-IN060C-EN-P - May 2002
Notes:
Compact I/O DeviceNet Scanner Module 23
Publication 1769-IN060C-EN-P - May 2002
Publication 1769-IN060C-EN-P - May 2002 PN 40072-107-01(3)
Supersedes Pub lication 1769-IN060B-EN -P - September 2001 Copyright © 2002 Rockwell Automa tion. All rights reser ved. Printed in the U.S.A.
Loading...