About the Power Supplies
Compact I/O power supplies provide 120/240V AC and 24V DC power to modules, which
can be placed to the left or the right side of the 1769 power supply. As many as eight I/O
modules can be placed on each side of the power supply.
2 Compact I/O Expansion Power Supplies
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
SGI-1.1 available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the
wide variety of uses for solid state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
) describes some important differences between solid state
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
Identifies information about practices or circumstances that can cause an explosion in
a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
Identifies information that is critical for successful application and understanding of
the product.
Identifies information about practices or circumstances that can lead to personal injury
or death, property damage, or economic loss. Attentions help you identify a hazard,
avoid a hazard and recognize the consequences.
Labels may be on or inside the equipment (for example, drive or motor) to alert people
that dangerous voltage may be present.
BURN HAZARD
Labels may be on or inside the equipment (for example, drive or motor) to alert people
that surfaces may reach dangerous temperatures.
Publication 1769-IN028B-EN-P - October 2008
Environment and Enclosure
Compact I/O Expansion Power Supplies 3
ATTENTION
This equipment is intended for use in a Pollution Degree 2 industrial environment, in
overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes
up to 2000 meters (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to
IEC/CISPR Publication 11. Without appropriate precautions, there may be potential
difficulties ensuring electromagnetic compatibility in other environments due to
conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an
enclosure that is suitably designed for those specific environmental conditions that will
be present and appropriately designed to prevent personal injury resulting from
accessibility to live parts. The enclosure must have suitable flame-retardant properties to
prevent or minimize the spread of flame, complying with a flame spread rating of 5VA,
V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible
only by the use of a tool. Subsequent sections of this publication may contain additional
information regarding specific enclosure type ratings that are required to comply with
certain product safety certifications.
In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, for additional installation
requirements, Allen-Bradley publication 1770-4.1
• NEMA Standards publication 250 and IEC publication 60529, as applicable, for
explanations of the degrees of protection provided by different types of enclosure.
.
Prevent Electrostatic Discharge
ATTENTION
This equipment is sensitive to electrostatic discharge, which can cause internal damage
and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Publication 1769-IN028B-EN-P - October 2008
4 Compact I/O Expansion Power Supplies
North American Hazardous Location Approval
The following information applies when
operating this equipment in hazardous
locations:
Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for use in
Class I Division 2 Groups A, B, C, D, Hazardous Locations and
nonhazardous locations only. Each product is supplied with
markings on the rating nameplate indicating the hazardous
location temperature code. When combining products within a
system, the most adverse temperature code (lowest "T" number)
may be used to help determine the overall temperature code of
the system. Combinations of equipment in your system are subject
to investigation by the local Authority Having Jurisdiction at the
time of installation.
WARNING
EXPLOSION HAZARD -
• Do not disconnect equipment
unless power has been removed
or the area is known to be
nonhazardous.
• Do not disconnect connections to
this equipment unless power has
been removed or the area is
known to be nonhazardous.
Secure any external connections
that mate to this equipment by
using screws, sliding latches,
threaded connectors, or other
means provided with this product.
• Substitution of components may
impair suitability for Class I,
Division 2.
• If this product contains batteries,
they must only be changed in an
area known to be nonhazardous.
Informations sur l’utilisation de cet
équipement en environnements dangereux:
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent
qu'à une utilisation en environnements de Classe I Division 2
Groupes A, B, C, D dangereux et non dangereux. Chaque produit
est livré avec des marquages sur sa plaque d'identification qui
indiquent le code de température pour les environnements
dangereux. Lorsque plusieurs produits sont combinés dans un
système, le code de température le plus défavorable (code de
température le plus faible) peut être utilisé pour déterminer le
code de température global du système. Les combinaisons
d'équipements dans le système sont sujettes à inspection par les
autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT
RISQUE D’EXPLOSION –
• Couper le courant ou s'assurer
que l'environnement est classé
non dangereux avant de
débrancher l'équipement.
• Couper le courant ou s'assurer
que l'environnement est classé
non dangereux avant de
débrancher les connecteurs. Fixer
tous les connecteurs externes
reliés à cet équipement à l'aide
de vis, loquets coulissants,
connecteurs filetés ou autres
moyens fournis avec ce produit.
• La substitution de composants
peut rendre cet équipement
inadapté à une utilisation en
environnement de Classe I,
Division 2.
• S'assurer qu e l'environnement est
classé non dangereux avant de
changer les piles.
Install Safety Circuits
WARNING
Circuits that are installed on the machine for safety reasons, like overtravel limit switches, stop
push buttons, and interlocks, should always be hard-wired directly to the master control relay.
These devices must be wired in series so that when any one device opens, the master control
relay is de-energized, thereby removing power to the machine.
ATTENTION
Publication 1769-IN028B-EN-P - October 2008
Explosion Hazard - Do not connect or disconnect connectors while circuit is live.
Never alter these circuits to defeat their function. Serious injury or machine damage
could result.
Compact I/O Expansion Power Supplies 5
European Hazardous Location Approval
1769-PB2, 1769-PB4 Only
European Zone 2 Certification (The following applies when the product bears the Ex or EEx
Marking)
This equipment is intended for use in potentially explosive atmospheres as defined by European Union
Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements
relating to the design and construction of Category 3 equipment intended for use in potentially explosive
atmospheres, given in Annex II to this Directive.
Compliance with the Essential Health and Safety Requirements has been assured by compliance with EN
60079-15 and EN 60079-0.
WARNING
ATTENTION
• This equipment must be installed in an enclosure providing at least IP54 protection
when applied in Zone 2 environments.
• This equipment shall be used within its specified ratings defined by Allen-Bradley.
• Provisions shall be made to prevent the rated voltage from being exceeded by
transient disturbances of more than 40% when applied in Zone 2 environments.
• This equipment must be used only with ATEX certified backplanes.
• Secure any external connections that mate to this equipment by using screws, sliding
latches, threaded connectors, or other means provided with this product.
• Do not disconnect equipment unless power has been removed or the area is known to
be nonhazardous.
This equipment is not resistant to sunlight or other sources of UV radiation.
Publication 1769-IN028B-EN-P - October 2008
6 Compact I/O Expansion Power Supplies
Before You Begin
There are some points about power distribution that you should know.
• The master control relay must be able to inhibit all machine motion by removing
power to the machine I/O devices when the relay is de-energized. We recommend
that the controller remains powered even when the master control relay is
de-energized.
• If you are using a DC power supply, interrupt the load side rather than the AC line
power. This avoids the additional delay of power supply turn-off. The DC power
supply should be powered directly from the fused secondary of the transformer.
Power to the DC input and output circuits should be connected through a set of
master control relay contacts.
Perform Periodic Tests of Master Control Relay Circuit
Any part can fail, including the switches in a master control relay circuit. The failure of one of
these switches would most likely cause an open circuit, which would be a safe power-off
failure. However, if one of these switches shorts out, it no longer provides any safety
protection. These switches should be tested periodically to assure they will stop machine
motion when needed.
Publication 1769-IN028B-EN-P - October 2008
Compact I/O Expansion Power Supplies 7
Parts Illustration of a Power Supply
The sample illustrations of a 1769-PA4 power supply let you review the various components
that comprise a power supply, which is attached to a DIN rail.
1
9
2a
3
5b
10
11
12
2b
ItemDescription
1769-PA4
44716
44717
4
8a
7a
5a
7b
8b
6
44718
7a
7b
44719
1
2a
2b
3
4
5a
5b
6
Bus lever (with locking function)
Upper panel mounting tabs
Lower panel mounting tabs
Status Indicator
Power supply door with terminal identification label
Movable bus connector with female pins
Stationary bus connector with male pins
Nameplate label
Publication 1769-IN028B-EN-P - October 2008
8 Compact I/O Expansion Power Supplies
ItemDescription
7a
7b
8a
8b
9
10
11
12
Upper tongue-and-groove slots
Lower tongue-and-groove slots
Upper DIN rail latches
Lower DIN rail latches
Terminal block with finger-safe cover
Fuse housing cover for replaceable fuse
120V AC or 240V AC line input power selector switch (PA4 only)
Removable selector switch label (PA4 only)
Install an I/O Expansion Power Supply
Compact I/O Expansion Power Supplies are suitable for use in an industrial environment
when installed in accordance with these instructions. Specifically, this equipment is intended
for use in clean, dry environments (Pollution degree 2
Voltage Category II
(2)
(IEC 60664-1).
(3)
(1)
) and to circuits not exceeding Over
Disconnect the Power
WARNING
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a
temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are
controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Remove power before removing or inserting this power supply from the 1769 I/O system.
When you remove or insert a power supply with power applied, an electrical arc may
occur. An electrical arc can cause personal injury or property damage by:
• sending an erroneous signal to your system’s field devices, causing unintended
machine motion.
• causing an explosion in a hazardous environment.
Electrical arcing causes excessive wear to contacts on both the power supply and its
mating connector. Worn contacts may create electrical resistance.
Publication 1769-IN028B-EN-P - October 2008
Compact I/O Expansion Power Supplies 9
Assemble the System
1769 Compact I/O power supplies distribute power from either side of the power supply.
EXAMPLE
A 2 amp at 5V DC power supply (1769-PA2, 1769-PB2) can provide 1 amp to the right side
of the power supply and 1 amp to the left. A 4 amp at 5V DC power supply (1769-PA4,
1769-PB4) can provide 2 amps to the right side of the power supply and 2 amps to the
left.
The maximum amount of current the system supports in both directions is:
• 1769-PA2, 1769-PB2: 2 amps at 5V DC; 1 amp at 24V DC.
• 1769-PA4, 1769-PB4: 4 amps at 5V DC; 2 amps at 24V DC.
IMPORTANT
The maximum amount of current that can be distributed from either side of any 1769
power supply is 2 amps at 5V DC and 1 amp at 24V DC.
This is a limit of the 1769 Compact I/O Bus.
The power supply can be attached to an adjacent I/O module before or after
mounting.
3
44721
2
1
44720
1
ItemDescription
1Upper and lower tongue-and-groove slots
2Bus connectors
3Positioning tab
4Direction of the bus lever of the power supply to the I/O modules
5End cap terminator
6End cap bus terminator
4
6
5
Publication 1769-IN028B-EN-P - October 2008
10 Compact I/O Expansion Power Supplies
Follow these steps to assemble the Compact I/O system.
1. Disconnect your line power.
The power supply does not support removal or insertion of modules under power.
WARNING
If you connect or disconnect wiring while the field-side power is on, an electrical arc can
occur. This could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.
2. Check that the bus lever of the power supply to be installed is in the unlocked (fully
right) position.
3. Use the upper and lower tongue-and-groove slots to secure the power supply to an
I/O module.
4. Move the power supply back along the tongue-and-groove slots until the bus
connectors line up with each other.
5. Push the bus lever back slightly to clear the positioning tab.
Use your fingers or a small screwdriver.
6. To allow communication between the controller and the I/O, move the bus lever of
the power supply and its adjacent I/O modules fully to the left until it clicks.
Make sure it is locked firmly in place.
ATTENTION
When attaching expansion I/O power supplies, it is very important that the bus
connectors are securely locked together to ensure proper electrical connection.
7. Attach an end cap terminator to the last I/O module in the system by using the
tongue-and-groove slots as before.
8. Lock the end cap bus terminator.
IMPORTANT
A 1769-ECR or 1769-ECL right or left end cap (respectively) must be used to terminate the
end of the serial communication bus.
Publication 1769-IN028B-EN-P - October 2008
Compact I/O Expansion Power Supplies 11
Mount an I/O Expansion Power Supply
ATTENTION
During panel or DIN rail mounting of all devices, be sure that all debris (for example,
metal chips, wire strands) is kept from falling into the module. Debris that falls into the
module could cause damage on power up.
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment, and so forth. Allow 50
mm (2 in.) of space on all sides for adequate ventilation.
50 mm
(2 in.)
Side
Power Supply
Compact I/O
Compact I/O
Compact I/O
End Cap
Side
50 mm
(2 in.)
To p
(1)(2)
End Cap
Compact I/O
Bottom
ItemDescription
1This could be an end cap, controller, adapter, or
expansion cable depending on your system
configuration.
2This could be an end cap or expansion cable
depending on your system configuration.
Prevent Excessive Heat
For most applications, normal convective cooling keeps the system within the specified
operating range. Verify that the specified temperature range is maintained. Proper spacing of
components within an enclosure is usually sufficient for heat dissipation.
In some applications, a substantial amount of heat is produced by other equipment inside or
outside the enclosure. In this case, place blower fans inside the enclosure to assist in air
circulation and to reduce hot spots near the system.
Publication 1769-IN028B-EN-P - October 2008