Rockwell Automation 1763 User Manual

MicroLogix 1100 Programmable Controllers
Bulletin 1763 Controllers and 1762 Expansion I/O
User Manual

Important User Information

WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to: personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Labels may be on or inside the equipment, such as a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, such as a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Rockwell Automation, DeviceNet, ModBus, Allen-Bradley, SLC 5/02, SLC 5/03, PLC-5, MicroLogix, SLC 500, RSLogix, RSLinx, and RSLogix 500 are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 1763-UM001D-EN-P - March 2011

Summary of Changes

To help you find new and updated information in this release of the manual, we have included change bars as shown to the right of this paragraph.

Firmware Revision History

Features are added to the controllers through firmware upgrades. See the latest release notes, 1763-RN003 level you need. Firmware upgrades are not required, except to allow you access to the new features.
, to be sure that your controller’s firmware is at the
1 Publication 1763-UM001D-EN-P - March 2011
Summary of Changes 2
Notes:
Publication 1763-UM001D-EN-P - March 2011

Table of Contents

Summary of Changes
Firmware Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents Preface
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Common Techniques Used in this Manual. . . . . . . . . . . . . . . . . . . . . . 10
Chapter 1
Hardware Overview
Hardware Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Component Descriptions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
MicroLogix 1100 Memory Module and Built-in Real-Time Clock 12
1762 Expansion I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Communication Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Communication Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Chapter 2
Installing Your Controller
Agency Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Compliance to European Union Directives . . . . . . . . . . . . . . . . . . . . . 19
EMC Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Low Voltage Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Safety Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Hazardous Location Considerations. . . . . . . . . . . . . . . . . . . . . . . . 21
Disconnecting Main Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Safety Circuits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Power Distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Periodic Tests of Master Control Relay Circuit . . . . . . . . . . . . . . . 23
Power Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Isolation Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Power Supply Inrush . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Loss of Power Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Input States on Power Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Other Types of Line Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Preventing Excessive Heat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Master Control Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Using Emergency-Stop Switches . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Schematic (Using IEC Symbols) . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Schematic (Using ANSI/CSA Symbols). . . . . . . . . . . . . . . . . . . . . 29
Installing a Memory Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Using the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Connecting the Battery Wire Connector . . . . . . . . . . . . . . . . . . . . 32
Controller Mounting Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Controller and Expansion I/O Spacing . . . . . . . . . . . . . . . . . . . . . . . . 33
Mounting the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
DIN Rail Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3 Publication 1763-UM001D-EN-P - March 2011
4 Table of Contents
Wiring Your Controller
Panel Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1762 Expansion I/O Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Mounting 1762 Expansion I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
DIN Rail Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Panel Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Connecting Expansion I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Chapter 3
Wiring Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Wiring Recommendation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Wiring the Terminal Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Using Surge Suppressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Recommended Surge Suppressors . . . . . . . . . . . . . . . . . . . . . . . . . 45
Grounding the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Terminal Block Layouts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Terminal Groupings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Sinking and Sourcing Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . 50
1763-L16AWA, 1763-L16BWA, 1763-L16BBB and 1763-L16DWD
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Controller I/O Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Minimizing Electrical Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Wiring Your Analog Channels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Analog Channel Wiring Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . 53
Minimizing Electrical Noise on Analog Channels . . . . . . . . . . . . . 54
Grounding Your Analog Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Expansion I/O Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Digital Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Analog Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Communication Connections
Publication 1763-UM001D-EN-P - March 2011
Chapter 4
Supported Communication Protocols. . . . . . . . . . . . . . . . . . . . . . . . . . 71
Default Communication Configuration . . . . . . . . . . . . . . . . . . . . . . . . 72
Using the Communications Toggle Functionality . . . . . . . . . . . . . . . . 72
Changing Communication Configuration . . . . . . . . . . . . . . . . . . . 73
Connecting to the RS-232 Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Making a DF1 Point-to-Point Connection. . . . . . . . . . . . . . . . . . . 77
Using a Modem . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Connecting to a DF1 Half-Duplex Network . . . . . . . . . . . . . . . . . 80
Connecting to a DH-485 Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
DH-485 Configuration Parameters. . . . . . . . . . . . . . . . . . . . . . . . . 83
Recommended Tools. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
DH-485 Communication Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Connecting the Communication Cable to the DH-485 Connector .
86
Using the LCD
Table of Contents 5
Grounding and Terminating the DH-485 Network . . . . . . . . . . . 87
Connecting the AIC+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Cable Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Recommended User-Supplied Components . . . . . . . . . . . . . . . . . 93
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Install and Attach the AIC+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Powering the AIC+ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Connecting to DeviceNet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Cable Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Connecting to Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Ethernet Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Chapter 5
Operating Principles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Startup Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Main Menu and Default Screen . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Operating Buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Using Menus to Choose Values . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Selecting Between Menu Items . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Cursor Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Setting Values. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
I/O Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Viewing I/O Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Monitoring Bit File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Target Bit File Number (TBF) . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Monitoring a Bit File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Monitoring Integer File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Target Integer File Number (TIF) . . . . . . . . . . . . . . . . . . . . . . . . 117
Monitoring an Integer File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Using the Mode Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Controller Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Changing Mode Switch Position. . . . . . . . . . . . . . . . . . . . . . . . . . 125
Using a User Defined LCD Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
User Defined LCD Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 128
Configuring Advanced Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Changing Key In Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Key In Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 130
Changing Key In Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
Using Communications Toggle Functionality . . . . . . . . . . . . . . . . . . 133
Viewing Ethernet Port Configuration. . . . . . . . . . . . . . . . . . . . . . . . . 133
Using Trim Pots . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Trim Pot Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135
Changing Data Value of a Trim Pot . . . . . . . . . . . . . . . . . . . . . . . 135
Trim Pot Configuration in LCD Function File . . . . . . . . . . . . . . 137
Error Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Viewing System Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Publication 1763-UM001D-EN-P - March 2011
6 Table of Contents
Using Real-Time Clock and Memory Modules
Viewing Fault Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Chapter 6
Real-Time Clock Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Operation at Power-up and Entering a Run or
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Writing Data to the Real-Time Clock. . . . . . . . . . . . . . . . . . . . . . 142
RTC Battery Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Memory Module Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
User Program , User Data and Recipe Back-up. . . . . . . . . . . . . . 143
Program Compare . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
Data File Download Protection . . . . . . . . . . . . . . . . . . . . . . . . . . 144
Memory Module Write Protection . . . . . . . . . . . . . . . . . . . . . . . . 144
Removal/Insertion Under Power . . . . . . . . . . . . . . . . . . . . . . . . . 144
Memory Module Information File . . . . . . . . . . . . . . . . . . . . . . . . 144
Program /Data Download . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Program /Data Upload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
Online Editing
Specifications
Chapter 7
Overview of Online Editing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Online Editing Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Effects of Online Editing On Your System . . . . . . . . . . . . . . . . . . . . 149
System Impacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 149
Data Table File Size. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Online Edit Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Directions and Cautions for MicroLogix 1100 Online
Edit User. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Change the RSLinx "Configure CIP Option"
(OS Series A FRN 1,2, and 3 only) . . . . . . . . . . . . . . . . . . . . . . . . 150
A Download Before Starting Online Edit . . . . . . . . . . . . . . . . . . 151
Types of Online Editing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153
Edit Functions in Runtime Online Editing . . . . . . . . . . . . . . . . . 154
Edit Functions in Program Online Editing . . . . . . . . . . . . . . . . . 154
Appendix A
Expansion I/O Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Digital I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
Analog Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Replacement Parts
Publication 1763-UM001D-EN-P - March 2011
Appendix B
MicroLogix 1100 Replacement Kits . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Lithium Battery (1763-BA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Battery Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Troubleshooting Your System
Table of Contents 7
Transportation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Appendix C
Understanding the Controller Indicator Status. . . . . . . . . . . . . . . . . . 185
Controller Status LED Indicators. . . . . . . . . . . . . . . . . . . . . . . . . 185
Status Indicators on the LCD . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
I/O Status Indicators on the LCD . . . . . . . . . . . . . . . . . . . . . . . . 187
Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Error Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Controller Error Recovery Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Analog Expansion I/O Diagnostics and Troubleshooting . . . . . . . . 190
Module Operation and Channel Operation . . . . . . . . . . . . . . . . . 190
Power-up Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 190
Critical and Non-Critical Errors . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Module Error Definition Table. . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Calling Rockwell Automation for Assistance . . . . . . . . . . . . . . . . . . . 194
Using Control Flash to Upgrade Your Operating System
Connecting to Networks via RS-232/RS-485 Interface
Appendix D
Preparing for Upgrade . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Install ControlFlash Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Prepare the Controller for Updating. . . . . . . . . . . . . . . . . . . . . . . 196
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
Missing/Corrupt OS LED Pattern . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Appendix E
RS-232 Communication Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
RS-485 Communication Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
DF1 Full-Duplex Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
DF1 Half-Duplex Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
DF1 Half-Duplex Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Considerations When Communicating as a DF1 Slave
on a Multi-drop Link . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Using Modems with MicroLogix™ Programmable Controllers . 203
DH-485 Communication Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
DH-485 Configuration Parameters. . . . . . . . . . . . . . . . . . . . . . . . 205
Devices that use the DH-485 Network . . . . . . . . . . . . . . . . . . . . 206
Important DH-485 Network Planning Considerations . . . . . . . . 206
Example DH-485 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . 210
Modbus Communication Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
ASCII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Appendix F
Publication 1763-UM001D-EN-P - March 2011
8 Table of Contents
Connecting to Networks via Ethernet Interface
System Loading and Heat Dissipation
MicroLogix 1100 Controllers and Ethernet Communication . . . . . . 213
MicroLogix 1100 Performance Considerations . . . . . . . . . . . . . . . . . 214
MicroLogix 1100 and PC Connections to the
Ethernet Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Ethernet Network Topology. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Connecting an Ethernet switch on the Ethernet Network . . . . . 216
Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 217
Ethernet Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Duplicate IP address Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Configuring the Ethernet Channel on the MicroLogix 1100. . . . . . . 221
Configuration Using RSLogix 500 Programming Software . . . . . . . . 222
Configuration Via BOOTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Using the Rockwell BOOTP/DHCP Utility . . . . . . . . . . . . . . . . 224
Using a DHCP Server To Configure Your Processor . . . . . . . . . . . . 226
Using Subnet Masks and Gateways. . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Manually Configuring Channel 1 for Controllers on Subnets . . . 228
MicroLogix 1100 Embedded Web Server Capability . . . . . . . . . . . . . 229
Appendix G
System Loading Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
System Loading Example Calculations . . . . . . . . . . . . . . . . . . . . 232
System Loading Worksheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Current Loading. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Calculating Heat Dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Glossary
Index
Publication 1763-UM001D-EN-P - March 2011
Preface
Read this preface to familiarize yourself with the rest of the manual. It provides information concerning:
who should use this manual
the purpose of this manual
related documentation
conventions used in this manual
Rockwell Automation support

Who Should Use this Manual

Purpose of this Manual

Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use MicroLogix™™ 1100 controllers.
You should have a basic understanding of electrical circuitry and familiarity with relay logic. If you do not, obtain the proper training before using this product.
This manual is a reference guide for MicroLogix™ 1100 controllers and expansion I/O. It describes the procedures you use to install, wire, and troubleshoot your controller. This manual:
explains how to install and wire your controllers
gives you an overview of the MicroLogix™ 1100 controller system
Refer to publication 1763-RM001, MicroLogix 1100 Programmable Controllers Instruction Set Reference Manual for the MicroLogix 1100 instruction set and for application examples to show the instruction set in use. Refer to your RSLogix 500 programming software user documentation for more information on programming your MicroLogix™ 1100 controller.
9 Publication 1763-UM001D-EN-P - March 2011
10
Related Documentation
The following documents contain additional information concerning Rockwell Automation products. To obtain a copy, contact your local Rockwell Automation office or distributor.
Resource Description
MicroLogix 1100 Programmable Controllers Instruction Set Reference Manual, publication 1763-RM001
MicroLogix™ 1100 Programmable Controllers Installation Instructions, publication 1763-IN001
Advanced Interface Converter (AIC+) User Manual, publication 1761-UM004
DeviceNet Interface User Manual, publication 1761-UM005
DF1 Protocol and Command Set Reference Manual, publication 1770-6.5.16
Modbus Protocol Specifications Available from www.modbus.org
Allen-Bradley Programmable Controller Grounding and Wiring Guidelines, publication 1770-4.1
Application Considerations for Solid-State Controls, publication SGI-1.1
National Electrical Code - Published by the National Fire Protection Association of Boston, MA.
Allen-Bradley Publication Index SD499 A complete listing of current documentation, including ordering instructions.
Information on the MicroLogix 1100 Controllers instruction set.
Information on mounting and wiring the MicroLogix™ 1100 Controllers, including a mounting template for easy installation.
A description on how to install and connect an AIC+. This manual also contains information on network wiring.
Information on how to install, configure, and commission a DNI.
Information on DF1 open protocol.
Information about the Modbus protocol.
In-depth information on grounding and wiring Allen-Bradley programmable controllers.
A description of important differences between solid-state programmable controller products and hard-wired electromechanical devices.
An article on wire sizes and types for grounding electrical equipment.
Also indicates whether the documents are available on CD-ROM or in multi-languages.
Allen-Bradley Industrial Automation Glossary, publication AG-7.1

Common Techniques Used in this Manual

Publication 1763-UM001D-EN-P - March 2011
A glossary of industrial automation terms and abbreviations.
The following conventions are used throughout this manual:
Bulleted lists such as this one provide information, not procedural steps.
Numbered lists provide sequential steps or hierarchical information.
Italic type is used for emphasis.
Hardware Overview
12
11
1
2
3
5
6
7
8
9
10
4
ESC OK
Side View
Top View
Chapter
1

Hardware Features

The Bulletin 1763, MicroLogix 1100 programmable controller contains a power supply, input and output circuits, a processor, an isolated combination RS-232/485 communication port, and an Ethernet port. Each controller supports 18 I/O points (10 digital inputs, 2 analog inputs, and 6 discrete outputs).
The hardware features of the controller are shown below.
Hardware Features
Feature Description Feature Description
1 Output Terminal Block 7 LCD Keypad
2 Battery Connector 8 Status LED indicators 3 Bus Connector Interface to Expansion I/O 9
4 Battery 10 DIN Rail Latches 5 Input Terminal Block 11 RS-232/485 Communication Port
6 LCD 12 Ethernet Port
(1)
Shipped with controller.
(2)
Optional equipment.
(ESC, OK, Up, Down, Left, Right)
Memory Module Port Cover Memory Module
(Channel 0, isolated)
(Channel 1)
(2)
Publication 1763-UM001D-EN-P - March 2011
(1)
-or-
12 Hardware Overview
Controller Input Power and Embedded I/O
Catalog Number Description
Input Power Digital Inputs Analog Inputs Digital Outputs
1763-L16AWA 120/240V AC (10) 120V AC (2) voltage input
(6) relay
0...10V DC
1763-L16BWA 120/240V AC (6) 24V DC
(4) high-speed 24V DC
1763-L16BBB 24V DC (6) 24V DC
(4) high-speed 24V DC
1763-L16DWD 12...24V DC (6) 12...24V DC
(4) high-speed 12/24V
(1)
DC
(1)
The 4 high-speed inputs (inputs 0 through 3) can be used individually for pulse catch/latching inputs or combined as a high speed counter. Refer to Digital Input Specifications on page 157 and the MicroLogix 1100 Instruction Set Reference Manual, publication 1763-RM001, for more information.

Component Descriptions

MicroLogix 1100 Memory Module and Built-in Real-Time Clock
(2) voltage input
(1)
0...10V DC (2) voltage input
(1)
0...10V DC (2) voltage input
0...10V DC
All individually isolated (6) relay
All individually isolated (2) relay (isolated)
(2) 24V DC FET (2) high-speed 24V DC FET
(6) relay
All individually isolated
The controller has a built-in real-time clock to provide a reference for applications that need time-based control.
The controller is shipped with a memory module port cover in place. You can order a memory module, 1763-MM1, as an accessory. The memory module provides optional backup of your user program and data, and is a means to transport your programs between controllers.
Publication 1763-UM001D-EN-P - March 2011
The program and data in your MicroLogix 1100 is non-volatile and is stored when the power is lost to the controller. The memory module provides additional backup that can be stored separately. The memory module does not increase the available memory of the controller.
1763-MM1 Memory Module
TIP
1762 Expansion I/O 1762 Expansion I/O Connected to MicroLogix 1100 Controller
1762 Expansion I/O
Hardware Overview 13
1762 expansion I/O can be connected to the MicroLogix 1100 controller, as shown below.
A maximum of four I/O modules, in any combination, can be connected to a controller. See Appendix G to determine how much heat a certain combination generates.
1762 Expansion I/O
Publication 1763-UM001D-EN-P - March 2011
14 Hardware Overview
Expansion I/O
Catalog Number Description
Digital 1762-IA8 8-Point 120V AC Input Module 1762-IQ8 8-Point Sink/Source 24V DC Input Module 1762-IQ16 16-Point Sink/Source 24V DC Input Module 1762-IQ32T 32-Point Sink/Source 24V DC Input Module 1762-OA8 8-Point 120/240V AC Triac Output Module 1762-OB8 8-Point Sourcing 24V DC Output Module 1762-OB16 16-Point Sourcing 24V DC Output Module 1762-OB32T 32-Point Sourcing 24V DC Output Module 1762-OV32T 32-Point Sinking 24V DC Output Module 1762-OW8 8-Point AC/DC Relay Output Module 1762-OW16 16-Point AC/DC Relay Output Module 1762-OX6I 6-Point Isolated AC/DC Relay Output Module 1762-IQ8OW6 8-Point Sink/Source 24V DC Input and 6-Point AC/DC Relay
Output Module Analog 1762-IF4 4-Channel Voltage/Current Analog Input Module 1762-OF4 4-Channel Voltage/Current Analog Output Module 1762-IF2OF2 Combination 2-Channel Input 2-Channel Output
Voltage/Current Analog Module Temperature 1762-IR4 4-Channel RTD/Resistance Input Module 1762-IT4 4-Channel Thermocouple/mV Input Module

Communication Cables

Publication 1763-UM001D-EN-P - March 2011
Use only the following communication cables with the MicroLogix 1100 controllers. These cables are required for Class I Div. 2 applications.
1761-CBL-AM00 Series C or later
1761-CBL-AP00 Series C or later
1761-CBL-PM02 Series C or later
1761-CBL-HM02 Series C or later
2707-NC9 Series C or later
1763-NC01 Series A or later
Hardware Overview 15
ATTENTION
UNSUPPORTED CONNECTION
Do not connect a MicroLogix 1100 controller to another MicroLogix family controller such as MicroLogix 1000, MicroLogix 1200, MicroLogix 1500, or the network port of a 1747-DPS1 Port Splitter using a 1761- CBL-AM00 (8-pin mini-DIN to 8-pin mini-DIN) cable or equivalent.
This type of connection will cause damage to the RS-232/485 communication port (Channel 0) of the MicroLogix 1100 and/or the controller itself. The communication pins used for RS-485 communications on the MicroLogix 1100 are alternately used for 24V power on the other MicroLogix controllers and the network port of the 1747-DPS1 Port Splitter.
Publication 1763-UM001D-EN-P - March 2011
16 Hardware Overview

Programming

Communication Options

Programming the MicroLogix 1100 controller is done using RSLogix 500, Revision 7.0 or later. To use all of the latest features, RSLogix 500 programming software must be version 7.20.00 or later. Communication cables for programming are available separately from the controller and software.
The MicroLogix 1100 controllers provide two communications ports, an isolated combination RS-232/485 communication port (Channel 0) and an Ethernet port (Channel 1).
The isolated Channel 0 port on the MicroLogix 1100 can be connected to the following:
operator interfaces, personal computers, etc. using DF1 Full Duplex
point-to-point
a DH-485 network
a DF1 Radio Modem network
a DF1 half-duplex network as an RTU Master or RTU Slave
a Modbus network as an RTU Master or RTU Slave
an ASCII network
a DeviceNet network as a slave or peer using a DeviceNet Interface
(catalog number 1761-NET-DNI)
an Ethernet network using the Ethernet Interface module (catalog
number 1761-NET-ENI, or 1761-NET-ENIW)
(1)
When connecting to a DH-485 network, DF1 half-duplex network
or a Modbus network, the MicroLogix 1100 can be connected directly via Channel 0 (without an Advanced Interface Converter, catalog number 1761-NET-AIC). The Channel 0 combo port provides both RS-232 and RS-485 isolated connections. The appropriate electrical interface is selected through your choice of communication cable. The existing MicroLogix 1761 communication cables provide an interface to the RS-232 drivers. The 1763-NC01 cable provides an interface to the RS-485 drivers (for DH-485,
(1)
Modbus RTU Master, RTU slave networks, DF1 half-duplex Master
(1)
DF1 half-duplex Slave
).
and
The controller may also be connected to serial devices, such as bar code readers, weigh scales, serial printers, and other intelligent devices, using ASCII. See Default Communication Configuration on page 72 for the configuration settings for Channel 0. MicroLogix 1100 can be connected directly to RS-485
(1)
network via channel 0, using ASCII
(1)
OS Series B FRN4 or later.
.)
Publication 1763-UM001D-EN-P - March 2011
Hardware Overview 17
The MicroLogix 1100 supports Ethernet communication via the Ethernet communication Channel 1. You can connect your controller to a local area network that provides communication between various devices at 10 Mbps or 100 Mbps. This port supports CIP explicit messaging (message exchange) only. The controller cannot be used for CIP implicit messaging (real-time I/O messaging). The controller also includes an embedded web server which allows viewing of not only module information, TCP/IP configuration, and diagnostic information, but also includes the data table memory map and data table monitor screen using a standard web browser.
See Chapter 4 for more information on connecting to the available communication options.
Publication 1763-UM001D-EN-P - March 2011
18 Hardware Overview
Notes:
Publication 1763-UM001D-EN-P - March 2011
Chapter
Installing Your Controller
This chapter shows you how to install your controller. The only tools you require are a flat or Phillips head screwdriver and drill. Topics include:
agency certifications
compliance to European Union Directives
installation considerations
safety considerations
power considerations
preventing excessive heat
master control relay
installing a memory module
using the battery
controller mounting dimensions
controller and expansion I/O spacing
mounting the controller
mounting 1762 expansion I/O
connecting 1762 expansion I/O
2

Agency Certifications

Compliance to European Union Directives

19 Publication 1763-UM001D-EN-P - March 2011
UL Listed Industrial Control Equipment for use in Class I, Division 2,
Hazardous Locations, Groups A, B, C, D
C-UL Listed Industrial Control Equipment for use in Canada
CE marked for all applicable directives
C-Tick marked for all applicable acts
This product has the CE mark and is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
20 Installing Your Controller
EMC Directive
This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
EN 61000-6-4
EMC - Part 6-4: Generic Standards - Emission Standard for Industrial Environments
EN 61000-6-2
EMC - Part 6-2: Generic Standards - Immunity for Industrial Environments
This product is intended for use in an industrial environment.
Low Voltage Directive

Installation Considerations

This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 - Equipment Requirements and Tests.
For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications:
Industrial Automation Wiring and Grounding Guidelines for Noise Immunity,
publication 1770-4.1
Guidelines for Handling Lithium Batteries, publication AG-5.4
Automation Systems Catalog, publication B115
Most applications require installation in an industrial enclosure (Pollution
(1)
Degree 2 Category II
) to reduce the effects of electrical interference (Over Voltage
(2)
) and environmental exposure. Locate your controller as far as possible from power lines, load lines, and other sources of electrical noise such as hard-contact switches, relays, and AC motor drives. For more information on proper grounding guidelines, see the Industrial Automation Wiring and Grounding Guidelines publication 1770-4.1.
Publication 1763-UM001D-EN-P - March 2011
(1)
Pollution Degree 2 is an environment where normally only non-conductive pollution occurs except that occasionally temporary conductivity caused by condensation shall be expected.
(2)
Overvoltage Category II is the load level section of the electrical distribution system. At this level, transient voltages are controlled and do not exceed the impulse voltage capability of the products insulation.
Installing Your Controller 21
ATTENTION
ATTENTION
ATTENTION
WARNING
Electrostatic discharge can damage semiconductor devices inside the controller. Do not touch the connector pins or other sensitive areas.
Vertical mounting of the controller is not supported due to heat build-up considerations.
Be careful of metal chips when drilling mounting holes for your controller or other equipment within the enclosure or panel. Drilled fragments that fall into the controller or I/O modules could cause damage. Do not drill holes above a mounted controller if the protective debris shields are removed or the processor is installed.

Safety Considerations

Safety considerations are an important element of proper system installation. Actively thinking about the safety of yourself and others, as well as the condition of your equipment, is of primary importance. We recommend reviewing the following safety considerations.
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.
EXPLOSION HAZARD
Substitution of components may impair suitability for
Class I, Division 2.
Do not replace components or disconnect equipment
unless power has been switched off.
Do not connect or disconnect components unless
power has been switched off.
This product must be installed in an enclosure. All
cables connected to the product must remain in the enclosure or be protected by conduit or other means.
All wiring must comply with N.E.C. article 501-10(b).
Publication 1763-UM001D-EN-P - March 2011
22 Installing Your Controller
WARNING
WARNING
Use only the following communication cables in Class I, Division 2 hazardous locations.
Communication Cables for Class I, Division 2 Hazardous Locations
1761-CBL-AM00 Series C or later 1761-CBL-AP00 Series C or later 1761-CBL-PM02 Series C or later 1761-CBL-HM02 Series C or later 2707-NC9 Series C or later 1763-NC01 Series A or later
Disconnecting Main Power
Explosion Hazard
Do not replace components, connect equipment, or disconnect equipment unless power has been switched off.
The main power disconnect switch should be located where operators and maintenance personnel have quick and easy access to it. In addition to disconnecting electrical power, all other sources of power (pneumatic and hydraulic) should be de-energized before working on a machine or process controlled by a controller.
Safety Circuits
Explosion Hazard
Do not connect or disconnect connectors while circuit is live.
Circuits installed on the machine for safety reasons, like overtravel limit switches, stop push buttons, and interlocks, should always be hard-wired directly to the master control relay. These devices must be wired in series so that when any one device opens, the master control relay is de-energized, thereby removing power to the machine. Never alter these circuits to defeat their function. Serious injury or machine damage could result.
Publication 1763-UM001D-EN-P - March 2011
Installing Your Controller 23
Power Distribution
There are some points about power distribution that you should know:
The master control relay must be able to inhibit all machine motion by
removing power to the machine I/O devices when the relay is de-energized. It is recommended that the controller remain powered even when the master control relay is de-energized.
If you are using a DC power supply, interrupt the load side rather than
the AC line power. This avoids the additional delay of power supply turn-off. The DC power supply should be powered directly from the fused secondary of the transformer. Power to the DC input and output circuits should be connected through a set of master control relay contacts.
Periodic Tests of Master Control Relay Circuit
Any part can fail, including the switches in a master control relay circuit. The failure of one of these switches would most likely cause an open circuit, which would be a safe power-off failure. However, if one of these switches shorts out, it no longer provides any safety protection. These switches should be tested periodically to assure they will stop machine motion when needed.
Publication 1763-UM001D-EN-P - March 2011
24 Installing Your Controller

Power Considerations

The following explains power considerations for the micro controllers.
Isolation Transformers
You may want to use an isolation transformer in the AC line to the controller. This type of transformer provides isolation from your power distribution system to reduce the electrical noise that enters the controller and is often used as a step-down transformer to reduce line voltage. Any transformer used with the controller must have a sufficient power rating for its load. The power rating is expressed in volt-amperes (VA).
Power Supply Inrush
During power-up, the MicroLogix 1100 power supply allows a brief inrush current to charge internal capacitors. Many power lines and control transformers can supply inrush current for a brief time. If the power source cannot supply this inrush current, the source voltage may sag momentarily.
The only effect of limited inrush current and voltage sag on the MicroLogix 1100 is that the power supply capacitors charge more slowly. However, the effect of a voltage sag on other equipment should be considered. For example, a deep voltage sag may reset a computer connected to the same power source. The following considerations determine whether the power source must be required to supply high inrush current:
The power-up sequence of devices in a system.
The amount of the power source voltage sag if the inrush current
cannot be supplied.
The effect of voltage sag on other equipment in the system.
If the entire system is powered-up at the same time, a brief sag in the power source voltage typically will not affect any equipment.
Loss of Power Source
The power supply is designed to withstand brief power losses without affecting the operation of the system. The time the system is operational during power loss is called program scan hold-up time after loss of power. The duration of the power supply hold-up time depends on the type and state of the I/O, but is typically between 10 milliseconds and 3 seconds. When the duration of power loss reaches this limit, the power supply signals the processor that it can no longer provide adequate DC power to the system.
Publication 1763-UM001D-EN-P - March 2011
Installing Your Controller 25
TIP
This is referred to as a power supply shutdown. The processor then performs an orderly shutdown of the controller.
Input States on Power Down
The power supply hold-up time as described above is generally longer than the turn-on and turn-off times of the inputs. Because of this, the input state change from “On” to “Off ” that occurs when power is removed may be recorded by the processor before the power supply shuts down the system. Understanding this concept is important. The user program should be written to take this effect into account.
Other Types of Line Conditions
Occasionally the power source to the system can be temporarily interrupted. It is also possible that the voltage level may drop substantially below the normal line voltage range for a period of time. Both of these conditions are considered to be a loss of power for the system.

Preventing Excessive Heat

For most applications, normal convective cooling keeps the controller within the specified operating range. Ensure that the specified temperature range is maintained. Proper spacing of components within an enclosure is usually sufficient for heat dissipation.
In some applications, a substantial amount of heat is produced by other equipment inside or outside the enclosure. In this case, place blower fans inside the enclosure to assist in air circulation and to reduce “hot spots” near the controller.
Additional cooling provisions might be necessary when high ambient temperatures are encountered.
Do not bring in unfiltered outside air. Place the controller in an enclosure to protect it from a corrosive atmosphere. Harmful contaminants or dirt could cause improper operation or damage to components. In extreme cases, you may need to use air conditioning to protect against heat build-up within the enclosure.
Publication 1763-UM001D-EN-P - March 2011
26 Installing Your Controller
ATTENTION
TIP

Master Control Relay

A hard-wired master control relay (MCR) provides a reliable means for emergency machine shutdown. Since the master control relay allows the placement of several emergency-stop switches in different locations, its installation is important from a safety standpoint. Overtravel limit switches or mushroom-head push buttons are wired in series so that when any of them opens, the master control relay is de-energized. This removes power to input and output device circuits. Refer to the figures on pages 28 and 29.
Never alter these circuits to defeat their function since serious injury and/or machine damage could result.
If you are using an external DC power supply, interrupt the DC output side rather than the AC line side of the supply to avoid the additional delay of power supply turn-off.
The AC line of the DC output power supply should be fused.
Connect a set of master control relays in series with the DC power supplying the input and output circuits.
Place the main power disconnect switch where operators and maintenance personnel have quick and easy access to it. If you mount a disconnect switch inside the controller enclosure, place the switch operating handle on the outside of the enclosure, so that you can disconnect power without opening the enclosure.
Whenever any of the emergency-stop switches are opened, power to input and output devices should be removed.
When you use the master control relay to remove power from the external I/O circuits, power continues to be provided to the controller’s power supply so that diagnostic indicators on the processor can still be observed.
The master control relay is not a substitute for a disconnect to the controller. It is intended for any situation where the operator must quickly de-energize I/O devices only. When inspecting or installing terminal connections, replacing output fuses, or working on equipment within the enclosure, use the disconnect to shut off power to the rest of the system.
Publication 1763-UM001D-EN-P - March 2011
Installing Your Controller 27
TIP
TIP
Do not control the master control relay with the controller. Provide the operator with the safety of a direct connection between an emergency-stop switch and the master control relay.
Using Emergency-Stop Switches
When using emergency-stop switches, adhere to the following points:
Do not program emergency-stop switches in the controller program.
Any emergency-stop switch should turn off all machine power by turning off the master control relay.
Observe all applicable local codes concerning the placement and
labeling of emergency-stop switches.
Install emergency-stop switches and the master control relay in your
system. Make certain that relay contacts have a sufficient rating for your application. Emergency-stop switches must be easy to reach.
In the following illustration, input and output circuits are shown with
MCR protection. However, in most applications, only output circuits require MCR protection.
The following illustrations show the Master Control Relay wired in a grounded system.
In most applications input circuits do not require MCR protection; however, if you need to remove power from all field devices, you must include MCR contacts in series with input power wiring.
Publication 1763-UM001D-EN-P - March 2011
28 Installing Your Controller
Disconnect
Isolation Transformer
Emergency-Stop Push Button
Fuse
MCR
230V AC I/O
Circuits
Operation of either of these contacts will remove power from the external I/O circuits, stopping machine motion.
Fuse
Overtravel Limit Switch
MCR
MCR
MCR
Stop
Start
Line Terminals: Connect to terminals of Power Supply (1763-L16AWA, 1763-L16BWA).
115V AC or 230V AC I/O Circuits
L1
L2
230V AC
Master Control Relay (MCR) Cat. No. 700-PK400A1
Suppressor Cat. No. 700-N24
MCR
Suppr.
24V DC I/O Circuits
(Lo)
(Hi)
DC Power Supply. Use IEC 950/EN 60950
X1
X2
115V AC or 230V AC
Line Terminals: Connect to 24V DC terminals of Power Supply (1763-L16BBB).
_
+
Schematic (Using IEC Symbols)
Publication 1763-UM001D-EN-P - March 2011
Schematic (Using ANSI/CSA Symbols)
Emergency-Stop Push Button
230V AC
Operation of either of these contacts will remove power from the external I/O circuits, stopping machine motion.
Fuse
MCR
Fuse
MCR
MCR
MCR
Stop
Start
Line Terminals: Connect to terminals of Power Supply (1763-L16AWA, 1763-L16BWA).
Line Terminals: Connect to 24V DC terminals of Power Supply (1763-L16BBB).
230V AC Output Circuits
Disconnect
Isolation Transformer
115V AC or 230V AC I/O Circuits
L1
L2
Master Control Relay (MCR) Cat. No. 700-PK400A1
Suppressor Cat. No. 700-N24
(Lo)
(Hi)
DC Power Supply. Use NEC Class 2 for UL Listing
.
X1
X2
115V AC or 230V AC
_
+
MCR
24 V DC I/O Circuits
Suppr.
Overtravel Limit Switch
Installing Your Controller 29
Publication 1763-UM001D-EN-P - March 2011
30 Installing Your Controller
MODULE
MEMORY
MODULE
MEMORY
MODULE
MEMORY

Installing a Memory Module

1. Remove the memory module port cover.
2. Align the connector on the memory module with the connector pins on
the controller.
3. Firmly seat the memory module into the controller.
Publication 1763-UM001D-EN-P - March 2011
Installing Your Controller 31
IMPORTANT
IMPORTANT

Using the Battery

The MicroLogix 1100 controller is equipped with a replaceable battery. The Battery Low indicator on the LCD display of the controller shows the status of the replaceable battery. When the battery is low, the indicator is set (displayed as a solid rectangle). This means that either the battery wire connector is disconnected, or the battery may fail within 2 weeks if it is connected. When the battery level is acceptable, the indicator is clear (displayed as an empty rectangle).
The MicroLogix 1100 controller ships with the battery wire connector connected.
Ensure that the battery wire connector is inserted into the connector port if your application needs battery power. For example, when using a real-time clock (RTC), or to store the program in the controller's memory for an extended period of time while the power is removed.
See Lithium Battery (1763-BA) in the appendix B, for more information on installation, handling, usage, storage, and disposal of the battery.
SeeRTC Battery Operation on page 142, for more information on the use of the battery in relation with RTC.
When the controller’s Battery Low indicator is set (displayed as a solid rectangle) with the battery wire connector connected, we recommend strongly to install a new battery immediately.
Publication 1763-UM001D-EN-P - March 2011
32 Installing Your Controller
ESC OK
Wire Guide
Battery Connector Wires
Replaceable Battery
Replaceable Battery Pocket
Battery Wire Connector
Battery Connector
Connecting the Battery Wire Connector
Follow the procedure below to connect the battery wire connector to the battery connector.
1. Insert the replaceable battery wire connector into the battery connector.
2. Secure the battery connector wires along the wire guide as shown below.
Publication 1763-UM001D-EN-P - March 2011
Controller Mounting
C
B
A
1763-L16AWA, 1763-L16BWA, 1763-L16BBB
MicroLogix
1100
1762 I/O
1762 I/O
1762 I/O
Side Side
To p
Bottom
Dimensions
Installing Your Controller 33

Controller and Expansion I/O Spacing

Controller Dimensions
Dimension 1763-L16AWA 1763-L16BWA 1763-L16BBB 1763-L16DWD
A 90 mm (3.5 in.) B 110 mm (4.33 in.) C 87 mm (3.43 in.)
The controller mounts horizontally, with the expansion I/O extending to the right of the controller. Allow 50 mm (2 in.) of space on all sides of the controller system for adequate ventilation. Maintain spacing from enclosure walls, wireways, adjacent equipment, etc., as shown below.
Publication 1763-UM001D-EN-P - March 2011
34 Installing Your Controller
ATTENTION
ATTENTION
TIP
debris shield

Mounting the Controller

MicroLogix™ 1100 controllers are suitable for use in an industrial environment when installed in accordance with these instructions. Specifically, this equipment is intended for use in clean, dry environments (Pollution
degree 2 60664-1).
(1)
) and to circuits not exceeding Over Voltage Category II
(3)
(2)
(IEC
Do not remove the protective debris shield until after the controller and all other equipment in the panel near the controller are mounted and wiring is complete. Once wiring is complete, remove protective debris shield. Failure to remove shield before operating can cause overheating.
Electrostatic discharge can damage semiconductor devices inside the controller. Do not touch the connector pins or other sensitive areas.
For environments with greater vibration and shock concerns, use the panel mounting method described on page 36, rather than DIN rail mounting.
(1)
Pollution Degree 2 is an environment where, normally, only non-conductive pollution occurs except that occasionally a temporary conductivity caused by condensation shall be expected.
(2)
Over Voltage Category II is the load level section of the electrical distribution system. At this level transient voltages are controlled and do not exceed the impulse voltage capability of the product’s insulation.
(3)
Pollution Degree 2 and Over Voltage Category II are International Electrotechnical Commission (IEC) designations.
Publication 1763-UM001D-EN-P - March 2011
Installing Your Controller 35
27.5 mm (1.08 in.)
27.5 mm (1.08 in.)
90 mm (3.5 in.)
DIN Rail Mounting
The maximum extension of the latch is 14 mm (0.55 in.) in the open position. A flat-blade screwdriver is required for removal of the controller. The controller can be mounted to EN50022-35x7.5 or EN50022-35x15 DIN rails. DIN rail mounting dimensions are shown below.
Follow this procedure to install your controller on the DIN rail.
1. Mount your DIN rail. (Make sure that the placement of the controller on the DIN rail meets the recommended spacing requirements, see Controller and Expansion I/O Spacing on page 33. Refer to the mounting template inside the back cover of this document.)
2. Close the DIN latch, if it is open.
3. Hook the top slot over the DIN rail.
4. While pressing the controller down against the top of the rail, snap the
bottom of the controller into position.
5. Leave the protective debris shield attached until you are finished wiring the controller and any other devices.
To remove your controller from the DIN rail:
1. Place a flat-blade screwdriver in the DIN rail latch at the bottom of the controller.
2. Holding the controller, pry downward on the latch until the latch locks in the open position.
3. Repeat steps 1 and 2 for the second DIN rail latch.
4. Unhook the top of the DIN rail slot from the rail.
Publication 1763-UM001D-EN-P - March 2011
36 Installing Your Controller
ESC OK
open
closed
Mounting Template (Remove before installing controller)
Debris Shield
Panel Mounting
Mount to panel using #8 or M4 screws. To install your controller using mounting screws:
1. Remove the mounting template from inside the back cover of the
MicroLogix 1100 Programmable Controllers Installation Instructions, publication 1763-IN001.
2. Secure the template to the mounting surface. (Make sure your controller is spaced properly. See Controller and Expansion I/O Spacing on page
33.)
3. Drill holes through the template.
4. Remove the mounting template.
5. Mount the controller.
6. Leave the protective debris shield in place until you are finished wiring
the controller and any other devices.
Publication 1763-UM001D-EN-P - March 2011
1762 Expansion I/O
A
B
C
ATTENTION
Dimensions
Installing Your Controller 37
Dimension Expansion I/O Module
A 90 mm (3.5 in.) B 40 mm (1.57 in.) C 87 mm (3.43 in.)

Mounting 1762 Expansion I/O

DIN Rail Mounting
The module can be mounted using the following DIN rails:
35 x 7.5 mm (EN 50 022 - 35 x 7.5), or
35 x 15 mm (EN 50 022 - 35 x 15).
Before mounting the module on a DIN rail, close the DIN rail latch. Press the DIN rail mounting area of the module against the DIN rail. The latch momentarily opens and locks into place.
During panel or DIN rail mounting of all devices, be sure that all debris (metal chips, wire stands, etc.) is kept from falling into the module. Debris that falls into the module could cause damage when the module is under power.
Publication 1763-UM001D-EN-P - March 2011
38 Installing Your Controller
TIP
TIP
End Anchor
End Anchor
90 (3.54)
100 (3.94)
40.4 (1.59)
A
40.4 (1.59)
14.5 (0.57)
MicroLogix
1100
1762 I/O
1762 I/O
1762 I/O
For more than 2 modules: (number of modules - 1) x 40 mm (1.59 in.)
NOTE: All dimensions are in mm (inches). Hole spacing tolerance: ±0.4 mm (0.016 in.).
A = 95 mm (3.740 in.)
1763-L16AWA, 1763-L16BWA, 1763-L16BBB
Use DIN rail end anchors (Allen-Bradley part number 1492-EA35 or 1492-EAH35) for vibration or shock environments. The following illustration shows the location of the end anchors.
1762 expansion I/O must be mounted horizontally as illustrated.
Panel Mounting
Use the dimensional template shown below to mount the module. The preferred mounting method is to use two M4 or #8 panhead screws per module. Mounting screws are required on every module.
For environments with greater vibration and shock concerns, use the panel mounting method described below, instead of DIN rail mounting.
Publication 1763-UM001D-EN-P - March 2011
Installing Your Controller 39
TIP
TIP
ATTENTION
WARNING

Connecting Expansion I/O

The expansion I/O module is attached to the controller or another I/O module by means of a flat ribbon cable after mounting, as shown below.
Use the pull loop on the connector to disconnect modules. Do not pull on the ribbon cable.
Up to four expansion I/O modules can be connected to a controller.
Remove power before removing or inserting an I/O module. When you remove or insert a module with power applied, an electrical arc may occur. An electrical arc can cause personal injury or property damage by:
sending an erroneous signal to your system’s field
devices, causing the controller to fault
causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its mating connector. Worn contacts may create electrical resistance, reducing product reliability.
EXPLOSION HAZARD
In Class I, Division 2 applications, the bus connector must be fully seated and the bus connector cover must be snapped in place.
In Class I, Division 2 applications, all modules must be mounted in direct contact with each other as shown on page 39. If DIN rail mounting is used, an end stop must be installed ahead of the controller and after the last 1762 I/O module.
Publication 1763-UM001D-EN-P - March 2011
40 Installing Your Controller
Notes:
Publication 1763-UM001D-EN-P - March 2011
Chapter
ATTENTION
ATTENTION
3
Wiring Your Controller
This chapter describes how to wire your controller and expansion I/O. Topics include:
wire requirements
using surge suppressors
grounding the controller
wiring diagrams
sinking and sourcing wiring diagrams
controller I/O wiring
wiring your analog channels
expansion I/O wiring

Wiring Requirements

Wiring Recommendation
Before you install and wire any device, disconnect power to the controller system.
Calculate the maximum possible current in each power and common wire. Observe all electrical codes dictating the maximum current allowable for each wire size. Current above the maximum ratings may cause wiring to overheat, which can cause damage.
United States Only: If the controller is installed within a potentially hazardous environment, all wiring must comply with the requirements stated in the National Electrical Code 501-10 (b).
Allow for at least 50 mm. (2 in.) between I/O wiring ducts or terminal
strips and the controller.
Route incoming power to the controller by a path separate from the
device wiring. Where paths must cross, their intersection should be perpendicular.
41 Publication 1763-UM001D-EN-P - March 2011
42 Wiring Your Controller
TIP
Do not run signal or communications wiring and power wiring in the same conduit. Wires with different signal characteristics should be routed by separate paths.
Separate wiring by signal type. Bundle wiring with similar electrical
characteristics together.
Separate input wiring from output wiring.
Label wiring to all devices in the system. Use tape, shrink-tubing, or
other dependable means for labeling purposes. In addition to labeling, use colored insulation to identify wiring based on signal characteristics. For example, you may use blue for DC wiring and red for AC wiring.
Wire Requirements
Wire Type Wire Size (2 wire maximum per terminal screw)
1 wire per terminal 2 wire per terminal
Solid Cu-90°C (194°F) #12 to #20 AWG #16 to #20 AWG Stranded Cu-90°C (194°F) #14 to #20 AWG #18 to #20 AWG Wiring torque = 0.56 Nm (5.0 in-lb) rated
Wiring the Terminal Block
The MicroLogix 1100 controllers have screw-cage clamps on the input and output terminal blocks. With screw-cage clamp terminal blocks, there is no need to attach additional hardware such as a spade lug to the wire, or use a finger-safe cover.
To wire the terminal block:
1. Strip the end of the wire.
The recommended length for the stripped end of the wire is 11.0 mm (0.440 in.).
2. Insert it into an open clamp.
3. Using a small, flat-blade screwdriver, tighten the terminal screw. To
ensure that the wire conductor is secured inside the clamp, tighten it to the rated torque, 0.56 Nm (5.0 in-lb).
The diameter of the terminal screw head is 5.5 mm (0.220 in.).
Publication 1763-UM001D-EN-P - March 2011
Wiring Your Controller 43
Screw-cage clamp terminal block
+DC or L1
Suppression Device
DC COM or L2
AC or DC Outputs
Load
VAC/DC
Out 0 Out 1
Out 2 Out 3 Out 4 Out 5
Out 6 Out 7
COM

Using Surge Suppressors

Because of the potentially high current surges that occur when switching inductive load devices, such as motor starters and solenoids, the use of some type of surge suppression to protect and extend the operating life of the controllers output contacts is required. Switching inductive loads without surge suppression can significantly reduce the life expectancy of relay contacts. By adding a suppression device directly across the coil of an inductive device, you prolong the life of the output or relay contacts. You also reduce the effects of voltage transients and electrical noise from radiating into adjacent systems.
The following diagram shows an output with a suppression device. We recommend that you locate the suppression device as close as possible to the load device.
If the outputs are DC, we recommend that you use an 1N4004 diode for surge suppression, as shown below. For inductive DC load devices, a diode is suitable. A 1N4004 diode is acceptable for most applications. A surge
Publication 1763-UM001D-EN-P - March 2011
44 Wiring Your Controller
+24V DC
IN4004 Diode
Relay or Solid State DC Outputs
24V DC common
VAC/DC Out 0
Out 1 Out 2 Out 3 Out 4 Out 5
Out 6 Out 7 COM
(A surge suppressor can also be used.)
Surge Suppression for Inductive AC Load Devices
Output Device Output DeviceOutput Device
Varistor
RC Network
Surge Suppressor
suppressor can also be used. See for recommended suppressors. As shown below, these surge suppression circuits connect directly across the load device.
Suitable surge suppression methods for inductive AC load devices include a varistor, an RC network, or an Allen-Bradley surge suppressor, all shown below. These components must be appropriately rated to suppress the switching transient characteristic of the particular inductive device. See the table on 45 for recommended suppressors.
Publication 1763-UM001D-EN-P - March 2011
Wiring Your Controller 45
Recommended Surge Suppressors
Use the Allen-Bradley surge suppressors shown in the following table for use with relays, contactors, and starters.
Recommended Surge Suppressors
Device Coil Voltage Suppressor Catalog
Number
Bulletin 509 Motor Starter Bulletin 509 Motor Starter
Bulletin 100 Contactor Bulletin 100 Contactor
Bulletin 709 Motor Starter 120V AC
120V AC 240V AC
120V AC 240V AC
599-K04 599-KA04
199-FSMA1 199-FSMA2
1401-N10 Bulletin 700 Type R, RM Relays AC coil None Required Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay Bulletin 700 Type R Relay
Bulletin 700 Type RM Relay Bulletin 700 Type N, P, or PK Relay 150V max, AC or DC
Miscellaneous electromagnetic
12V DC 12V DC
24V DC 24V DC
48V DC 48V DC
115-125V DC 115-125V DC
230-250V DC 230-250V DC
150V max, AC or DC
199-FSMA9
199-FSMA9
199-FSMA9
199-FSMA10
199-FSMA11
700-N24
700-N24 devices limited to 35 sealed VA
(1)
Varistor – Not recommended for use on relay outputs.
(2)
RC Type – Do not use with Triac outputs.
(1)
(1)
(2) (2)
(2)
(2)
(2)
Publication 1763-UM001D-EN-P - March 2011
46 Wiring Your Controller
ATTENTION
TIP
ATTENTION
ESC OK
Grounding stamping

Grounding the Controller

All devices connected to the RS-232/485 communication port must be referenced to controller ground, or be floating (not referenced to a potential other than ground). Failure to follow this procedure may result in property damage or personal injury.
For 1763-L16BWA controllers, the COM of the sensor supply is also connected to
chassis ground internally. The 24V DC sensor power source should not be used to power output circuits. It should only be used to power input devices.
For 1763-L16BBB and 1763-L16DWD controllers, the VDC NEUT or common terminal
of the power supply is also connected to chassis ground internally.
In solid-state control systems, grounding and wire routing helps limit the effects of noise due to electromagnetic interference (EMI). Run the ground connection from the ground screw of the controller to the ground bus prior to connecting any devices. Use AWG #14 wire. For AC-powered controllers, this connection must be made for safety purposes.
This product is intended to be mounted to a well grounded mounting surface such as a metal panel. Refer to the Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1, for additional information. Additional grounding connections from the mounting tab or DIN rail, if used, are not required unless the mounting surface cannot be grounded.
Use all four mounting positions for panel mounting installation.
Remove the protective debris strip before applying power to the controller. Failure to remove the strip may cause the controller to overheat.
Publication 1763-UM001D-EN-P - March 2011
Wiring Your Controller 47
TIP
AC
COM
NOT
USED
VAC O/0 VDC
VAC O/1 VDC
VAC O/2 VDC
VAC O/3 VDC
VAC O/4 VDC
VAC O/5 VDC
NOT
USED
NOT
USED
L1 L2/N 100-240 VAC
NOT
USED
I/1I/0 I/2 I/3
AC
COM
I/4 I/5
IA
COM
IV1(+) IV2(+)I/6 I/7 I/8 I/9
Input Terminal Block
Output Terminal Block
Group 1 Group 2
G
r
oup
0
G
r
oup
1
G
r
o
up
2
G
r
oup
3
G
r
ou
p
4
G
r
oup
5
Group 0

Wiring Diagrams

The following illustrations show the wiring diagrams for the MicroLogix 1100 controllers. Controllers with DC inputs can be wired as either sinking or sourcing inputs. (Sinking and sourcing does not apply to AC inputs.) Refer to Sinking and Sourcing Wiring Diagrams on page 3-50.
The controller terminal block layouts are shown below. The shading on the labels indicates how the terminals are grouped. A detail of the groupings is shown in the table following the terminal block layouts.
This symbol denotes a protective earth ground terminal which provides a low impedance path between electrical circuits and earth for safety purposes and provides noise immunity improvement. This connection must be made for safety purposes on AC-powered controllers.
This symbol denotes a functional earth ground terminal which provides a low impedance path between electrical circuits and earth for non-safety purposes, such as noise immunity improvement.
Terminal Block Layouts
1763-L16AWA
Publication 1763-UM001D-EN-P - March 2011
48 Wiring Your Controller
DC
COM-
VAC O/0 VDC
VAC O/1 VDC
VAC O/2 VDC
VAC O/3 VDC
VAC O/4 VDC
VAC O/5 VDC
NOT
USED
NOT
USED
L1 L2/N 100-240 VAC
DC OUT
+ 24V
I/1I/0 I/2 I/3
DC
COM
I/4 I/5
IA
COM
IV1(+) IV2(+)I/6 I/7 I/8 I/9
Input Terminal Block
Output Terminal Block
Group 1 Group 2
G
r
oup
0
G
r
oup
1
G
r
oup
2
G
r
oup
3
G
r
oup
4
G
r
ou
p
5
Group 0
ATTENTION
DC
COM
NOT
USED
VAC O/0 VDC
VAC O/1 VDC
NOT
USED
NOT
USED
DC O/2 O/3
24V+
DC
24V-
O/4 O/5NOT
USED
NOT
USED
+ 24V -
DC IN
NOT
USED
I/1I/0 I/2 I/3
DC
COM
I/4 I/5
IA
COM
IV1(+) IV2(+)I/6 I/7 I/8 I/9
Input Terminal Block
Output Terminal Block
Group 1 Group 2
G
r
o
up
0
G
r
o
up
1
G
r
o
up
2
Group 0
Input Terminal Block
Output Terminal Block
Group 1 Group 2
G
r
ou
p
0
G
r
ou
p
1
G
r
ou
p
2
G
r
ou
p
3
G
r
ou
p
4
G
r
ou
p
5
Group 0
DC
COM
NOT
USED
+ 12/24V -
DC IN
NOT
USED
I/1I/0 I/2 I/3
DC
COM
I/4 I/5
IA
COM
IV1(+) IV2(+)I/6 I/7 I/8 I/9
VAC O/0 VDC
VAC O/1 VDC
VAC O/2 VDC
VAC O/3
VDC
VAC O/4 VDC
VAC O/5 VDC
NOT
USED
NOT
USED
1763-L16BWA
The 24V DC sensor supply of the 1763-L16BWA should not be used to power output circuits. It should only be used to power input devices (e.g. sensors, switches). See Master Control Relay on page 2-26 for information on MCR wiring in output circuits.
1763-L16BBB
Publication 1763-UM001D-EN-P - March 2011
1763-L16DWD
Terminal Groupings
Input Terminal Grouping
Controller Inputs
Input Group Common Terminal Input Terminal
Group 0 AC COM 0 I/0 through I/3
1763-L16AWA
1763-L16BWA
1763-L16BBB
1763-L16DWD
Output Terminal Grouping
Controller Outputs
1763-L16AWA 1763-L16BWA 1763-L16DWD
1763-L16BBB
Group 1 AC COM 1 I/4 through I/9 Group 2 IA COM IV1(+) and IV2(+) Group 0 DC COM 0 I/0 through I/3 Group 1 DC COM 1 I/4 through I/9 Group 2 IA COM IV1(+) and IV2(+) Group 0 DC COM 0 I/0 through I/3 Group 1 DC COM 1 I/4 through I/9 Group 2 IA COM IV1(+) and IV2(+)
Output Group
Group 0 VAC/VDC O/0 Isolated Relay output Group 1 VAC/VDC O/1 Isolated Relay output Group 2 VAC/VDC O/2 Isolated Relay output Group 3 VAC/VDC O/3 Isolated Relay output Group 4 VAC/VDC O/4 Isolated Relay output Group 5 VAC/VDC O/5 Isolated Relay output Group 0 VAC/VDC O/0 Isolated Relay output Group 1 VAC/VDC O/1 Isolated Relay output Group 2 DC +24V,
Voltage Terminal
DC -24V
Output Terminal
O/2 through O/5
Wiring Your Controller 49
Description
FET output
Publication 1763-UM001D-EN-P - March 2011
50 Wiring Your Controller
ATTENTION
TIP
L1a
L2a
L1b
L2b
L1c
L2c
AC
COM
NOT
USED
NOT
USED
I/1I/0 I/2 I/3
AC
COM
I/4 I/5
IA
COM
IV1(+) IV2(+)I/6 I/7 I/8 I/9

Sinking and Sourcing Wiring Diagrams

Any of the MicroLogix 1100 DC embedded input groups can be configured as sinking or sourcing depending on how the DC COM is wired on the group. Refer to pages 51 through 51 for sinking and sourcing wiring diagrams.
Type Definition
Sinking Input The input energizes when high-level voltage is applied to the input
terminal (active high). Connect the power supply VDC (-) to the input group’s COM terminal.
Sourcing Input The input energizes when low-level voltage is applied to the input
terminal (active low). Connect the power supply VDC (+) to the input group’s COM terminal.
The 24V DC sensor power source must not be used to power output circuits. It should only be used to power input devices (e.g. sensors, switches). See Master Control Relay on page 2-26 for information on MCR wiring in output circuits.
1763-L16AWA, 1763-L16BWA, 1763-L16BBB and 1763-L16DWD Wiring Diagrams
In the following diagrams, lower case alphabetic subscripts are appended to common-terminal connections to indicate that different power sources may be used for different isolated groups, if desired.
1763-L16AWA Input Wiring Diagram
(1) “NOT USED” terminals are not intended for use as connection points.
(1)
Publication 1763-UM001D-EN-P - March 2011
1763-L16BWA Sinking Input Wiring Diagram
+DCa
-DCa+DC -DC
+DCb
-DCb
L1c
L2c
DC
COM-
DC OUT
+ 24V
I/1I/0 I/2 I/3
DC
COM
I/4 I/5
IA
COM
IV1(+) IV2(+)I/6 I/7 I/8 I/9
24V DC Sensor Power
-DCa
+DCa+DC -DC
-DCb
+DCb
L1c
L2c
DC
COM-
DC OUT
+ 24V
I/1I/0 I/2 I/3
DC
COM
I/4 I/5
IA
COM
IV1(+) IV2(+)I/6 I/7 I/8 I/9
24V DC Sensor Power
+DCa
-DCa
+DCb
-DCb
L1c
L2c
DC
COM
NOT
USED
NOT
USED
I/1I/0 I/2 I/3
DC
COM
I/4 I/5
IA
COM
IV1(+) IV2(+)I/6 I/7 I/8 I/9
-DCa
+DCa
-DCb
+DCb
L1c
L2c
DC
COM
NOT
USED
NOT
USED
I/1I/0 I/2 I/3
DC
COM
I/4 I/5
IA
COM
IV1(+) IV2(+)I/6 I/7 I/8 I/9
1763-L16BWA Sourcing Input Wiring Diagram
Wiring Your Controller 51
1763-L16BBB and 1763-L16DWD Sinking Input Wiring Diagram
1763-L16BBB and 1763-L16DWD Sourcing Input Wiring Diagram
Publication 1763-UM001D-EN-P - March 2011
52 Wiring Your Controller
L2
L1
+DCa
CR
L2b
-DCa
L1a L1b
L2a
VAC O/0 VDC
VAC O/1 VDC
VAC O/2 VDC
VAC O/3 VDC
VAC O/4
VDC
VAC O/5
VDC
NOT
USED
NOT
USED
L1 L2/N
100-240 VAC
CR
L2d
L1c L1d
L2c
L1e
L2e
-DC
+DC
+DCa +DCc
-DCa
+DCb
-DCb
CR
CR
-DCc
VAC O/0 VDC
VAC O/1 VDC
NOT
USED
NOT
USED
DC O/2 O/3
24V+
DC
24V-
O/4 O/5NOT
USED
NOT
USED
+ 24V -
DC IN
CR
+DCa
CR
L2b
-DCa
L1a L1b
L2a
VAC O/0 VDC
VAC O/1 VDC
VAC O/2 VDC
VAC O/3 VDC
VAC O/4 VDC
VAC O/5
VDC
NOT
USED
NOT
USED
CR
L2d
L1c L1d
L2c
L1e
L2e
-DC
+DC
+-
DC IN
-DC
+DC
+-
12/24V
1763-L16AWA and 1763-L16BWA Output Wiring Diagram
1763-L16BBB Output Wiring Diagram
1763-L16DWD Output Wiring Diagram
Publication 1763-UM001D-EN-P - March 2011
Wiring Your Controller 53
IA
COM
IV1(+) IV2(+)
Sensor 2 (V) Voltage
Sensor 1 (V) Voltage

Controller I/O Wiring

Wiring Your Analog Channels

Minimizing Electrical Noise
Because of the variety of applications and environments where controllers are installed and operating, it is impossible to ensure that all environmental noise will be removed by input filters. To help reduce the effects of environmental noise, install the MicroLogix 1100 system in a properly rated (for example, NEMA) enclosure. Make sure that the MicroLogix 1100 system is properly grounded.
A system may malfunction due to a change in the operating environment after a period of time. We recommend periodically checking system operation, particularly when new machinery or other noise sources are installed near the MicroLogix 1100 system.
Analog input circuits can monitor voltage signals and convert them to serial digital data.
Analog Channel Wiring Guidelines
Consider the following when wiring your analog channels:
The analog common (COM) is connected to earth ground inside the
module. These terminals are not electrically isolated from the system. They are connected to chassis ground.
Analog channels are not isolated from each other.
Use Belden™ 8761, or equivalent, shielded wire.
Under normal conditions, the drain wire (shield) should be connected to
the metal mounting panel (earth ground). Keep the shield connection to earth ground as short as possible.
To ensure optimum accuracy for voltage type inputs, limit overall cable
impedance by keeping all analog cables as short as possible. Locate the I/O system as close to your voltage type sensors or actuators as possible.
Publication 1763-UM001D-EN-P - March 2011
54 Wiring Your Controller
IV1(+) or IV2(+) IA COM
IV1(+) or IV2(+) IA COM
+-
+-+
-
IV1(+) or IV2(+) IA COM
+
-
+
-
GND
+
-
Transmitter
Transmitter
Transmitter
Supply Signal
Supply
Signal
Controller
Controller
Controller
Power Supply
3-Wire Transmitter
4-Wire Transmitter
2-Wire Transmitter
Power Supply
Power Supply
The controller does not provide loop power for analog inputs. Use a
power supply that matches the transmitter specifications as shown below.
Minimizing Electrical Noise on Analog Channels
Inputs on analog channels employ digital high-frequency filters that significantly reduce the effects of electrical noise on input signals. However, because of the variety of applications and environments where analog controllers are installed and operated, it is impossible to ensure that all environmental noise will be removed by the input filters.
Several specific steps can be taken to help reduce the effects of environmental noise on analog signals:
install the MicroLogix 1100 system in a properly rated (i.e., NEMA)
enclosure. Make sure that the MicroLogix 1100 system is properly grounded.
use Belden cable #8761 for wiring the analog channels, making sure that
the drain wire and foil shield are properly earth grounded.
route the Belden cable separately from any AC wiring. Additional noise
immunity can be obtained by routing the cables in grounded conduit.
Publication 1763-UM001D-EN-P - March 2011
Wiring Your Controller 55
IMPORTANT
Foil shield
Black wire
Drain wire
Clear wire
Insulation
44531
Grounding Your Analog Cable
Use shielded communication cable (Belden #8761). The Belden cable has two signal wires (black and clear), one drain wire, and a foil shield. The drain wire and foil shield must be grounded at one end of the cable.
Do not ground the drain wire and foil shield at both ends of the cable
Publication 1763-UM001D-EN-P - March 2011
56 Wiring Your Controller
IN 7
IN 5
IN 3
IN 1
AC
COM
IN 6
IN 4
IN 2
IN 0
L1
L2
100/120V ac
AC
COM
Common connected internally.
IN 7
IN 5
IN 3
IN 1
DC
COM
IN 6
IN 4
IN 2
IN 0
24V dc
DC
COM
Common connected internally.
-DC (sinking) +DC (sourcing)
+DC (sinking)
-DC (sourcing)

Expansion I/O Wiring

Digital Wiring Diagrams
The following illustrations show the digital expansion I/O wiring diagrams.
1762-IA8 Wiring Diagram
Publication 1763-UM001D-EN-P - March 2011
1762-IQ8 Wiring Diagram
1762-IQ16 Wiring Diagram
IN 7
IN 5
IN 3
IN 1
IN 6
IN 4
IN 2
IN 0
24V dc
IN 15
IN 13
IN 11
IN 9
DC
COM 0
IN 14
IN 12
IN 10
IN 8
24V dc
DC
COM 1
+DC (Sinking)
-DC (Sourcing)
-DC (Sinking) +DC (Sourcing)
+DC (Sinking)
-DC (Sourcing)
-DC (Sinking) +DC (Sourcing)
Wiring Your Controller 57
Publication 1763-UM001D-EN-P - March 2011
58 Wiring Your Controller
44920
OUT 5
VAC
1
OUT 2
OUT 0
OUT 7
OUT 4
OUT 3
OUT 1
VAC
0
OUT 6
CR
CR
CR
CR
CR
CR
L2
L1
L2
L1
1762-IQ32T Wiring Diagram
1762-OA8 Wiring Diagram
Publication 1763-UM001D-EN-P - March 2011
1762-OB8 Wiring Diagram
+DC
24V dc (source)
-DC
OUT 6
OUT 4
OUT 2
OUT 0
OUT 7
OUT 5
OUT 3
OUT 1
+VDC
CR
CR
CR
CR
CR
CR
DC COM
OUT 6
OUT 2
OUT 0
OUT 10
OUT 5
OUT 7
OUT 9
OUT 11
OUT 13
OUT 15
OUT 14
OUT 3
OUT 1
VDC+
OUT 8
OUT 12
CR
CR
CR
CR
CR
CR
CR
CR
CR
CR
OUT 4
DC COM
24V dc (source)
+DC
-DC
1762-OB16 Wiring Diagram
Wiring Your Controller 59
Publication 1763-UM001D-EN-P - March 2011
60 Wiring Your Controller
44925
44915
1762-OB32T Wiring Diagram
1762-OV32T Wiring Diagram
Publication 1763-UM001D-EN-P - March 2011
1762-OW8 Wiring Diagram
OUT 5
VAC-VDC2
OUT 2
OUT 0
OUT 7
OUT 4
OUT3
OUT 1
VAC-VDC 1
OUT 6
CR
CR
CR
CR
CR
CR
L1 VAC1 +
L2 DC1 COM
L1 VAC2 +
L2 DC2 COM
OUT 2
OUT 0
OUT 3
OUT 1
VAC-VDC
0
CR
CR
CR
OUT 6
OUT 4
OUT 7
OUT 5
CR
CR
CR
OUT 10
OUT 8
OUT 11
OUT 9
VAC-VDC
1
CR
CR
CR
OUT 14
OUT 12
OUT 15
OUT 13
CR
CR
CR
L1
L2
+DC
-DC
1762-OW16 Wiring Diagram
Wiring Your Controller 61
Publication 1763-UM001D-EN-P - March 2011
62 Wiring Your Controller
L1-0
L1-1
L1-2
L1-3
L1-4
L1-5
OUT0 N.C.
OUT0 N.O.
OUT1 N.C.
OUT1 N.O.
OUT2 N.C.
OUT2 N.O.
OUT3 N.O.
OUT3 N.C.
OUT4 N.C.
OUT4 N.O.
OUT5 N.C.
OUT5 N.O.
CR
CR
CR
CR
CR
CR
L1 OR +DC
L1 OR +DC
L1 OR +DC
L1 OR +DC
L1 OR +DC
L1 OR +DC
L2 OR -DC
L2 OR -DC
L2 OR -DC
L2 OR -DC
L2 OR -DC
L2 OR -DC
1762-OX6I Wiring Diagram
Publication 1763-UM001D-EN-P - March 2011
1762-IQ8OW6 Wiring Diagram
IN 6
IN 4
IN 3
IN 1
IN 5
IN 2
IN 0
OUT 4
OUT 2
OUT 0
VAC VDC
VAC VDC
DC
COM 1
OUT 3
OUT 1
IN 7
L1 or +DC
L1 or +DC
-DC (Sinking) +DC (Sourcing)
Connected Internally
+DC (Sinking)
-DC (Sourcing)
L2 or -DC
OUT 5
+DC (Sinking)
-DC (Sourcing)
-DC (Sinking) +DC (Sourcing)
DC
COM 0
CR
CR
CR
CR
Wiring Your Controller 63
Analog Wiring
Consider the following when wiring your analog modules:
The analog common (COM) is not connected to earth ground inside the
module. All terminals are electrically isolated from the system.
Channels are not isolated from each other.
Use Belden 8761, or equivalent, shielded wire.
Under normal conditions, the drain wire (shield) should be connected to
the metal mounting panel (earth ground). Keep the shield connection to earth ground as short as possible.
To ensure optimum accuracy for voltage type inputs, limit overall cable
impedance by keeping all analog cables as short as possible. Locate the I/O system as close to your voltage type sensors or actuators as possible.
The module does not provide loop power for analog inputs. Use a
power supply that matches the input transmitter specifications.
Publication 1763-UM001D-EN-P - March 2011
64 Wiring Your Controller
ATTENTION
1
ON
2
Ch0 Ch1
Current (ON) Default
Voltage (OFF)
Switch Location
1762-IF2OF2 Input Type Selection
Select the input type, current or voltage, using the switches located on the module’s circuit board and the input type/range selection bits in the Configuration Data File. Refer to MicroLogix 1100 Programmable Controllers Instruction Set Reference Manual, publication 1763-RM001. You can access the switches through the ventilation slots on the top of the module. Switch 1 controls channel 0; switch 2 controls channel 1. The factory default setting for both switch 1 and switch 2 is Current. Switch positions are shown below.
1762-IF2OF2 Output Type Selection
The output type selection, current or voltage, is made by wiring to the appropriate terminals, Iout or Vout, and by the type/range selection bits in the Configuration Data File. Refer to MicroLogix 1100 Programmable Controllers Instruction Set Reference Manual, publication 1763-RM001.
Analog outputs may fluctuate for less than a second when power is applied or removed. This characteristic is common to most analog outputs. While the majority of loads will not recognize this short signal, it is recommended that preventive measures be taken to ensure that connected equipment is not affected.
Publication 1763-UM001D-EN-P - March 2011
Wiring Your Controller 65
V Out 1
V Out 0
IN 1 (+)
IN 0 (+)
I Out 1
I Out 0
IN 1 (-)
IN 0 (-)
COM
COM
Common connected internally.
IN 0 (+) IN 0 (-)
V out 0
V out 1
I out 0 I out 1
COM
IN 1 (-)
IN 1 (+)
COM
Analog Sensor
Load
1762-IF2OF2 Wiring
The following illustration shows the 1762-IF2OF2 analog expansion I/O terminal block.
1762-IF2OF2 Terminal Block Layout
Differential Sensor Transmitter Types
Publication 1763-UM001D-EN-P - March 2011
66 Wiring Your Controller
+
+
-
-
+-+
-
IN + IN ­COM
+
-
IN + IN ­COM
+
-
IN + IN ­COM
Power Supply
(1)
Tra ns mi tt er
Tra ns mi tt er
Tra ns mi tt er
Supply
Supply
Signal
Signal
Module
Module
Module
2-Wire Transmitter
3-Wire Transmitter
4-Wire Transmitter
Power Supply
(1)
Power Supply
(1)
(1) All power supplies rated N.E.C. Class 2.
1
Ch0 Ch1 Ch2 Ch3
ON
2 1ON2
Current (ON Default)
Voltage (OFF)
Switch Location
Single-ended Sensor/Transmitter Types
Publication 1763-UM001D-EN-P - March 2011
1762-IF4 Input Type Selection
Select the input type, current or voltage, using the switches located on the module’s circuit board and the input type/range selection bits in the Configuration Data File. Refer to MicroLogix 1100 Programmable Controllers Instruction Set Reference Manual, publication 1763-RM001. You can access the switches through the ventilation slots on the top of the module.
1762-IF4 Terminal Block Layout
TIP
IN 1 (+)
IN 0 (+)
IN 1 (-)
IN 0 (-)
IN 3 (+)
IN 2 (+)
IN 3 (-)
IN 2 (-)
COM
COM
Commons internally connected.
IN 0 (+) IN 0 (-)
IN 3 (+)
IN 3 (-)
IN 2 (+) IN 2 (-)
COM
IN 1 (-)
IN 1 (+)
COM
Analog Sensor
Differential Sensor Transmitter Types
Wiring Your Controller 67
Grounding the cable shield at the module end only usually provides sufficient noise immunity. However, for best cable shield performance, earth ground the shield at both ends, using a 0.01µF capacitor at one end to block AC power ground currents, if necessary.
Publication 1763-UM001D-EN-P - March 2011
68 Wiring Your Controller
+
+
-
-
+-+
-
IN + IN ­COM
+
-
IN + IN ­COM
+
-
IN + IN ­COM
Power Supply
(1)
Power Supply
(1)
Power Supply
(1)
Transmitter
Transmitter
Transmitter
Module
Module
Module
Supply Signal
Supply
Signal
2-Wire Transmitter
3-Wire Transmitter
4-Wire Transmitter
(1) All power supplies rated N.E.C. Class 2.
V out 3
V out 2
V out 1
V out 0
I out 3
I out 2
I out 1
I out 0
COM
COM
Commons connected internally
Sensor/Transmitter Types
Publication 1763-UM001D-EN-P - March 2011
1762-OF4 Output Type Selection
The output type selection, current or voltage, is made by wiring to the appropriate terminals, Iout or Vout, and by the type/range selection bits in the Configuration Data File.
1762-OF4 Terminal Block Layout
1762-OF4 Wiring
I out 0 I out 1
V out 2
V out 3
V out 0 V out 1
COM
I out 3
I out 2
COM
Current Load
Voltage Load
Wiring Your Controller 69
Publication 1763-UM001D-EN-P - March 2011
70 Wiring Your Controller
Notes:
Publication 1763-UM001D-EN-P - March 2011
Chapter
4
Communication Connections
This chapter describes how to communicate with your control system. The method you use and cabling required to connect your controller depends on what type of system you are employing. This chapter also describes how the controller establishes communication with the appropriate network. Topics include:
supported communication protocols
default communication configurations
using communications toggle functionality
connecting to RS-232 port
connecting to DH-485 network
connecting to AIC+
connecting to DeviceNet
connecting to Ethernet

Supported Communication Protocols

The MicroLogix 1100 controllers provide two communication channels, an isolated RS-232/485 communication port (Channel 0) and an Ethernet port (Channel 1).
MicroLogix 1100 controllers support the following communication protocols from the primary RS-232/485 communication channel, Channel 0:
DH-485
DF1 Full-Duplex
DF1 Half-Duplex Master and Slave
DF1 Radio Modem
Modbus Master and Slave
ASCII
The Ethernet communication channel, Channel 1, allows your controller to be connected to a local area network for various devices providing 10 Mbps/100 Mbps transfer rate. MicroLogix 1100 controllers support CIP explicit messaging (message exchange). MicroLogix 1100 controllers do not support Ethernet I/O master capability through CIP implicit messaging (real-time I/O messaging).
71 Publication 1763-UM001D-EN-P - March 2011
72 Communication Connections
TIP
For more information on MicroLogix 1100 communications, refer to the MicroLogix 1100 Programmable Controllers Instruction Set Reference Manual, publication 1763-RM001.

Default Communication Configuration

The MicroLogix 1100 communication Channel 0 has the following default communication configuration.
For Channel 0, the default configuration is present when:
The controller is powered-up for the first time.
The communications toggle functionality
specifies default communications (specified using the LCD Display. The DCOMM indicator on the LCD Display is on, i.e., lit in solid rectangle).
An OS upgrade is completed.
See Chapter 5 for more information about using the LCD Display.
See Appendix E for more information about communicating.
DF1 Full-Duplex Default Configuration Parameters
Parameter Default
Baud Rate 19.2 KBps Parity none Source ID (Node Address) 1 Control Line no handshaking Error Detection CRC Embedded Responses auto detect Duplicate Packet (Message) Detect enabled ACK Timeout 50 counts NAK retries 3 retries ENQ retries 3 retries Stop Bits 1 Data Bits 8

Using the Communications Toggle Functionality

Publication 1763-UM001D-EN-P - March 2011
The Communications Toggle Functionality can be operated using the LCD display on the controller, as shown below.
Use the Communications Toggle Functionality to change from the user-defined communication configuration to the default communications mode and back on Channel 0. The Default Communications (DCOMM)
Communication Connections 73
TIP
COM
M
0
COM
M
1
DCOMM
BAT. LO
U-MSG
indicator on the LCD display operates to show when the controller is in the default communications mode (settings shown on 72).
The Communication Toggle Functionality only affects the communication configuration of Channel 0.
Changing Communication Configuration
Follow the procedure below to change from the user-defined communication configuration to the default communications mode and back. In this example, we will start from the Main Menu screen of the LCD display, as shown below. If necessary, press ESC repeatedly until you return to the Main Menu screen.
1. On the Main Menu screen, select Advance Set by using the Up and Down keys on the LCD keypad, as shown below. If the menu items shown in the figure below are not displayed on the Main Menu screen, you need to scroll down the screen by pressing the Down key.
Publication 1763-UM001D-EN-P - March 2011
74 Communication Connections
CO
MM0
COMM
1
DCOMMBA
T
.
L
O
U-MSG
2. Then, press the OK key on the LCD keypad. The Advanced Settings
Menu screen is displayed, as shown below.
3. Select DCOMM Cfg using the Up and Down keys, as shown below, and
then press the OK key.
4. The DCOMM Configuration screen is displayed, as shown below. The
current status, Disable in this example, is selected by default.
The DCOMM status indicator, which is the third of the five indicators at the top left of the LED display, is displayed in empty rectangle. It means that the communication configuration is set to a user-defined communication mode at present.
Publication 1763-UM001D-EN-P - March 2011
Communication Connections 75
COMM0
COMM
1
DCOMMBA
T
.
L
O
U-
M
SG
If the communication configuration is set to the default communication mode, the DCOMM Configuration screen is displayed as shown below. The DCOMM status indicator is displayed in solid rectangle.
5. Use the up arrow to change the indicator position so that it is pointing to Enable.Press the OK key to change to the default communication mode. The DCOMM Mode Change Notification screen is displayed, as shown below. It indicates that the communication configuration is changed to the default communication mode. The DCOMM status indicator is displayed in solid rectangle.
If you change to the user-defined configuration from the default configuration mode by selecting Disable and pressing the OK key, the DCOMM Mode Change Notification will be displayed as shown below.
Publication 1763-UM001D-EN-P - March 2011
76 Communication Connections
ATTENTION
6. Press the ESC key to return to the Advanced Settings Menu screen, as shown in step 3.

Connecting to the RS-232 Port

There are two ways to connect the MicroLogix™ 1100 programmable controller to your personal computer using the DF1 protocol: using a point-to-point connection, or using a modem. Descriptions of these methods follow.
All devices connected to the RS-232/485 communication port must be referenced to controller ground, or be floating (not referenced to a potential other than ground). Failure to follow this procedure may result in property damage or personal injury.
For 1763-L16BWA controllers, the COM of the
sensor supply is also connected to chassis ground internally. The 24V DC sensor power source should not be used to power output circuits. It should only be used to power input devices.
For 1763-L16BBB and 1763-L16DWD controllers,
the VDC NEUT or common terminal of the power supply is also connected to chassis ground internally.
Available Communication Cables
Communication Cables Length
1761-CBL-AM00 Series C or later cables are required for Class I Div 2 applications. 45 cm (17.7 in.) 1761-CBL-AP00 Series C or later cables are required for Class I Div 2 applications. 45 cm (17.7 in.) 1761-CBL-PM02 Series C or later cables are required for Class I Div 2 applications. 2 m (6.5 ft) 1761-CBL-HM02 Series C or later cables are required for Class I Div 2 applications. 2 m (6.5 ft) 2707-NC9 Series C or later cables are required for Class I Div 2 applications. 15 m (49.2 ft) 1763-NC01 Series A or later 30 cm (11.8 in.)
Publication 1763-UM001D-EN-P - March 2011
Communication Connections 77
ATTENTION
MicroLogix 1100 Channel 0
Personal Computer
1761-CBL-AP00 or 1761-CBL-PM02
1)
UNSUPPORTED CONNECTION
Do not connect a MicroLogix 1100 controller to another MicroLogix family controller such as MicroLogix 1000, MicroLogix 1200, MicroLogix 1500, or to the 1747-DPS1 Network port using a 1761-CBL-AM00 (8-pin mini-DIN to 8-pin mini-DIN) cable or equivalent.
This type of connection will cause damage to the RS-232/485 communication port (Channel 0) of the MicroLogix 1100 and/or the controller itself. Communication pins used for RS-485 communications are alternately used for 24V power on the other MicroLogix controllers and the 1747-DPS1network port .
Making a DF1 Point-to-Point Connection
You can connect the MicroLogix™ 1100 programmable controller to your personal computer using a serial cable (1761-CBL-PM02) from your personal computer’s serial port to the controller’s Channel 0. The recommended protocol for this configuration is DF1 Full-Duplex.
You can connect a MicroLogix 1100 controller to your personal computer directly without using an external optical isolator, such as Advanced Interface Converter (AIC+), catalog number 1761-NET-AIC, as shown in the illustration below, because Channel 0 is isolated within the controller.
(1) Series C or later cables are required for Class I Div 2 applications.
Publication 1763-UM001D-EN-P - March 2011
78 Communication Connections
IMPORTANT
Modem Cable
(straight-through)
Personal Computer
Modem
Modem
MicroLogix 1100 Channel 0
Protocol Options
DF1 Full-Duplex protocol (to 1 controller)
DF1 Half-Duplex protocol (to multiple controllers)
Modbus RTU Slave protocol
1761-CBL-AP00 or 1761-CBL-PM02
(1)
(straight-through)
Using a Modem
You can use modems to connect a personal computer to one MicroLogix™ 1100 controller (using DF1 Full-Duplex protocol), to multiple controllers (using DF1 Half-Duplex protocol), or Modbus RTU Slave protocol via Channel 0, as shown in the following illustration. (See Appendix E for information on types of modems you can use with the micro controllers.)
Do not attempt to use DH-485 protocol through modems under any circumstance. The communication timing using DH-485 protocol is not supported by modem communications.
Publication 1763-UM001D-EN-P - March 2011
(1) Series C or later cables are required for Class I Div 2 applications.
You can connect a MicroLogix 1100 controller to your modem directly without using an external optical isolator, such as AIC+, catalog number 1761-NET-AIC, as shown in the illustration below, because Channel 0 is isolated within the controller.
Communication Connections 79
ATTENTION
DTE Device (MicroLogix 1100 Channel 0)
DCE Device (Modem, PanelView,
etc.) 8-Pin 25-Pin 9-Pin 7 TXD TXD 2 3 4 RXD RXD 3 2 2GND GND7 5 1B(+) DCD8 1 8A(-) DTR204 5N.C. DSR6 6 6 CTS CTS 5 8 3 RTS RTS 4 7
MicroLogix 1100 Channel 0 to Modem Cable Pinout
When connecting MicroLogix 1100 Channel 0 to a modem using an RS-232 cable, the maximum that the cable length may be extended is 15.24 m (50 ft).
Do not connect pin 1,8, and 5. This connection will cause damage to the RS-232/485 communication port (channel 0) of the MicroLogix 1100 and/or the controller itself.
Publication 1763-UM001D-EN-P - March 2011
80 Communication Connections
Connecting to a DF1 Half-Duplex Network
When a communication port is configured for DF1 Half-Duplex Slave, available parameters include the following:
DF1 Half-Duplex Configuration Parameters
Parameter Options
Baud Rate 300, 600, 1200, 2400, 4800, 9600, 19.2 KBps, 38.4 KBps Parity none, even Node Address 0...254 decimal Control Line no handshaking, half duplex modem (RTS/CTS handshaking, no handshaking (485 network) Error Detection CRC, BCC EOT Suppression enabled, disabled
When EOT Suppression is enabled, the slave does not respond when polled if no message is queued. This saves modem transmission power and time when there is no message to transmit.
Duplicate Packet (Message) Detect
Poll Timeout (x20 ms) 0...65,535 (can be set in 20 ms increments)
RTS Off Delay (x20 ms) 0...65,535 (can be set in 20 ms increments)
RTS Send Delay (x20 ms) 0...65,535 (can be set in 20 ms increments)
enabled, disabled Detects and eliminates duplicate responses to a message. Duplicate packets may be sent under noisy communication conditions if the sender’s Message Retries are not set to 0.
Poll Timeout only applies when a slave device initiates a MSG instruction. It is the amount of time that the slave device waits for a poll from the master device. If the slave device does not receive a poll within the Poll Timeout, a MSG instruction error is generated, and the ladder program needs to requeue the MSG instruction. If you are using a MSG instruction, it is recommended that a Poll Timeout value of zero not be used. Poll Timeout is disabled when set to zero.
Specifies the delay time between when the last serial character is sent to the modem and when RTS is deactivated. Gives the modem extra time to transmit the last character of a packet.
Specifies the time delay between setting RTS until checking for the CTS response. For use with modems that are not ready to respond with CTS immediately upon receipt of RTS.
Message Retries 0...255
Specifies the number of times a slave device attempts to resend a message packet when it does not receive an ACK from the master device. For use in noisy environments where message packets may become corrupted in transmission.
Pre Transmit Delay (x1 ms)
Publication 1763-UM001D-EN-P - March 2011
0...65,535 (can be set in 1 ms increments)
When the Control Line is set to no handshaking, this is the delay time before transmission.
When the Control Line is set to DF1 Half-Duplex Modem, this is the minimum time delay between
Required for 1761-NET-AIC physical Half-Duplex networks. The 1761-NET-AIC needs delay time to change from transmit to receive mode.
receiving the last character of a packet and the RTS assertion.
Communication Connections 81
(1)
(1)
(2)
(2)
(3)
(3)
SLC 5/03 processor
MicroLogix 1100
MicroLogix 1100
MicroLogix 1100
CH0
CH0
CH0
CH0
1761-CBL-AP00 or 1761-CBL-PM02
(4)
1761-CBL-AM00 or 1761-CBL-HM02
(4)
DF1 Master
DF1 Slave
DF1 Slave
straight 9-25 pin cable
straight 9-25 pin cable
radio modem or lease line
radio modem or lease line
AIC+
RS-485 DF1 Half-Duplex
RS-485 DF1 Half-Duplex
DF1 Slave
1763-NC01 (daisy chain) to AIC+
(4)
AIC+
24V DC power (User Supplied)
1763-NC01 (daisy chain) to AIC+
(4)
DF1 Half-Duplex Master-Slave Network
Use the following diagram for DF1 Half-Duplex Master-Slave protocol without hardware handshaking.
(1) DB-9 RS-232 port (2) mini-DIN 8 RS-232 port (3) RS-485 port (4) Series C or later cables are required for Class I Div 2 applications.
Publication 1763-UM001D-EN-P - March 2011
82 Communication Connections
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
TX
DC SOURCE CABLE
EXTERNAL
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
TX
DC SOURCE CABLE
EXTERNAL
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
TX
DC SOURCE CABLE
EXTERNAL
Rockwell Software RSLinx 2.0 (or higher), SLC 5/03, SLC 5/04,
SLC 5/05, PLC-5, or MicroLogix 1000, 1200, and 1500 processors configured for DF1Half-Duplex Master. Rockwell Software RSLinx
2.5 required for MicroLogix 1100.
DF1 Half-Duplex Protocol
MicroLogix 1500 with 1764-LSP or 1764-LRP Processor (Slave)
SLC 5/03 (Slave)MicroLogix
1000 (Slave)
MicroLogix 1500 with 1764-LRP Processor (Slave)
MicroLogix 1100 (Slave)
Modem
MicroLogix 1200 (Slave)
DF1 Half-Duplex Network (Using PC and Modems)
Publication 1763-UM001D-EN-P - March 2011
Communication Connections 83
TIP

Connecting to a DH-485 Network

The network diagrams on the next pages provide examples of how to connect MicroLogix 1100 controllers to the DH-485 network.
You can connect a MicroLogix 1100 controller to your DH-485 network directly without using an external optical isolator, such as Advanced Interface Converter (AIC+), catalog number 1761-NET-AIC, as shown in the illustrations below, because Channel 0 is isolated within the controller.
Use a 1763-NC01 Series A or later (8-pin mini-DIN to 6-pin DH-485 connector) cable or equivalent to connect a MicroLogix 1100 controller to a DH-485 network.
A
TERMBCOM
SHLD
CHS GND
We recommend that you use a 1747-UIC USB interface to connect your PC to a DH-485 network. For more information on the 1747-UIC, see the Universal Serial Bus to DH-485 Interface Converter Installation Instructions, publication 1747-IN063.
DH-485 Configuration Parameters
When MicroLogix communications are configured for DH-485, the following parameters can be changed:
DF1 Full-Duplex Configuration Parameters
Parameter Options
Baud Rate 9600, 19.2 KBps Node Address 1...31 decimal Token Hold Factor 1...4
See Software Considerations on page 208 for tips on setting the parameters listed above.
Publication 1763-UM001D-EN-P - March 2011
84 Communication Connections
A-B
PanelView
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
TX
DC SOURCE
CABLE
EXTERNAL
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
TX
DC SOURCE
CABLE
EXTERNAL
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
TX
DC SOURCE
CABLE
EXTERNAL
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
TX
DC SOURCE
CABLE
EXTERNAL
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
TX
DC SOURCE
CABLE
EXTERNAL
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
TX
DC SOURCE
CABLE
EXTERNAL
ESC OK
(2)
AIC+
(1)
(3)
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
TX
DC SOURCE CABLE
EXTERNAL
ESC OK
AIC+
AIC+
AIC+
AIC+
DH-485 Network
SLC 5/04
PanelView 550
MicroLogix 1500
MicroLogix 1000
MicroLogix 1200
Personal Computer
AIC+
AIC+
MicroLogix 1100
DH-485 Network
1763-NC01
(4)
Belden, shielded, twisted-pair cable
Belden, shielded, twisted-pair cable
1761-CBL-AP00 or 1761-CBL-PM02
1747-CP3 or 1761-CBL-AC00
port 1 or port 2
to PC
24V DC (user supplied)
(1) DB-9 RS-232 port (2) mini-DIN 8 RS-232 port (3) RS-485 port (4) Series A or later cables are required.
DH-485 Network with a MicroLogix 1100 Controller
Publication 1763-UM001D-EN-P - March 2011
Typical 3-Node Network (Channel 0 Connection)
TERM
A
B
COM
SHLD
CHS GND
TX
TX PWR
TX
DC SOURCE
CABLE
EXTERNAL
A-B
PanelView
PanelView 550
MicroLogix 1100
1761-CBL-AM00 or 1761-CBL-HM02
1747-CP3 or 1761-CBL-AC00
RJ45 port
1761-CBL-AS09 or 1761-CBL-AS03
CH0
Communication Connections 85
Recommended Tools
To connect a DH-485 network to additional devices, you need tools to strip the shielded cable and to attach the cable to the AIC+ Advanced Interface Converter. We recommend the following equipment (or equivalent):
Working with Cable for DH-485 Network
Description Part Number Manufacturer
Shielded Twisted Pair Cable #3106A or #9842 Belden Stripping Tool Not Applicable Not Applicable 1/8” Slotted Screwdriver Not Applicable Not Applicable
DH-485 Communication Cable
The suggested DH-485 communication cable is either Belden #3106A or #9842. The cable is jacketed and shielded with one or two twisted-wire pairs and a drain wire.
One pair provides a balanced signal line and one additional wire is used for a common reference line between all nodes on the network. The shield reduces the effect of electrostatic noise from the industrial environment on network communication.
The communication cable consists of a number of cable segments daisy-chained together. The total length of the cable segments cannot exceed 1219 m (4000 ft). However, two segments can be used to extend the DH-485
Publication 1763-UM001D-EN-P - March 2011
86 Communication Connections
TIP
Belden #3106A or #9842
Belden #3106A or #9842
Belden #3106A or #9842
Connector
Connector
Connector
Incorrect
Orange with White Stripes
White with Orange Stripes
Shrink Tubing Recommended
Blue (#3106A) or Blue with White Stripes (#9842)
Drain Wire
6 Termination
5 A
4 B
3 Common 2 Shield
1 Chassis Ground
network to 2438 m (8000 ft). For additional information on connections using the AIC+, refer to the Advanced Interface Converter (AIC+) User Manual, publication 1761-6.4.
When cutting cable segments, make them long enough to route them from one AIC+ to the next, with sufficient slack to prevent strain on the connector. Allow enough extra cable to prevent chafing and kinking in the cable.
Use these instructions for wiring the Belden #3106A or #9842 cable. (See
Cable Selection Guide on page 90 if you are using standard Allen-Bradley
cables.)
Connecting the Communication Cable to the DH-485 Connector
A daisy-chained network is recommended. Do not make the incorrect connection shown below:
Publication 1763-UM001D-EN-P - March 2011
Single Cable Connection
When connecting a single cable to the DH-485 connector, use the following diagram.
Communication Connections 87
to Next Device
to Previous Device
Multiple Cable Connection
When connecting multiple cables to the DH-485 connector, use the following diagram.
Connections using Belden #3106A Cable
For this Wire/Pair Connect this Wire To this Terminal
Shield/Drain Non-jacketed Terminal 2 - Shield Blue Blue Terminal 3 - (Common) White/Orange White with Orange Stripe Terminal 4 - (Data B)
Orange with White Stripe Terminal 5 - (Data A)
Connections using Belden #9842 Cable
For this Wire/Pair Connect this Wire To this Terminal
Shield/Drain Non-jacketed Terminal 2 - Shield Blue/White White with Blue Stripe
Blue with White Stripe Terminal 3 - (Common)
White/Orange White with Orange Stripe Terminal 4 - (Data B)
Orange with White Stripe Terminal 5 - (Data A)
(1)
To prevent confusion when installing the communication cable, cut back the white with blue stripe wire immediately after the insulation jacket is removed. This wire is not used by DH-485.
Cut back - no connection
(1)
Grounding and Terminating the DH-485 Network
Only one connector at the end of the link must have Terminals 1 and 2 jumpered together. This provides an earth ground connection for the shield of the communication cable.
Both ends of the network must have Terminals 5 and 6 jumpered together, as shown below. This connects the termination impedance (of 120 ohm) that is built into each AIC+ or the 1763-NC01 cable as required by the DH-485 specification.
Publication 1763-UM001D-EN-P - March 2011
88 Communication Connections
Jumper
Jumper
Belden #3106A or #9842 Cable 1219 m (4000ft) Maximum
Jumper
DTE Device (MicroLogix 1100 Channel 0)
DCE Device (DH-485 connector)
8-Pin 6-pin 7 TXD 6 Termination 4RXD 5A 2GND 4B 1 B(+) 3 Common 8 A(-) 2 Shield 5 N.C. 1 ChassisGround 6CTS 3RTS
End-of-Line Termination
MicroLogix 1100 Channel 0 to DH-485 Communication Cable Pinout
When connecting MicroLogix 1100 Channel 0 to DH-485 communication cable pinout using an RS-232 cable, the maximum that the cable length may be extended is 15.24 m (50 ft). Refer to the following typical pinout:
Publication 1763-UM001D-EN-P - March 2011
Communication Connections 89
AIC+ Advanced Interface Converter (1761-NET-AIC)
3
2
4
5
1

Connecting the AIC+

You can connect a MicroLogix 1100 controller to a DH-485 network via Channel 0 directly without using an optical isolator, such as AIC+, catalog number 1761-NET-AIC, because Channel 0 is isolated. However, you need to use an AIC+ to connect your PC or other MicroLogix Family products, such as MicroLogix 1200, to a DH-485 network.
The following figure shows the external wiring connections and specifications of the AIC+.
Item Description
1 Port 1 - DB-9 RS-232, DTE 2 Port 2 - mini-DIN 8 RS-232 DTE 3 Port 3 - RS-485 Phoenix plug 4 DC Power Source selector switch
(cable = port 2 power source, external = external power source connected to item 5)
5 Terminals for external 24V DC power supply and chassis ground
For additional information on connecting the AIC+, refer to the Advanced Interface Converter (AIC+) User Manual, publication 1761-UM00.
Publication 1763-UM001D-EN-P - March 2011
90 Communication Connections
1761-CBL-PM02
(2)
1761-CBL-AP00
(2)
1761-CBL-HM02
(2)
1761-CBL-AM00
(2)
Cable Selection Guide
Cable Length Connections from to AIC+ External
Power Supply Required
1761-CBL-AP00 1761-CBL-PM02
(2)
(2)
45 cm (17.7 in.)
2 m (6.5 ft)
SLC 5/03 or SLC 5/04 processors, ch 0 port 2 yes external MicroLogix™ 1000, 1200, or 1500 ch 0 port 1 yes external MicroLogix™ 1100 ch 0 port 1 yes external PanelView 550 through NULL modem
port 2 yes external
adapter DTAM Plus / DTAM Micro port 2 yes external PC COM port port 2 yes external
(1)
External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to cable.
(2)
Series C or later cables are required.
Cable Length Connections from to AIC+ External
Power Supply Required
1761-CBL-AM00 1761-CBL-HM02
(2)
(2)
45 cm (17.7 in.) 2 m (6.5 ft)
MicroLogix™ 1000, 1200, or 1500 ch 0 port 2 no cable MicroLogix™ 1100 ch 0 port 2 Yes external
(1)
(1)
Power Selection Switch Setting
Power Selection Switch
(1)
Setting
to port 2 on another AIC+ port 2 yes external
(1)
External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to cable.
(2)
Series C or later cables are required.
Publication 1763-UM001D-EN-P - March 2011
Communication Connections 91
1761-CBL-AC00
1747-CP3
user-supplied cable
1761-CBL-AS03
1761-CBL-AS09
Cable Length Connections from to AIC+ External
Power Supply Required
1747-CP3
1761-CBL-AC00
(1)
3 m (9.8 ft)
45 cm (17.7 in.)
SLC 5/03 or SLC 5/04 processor, channel 0port 1 yes external
PC COM port port 1 yes external PanelView 550 through NULL modem
port 1 yes external
adapter DTAM Plus / DTAM Micro™ port 1 yes external Port 1 on another AIC+ port 1 yes external
(1)
External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to cable.
Cable Length Connections from to AIC+ External
Power Supply Required
(1)
(1)
Power Selection Switch
Setting
Power Selection Switch
(1)
Setting
(1)
straight 9-25 pin modem or other communication device port 1 yes external
(1)
External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to cable.
Cable Length Connections from to AIC+ External
Power Supply Required
(1)
Power Selection Switch
Setting
1761-CBL-AS03
1761-CBL-AS09
3 m (9.8 ft)
9.5 m (31.17 ft)
SLC 500 Fixed,
SLC 5/01, SLC 5/02, and SLC 5/03
port 3 yes external
processors PanelView 550 RJ45 port port 3 yes external
(1)
External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to cable.
(1)
Publication 1763-UM001D-EN-P - March 2011
92 Communication Connections
1
2
3
4
6
5
7
8
9
12
3
5
6
8
7
4
Programming Device
Controller
9-Pin D-Shell 8-Pin Mini Din 9RI 24V1 8CTS GND2 7RTS RTS3 6 DSR RXD 4 5GND DCD5 4DTR CTS6 3TXD TXD7 2RXD GND8 1DCD
1761-CBL-PM02 Series C (or equivalent) Cable Wiring Diagram
Publication 1763-UM001D-EN-P - March 2011
Communication Connections 93
1761-CBL-AP00 or 1761-CBL-PM02
DB-9 RS-232
RS-485 connector
cable straight D connector
Port 1
Port 2
Port 3
6
7
8
9
1
2
3 4
5
4
1
2
5
876
3
6
5
4
3
2
1
Recommended User-Supplied Components
These components can be purchased from your local electronics supplier.
User Supplied Components
Component Recommended Model
external power supply and chassis ground power supply rated for 20.4...28.8V DC NULL modem adapter standard AT straight 9-25 pin RS-232 cable see table below for port information if
making own cables
AIC+ Terminals
Pin Port 1: DB-9 RS-232
1 received line signal detector
Port 2 cable)
(2)
: (1761-CBL-PM02
Port 3: RS-485 Connector
24V DC chassis ground
(DCD) 2 received data (RxD) ground (GND) cable shield 3 transmitted data (TxD) request to send (RTS) signal ground 4
DTE ready (DTR)
(1)
received data (RxD)
5 signal common (GND) received line signal detector
(3)
DH-485 data B DH-485 data A
(DCD)
6
DCE ready (DSR)
(1)
clear to send (CTS)
(3)
termination
7 request to send (RTS) transmitted data (TxD) not applicable 8 clear to send (CTS) ground (GND) not applicable 9 not applicable not applicable not applicable
(1)
On port 1, pin 4 is electronically jumpered to pin 6. Whenever the AIC+ is powered on, pin 4 will match the state of pin 6.
(2)
An 8-pin mini DIN connector is used for making connections to port 2. This connector is not commercially available. If you are making a cable to connect to port 2, you must configure your cable to connect to the Allen-Bradley cable shown above.
(3)
In the 1761-CBL-PM02 cable, pins 4 and 6 are jumpered together within the DB-9 connector.
Publication 1763-UM001D-EN-P - March 2011
94 Communication Connections
WARNING
Safety Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D or non-hazardous locations only.
EXPLOSION HAZARD
AIC+ must be operated from an external power source.
This product must be installed in an enclosure. All cables connected to the product must remain in the enclosure or be protected by conduit or other means.
See Safety Considerations on page 21 for additional information.
Install and Attach the AIC+
1. Take care when installing the AIC+ in an enclosure so that the cable connecting the MicroLogix™ controller to the AIC+ does not interfere with the enclosure door.
2. Carefully plug the terminal block into the RS-485 port on the AIC+ you are putting on the network. Allow enough cable slack to prevent stress on the plug.
3. Provide strain relief for the Belden cable after it is wired to the terminal block. This guards against breakage of the Belden cable wires.
Publication 1763-UM001D-EN-P - March 2011
Communication Connections 95
ATTENTION
ATTENTION
24V DC
DC NEUT
CHS GND
Bottom View
Powering the AIC+
MicroLogix 100, 1200, and 1500 programmable controllers support 24V DC communication power on Channel 0. When connected to the 8 pin mini-DIN connector on the 1761-NET-AIC, 1761-NET-ENI, and the 1761-NET-ENIW, these controllers provide the power for the interface converter modules. The MicroLogix 1100 does not provide 24V DC communication power. Instead these pins are used to provide RS-485 communications directly. Any AIC+, ENI, or ENIW not connected to a MicroLogix 1000, 1200, or 1500 controller requires a 24V DC power supply.
If both the controller and external power are connected to the AIC+, the power selection switch determines what device powers the AIC+.
If you use an external power supply, it must be 24V DC (-15%/+20%). Permanent damage results if a higher voltage supply is used.
Set the DC Power Source selector switch to EXTERNAL before connecting the power supply to the AIC+. The following illustration shows where to connect external power for the AIC+.
Always connect the CHS GND (chassis ground) terminal to the nearest earth ground. This connection must be made whether or not an external 24V DC supply is used.
Publication 1763-UM001D-EN-P - March 2011
96 Communication Connections
ATTENTION
Power Options
Below are two options for powering the AIC+:
Use the 24V DC user power supply built into the MicroLogix™ 1000,
1200, or 1500 controller. The AIC+ is powered through a hard-wired connection using a communication cable (1761-CBL-HM02, or equivalent) connected to port 2.
Use an external DC power supply with the following specifications:
operating voltage: 24V DC (-15%/+20%)output current: 150 mA minimumrated NEC Class 2
Make a hard-wired connection from the external supply to the screw terminals on the bottom of the AIC+.
If you use an external power supply, it must be 24V DC (-15%/+20%). Permanent damage results if miswired with the wrong power source.
Publication 1763-UM001D-EN-P - March 2011
Communication Connections 97
V– CAN_L
SHIELD CAN_H
V+
NET
MOD
NODE
DANGER
GND
TX/RX
DeviceNet Node (Port 1) (Replacement connector part no. 1761-RPL-RT00)
Use this write-on area to mark the DeviceNet node address.
RS-232 (Port 2)
1761-CBL-AM00
1761-CBL-HM02
1761-CBL-AP00
1761-CBL-PM02

Connecting to DeviceNet

You can connect a MicroLogix™ 1100 as a slave to a DeviceNet network using the DeviceNet Interface (DNI), catalog number 1761-NET-DNI. For additional information on using the DNI, refer to the DeviceNet Interface User Manual, publication 1761-UM005. The following figure shows the external wiring connections of the DNI.
Cable Selection Guide
(1)
Cable Length Connections from to DNI
1761-CBL-AM00 1761-CBL-HM02
Cable Length Connections from to DNI
1761-CBL-AP00 1761-CBL-PM02
(1)
Series C (or later) cables are required.
45 cm (17.7 in.) 2 m (6.5 ft)
45 cm (17.7 in.) 2 m (6.5 ft)
MicroLogix 1000 port 2 MicroLogix 1100 port 2 MicroLogix 1200 port 2 MicroLogix 1500 port 2
SLC 5/03 or SLC 5/04 processors, channel 0
PC COM port port 2 1764-LRP processor, channel 1 port 2
Publication 1763-UM001D-EN-P - March 2011
port 2
98 Communication Connections
RS-232/485 Port (Channel 0)
Ethernet Port (Channel 1)
8 7 6 5 4 3 2 11 2 3 4 5 6 7 8
End view of RJ 45 Plug Looking into a RJ45 Jack

Connecting to Ethernet

You can connect directly a MicroLogix™ 1100 to an Ethernet network via the Ethernet port (Channel 1). You do not need to use an Ethernet interface card, such as the Ethernet Interface (ENI) and (ENIW), catalog number 1761-NET-ENI and 1761-NET-ENIW, to connect your MicroLogix 1100 controller to an Ethernet network. For additional information on connecting to an Ethernet network, see Appendix F.
Ethernet Connections
The Ethernet connector, Channel 1, is an RJ45, 10/100Base-T connector. The pin-out for the connector is shown below.
Pin Pin Name
1Tx+ 2Tx­3Rx+ 4 not used by 10/100Base-T 5 not used by 10/100Base-T 6Rx­7 not used by 10/100Base-T 8 not used by 10/100Base-T
Publication 1763-UM001D-EN-P - March 2011
Loading...