Rockwell Automation 1747-ACNR15 User Manual

ControlNet™ Adapter Module
(Catalog Numbers 1747-ACN15, 1747-ACNR15)
User Manual

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss
!!!!
Attention statements help you to:
identify a hazard
avoid a hazard
recognize the consequences
IMPORTANT
ControlNet and SLC 500 are trademarks of Rockwell Automation.
PLC-5 is a registered trademark of Rockwell Automation.
Identifies information that is critical for successful application and understanding of the product.

Table of Contents

Preface
Introducing the ControlNet Adapter Module
Installing Your ControlNet Adapter Module
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Common Techniques Used in this Manual. . . . . . . . . . . . . . . . . . . P-1
Rockwell Automation Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Local Product Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Technical Product Assistance. . . . . . . . . . . . . . . . . . . . . . . . . . . P-2
Your Questions or Comments on this Manual . . . . . . . . . . . . . P-2
Chapter 1
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Module Description and Features . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Hardware Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Diagnostic Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Network Access Port (NAP) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
ControlNet Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Network Address Switch Assemblies . . . . . . . . . . . . . . . . . . . . . 1-3
Chapter 2
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Compliance to European Union Directives. . . . . . . . . . . . . . . . . . . 2-1
EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Low Voltage Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Determining Power Requirements . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Setting the Network Address Switches. . . . . . . . . . . . . . . . . . . . . . . 2-2
Installing the Adapter Module in the Chassis . . . . . . . . . . . . . . . . . 2-3
Connecting Your Adapter to the ControlNet Network . . . . . . . 2-4
Connecting Programming Terminals to the Network via the NAP . 2-6
Powerup Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Chapter 3
Planning to Use Your ControlNet Adapter Module
i Publication 1747-UM003 A-EN-P
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Compatible 1746 and 1747 I/O Modules . . . . . . . . . . . . . . . . . . . . 3-1
Overview of Adapter Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Software Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Rack and Module Connections . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Optimizing SLC ControlNet Adapter Rack Connections . . . . . 3-4
Module Keying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Output Operation During Fault and Idle Modes . . . . . . . . . . . 3-6
Understanding ControlNet I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Scheduled Data-Transfer Connections on a
ControlNet Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Table of Contents ii
Application Examples
Chapter 4
Example 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Configuring The ControlNet Network with
RSNetWorx™ for ControlNet . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
Create a Ladder Logic Program . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11
Configuring The ControlNet Network with
RSNetWorx™ for ControlNet . . . . . . . . . . . . . . . . . . . . . . . . 4-12
Create a Ladder Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
Example 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21
Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21
Configuring The ControlNet Network with
RSNetWorx™ for ControlNet . . . . . . . . . . . . . . . . . . . . . . . . 4-22
Create a Ladder Logic Program . . . . . . . . . . . . . . . . . . . . . . . . 4-30
Example 4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-31
Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-31
Configuring The ControlNet Network with
RSNetWorx™ for ControlNet . . . . . . . . . . . . . . . . . . . . . . . . 4-32
Create Ladder Logic and Basic Module Programs . . . . . . . . . . 4-43
Example 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-46
Hardware Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-46
Configuring The ControlNet Network with
RSNetWorx for ControlNet . . . . . . . . . . . . . . . . . . . . . . . . . . 4-47
Create a Ladder Logic Program . . . . . . . . . . . . . . . . . . . . . . . . 4-57
Troubleshooting
Specifications
Understanding Your SLC 500/1746 Control System
Publication 1747-UM003A-EN-P
Chapter 5
Chapter Objectives . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Troubleshooting With the Status Indicators and Status Display . . . 5-1
Health Indicators and Display Mnemonics . . . . . . . . . . . . . . . . 5-2
ControlNet Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Appendix A
Appendix B
Selecting Your SLC 500/1746 Control Power Supply. . . . . . . . . . . B-1
Power Supply Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
SLC 500 System Installation Recommendations . . . . . . . . . . . . . . . B-6
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Selecting an Enclosure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-6
Spacing Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-7
Preventing Excessive Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-8
Wiring Layout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-8
Table of Contents iii
Grounding Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-9
Master Control Relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-11
Emergency-Stop Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-13
Common Power Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-15
Loss of Power Source. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-16
Input States on Power Down . . . . . . . . . . . . . . . . . . . . . . . . . B-16
Other Types of Line Conditions . . . . . . . . . . . . . . . . . . . . . . . B-16
Power Conditioning Considerations . . . . . . . . . . . . . . . . . . . . B-16
Special Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-18
Output Contact Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . B-20
Mounting Your Control System . . . . . . . . . . . . . . . . . . . . . . . . . . B-21
Mounting Modular Hardware Style Units. . . . . . . . . . . . . . . . B-21
Installing Your I/O Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-25
Features of an SLC 500 I/O Module. . . . . . . . . . . . . . . . . . . . B-25
Definition of Sinking and Sourcing. . . . . . . . . . . . . . . . . . . . . B-26
Inserting I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-28
Removing I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-30
Wiring the I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-31
Using Removable Terminal Blocks . . . . . . . . . . . . . . . . . . . . . B-32
Calculating Heat Dissipation for Your Control System. . . . . . . . . B-34
Module Heat Dissipation: Calculated Watts
vs. Maximum Watts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-34
Calculating the Power Supply Loading . . . . . . . . . . . . . . . . . . B-35
Determining the Power Supply Dissipation. . . . . . . . . . . . . . . B-38
Glossary
Index
Publication 1747-UM003 A-EN-P
Table of Contents iv
Publication 1747-UM003A-EN-P

Preface

Read this preface to familiarize yourself with the rest of the manual. It provides information concerning:
who should use this manual
the purpose of this manual
related documentation
conventions used in this manual
Allen-Bradley support

Who Should Use this Manual

Purpose of this Manual

Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use the ControlNet Adapter Module.
You should have a basic understanding of electrical circuitry and familiarity with relay logic. If you do not, obtain the proper training before using this product.
This manual is a reference guide for the ControlNet Adapter Module. It describes the procedures you use to install, program and troubleshoot your module. This manual also includes several application examples.

Related Documentation

The following documents contain additional information concerning Allen-Bradley products. To obtain a copy, contact your local Allen-Bradley office or distributor.
Publication Publication
Number
ControlNet PLC-5 Programmable Controllers User Manual Phase 1.5 1785-6.5.22 ControlNet Cable System Component List AG-2.2 ControlNet Cable System Planning and Installation Manual 1786-6.2.1 ControlNet Coax Tap Installation Instructions 1786-2.3 ControlNet Network Access Cable Installation Instructions 1786-2.6 ControlNet Repeater Installation Instructions 1786-2.7 Industrial Automation Wiring and Grounding Guidelines 1770-4.1 SLC 500™ Modular Hardware Style User Manual 1747-6.2 ControlNet Scanner Module Reference Manual 1747-6.23

Common Techniques Used in this Manual

1 Publication 1747-UM003 A-EN-P
The following conventions are used throughout this manual:
Bulleted lists such as this one provide information, not procedural steps.
Numbered lists provide sequential steps or hierarchical information.
Italic type is used for emphasis.
Preface 2

Rockwell Automation Support

Rockwell Automation offers support services worldwide, with over 75 Sales/ Support Offices, 512 authorized Distributors and 260 authorized Systems Integrators located throughout the United States alone, plus Rockwell Automation representatives in every major country in the world.

Local Product Support

Contact your local Rockwell Automation representative for:
sales and order support
product technical training
warranty support
support service agreements

Technical Product Assistance

If you need to contact Rockwell Automation for technical assistance, please review the Troubleshooting appendix in your controller’s User Manual first. Then call your local Rockwell Automation representative.

Your Questions or Comments on this Manual

If you find a problem with this manual, or you have any suggestions for how this manual could be made more useful to you, please contact us at the address below:
Rockwell Automation Control and Information Group Technical Communication, Dept. A602V P.O. Box 2086 Milwaukee, WI 53201-2086
or visit our internet page at:
http://www.rockwellautomation.com
Publication 1747-UM003A-EN-P
Chapter
1
Introducing the ControlNet Adapter Module

Chapter Objectives

Module Description and Features

This chapter describes the ControlNet adapter modules (cat. no. 1747-ACN15 and 1747-ACNR15):
features
hardware components, including
diagnostic indicatorsnetwork access port (NAP)ControlNet connectorsnetwork address switch assemblies
The 1747-ACN15 and 1747-ACNR15 adapters control remote 1746 I/O on the ControlNet network. The ControlNet network is a communication architecture that allows the exchange of messages between ControlNet products compliant with the CI specification.
The 1747-ACN15 and 1747-ACNR15 adapters features include:
high-speed data transfer
diagnostic messages
local communication network access through the network access port
(NAP)
redundant media (1747-ACNR15 only)

Hardware Components

1 Publication 1747-UM003 A-EN-P
The adapter module consists of the following major components:
ControlNet status indicators
status display
network access port (NAP)
ControlNet connectors (one on 1747-ACN15; two on 1747-ACNR15)
module net address switch assemblies (on top of module)
1-2 Introducing the ControlNet Adapter Module
Figure 1.1 ControlNet Adapter Module
Module Network Address Switches (accessible through top of module)
1747-ACN15
ADDRESS/STATUS
OK OK
A
ADDRESS/STATUS
BAA
B

Diagnostic Indicators

Status Display and Net Address
Health Indicators
ControlNet Status Indicators

Network Access Port (NAP)

1747-ACNR15
A
ControlNet Media Port ControlNet Redundant Media Port (1747-ACNR15 only)
Diagnostic Indicators
Health indicators are located on the front panel of the adapter module, See Figure 1.1. They show both normal operation and error conditions in your remote I/O system.
In addition, an alphanumeric display (net address/status) provides status code indications when an error occurs during initialization or operation.
A complete description of the diagnostic indicators and status display and how to use them for troubleshooting is explained in Chapter 5.
Network Access Port (NAP)
The network access port provides a bidirectional electrical interface for programming, maintenance, and I/O monitoring devices in both redundant and non-redundant connections. See Figure 1.1 connecting programming terminals to the network using the NAP above.
Publication 1747-UM003A-EN-P
Introducing the ControlNet Adapter Module 1-3

ControlNet Connectors

Cable connection to the module is through standard BNC connectors on the module frontplate.
Figure 1.2 Redundant Media System
Terminator
Terminator
trunkline A =
trunkline B =
PLC-5C or SLC 5/02 or later with 1747-SCNR
(1) End device supporting redundant cabling is a 1747-ACNR15.
A
Terminator
B
Terminator
end device
(1)
end device
(1)
Refer to the ControlNet Cable System Planning and Installation User Manual, publication 1786-6.2.1 for more information.

Network Address Switch Assemblies

You must set two switch assemblies to configure your adapter module with its unique network address. You access these switches through the top of the module. Figure 1.3 shows the location of the switches. These switches are read on powerup to establish the network address of the module. Network address switch settings are described in Chapter 2.
For optimum throughput, assign sequential addresses to ControlNet nodes.
Publication 1747-UM003 A-EN-P
1-4 Introducing the ControlNet Adapter Module
Publication 1747-UM003A-EN-P
Chapter
2
Installing Your ControlNet Adapter Module

Chapter Objectives

Compliance to European Union Directives

This chapter describes the procedures for installing your ControlNet adapter module. These include:
European Directive compliance
determining power requirements
setting the network address switches
setting the I/O chassis switches
installing the adapter module in the chassis
connecting programming terminals to the network via the network access
port (NAP)
powerup sequence
For general installation guidelines, see SLC 500 System Installation Recommendations on page B-6. If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive

This product is tested to meet Council Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the following standards, in whole or in part, documented in a technical construction file:
EN 50081-2
EMC - Generic Emission Standard, Part 2 - Industrial Environment
EN 50082-2
EMC - Generic Immunity Standard, Part 2 - Industrial Environment
This product is intended for use in an industrial environment.
1 Publication 1747-UM003 A-EN-P
2-2 Installing Your ControlNet Adapter Module

Low Voltage Directive

This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61131-2 Programmable Controllers, Part 2 - Equipment Requirements and Tests.
For specific information required by EN 61131-2, see the appropriate sections in this publication, as well as the following Allen-Bradley publications:
Industrial Automation Wiring and Grounding Guidelines For Noise Immunity, publication 1770-4.1
Automation Systems Catalog, publication B111

Determining Power Requirements

Setting the Network Address Switches

The ControlNet adapter module requires a maximum backplane current of 900 mA at 5V dc. Remember to add this amount to other current requirements for your I/O chassis.
The switches on the top of the adapter module determine the network address of the adapter. The two switches are:
the ten’s switch
the one’s switch
The combination of these switches allows selection of network addresses from 01 to 99.
NOTE
Figure 2.1 Setting the Network Address
00 is an invalid number.
Ten ’s Selection
One’s Selection
Publication 1747-UM003A-EN-P
Installing Your ControlNet Adapter Module 2-3

Installing the Adapter Module in the Chassis

Power Supply
Card Guide
Once you’ve set the appropriate switch assemblies for your adapter module, follow these procedures for installation.
Refer to the Industrial Controller Wiring and Grounding Guidelines, Publication 1770-4.1 for proper grounding and wiring methods to use when installing your module.
ATTENTION
Remove system power before removing or installing your module in the I/O chassis. Failure to observe this warning could damage module circuitry and injure people.
!!!!
1. Remove power from the I/O chassis before inserting (or removing) the module.
2. Align the circuit board with the chassis card guide in the left slot.
3. Slide the module into the chassis until the top and bottom latches are
Latch
latched. To remove the module, press the releases at the top and bottom of the module and slide it out.
4. Press firmly and evenly to seat the module in its backplane connectors.
ATTENTION
!!!!
Do not force the module into the backplane connector. If you cannot seat the module with firm pressure, check the alignment. Forcing the module can damage the backplane connector or the module.
Publication 1747-UM003 A-EN-P
2-4 Installing Your ControlNet Adapter Module

Connecting Your Adapter to the ControlNet Network

You connect your 1747-ACN15 or -ACNR15 adapter module to a ControlNet network via taps. These taps are available:
Straight T-tap
1786-TPS 1786-TPYS
IMPORTANT
1. Remove the tap’s dust cap (located on the straight or right angle connector).
If your node supports:
Non-redundant media to the channel A connector on the 1747-ACN15 or
Redundant media from trunkline A to channel A on the 1747-ACNR15
(1)
While both channels are active, Allen-Bradley recommends using channel A for non-redundant media.
Straight Y-tap
Taps contain passive electronics and must be purchased from Allen-Bradley for the network to function properly.
Connect the tap’s straight or right angle connector:
1747-ACNR15 (channel B on the 1747-ACNR is not used)
from trunkline B to channel B on the 1747-ACNR15
Right-angle T-tap Right-angle Y-tap
1786-TPR
1786-TPYR
(1)
Publication 1747-UM003A-EN-P
ATTENTION
!!!!
Do not allow any metal portions of the tap to contact any conductive material. If you disconnect the tap from the adapter, place the dust cap back on the straight or right angle connector to prevent the connector from accidentally contacting a metallic grounded surface.
Installing Your ControlNet Adapter Module 2-5
segment 1
Tap
dust cap
2. Remove and discard the dust caps from the adapter BNC jacks.
3. Connect this tap’s straight or right angle connector to the BNC connector on the adapter.
IMPORTANT
To prevent inadvertent reversal of the tap connections (resulting in incorrect LED displays and troubleshooting), check the tap drop cable for a label indicating the attached segment before making your connection.
4. For redundant adapters (1747-ACNR15), remove (and save) the dust cap located on the straight or right angle connector of the designated tap on the second segment (segment 2).
segment 2
tap
dust cap
5. Connect this tap’s straight or right angle connector to the BNC connector on the adapter.
segment 1
tap
segment 2
tap
After terminating your segments, connect the node to the network.
Publication 1747-UM003 A-EN-P
2-6 Installing Your ControlNet Adapter Module

Connecting Programming Terminals to the Network via the NAP

Using 1784-KTC or -KTCx Communication Card and NAP
Programming Terminal
1784-KTC or
-KTCx
ControlNet network
You can connect programming terminals to the ControlNet network by connecting to the network access port (NAP). Two methods are shown below.
Using 1770-KFC Communication Interface and NAP
Programming Terminal
1770-KFC
(1)
1786-CP
ControlNet product
(1) The 1786-CP cable can be plugged into any ControlNet product’s NAP to provide
programming capability on the ControlNet network. A programming terminal connected through this cable is counted as a node and must have a unique address.
Serial or Parallel Connection
ControlNet Network
1786-CP
ControlNet product
(1)
ATTENTION
!!!!
Use the 1786-CP cable when connecting a programming terminal to the network through NAPs. Using a commercially available RJ-style cable could result in possible network failures.
Publication 1747-UM003A-EN-P
Installing Your ControlNet Adapter Module 2-7

Powerup Sequence

There are three health indicators on the module. The LED on the right (labeled “OK”) is the generic module health indicator. The LED in the middle (labeled “A”) is the health indicator of cable A. On the 1747-ACNR15, the LED on the left (labeled “B”) is the health indicator for cable B. In addition, the alphanumeric display can display module status. The following describes the normal power-up sequence for the adapter module. (Refer to Troubleshooting With the Status Indicators and Status Display on page 5-1 and ControlNet Status Indicators on page 5-3 for explanation of the LED’s and alphanumeric display.)
ADDRESS/STATUS
B
A
Status
Health Indicators Channel A and B
OK
indicators
1. Apply power to the chassis - notice that all three health indicators should be off and the status window indicates “POST” (Power On Self Test).
2. After “POST”, the status window displays the sequence “0000”, “1111”, “2222”, through “9999”. During this time, the A and B LEDs are off and the OK LED toggles between red and green; this happens so fast, the OK LED appears amber.
3. The series and revision levels are then displayed in the status window. A series A revision level B module would display “A/B”. During this time, the A and B LEDs are off and the OK LED toggles between red and green; this happens so fast, the OK LED appears amber.
4. After the operating system is loaded and initialized, the status window and the LEDs indicate the status of the module and its connections to the cable(s). If the module address is not zero and a valid ControlNet connection is made to either channel A or B, the status window toggles between “ACTV” (Active) and the module node address (“A#02”, node address number 2). If there are no active connectors, the status window displays “IDLE”.
5. If there is a hardware problem of any kind, the health LED turns red and the status window toggles between “FATL” and up to four alphanumeric characters. The “FATL” indicates that there was a fatal error and the characters indicate what the error is.
For detailed information on planning and installing your ControlNet system, refer to Related Publication on page P-1.
Publication 1747-UM003 A-EN-P
2-8 Installing Your ControlNet Adapter Module
Publication 1747-UM003A-EN-P
Chapter
3
Planning to Use Your ControlNet Adapter Module

Chapter Objectives

Compatible 1746 and 1747 I/O Modules

This chapter explains how the adapter operates on ControlNet and provides information to assist in configuring your system. This includes:
compatible 1746 and 1747 I/O modules
overview of adapter operation
software requirements
rack and module connections
optimizing SLC ControlNet Adapter connections
module keying
output operation during Fault and Idle modes
understanding ControlNet I/O
scheduled Data-Transfer connections on a ControlNet network
The majority of 1746 and 1747 discrete, analo g and specialty modules are compatible with the 1747-ACN15 and 1747-ACNR15 adapters. Exceptions include any modules that require G file configuration. These include:
1747-SN Remote I/O Scanner module
1747-BSN Back-Up Remote I/O Scanner module
1746-QV Open Loop Velocity Control module
1203-SM1 Scanport module (Class 4 operation) (This module is
compatible when configured for class 1 operation.)
1747-SCNR ControlNet Scanner module (G files not required,
however, this module is not supported by the 1747-ACN15/ ACNR15)
A small number of 1746 modules are currently not supported by the adapter due to lack of an EDS (electronic data sheet) file. These modules will be supported once EDS development is completed. A complete list of compatible 1746 and 1747 modules can be found on the Allen-Bradley Technical Support Knowledge Base at:
http://www.ab.com/support/kbhome.html.
3-2 Planning to Use Your ControlNet Adapter Module

Overview of Adapter Operation

Connections are established between a scanner and an adapter to exchange input and output data on the network. Status information is transferred along with the I/O data and status.
1747-ACN15/ACNR15 adapters support connections to individual modules and rack connections to a group of modules. The adapters support multiple rack and group connections to the same modules, as long as only one scanner controls any module’s outputs. Up to 64 connections per adapter are possible with 240 words (max) supported per connection. An adapter can control up to 30 slots of 1746 I/O (3 chassis max). The input data attributes correspond directly to the read area of the I/O module’s data table image. The output attributes correspond directly to the write area of the I/O module’s data table image.
RSNetWorx is the software tool that is used to schedule network bandwidth for all scheduled traffic originators that reside on a ControlNet network segment. RSLinx is the communication software tool used by RSNetWorx to access the ControlNet network. A 1784-KTCX15 PC card or 1784-PCC ControlNet card can be used as the hardware interface to the network.

Software Requirements

RSNetWorx for ControlNet version 2.23.00 or greater is required to configure the 1747-ACN15/ACNR15 adapters. If you only have RSNetWorx for ControlNet version 2.22.18, it is necessary to add the Service Pack in order to configure connections with the 1747-ACNR15 adapter. To add the Service Pack, follow the steps below.
1. Access the Rockwell Software support page at: http://www.software.rockwell.com/support
2. Click Downloads form the list of choices in the left column.
3. Locate section 2, “Choose a Product”.
4. Click the down arrow and select RSNetWorx from the drop down list.
5. In section 4, click Search.
6. Click Service Pack 1, or click a later version for the Service Pack if it is
not the only Service Pack available.
7. After the download is completed, close all programs and run the installation of the software. Follow the screen prompts to guide you through the installation process. If you experience problems performing the install, contact Rockwell Software Technical Support.
Publication 1747-UM003A-EN-P
When Service Pack 1 is installed, the version of RSNetWorx for ControlNet is
2.23.00 or greater.
Planning to Use Your ControlNet Adapter Module 3-3

Rack and Module Connections

There are two types of scheduled connections supported by the 1747-ACN15,
-ACNR15: the rack connection and the individual module connection.
Rack Connections
For each rack connection, RSNetWorx maps 8, 16, or 32 input and output bits per slot.
Operation Description
8-bit Rack Connections
16-bit Rack Connections
32-bit Rack Connections
Performed in a deterministic and repeatable manner. This connection allows a memory and ControlNet bandwidth efficient way to connect to a rack of 8-bit modules
Performed in a deterministic and repeatable manner. This connection allows a memory and ControlNet bandwidth efficient way to connect to a rack of 16-bit modules.
Performed in a deterministic and repeatable manner. This connection allows a memory and ControlNet bandwidth efficient way to connect to a rack of 32-bit modules.
The rack connection is used to define a single connection for the discrete I/O in the SLC backplane. Multiple rack connections, with limitations, are supported in the SLC adapter. For example, a connection originator might specify an 8-bit, 16-bit, or 32-bit data size.
IMPORTANT
RSNetWorx allows more than one exclusive owner rack connection type to be configured to a 1747 adapter (e.g. 8-bit exclusive owner, 16-bit exclusive owner, and 32-bit exclusive owner), however onl y one exclusive owner rack connection can be operational at one time. It is recommended that only one exclusive owner rack connection type be configured to the adapter to avoid contention between multiple connections.
IMPORTANT
If a rack connection type is changed to a smaller bit configuration e.g. 32-bit to 16-bit, or 16-bit to 8-bit, the unused bits for the new connection are reset to zero.
Publication 1747-UM003 A-EN-P
3-4 Planning to Use Your ControlNet Adapter Module
Module Connections
Module connections are performed in a deterministic and repeatable manner. This connection allows a memory and ControlNet bandwidth efficient way to connect to an individual module with more I/O data than could be attempted in the above rack connections, or to transfer M0/M1 file data.
Each rack and module connection can be configured with the following connection types:
1. Exclusive Owner - specifies an independent connection where a single device controls the output states in the target device. If you have an existing Exclusive Owner connection to a target device, you cannot specify another Exclusive Owner or Redundant connection to that same target device.
2. Input Only - specifies an independent connection where a device receives inputs fro m the target device and sends c onfiguration data to the target device. An Input Only connection does not send outp uts; it only receives inputs. You can specify multiple Input Only connect ions to the target device from different originators.
3. Listen Only - specifies a dependent connection where a device receives inputs from the target device, but does not send configuration data with the target device. A Listen Only connection only functions properly when another non-Listen Only connection exists to the same target device. A Listen Only connection does not send outputs; it only receives inputs. You can specify multiple Listen Only connections to the target device from different originators.
NOTE
All Listen Only connections are terminated when all associated independent connections are terminated.

Optimizing SLC ControlNet Adapter Rack Connections

Consider the following example placement of ControlNet devices when you want to optimize your SLC ControlNet adapter connection:
Node Slot Device
1 1747-SCNR 2 0 1747-ACNR15
1 1746-IB16 2 1746-IB16 3 1746-OB16 4 1746-OB16 5 1746-NIO4I 6 1746-HSCE
Publication 1747-UM003A-EN-P
Planning to Use Your ControlNet Adapter Module 3-5
If we change the default number of words for the input and output values (to 4 and 4) when inserting the connection to the 1747-ACNR15 adapter, Node 2 will produce 4 input words over ControlNet and Node 1 will consume and place those words at addresses I:e.1-4, where the slot 1 inp uts corresp ond to I:e.3 and the slot 2 inputs correspond to I:e.4. In addition, Node 1 will produce 4 output words over ControlNet originating from addresses O:e.1-4 and Node 2 will consume them. A total of 8 words (4 input and 4 output) are transmitted on ControlNet.
NOTE
To optimize ControlNet network bandwidth, place the devices in the following order (left to right on the chassis):
1747-ACNR15 adapter
Discrete input modules
Discrete output modules
Any intelligent and/or analog I/O modules that you want
to establish individual module connections to
Consider the following:
The 1747-SCNR has 31 input words and 31 output words available for
rack connections to 1747-ACNR15 adapters.
Each 1747-ACNR15 adapter requires 2 input words for status in addition
to the input words assigned to the slots.
Adjust the rack connection size to match the maximum density I/O
module:
Discrete 8-bit Exclusive Owner for 4 and 8-point modulesDiscrete 16-bit Exclusive Owner for 16-point modulesDiscrete 32-bit Exclusive Owner for 32-point modules.

Module Keying

Missing or misplaced modules are detected if the module in question is configured with RSNetWorx as an individual module connection and “compatible module” is selected for electronic keying. If a module connection is attempted to a module which is a missing or misplaced module, the connection will fail. The green OK LED on the initiating scanner will flash and the module will display “I/O” with a partially filled bar indicating all connections are not established, as shown below.
I/O
Publication 1747-UM003 A-EN-P
3-6 Planning to Use Your ControlNet Adapter Module
NOTE
The electronic keying option offered by RSNetWorx for rack connections applies to the 1747-ACN15 and
-ACNR15 modules only.
Missing or misplaced modules are not detected if the module in question is configured within a rack connection. Critical I/O modules that need to be detected when missing or mispla ced must be configured with indiv idual module connections.

Output Operation During Fault and Idle Modes

RSNetworx allows configuration to characterize each module connection activity during certain operational states.
During idle mode and fault modes, outputs are configured for one of the following operation states:
Output Action
Reset outputs to off
Hold last state
Write Safe State data to outputs

Understanding ControlNet I/O

The ControlNet system is designed to:
provide high-speed, repeatable, deterministic I/O transmission
allow control and message information to co-exist on the same physical
media
make sure that I/O data transfers are not affected by
programming-terminal message activity
inter-processor message activity on the network

Scheduled Data-Transfer Connections on a ControlNet Network

Scheduled data transfer on a ControlNet processor:
is continuous
is asynchronous to the ladder-logic program scan
occurs at the actual rate displayed in the Actual Packet Interval field on the
RSNetWorx ControlNet I/O mapping (monitor) screen
Publication 1747-UM003A-EN-P
Planning to Use Your ControlNet Adapter Module 3-7
Private­Memory Buffers
Scheduled Data Transfers
Scheduled Data Transfer Program Scan
Data Update
Data­Tab le Files
Housekeeping
Logic Scan
The ControlNet system places your scheduled transfers in the first part of each Network Update Interval. Time is automatically reserved for network maintenance. Unscheduled transfers are performed during the time remaining in the interval.
You reserve a specific amount of time for all
scheduled operations.
The system reserves time for
network maintenance
Any time remaining is used for unscheduled operations
. . .. . .
Your application and your configuration-number of nodes, application program, NUT (Network Update Time), amount of scheduled bandwidth used, etc. determine how much time there is for unscheduled messaging.
IMPORTANT
The ControlNet network reserves time for at least one maximum-sized unscheduled transfer per update interval. Depending on how much time there is for unscheduled messaging, every node may not have a chance to send unscheduled data every update interval.
Publication 1747-UM003 A-EN-P
3-8 Planning to Use Your ControlNet Adapter Module
Publication 1747-UM003A-EN-P
Chapter
Application Examples
Table 4.A Table of Contents
Example Number Title Page
1 1747-SCNR ControlNet Scanner Controlling Discrete I/O on
ControlNet via a 1747-ACN15 ControlNet Adapter Using a Rack Connection
2 1747-SCNR ControlNet Scanner Controlling Discrete and
Analog I/O on ControlNet via a 1747-ACN15 ControlNet Adapter Using a Rack Connection
3 1747-SCNR ControlNet Scanner Controlling Discrete and
Analog I/O on ControlNet via a 1747-ACN15 ControlNet Adapter Using Rack and Module Connections
4 1747-SCNR ControlNet Scanner Controlling Discrete I/O and
Serial Data with a 1746-BAS Module on ControlNet via a 1747-ACN15 ControlNet Adapter Using Rack and Module Connections
5 1747-SCNR ControlNet Scanner Controlling Discrete I/O and
Specialty Modules Requiring M0 File Configuration on ControlNet via a 1747-ACN15 ControlNet Adapter Using Rack and Module Connections
4-2
4-11
4-21
4-31
4-46
4
1 Publication 1747-UM003 A-EN-P
4-2 Application Examples

Example 1

1747-SCNR ControlNet Scanner Controlling Discrete I/O on ControlNet via a 1747-ACN15 ControlNet Adapter Using a Rack Connection
This example is organized into the following sections:
Hardware Setup
Configuring The ControlNet Network with RSNetWorx™ for
ControlNet, Revision 2.23.02 or later
Create a Ladder Logic Program

Hardware Setup

The following hardware setup is referenced throughout this example.
Computer with:
RSLogix 500 Software
RSLinx Software
RSNetWorx Software for ControlNet
1784-KTCX15 ControlNet PC Card
tap
tap
ControlNet
SLC 5/04
tap
1747-SCNR
1747-ACN15
1746-IA16
1746-OB16
1746-IV16
Publication 1747-UM003A-EN-P
Application Examples 4-3

Configuring The ControlNet Network with RSNetWorx™ for ControlNet

Start RSNetWorx for ControlNet by double clicking on its icon. The following screen appears:
At this point, you could configure your ControlNet network off-line and then download it to the network. This example will, instead, go on-line and configure the network. Therefore, click on the on-line icon or click on the Network pull-down menu and select On-line.
A Browse for Network window appears, where you must select the communication path previously configured in RSLinx for communicating with your ControlNet network. In this example, a KTC ControlNet PC card was used. Click on the KTCX15 card to select it and then click OK.
Publication 1747-UM003 A-EN-P
4-4 Application Examples
The software attempts to communicate with all possible node numbers on the network, from 1 to 99. Click on the Edits Enabled box to allow changes to be made. For this example, the on-line network screen should look like the following, where node 99 is the programming terminal.
Node 1 is the 1747-SCNR and node 3 is the 1747-ACN15. The 1747-ACN15 resides in slot 0 of its chassis, while slot 1 contains a 1746-IA16, slot 2 contains a 1746-OB16, and slot 3 contains a 1746-IV16. For this example, a single 16-bit rack connection will be configured to read/write the three discrete I/O modules.
Before creating the connection, verify the chassis configuration for the 1747-ACN15 chassis. To do this, right click on the 1747-ACN15, then choose Edit Chassis. Verify that the chassis configuration is as follows:
slot 0: 1747-ACNR15 slot 1: 1746-IA16 slot 2: 1746-OB16 slot 3: 1746-IV16
If the chassis is not already configured, manually configure it by dragging the appropriate modules from the list on the right to the proper slot on the left of the chassis configuration screen. When on-line, the software reads the module types for you. When this is complete, click Apply, then OK.
Publication 1747-UM003A-EN-P
Application Examples 4-5
Configuring a Chassis Connection
You are now ready to configure the necessary ControlNet connection to read/ write data from the SLC processor to the discrete I/O modules. Right click on the 1747-SCNR and choose Scanlist Configuration. (If you are prompted to enter the edit mode, click YES.) The following screen appears:
Publication 1747-UM003 A-EN-P
4-6 Application Examples
The 1747-SCNR and 1747-ACN15 are shown as nodes 1 and 3 respectively. Under the 1747-ACN15, the 3 I/O modules in slots 1 through 3 of the 1747-ACN15 chassis are listed. In order to establish a 16-bit rack connection to the 1747-ACN15 chassis, right click on the 1747-ACN15 and choose Insert Connection. The following window opens:
Publication 1747-UM003A-EN-P
Note that addresses in the Connection Properties screen above are already filled in. To have RSNetWorx choose the next available valid I/O or M-file addresses for all connections, click on the Auto Address Preferences button. Next, click on the box next to Enable Automatic Addressing on Insert so a check mark appears in the box. Then click OK. Auto Addressing enabled is the default.
IMPORTANT
RSNetWorx allows more than one exclusive owner rack connection type to be configured to a 1747 adapter (e.g. 8-bit exclusive owner, 16-bit exclusive owner, and 32-bit exclusive owner), however only one exclusive owner rack connection can be operational at one time. It is recommended that only one exclusive owner rack connection type be configured to the adapter to avoid contention between multiple connections.
Application Examples 4-7
IMPORTANT
If a rack connection type is changed to a smaller bit configuration e.g. 32-bit to 16-bit, or 16-bit to 8-bit, the unused bits for the new connection remains in their previously programmed states for program mode or lost communications e.g. last state, safe state, reset off.
The Connection Name, by default, is Discrete 16-Bit Exclusive Owner and this is the 16-bit rack connection you want. The first available I/O addresses are I:3.1 and O:3.1, where the 1747-SCNR is in slot 3 of the processor chassis. The first available starting I/O addresses have been placed into the Input Address and Output Address fields, because automatic addressing was previously selected in the Auto Address Preference screen. Words I:3.0 and O:3.0 contain status and control data and are not used for I/O data.
Note that the input data from the 1746-IA16 is found in the processor’s input image word I:3.3 and the output data written to the 1746-OB16 module is from the processor’s output image word O:3.2. The input data from the 1746-IV16 is in the processor’s input image word I:3.5.
NOTE
There is a 2-word offset for input data for rack connections. Therefore, for this example, the input data for the input module in slot 1 of the remote 1747-ACN15 chassis is written to I:3.3 in the SLC processor’s input image. The input module in slot 3 is written to I:3.5.
The starting input address configured in RSNetWorx for this rack connection was I:3.1, but I:3.1 and I:3.2 are used for rack slot status information. Note the resulting input size of 5 shown in the Connection Properties screen. Therefore, the actual input data begins after the 2 words of status information. I:3.4 is not used in this example because an output module resides in slot 2.
Also, note that there is no offset for the outputs in a rack connection. O:3.2 is the output image word written to the output module located in slot 2 of the 1747-ACN15 chassis. O:3.1 is also not used in this example because an input card is in slot 1.
The Status Address field must also be filled in. This field supplies Connection Status information to the processor for each unique connection. The starting bit address for this field must be an even number because two consecutive bits are used as status for each connection. The even numbered bit indicates whether the connection is open or closed. The odd numbered bit indicates whether the connection is in normal operation or Idle mode. In this example, the starting address chosen is the first available bit pair, M1:3.600/00.
Publication 1747-UM003 A-EN-P
4-8 Application Examples
You have successfully configured a rack connection to the remote chassis to communicate with the discrete I/O modules. At this point, you may also configure the state of the outputs in the remote ControlNet chassis when the controlling processor is placed into the Program mode or if communications are lost to the remote chassis. This is optional. The default is to turn all outputs off when one of the two conditions occur. To select other options, click on the Advanced tab in the Connection Properties window. The following window appears:
Publication 1747-UM003A-EN-P
By default, outputs in all slots in the remote chassis are reset if the processor is placed into the Program mode or if communications are lost for any reason. Two other choices are offered when one of the two conditions occur. They are:
Hold Last Outputs
Outputs to Safe State
Hold Last Outputs holds outputs in their last state if one of the two conditions occur. Safe State allows you to choose the exact state of each output. If Safe
State is selected, you must click on the Configuration Settings tab and enter your Safe State data for each output word in decimal. Then, if the SLC processor is
Application Examples 4-9
placed in the Program mode or if communications are lost to the ACN15 adapter, the outputs revert to the Safe State data you entered for each output word.
Click Apply, then OK to return to the ScanList Configuration window which should look like the following:
You have now successfully configured your rack connection to read/write data between the SLC processor and the remote ControlNet chassis. All that remains is to Save this configuration to the network keeper which, in this case, is the 1747-SCNR.
Click on the Save icon or choose the File pull-down menu and select Save. You are prompted to Optimize and re-write schedule for all connections. Click OK, then click YES to the subsequent warning message. Your network configuration information is then written to the network keeper and scanner devices.
The display on the front of your 1747-SCNR should show a Full Glass next to I/O. This indicates that all configured connections have been successfully downloaded to the scanner. In addition, the A and OK LEDs should be solid green and the B LED should be off, unless you are using the redundant media option, which is not being used in this example. The 1747-ACN15 should be displaying that it is active (ACTV) and its LEDs should be solid green for A and OK.
Publication 1747-UM003 A-EN-P
4-10 Application Examples

Create a Ladder Logic Program

The final step is to write a ladder program for the SLC processor, including configuring the 1747-SCNR for slot 3 of the processor’s chassis. After downloading the program to your processor, place it into the RUN mode. Your program should now be able to read data from the 1746-IA16 in word I:3.3, write to the 1746-OB16 in word O:3.2 and read data from the 1746-IV16 in word I:3.5.
Note that your ladder program should also contain an unconditional rung with an OTE instruction addressed to the SCNR scanner’s RUN/IDLE bit, O:3.0/ 10 for this example. When the SLC processor is placed into the RUN mode, this rung sets the SCNR scanner’s RUN/IDLE bit and places the scanner into the RUN mode as well. The scanner begins executing the configured connections when the RUN/IDLE bit is set.
Publication 1747-UM003A-EN-P
Application Examples 4-11

Example 2

1747-SCNR ControlNet Scanner Controlling Discrete and Analog I/O on ControlNet via a 1747-ACN15 ControlNet Adapter Using a Rack Connection
This example is organized into the following sections:
Hardware Setup
Configuring The ControlNet Network with RSNetWorx™ for
ControlNet
Create a Ladder Program

Hardware Setup

The following hardware setup is referenced throughout this example.
Computer with:
RSLogix 500 Software
RSLinx Software
RSNetWorx Software for ControlNet
1784-KTCX15 ControlNet PC Card
tap
tap
ControlNet
SLC 5/04
tap
1747-SCNR
1747-ACN15
1746-IA16
1746-OB16
1746-NIO4V
Publication 1747-UM003 A-EN-P
4-12 Application Examples

Configuring The ControlNet Network with RSNetWorx™ for ControlNet

Start RSNetWorx for ControlNet by double clicking on its icon. The following screen appears:
Publication 1747-UM003A-EN-P
At this point, you could configure your ControlNet network off-line and then download it to the network. This example, instead, goes on-line and configure the network. Therefore, click on the on-line icon or click on the Network pull-down menu and select On-line.
A Browse for Network window appears, where you must select the communication path previously configured in RSLinx for communicating with your ControlNet network. In this example, a 1784-KTCX15 ControlNet PC card was used. Click on the KTC card to select it and then click OK.
Application Examples 4-13
The software attempts to communicate with all possible node numbers on the network, from 1 to 99. Click the Edits Enabled box to allow changes to be made. For this example, the on-line network screen should look like the following, where node 99 is the programming terminal.
Node 1 is the 1747-SCNR and node 3 is the 1747-ACN15. The 1747-ACN15 resides in slot 0 of its chassis, while slot 1 contains a 1746-IA16, slot 2 contains a 1746-OB16, and slot 3 contains a 1746-NIO4V. For this example, a single 32-bit rack controller is configured to read/write the three I/ O modules.
Before creating the connection, verify the chassis configuration for the 1747-ACN15 chassis. To do this, right click on the 1747-ACN15, then choose Edit Chassis. Verify that the chassis configuration is as follows:
slot 0: 1747-ACNR15 slot 1: 1746-IA16 slot 2: 1746-OB16 slot 3: 1746-NIO4V
If the chassis is not already configured, manually configure it by dragging the appropriate modules from the list on the right to the proper slot on the left of the chassis configuration screen. When on-line, the software reads the module types for you. When this is complete, click Apply, then OK.
Publication 1747-UM003 A-EN-P
4-14 Application Examples
Configuring a Rack Connection
You are now ready to configure the necessary ControlNet connection to read/ write data from the SLC processor to the discrete I/O modules and to the 1746-NIO4V analog module. Right click on the 1747-SCNR and choose Scanlist Configuration. (If you are prompted to enter the edit mode, click YES.) The following screen appears:
Publication 1747-UM003A-EN-P
Application Examples 4-15
The 1747-SCNR and 1747-ACN15 are shown as nodes 1 and 3 respectively. Under the 1747-ACN15, the 3 I/O modules in slots 1 through 3 of the 1747-ACN15 chassis are listed. We specify a 32-bit rack connection so that the two words of analog input and two words of analog output data from the 1746-NIO4V module can be transferred via the rack connection. In order to establish a 32-bit rack connection to the 1747-ACN15 chassis, right click on the 1747-ACN15 and choose Insert Connection. The following window opens:
Note that addresses in the Connection Properties screen above are already filled in. To have RSNetWorx choose the next available valid I/O or M-file addresses for all connections, click on the Auto Address Preferences button. Next, click on the box next to Enable Automatic Addressing on Insert so a check mark appears in the box. Then click OK. Automatic Addressing enabled is the default.
Publication 1747-UM003 A-EN-P
4-16 Application Examples
IMPORTANT
RSNetWorx allows more than one exclusive owner rack connection type to be configured to a 1747 adapter (e.g. 8-bit exclusive owner, 16-bit exclusive owner, and 32-bit exclusive owner), however only one exclusive owner rack connection can be operational at one time. It is recommended that only one exclusive owner rack connection type be configured to the adapter to avoid contention between multiple connections.
IMPORTANT
If a rack connection type is changed to a smaller bit configuration e.g. 32-bit to 16-bit, or 16-bit to 8-bit, the unused bits for the new connection remains in their previously programmed states for program mode or lost communications e.g. last state, safe state, reset off.
The Connection Name, by default, is Discrete 16-Bit Exclusive Owner. Change this to Discrete 32-bit Exclusive Owner. The first available I/O addresses are I:3.1 and O:3.1, where the 1747-SCNR is in slot 3 of the processor chassis. The first available starting I/O addresses have been placed into the Input Address and Output Address fields, because automatic addressing was previously selected in the Auto Address Preference screen. Words I:3.0 and O:3.0 are used for status and control data.
Note that the input data from the 1746-IA16 is found in the processor’s input image word I:3.3 and the output data written to the 1746-OB16 module is from the processor’s output image word O:3.3. The 1746-NIO4V input data is in I:3.7 and I:3.8, and the output data is in O:3.5 and O:3.6.
Publication 1747-UM003A-EN-P
Application Examples 4-17
NOTE
There is a 2-word offset for input data for rack connections. Therefore, for this example, the input data for the input module in slot 1 of the remote 1747-ACN15 chassis is written to I:3.3 in the SLC processor’s input image.
The starting input address configured in RSNetWorx for this rack connection was I:3.1, but I:3.1 and I:3.2 are used for rack slot status information. Therefore, the actual input data begins after the 2 words of status information. I:3.4 is not used in this example because although 32 input bits are assigned to slot 1, the 1746-IA16 only uses the first 16 input bits.
I:3.5 and I:3.6 are not used in this example because an output module resides in slot 2. Also, note that there is no offset for the outputs in a rack connection. O:3.3 is the output image word written to the output module located in slot 2 of the 1747-ACN15 chassis.
The Status Address field must also be filled in. This field supplies Connection Status information to the processor for each unique connection. The starting bit address for this field must be an even number because two consecutive bits are used as status for each connection. The even numbered bit indicates whether the connection is open or closed. The odd numbered bit indicates whether the connection is in normal operation or Idle mode. In this example, the starting address chosen is the first available bit pair, M1:3.600/00.
Publication 1747-UM003 A-EN-P
4-18 Application Examples
You have successfully configured a rack connection to the remote chassis to communicate with the two discrete and one analog I/O modules. At this point you may also configure the state of the outputs in the remote ControlNet chassis when the processor is placed into the Program mode or if communications are lost to the remote chassis. This is optional. The default is to turn all outputs off when one of the two conditions occur. To select other options, click on the Advanced tab in the Connection Properties window. The following window will appear:
Publication 1747-UM003A-EN-P
By default, outputs in all slots in the remote chassis are reset if the processor is placed into the Program mode or if communications are lost for any reason. Two other choices are offered when one of the two conditions occur. They are:
Hold Last Outputs
Outputs to Safe State
Hold Last Outputs holds outputs in their last state if one of the two conditions occur. Safe State allows you to choose the exact state of each output. If Safe
State is selected, you must click on the Configuration Settings tab and enter your Safe State data for each output word in decimal. Then, if the SLC processor is
placed in the Program mode or if communications are lost to the ACN15 adapter, the outputs revert to the Safe State data you entered for each output word.
Click Apply, then OK to return to the ScanList Configuration screen.
Application Examples 4-19
Click Apply, then OK. The Connection Properties window closes and the Scanlist Configuration window appears and looks like the following:
You have now successfully configured your connection to read/write data between the SLC processor and the remote ControlNet chassis. All that remains is to Save this configuration to the network keeper which, in this case, is the 1747-SCNR.
Click on the Save icon or choose the File pull-down menu and select Save. You are prompted to Optimize and re-write schedule for all connections. Click OK, then click YES to the subsequent warning message. Your network configuration information is then written to the network keeper.
The display on the front of your 1747-SCNR should show a Full Glass next to I/O. This indicates that all configured connections have been successfully downloaded to the scanner. In addition, the A and OK LEDs should be solid green and the B LED should be off, unless you are using the redundant media option, which is not being used in this example. The 1747-ACN15 should be displaying that it is active (ACTV) and its LEDs should be solid green for A and OK.
Publication 1747-UM003 A-EN-P
4-20 Application Examples

Create a Ladder Program

The final step is to write a ladder program for the SLC processor, including configuring the 1747-SCNR for slot 3 of the processor’s chassis. After downloading the program to your processor, place it into the RUN mode. Your program should now be able to read data from the 1746-IA16 in word I:3.3 and write to the 1746-OB16 in word O:3.3. The analog input data resides in words I:3.7 and I:3.8, while the analog output data must be copied to words O:3.5 and O:3.6.
Note that your ladder program should also contain an unconditional rung with an OTE instruction addressed to the SCNR scanner’s RUN/IDLE bit, O:3.0/ 10 for this example. When the SLC processor is placed into the RUN mode, this rung sets the SCNR scanner’s RUN/IDLE bit and places the scanner into the RUN mode as well. The scanner begins executing the configured connections when the RUN/IDLE bit is set.
Publication 1747-UM003A-EN-P
Application Examples 4-21

Example 3

1747-SCNR ControlNet Scanner Controlling Discrete and Analog I/O on ControlNet via a 1747-ACN15 ControlNet Adapter Using Rack and Module Connections
This example is organized into the following sections:
Hardware Setup
Configuring The ControlNet Network with RSNetWorx™ for
ControlNet
Create a Ladder Logic Program

Hardware Setup

The following hardware setup is referenced throughout this example.
Computer with:
RSLogix 500 Software
RSLinx Software
RSNetWorx Software for ControlNet
1784-KTCX15 ControlNet PC Card
tap
tap
ControlNet
SLC 5/04
tap
1747-SCNR
1747-ACN15
1746-IA16
1746-OB16
1746-NI8
Publication 1747-UM003 A-EN-P
4-22 Application Examples

Configuring The ControlNet Network with RSNetWorx™ for ControlNet

Start RSNetWorx for ControlNet by double clicking on its icon. The following screen appears:
Publication 1747-UM003A-EN-P
At this point, you could configure your ControlNet network off-line and then download it to the network. This example, instead, goes on-line and configure the network. Therefore, click on the on-line icon or click on the Network pull-down menu and select On-line.
A Browse for Network window appears, where you must select the communication path previously configured in RSLinx for communicating with your ControlNet network. In this example, a KTC ControlNet PC card was used. Click on the KTC card to select it and then click OK.
Application Examples 4-23
The software attempts to communicate with all possible node numbers on the network, from 1 to 99. Click on the Edits Enabled box allow changes to be made. For this example, the on-line network screen should look like the following, where node 99 is the programming terminal.
Node 1 is the 1747-SCNR and node 3 is the 1747-ACN15. The 1747-ACN15 resides in slot 0 of its chassis, while slot 1 contains a 1746-IA16, slot 2 contains a 1746-OB16, and slot 3 contains a 1746-NI8. For this example, 2 separate ControlNet connections are configured. The first is a Discrete 16 Bit Exclusive Owner rack connection for the 2 discrete I/O modules and the second is an Module Connection to the 1746-NI8 8-input analog module.
Before creating these necessary connections, verify the chassis configuration for the 1747-ACN15 chassis. To do this, right click on the 1747-ACN15, then choose Edit Chassis. Verify that the chassis configuration is as follows:
slot 0: 1747-ACNR15 slot 1: 1746-IA16 slot 2: 1746-OB16 slot 3: 1746-NI8
If the chassis is not already configured, manually configure it by dragging the appropriate modules from the list on the right to the proper slot on the left of the chassis configuration screen. When on-line, the software reads the module types for you. When this is complete, click Apply, then OK.
Publication 1747-UM003 A-EN-P
4-24 Application Examples
Configuring a Rack Connection
You are now ready to configure the necessary ControlNet connections to read/ write data from the SLC processor to the discrete I/O modules and to the analog input module. Right click on the 1747-SCNR and choose Scanlist Configuration. (If you are prompted to enter the edit mode, click YES.) The following screen appears:
Publication 1747-UM003A-EN-P
Application Examples 4-25
As you can see, the 1747-SCNR and 1747-ACN15 are shown as nodes 1 and 3 respectively. Under the 1747-ACN15, the 3 I/O modules in slots 1 through 3 of the 1747-ACN15 chassis are listed. In order to establish a 16-bit rack connection to the 1747-ACN15 chassis, right click on the 1747-ACN15 and choose ControlNet Configuration. The following window opens:
Note that addresses in the Connection Properties screen above are already filled in. To have RSNetWorx choose the next available valid I/O or M-file addresses for all connections, click on the Auto Address Preferences button. Next, click on the box next to Enable Automatic Addressing on Insert so a check mark appears in the box. Then click OK. Automatic Addressing enabled is the default.
IMPORTANT
RSNetWorx allows more than one exclusive owner rack connection type to be configured to a 1747 adapter (e.g. 8-bit exclusive owner, 16-bit exclusive owner, and 32-bit exclusive owner), however only one exclusive owner rack connection can be operational at one time. It is recommended that only one exclusive owner rack connection type be configured to the adapter to avoid contention between multiple connections.
Publication 1747-UM003 A-EN-P
4-26 Application Examples
IMPORTANT
If a rack connection type is changed to a smaller bit configuration e.g. 32-bit to 16-bit, or 16-bit to 8-bit, the unused bits for the new connection remains in their previously programmed states for program mode or lost communications e.g. last state, safe state, reset off.
The Connection Name by default is Discrete 16-Bit Exclusive Owner and this is the 16-bit rack connection you want. The first available I/O addresses are I:3.1 and O:3.1, where the 1747-SCNR is in slot 3 of the processor chassis. The first available starting I/O addresses have been placed into the Input Address and Output Address fields, because automatic addressing was previously selected in the Auto Address Preference screen. Words I:3.0 and O:3.0 are used for status and control data.
Note that the input data from the 1746-IA16 is found in the processor’s input image word I:3.3 and the output data written to the 1746-OB16 module is from the processor’s output image word O:3.2.
NOTE
There is a 2-word offset for input data for rack connections. Therefore, for this example, the input data for the input module in slot 1 of the remote 1747-ACN15 chassis is written to I:3.3 in the SLC processor’s input image.
The starting input address configured in RSNetWorx for this rack connection was I:3.1, but I:3.1 and I:3.2 are used for rack slot st atus information. Therefore, the actual input data begins after the 2 words of status information. I:3.4 and I:3.5 are not used in this example because an output module resides in slot 2 and an analog module resides in slot 3.
Also, note that there is no offset for the outputs in a rack connection. O:3.2 is the output image word written to the output module located in slot 2 of the 1747-ACN15 chassis. O:3.1 is not used because an input module resides in slot 1. In addition, no offset applies to module connections at all.
The Status Address field must also be filled in. This field supplies Connection Status information to the processor for each unique connection. The starting
bit address for this field must be an even number because two consecutive bits are used as status for each connection. The even numbered bit indicates whether the connection is open or closed. The odd numbered bit indicates whether the connection is in normal operation or Idle mode. In this example, the starting address chosen is the first available bit pair, M1:3.600/00.
Publication 1747-UM003A-EN-P
Application Examples 4-27
You have successfully configured a rack connection to the remote chassis to communicate with the two discrete I/O modules. At this point you may also configure the state of the outputs in the remote ControlNet chassis when the processor is placed into the Program Mode or if communications are lost to the remote chassis. This is optional. The default is to turn all outputs off when one of the two conditions occur. To select other options, click on the Advanced tab in the Connection Properties window. The following window appears:
By default, outputs in all slots in the remote chassis are reset if the processor is placed into the Program mode or if communications are lost for any reason. Two other choices are offered when one of the two conditions occur. They are:
Hold Last Outputs
Outputs to Safe State
Hold Last Output holds outputs in their last state if one of the two conditions occur. Safe State allows you to choose the exact state of each output. If Safe
State is selected, you must click on the Configuration Settings tab and enter you Safe State data for each output word in decimal. Then, if the SLC processor is
placed in the Program mode or if communications are lost to the ACN adapter, the outputs revert to the Safe State data you entered for each output word.
Publication 1747-UM003 A-EN-P
4-28 Application Examples
Configuring a Module Connection
Next, you need to configure a module connection for the 1746-NI8 8-input analog module. If the previous window is still open, click Apply, then OK to accept the rack connection.
Right click on the 1746-NI8 module in the Scanlist Configuration window and select Insert Connection. A Connection Properties window again appears. Choose Exclusive Owner for the Connection Name.
In this case choose M-file addresses for the 8-input analog module. The NI8 module must use Class 3 operation in a 1747-ACN15 chassis. It requires 12 output words and 16 input words. M-file words are used for this in the 1747-SCNR. M0:3.3 through M0:3.14 are used for the 12 output words to configure the module. M1:3.3 through M1:3.18 are used for the input information, including actual analog data and analog channel status. Refer to your 1746-NI8 User’s Manual for additional information on this module.
M-file words M1:3.0 through M1:3.2 and M0:3.0 through M0:3.2 are reserved. The next available Status Address is M1:3.600/02 since bits 0 and 1 are used by the 1747-SCNR for the rack connection. The Connection Properties window for the module connection should look like the following.
Publication 1747-UM003A-EN-P
4-29
Click Apply, then OK. The Connection Properties window closes and the Scanlist Configuration window appears and looks like the following:
You have now successfully confi gured your two connections to read/write data between the SLC processor and the remote ControlNet chassis. All that remains is to Save this configuration to the network keeper which, in this case, is the 1747-SCNR.
Click on the Save icon or choose the File pull-down menu and select Save. You are prompted to Optimize and re-write schedule for all connections. Click OK, then click YES to the subsequent warning message. Your net work configuration information is then written to the network keeper.
The display on the front of your 1747-SCNR should show a Full Glass next to I/O. This indicates that all configured connections were successfully downloaded to the scanner. In addition, t he A and OK LEDs should be solid green and the B LED shou ld be of f, unless you are using the redundant media option, which is not being used in this example. The 1747-ACN15 should be displaying that it is active (ACTV) and its LEDs should be solid green for A and OK and the B LED should be off.
Publication 1747-UM003 A-EN-P
4-30

Create a Ladder Logic Program

The final step is to write a ladder program for the SLC processor, including configuring the 1747-SCNR for slot 3 of the processor’s chassis. After downloading the program to your processor, place it into the RUN mode. Your program should now be able to read data from the 1746-IA16 in word I:3.3 and write to the 1746-OB16 in word O:3.2. The analog input data and channel status will reside in words M1:3.3 through M1:3.18, while the analog module configuration data must be copied to words M0:3.3 through M0:3.14.
Note that your ladder program should also contain an unconditional rung with an OTE instruction addressed to the SCNR scanner’s RUN/IDLE bit, O:3.0/10 for this example. When the SLC processor is placed into the RUN mode, this rung sets the SCNR scanner’s RUN/IDLE bit and places the scanner into the RUN mode as well. The scanner begins executing the configured connections when the RUN/IDLE bit is set.
Publication 1747-UM003A-EN-P
4-31

Example 4

1747-SCNR ControlNet Scanner Controlling Discrete I/O and Serial Data with a 1746-BAS Module on ControlNet via a 1747-ACN15 ControlNet Adapter Using Rack and Module Connections
This example is organized into the following sections:
Hardware Setup
Configuring The ControlNet Net work with RSNetWorx™ for ControlNet
Create Ladder Logic and Basic Module Programs

Hardware Setup

The following hardware setup is referenced throughout this example.
Computer with:
RSLogix 500 Software
RSLinx Software
RSNetWorx Software for ControlNet
1784-KTCX15 ControlNet PC Card
tap
tap
ControlNet
SLC 5/04
tap
1747-SCNR
1747-ACN15
1746-IA16
1746-OB16
1746-BAS, Series B
Publication 1747-UM003 A-EN-P
4-32

Configuring The ControlNet Network with RSNetWorx™ for ControlNet

Start RSNetWorx for ControlNet by double clicking on its icon. The following screen appears:
Publication 1747-UM003A-EN-P
At this point, you could configure your ControlNet network off-line and then download it to the network. This example, instead, goes on-line and configure the network. Therefore, click on the on-line icon or click on the Network pull-down menu and select On-line.
A Browse for Network window appears, where you must select the communication path previously configured in RSLinx for communicating with your ControlNet network. In this example, a KTCX ControlNet PC card was used. Click on the KTCX15 card to select it and then click OK.
4-33
The software attempts to communicate with all possible node numbers on the network, from 1 to 99. Click on the Edits Enabled box to allow changes to be made. For this example, the on-line network screen should look like the following, where node 99 is the programming terminal.
Node 1 is the 1747-SCNR and node 3 is the 1747-ACN15. The 1747-ACN15 resides in slot 0 of its chassis, while slot 1 contains a 1746-IA16, slot 2 contains a 1746-OB16, and slot 3 contains a Series B 1746-BAS. For this example, 2 separate ControlNet connections are configured. The first is a Discrete 16 Bit Exclusive Owner rack connection for the 2 discrete I/O modules and the second is an Exclusive Owner - Advanced module connection to the 1746-BAS module.
Before creating these necessary connections, verify the chassis configuration for the 1747-ACN15 chassis. To do this, right click on the 1747-ACN15, then choose Edit Chassis. Verify that the chassis configuration is as follows:
slot 0: 1747-ACNR15 slot 1: 1746-IA16 slot 2: 1746-OB16 slot 3: 1746-BAS
If the chassis is not already configured, manually configure it by dragging the appropriate modules from the list on the right to the proper slot on the left of the chassis configuration screen. When on-line, the software reads the module types for you. When this is complete, click Apply, then OK.
Publication 1747-UM003 A-EN-P
4-34
Configuring a Rack Connection
You are now ready to configure the necessary ControlNet connections to read/ write data from the SLC processor to the discrete I/O modules and to the Basic module. Right click on the 1747-SCNR and choose Scanlist Configuration. (If you are prompted to enter the edit mode, click YES.) The following screen appears:
As you can see, the 1747-SCNR and 1747-ACN15 are shown as nodes 1 and 3 respectively. Under the 1747-ACN15, the 3 I/O modules in slots 1 through 3 of the 1747-ACN15 chassis are listed. In order to establish a 16-bit rack connection to the 1747-ACN15 chassis, right click on the 1747-ACN15 and choose Insert Connection. The following window opens:
Publication 1747-UM003A-EN-P
4-35
NOTE
There is a 2-word offset for input data for rack connections. Therefore, for this example, the input data for the input module in slot 1 of the remote 1747-ACN15 chassis is written to I:3.3 in the SLC processor’s input image.
The starting input address configured in RSNetWorx for this rack connection was I:3.1, but I:3.1 and I:3.2 are used for status information. Therefore, the actual input data begins after the 2 words of status information. I:3.4 is not used in this example because an output module resides in slot 2.
Also, note that there is no offset for the outputs in a rack connection. O:3.2 is the output image word written to the output module located in slot 2 of the 1747-ACN15 chassis. O:3.1 is not used because an input module resides in slot 1. In addition, no offset applies to module connections at all.
Publication 1747-UM003 A-EN-P
4-36
IMPORTANT
RSNetWorx allows more than one exclusive owner rack connection type to be configured to a 1747 adapter (e.g. 8-bit exclusive owner, 16-bit exclusive owner, and 32-bit exclusive owner), however only one exclusive owner rack connection can be operational at one time. It is recommended that only one exclusive owner rack connection type be configured to the adapter to avoid contention between multiple connections.
IMPORTANT
If a rack connection type is changed to a smaller bit configuration e.g. 32-bit to 16-bit, or 16-bit to 8-bit, the unused bits for the new connection remains in their previously programmed st ates for program mode or lost communications e.g. last state, safe state, reset off.
You have successfully configured a rack connection to the remote chassis to communicate with the two discrete I/O modules. At this point you may also configure the state of the outputs in the remote ControlNet chassis when the processor is placed into the Program Mode or if communications are lost to the remote chassis. This is optional. The default is to turn all outputs off when one of the two conditions occur. To select other options, click on the Advanced tab in the Connection Properties window. The following window appears:
Publication 1747-UM003A-EN-P
4-37
By default, outputs in all slots in the remote chassis are reset if the processor is placed into the Pr ogram mode or if communication s are lost for any reason. Two other choices are offe red when one of the two conditions occur. They are:
Hold Last Outputs
Outputs to Safe State
Hold Last Outputs holds outputs in their last state if one of the two conditions occur. Safe State allows you to choose the exact state of each output. If Safe
State is selected, you must click on the Configuration Settings tab and enter you Safe State data for each output word in decimal. Then, if the SLC processor is
placed in the Program mode or if communications are lost to the ACN adapter, the outputs revert to the Safe State data you entered for each output word.
Publication 1747-UM003 A-EN-P
4-38
Configuring a Module Connection
Next, you need to configure a module connection for the 1746-BAS module. If the previous window is still open, click Apply, then OK to accept the rack connection.
Right click on the 1746-BAS module in the Scanlist Configuration window and select Insert Connection. A Connection Properties window again appears. Choose Exclusive Owner-Advanced for the Connection Name.
In this case, you must choose M-file addresses for this type of connection. The series B Basic module communicates via 8 I/O words and 64 M1 and 64 M0 file words. These Basic module M-file words are independent of the M-file words used to transfer up to 72 words to and from the Basic module. Those 72 M0 and 72 M1 file words reside in the 1747-SCNR and are used to store the data sent to the 1747-ACN15 from the SLC-5/04 processor and to store the data received from the 1747-ACN15 for the SLC-5/04 processor.
The M0 file words in the 1747-SCNR, which are assigned in the Connection Properties screen, are M0:3.3 through M0:3.74. These are the 72 words sent from the SLC-5/04 processor to the 1747-SCNR. Words M1:3.3 through M1:3.74 are the 72 words received from the 1747-ACN15. M-file words M1:3.0 through M1:3.2 and M0:3.0 through M0:3.2 are reserved (refer to the 1747-SCNR User Manual for details). The next available Status Address is M1:3.600/02, since bits 0 and 1 are used for the rack connection. The Connection Properties window for the module connection should look like the following.
Publication 1747-UM003A-EN-P
4-39
You must now configure this connection for the 8 I/O words and the 64 M0/M1 file words. Click on the “Advanced” tab in the Connection Properties window. The following screen appears:
Publication 1747-UM003 A-EN-P
4-40
By default, the Chunk 1 Output File is the output image file for the Basic module and the Chunk 1 Input File is the input image file for the Basic module. You must then assign the Chunk 2 Output File as the Basic module’s M0 file and the Chunk 2 Input File as the Basic module’s M1 file.
The size for each of these files is 64 words. The total number of words transferred bi-directionally between the SLC processor and the Basic module will be 72. The first 8 will be the Basic module’s I/O image and the last 64 words will be the Basic module’s M-file words. This order is determined by the Chunk numbers. The Advanced screen should then look like the following:
Publication 1747-UM003A-EN-P
4-41
Safe State data is available under the Configuration Settings tab. For 1746-BAS module connections, it is recommended that outputs be reset to 0 when the SLC processor is placed into the PROGRAM mode or if communications are lost to the 1747-ACN15. The Hold Last State option is not available for the 1746-BAS.
Click Apply, then OK. The Connection Properties window closes and the Scanlist Configuration window appears and looks like the following:
Publication 1747-UM003 A-EN-P
4-42
You have now successfully configured your two connections to read/write data between the SLC processor and the remote ControlNet chassis. All that remains is to Save this configuration to the network keeper which, in this case, is the 1747-SCNR.
Click on the Save icon or choose the File pull-down menu and select Save. You are prompted to Optimize and re-write schedule for all connections. Click OK, then click YES to the subsequent warning message. Your network configuration information is then written to the network keeper.
The display on the front of your 1747-SCNR should show a Full Glass next to I/O. This indicates that all configured connections were successfully downloaded to the scanner. In addition, the A and OK LEDs should be solid green and the B LED should be off, unless you are using the redundant media option, which is not being used in this example. The 1747-ACN15 should be displaying that it is active (ACTV) and its LEDs should be solid green for A and OK.
Publication 1747-UM003A-EN-P
4-43

Create Ladder Logic and Basic Module Programs

The final step is to write a ladder program for the SLC processor and a BASIC program for the Basic module. After downloading the program to your processor and to your basic module, place the processor into the RUN mode and run your BASIC program as well. Your programs should now be able to read data from the 1746-IA16 in word I:3.3 and write to the 1746-OB16 in word O:3.2.
The attached BASIC program contains a CALL 23 interrupt CALL for PRT1 and a CALL 22 interrupt CALL for PRT2. The CALL 23 sends data out PRT1 when data is received from the SLC processor and CALL 22 transfers data sent in PRT2 to the SLC. Remember, the first 8 words beginning with M1:3.3 and M0:3.3 are from the Basic module’s Input and Output image. The following 64 words are from the Basic module’s M1 and M0 files. The handshaking required between the SLC processor and the Basic module to transfer data, is shown in the ladder logic program to follow.
Please refer to the 1746-BAS User Manual for a complete description of CALL 22 and 23, as well as the required handshaking. The only difference in the handshake logic when using these Basic module CALLs is that the I/O image words used for the handshaking are stored in the SCNR’s M-files, so they appear as M-file addresses in the ladder logic instead of I/O addresses.
Connect an RS-232 cable between PRT1 and PRT2 on the Basic module. A 1747-CP3 cable works for this purpose. When up to 64 words of data are placed into the SLC processor’s data table beginning at N12:0, it is sent to the 1747-SCNR, then to the Basic module via ControlNet and the 1747-ACN15 and is ultimately sent out PRT1 of the BAS module. If you used a cable to loop the data back in PRT2, this data is sent to the 1747-SCNR via ControlNet and ultimately appears in the SLC processor’s data table beginning with address N13:0.
Note that your ladder program should also contain an unconditional rung with an OTE instruction addressed to the 1747-SCNR scanner’s RUN/IDLE bit, O:3.0/10 for this example. When the SLC processor is placed into the RUN mode, this rung sets the 1747-SCNR scanner’s RUN/IDLE bit and places the scanner into the RUN mode as well. The scanner begins executing the configured connections when the RUN/IDLE bit is set.
Publication 1747-UM003 A-EN-P
4-44
When the Basic module is placed into the RUN mode, any data placed into the SLC processor’s data table beginning with N12:0 is sent to the 1747-SCNR, which sends it to the 1747-ACN15 via ControlNet and then to the Basic module. The Basic module sends the data out PRT1 and this data is looped right back in the Basic module’s PRT2. The module sends the data to the 1747-ACN15, which sends it to the SCNR via ControlNet. The SLC processor then retrieves this data and places it into its data table beginning at N13:0.
Basic Module BASIC Program Listing
10 REM Test Program for CNET
20 MODE(PRT1,9600,N,8,1,N,R) 30 MODE(PRT2,9600,N,8,1,N,R) 40 PUSH 2 50 CALL 37 60 PUSH 2 70 CALL 96 80 REM CALL 23 for PRT1
90 PUSH 2 100 REM SEND DATA OUT PRT1 110 PUSH 1 120 REM GET DATA FROM M0 FILE 130 PUSH 0 140 REM NO OFFSET 150 PUSH 0 160 REM NO STRING USED 170 PUSH 1 180 REM ENABLE BYTE SWAPPING 190 CALL 23 200 POP S1 210 REM STATUS OF CALL 23 SETUP 220 IF (S1<>0) THEN P. "UNSUCCESSFUL CALL 23 SETUP" 230 REM CALL 22 FOR PRT2 240 PUSH 2 250 REM GET DATA FROM PRT2 260 PUSH 126 270 REM MAXIMUM OF 126 CHARACTERS PER TRANSFER 280 PUSH 13 290 REM CR TERMINATION CHARACTER 300 PUSH 1 310 REM SEND DATA TO M1 FILE 320 PUSH 0 330 REM NO OFFSET 340 PUSH O 350 REM NO STRING 360 PUSH 1 370 REM ENABLE BYTE SWAPPING 380 CALL 22 390 POP S2 400 REM CALL 22 SETUP STATUS 410 IF (S2<>0) THEN P. "UNSUCCESSFUL CALL 22 SETUP" 420 GOTO 420
Publication 1747-UM003A-EN-P
SLC Processor Ladder Program
This rung gives the next rung a false-to-true transition every 1 second.
4-45
0000
0001
0002
0003
T4:1
TON
Timer On Delay
DN
Timer T4:1 Time Base 0.01 Preset 100< Accum 86 <
This rung copies up to 64 words (beginning with N12:0) to the SCNR for transfer to the Basic module on ControlNet.
T4:1
Copy File
DN
Source #N12:0 Dest #M0:3.11 Length 64
This rung completes the handshaking between the SLC processor and, ultimately, the Basic module to accomplish the CALL 23.
CALL 23 Input Handshake Bit
M1:3.3
6
This rung copies up to 64 words of data received from the Basic module when the handshake bit, M1:3.3/9, is set. When data is received by the Basic module in PRT2, the CALL 22 transfers it to the SCNR and, ultimately, to the SLC processor.
CALL 22 Input Handshake Bit
M1:3.3
Copy File
9
Source #M1:3.11 Dest #N13:0 Length 64
EN
DN
COP
CALL 23 Output Handshake Bit
M0:3.3
L 6
CALL 23 Output Handshake Bit
M0:3.3
U
6
COP
0004
0005
CALL 22 Output Handshake Bit
M0:3.3
9
1747-SCNR RUN/IDLE Bit
O:3
10
1747-SCNR
END
Publication 1747-UM003 A-EN-P
4-46

Example 5

1747-SCNR ControlNet Scanner Controlling Discrete I/O and Specialty Modules Requiring M0 File Configuration on ControlNet via a 1747-ACN15 ControlNet Adapter Using Rack and Module Connections
This example is organized into the following sections:
Hardware Setup
Configuring The ControlNet Network with RSNetworx for ControlNet
Create Ladder Logic

Hardware Setup

The following hardware setup is referenced throughout this example.
Computer with:
RSLogix 500 Software
RSLinx Software
RSNetWorx Software for ControlNet
1784-KTCX15 ControlNet PC Card
tap
tap
ControlNet
SLC 5/04
tap
1747-SCNR
1747-ACN15
1746-IA16
1746-OB16
1746-HSCE
Publication 1747-UM003A-EN-P
4-47

Configuring The ControlNet Network with RSNetWorx for ControlNet

Start RSNetWorx for ControlNet by double clicking on its icon. The following screen should appear:
At this point, you could configure your ControlNet network off-line and then download it to the network. This example will, instead, go on-line and configure the network. Therefore, click on the on-line icon or click on the Network pull-down menu and select On-line.
A Browse for Network window appears, where you must select the communication path previously configured in RSLinx for communicating with your ControlNet network. In this example, a KTC ControlNet PC card was used. Click on the KTC card to select it and then click OK.
Publication 1747-UM003 A-EN-P
4-48
The software attempts to communicate with all possible node numbers on the network, from 1 to 99. Click on the Edits Enabled box allow changes to be made. For this example, the on-line network screen should look like the following, where node 99 is the programming terminal.
Node 1 is the 1747-SCNR and node 3 is the 1747-ACN15. The 1747-ACN15 resides in slot 0 of its chassis, while slot 1 contains a 1746-IA16, slot 2 contains a 1746-OB16, and slot 3 contains a 1746-HSCE. For this example, 2 separate ControlNet connections are configured. The first is a Discrete 16 Bit Exclusive Owner rack connection for the 2 discrete I/O module s and the second is an Exclusive Owner Advanced (module connection) to the 1746-HSCE high speed counter module.
Before creating these necessary connections, verify the chassis configuration for the 1747-ACN15 chassis. To do this, right click on the 1747-ACN15, then choose Edit Chassis. Verify that the chassis configuration is as follows:
slot 0: 1747-ACNR15 slot 1: 1746-IA16 slot 2: 1746-OB16 slot 3: 1746-HSCE
If the chassis is not already configured, manually configure it by dragging the appropriate modules from the list on the right t o the proper slot on the left of the chassis configur ation screen. When on-line, the software reads the modul e types for you. When this is complete, click Apply, then OK.
Publication 1747-UM003A-EN-P
4-49
Configuring a Rack Connection
You are now ready to configure the necessary ControlNet connections to read/write data from the SLC processor to the discrete I/O modules and to the high speed counter module. Right click on the 1747-SCNR and choose Scanlist Configuration. (If you are prompted to enter the edit mode, click YES.) The following screen appears:
Publication 1747-UM003 A-EN-P
4-50
As you can see, the 1747-SCNR and 1747-ACN15 are shown as nodes 1 and 3 respectively. Under the 1747-ACN15, the 3 I/O modules in slots 1 through 3 of the 1747-ACN15 chassis are listed. In order to establish a 16-bit rack connection to the 1747-ACN15 chassis, right click on the 1747-ACN15 and choose ControlNet Configuration. The following window opens:
Publication 1747-UM003A-EN-P
Note that addresses in the Connection Properties screen above are already filled in. To have RSNETWORX choose the next available valid I/O or M-file addresses for all connections, click on the Auto Address Preferences button. Next, click on the box next to Enable Automatic Addressing on Insert so a check mark appears in the box. Then click OK. Automatic Addressing enabled is the default.
IMPORTANT
RSNetWorx allows more than one exclusive owner rack connection type to be configured to a 1747 adapter (e.g. 8-bit exclusive owner, 16-bit exclusive owner, and 32-bit exclusive owner), however only one exclusive owner rack connection can be operational at one time. It is recommended that only one exclusive owner rack connection type be configured to the adapter to avoid contention between multiple connections.
4-51
IMPORTANT
If a rack connection type is changed to a smaller bit configuration e.g. 32-bit to 16-bit, or 16-bit to 8-bit, the unused bits for the new connection remains in their previously programmed st ates for program mode or lost communications e.g. last state, safe state, reset off.
The Connection Name by default is Discrete 16-Bit Exclusive Owner and this is the 16-bit rack connection you want. The first available I/O addresses are I:3.1 and O:3.1, where the 1747-SCNR is in slot 3 of the processor chassis. The first available starting I/O addresses have been placed into the Input Address and Output Address fields, because automatic addressing was previously selected in the Auto Address Preference screen. Wo rd s I:3.0 and O:3.0 are used for status and control data.
Note that the input data from the 1746-IA1 6 is found in the proces sor’s input image word I:3.3 and the output data written to the 1746-OB16 module is from the processor’s output image word O:3.2.
NOTE
There is a 2-word offset for input data for rack connections. Therefore, for this example, the input data for the input module in slot 1 of the remote 1747-ACN15 chassis is written to I:3.3 in the SLC processor’s input image.
The starting input address configured in RSNetWorx for this rack connection was I:3.1, but I:3.1 and I:3.2 are used for rack slot st atus information. There fore, the actual input data begins after the 2 words of status information. I:3.4 and I:3.5 are not used in this example because an output module resides in slot 2 and an analog module resides in slot 3.
Also, note that there is no offset for the outputs in a rack connection. O:3.2 is the output image word written to the output module located in slot 2 of the 1747-ACN15 chassis. O:3.1 is not used because an input module resides in slot 1. In addition, no offset applies to module connections at all.
The Status Addr ess field must also be filled in. This field supplies Connection Status information to the processor for each unique connection. The starting bit address for this field must be an even number because two consecutive bits are used as status for each connection. The even numbered bit indicates whether the connectio n is open or closed. The odd numbere d bit indicates whether the connection is in normal operation or Idle mode. In this example, the starting address chosen is the first available bit pair, M1:3.600/00.
Publication 1747-UM003 A-EN-P
4-52
You have successfully configured a rack connection to the remote chassis to communicate with the two discrete I/O modules. At this point you may also configure the state of the o utputs in the remote Control Net chassis when the processor is placed into the Program Mode or if communications are lost to the remote chassis. This is optional. The default is to turn all outputs off when one of the two conditions occur. To select other options, click on the Advanced tab in the Connection Properties window. The following window appears:
Publication 1747-UM003A-EN-P
By default, outputs in all slots in the remote chassis are reset if the processor is placed into the Pr ogram mode or if communications are lost for any reason. Two other choices are offe red when one of the two conditions occur. They are:
Hold Last Outputs
Outputs to Safe State
Hold Las t Outp uts holds outputs in their last state if one of the two condit ions occur. Safe State allow s you to choose the exact state of each output. If Safe
State is selected, you must click on the Configuration Settings tab and enter you Safe State data for each output word in decimal. Then, if the SLC processor is
placed in the Pr ogram mode or if communications are lost to the ACN adapter, the outputs revert to the Safe State data you entered for each output word.
4-53
Configuring a Module Connection
Next, you need to configure a module connection for the 1746-HSCE high speed counter module. If the previous window is still open, click Apply, then OK to accept the rack connection.
Right click on the 1746-HSCE module in the Scanlist Configuration window and select Insert Connection. A Connection Properties window again appears. Choose Exclusive Owner Advanced for the Connection Name.
In this case choose M-file addresses for the high speed counter module. It requires 1 output word and 8 input words. M-file words are used for this in the 1747-SCNR. M0:3.3 is used for the output word. M1:3.3 through M1:3.10 are used for the input information. Refer to your 1746-HSCE User’s Manual for additional information on this module.
M-file words M1:3.0 through M1:3.2 and M0:3.0 through M0:3.2 are reserved (refer to the 1747-SCNR User Manual for details). The next available Status
Address is M1:3.600/02 since bits 0 and 1 are used for the rack connection. The Connection Properties window for the module connection should look like the
following.
Publication 1747-UM003 A-EN-P
4-54
Since the 1746-HSCE module uses 42 M0 file words for configuration, the user must enter the configuration values under the Configurati on Setting tab so that the 1747-SCNR scanner can write the configuration values each time a module configuration i s made to the HSCE module. Below are the example configuration values for set ting up the 1746-HSCE module in basic count- only mode. See your 1746-HSCE User Manual for more information on configuring the module.
Publication 1747-UM003A-EN-P
4-55
Publication 1747-UM003 A-EN-P
4-56
Click Apply, then OK. The Connection Properties window closes and the Scanlist Configuration window appears and looks like the following:
You have now successfully confi gured your two connections to read/write data between the SLC processor and the remote ControlNet chassis. All that remains is to Save this configuration to the network keeper which, in this case, is the 1747-SCNR.
Click on the Save icon or choose the File pull-down menu and select Save. You are prompted to Optimize and re-write schedule for all connections. Click OK, then click YES to the subs equent warning message. Your network configuration information is then written to the network keeper.
The display on the front of your 1747-SCNR should show a Full Glass next to I/O. This indicates that all configured connections were successfully downloaded to the scanner. In addition, the A an d OK LEDs should be solid green and the B LED should be of f, unless you are using the redundant media option, which is not being used in this example. The 1747-ACN15 should be displaying that it is active (ACTV) and its LEDs should be solid green for A and OK.
Publication 1747-UM003A-EN-P
4-57

Create a Ladder Logic Program

The final step is to write a ladder program for the SLC processor, including configuring the 1747-SCNR for slot 3 of the processor’s chassis. After downloading the program to your processor, place it into the RUN mode. Your program should now be able to read data from the 1746-IA16 in word I:3.3 and write to the 1746-OB16 in word O:3.2. The HSCE input data will reside in words M1:3.3 through M1:3.18, while the HSCE module output data must be copied to word M0:3.3.
Note that your ladder program should also contain an unconditional rung with an OTE instruction addressed to the SCNR scanner’s RUN/IDLE bit, O:3.0/10 for this example. When the SLC processor is placed into the RUN mode, this rung sets the SCNR scanner’s RUN/IDLE bit and places the scanner into the RUN mode as well. The scanner begins executing the configured connections when the RUN/IDLE bit is set.
Publication 1747-UM003 A-EN-P
4-58
Publication 1747-UM003A-EN-P
Troubleshooting
Chapter
5

Chapter Objectives

Troubleshooting With the Status Indicators and Status Display

In this chapter, you will learn how to use the indicators on the module frontplate for troubleshooting the module. This includes:
troubleshooting with the status indicators and status display, including:
health indicators and display mnemonics
ControlNet status indicators
The module has indicators on the front plate, as shown below. These indicators consist of:
health indicators
status indicators
display of status and address
Use these indicators for troubleshooting the module.
ADDRESS/STATUS
OK OK
ADDRESS/STATUS
BAA
Status Display and Net Address
Health Indicators and ControlNet Status Indicators
B
A
1747-ACN
The following tables describe problems that may occur, probable causes, and recommended courses of action.
1 Publication 1747-UM003 A-EN-P
A
1747-ACNR
5-2 Troubleshooting

Health Indicators and Display Mnemonics

OK LED Display Description Probable Cause Recommended Action
Off None Module is not communicating. Power supply fault. Check power supply, and seat
adapter firmly in chassis.
None Module is not communicating. Defective adapter. Contact Allen-Bradley service.
POST Adapter is running Power On Self
Te s t.
None None
Amber 0000
through 9999
A/A Adapter is displaying Series and
INIT Adapter is loading and
Solid Red FATL
Number Number
Flashing Red
Flashing Green
A#00 ERR Module is not communicating. The node address switches are
DUP NODE Module is not communicating. The adapter has detected a
IDLE
NET ERR Module is not communicating. The adapter has detected a cable
Adapter is running Power On Self Te s t.
Revision level.
initializing operating system.
Module is not communicating. The Adapter has either failed a
None None
None None
None Adapter requires ControlNet
hardware test, or gone into a state from which it cannot recover. The numbers following the FATL describe the problem in detail.
set to 00 which is not valid.
duplicated node address on the network.
fault and is attempting to recover. The adapter is sending the three “NET ERR” packets.
configuration.
Document the numbers. Power cycle the adapter. Contact Allen-Bradley service.
Power the adapter off, remove the adapter from the chassis, change the node address switch to something other than 00, replace the adapter in the chassis, and apply power.
Correct the duplicate node address problem.
None, check cable if problem persists.
Solid Green ACTV A#XX Module is working properly. None None
BOOT A#XX
CODE UPDT
Publication 1747-UM003A-EN-P
Module is on network, but not supporting any connections.
Firmware update mode. Adapter firmware is being
The main code in the module has failed, or the main code is being updated.
updated via ControlFlash update utility.
Update the main code with the latest Series and Revision code.
None
Troubleshooting 5-3

ControlNet Status Indicators

The following table explains module status when indicators are:
steady - indicator is on continuously in the defined state.
alternating - the two indicators alternate between the two defined states at
the same time (applies to both indicators viewed together). The two indicators are always in opposite states, out of phase.
flashing - the indicator alternates between the two defined states (applies to
each indicator viewed independent of the other). If both indicators are flashing, they must flash together, in phase.
BA
Cause Action
Off No power None or power up
Steady red Faulted unit Cycle power
If fault persists, contact Allen-Bradley representative or distributor.
Alternating red/ green
Alternating red/ off
Off Channel disabled Program network for redundant media, if required
Self-test None
Incorrect node configuration
Check network address and other ControlNet configuration parameters
Steady green Normal operation None
Flashing green/ off
Flashing red/off Media fault Check media for broken cables, loose connectors,
Flashing red/ green
Temporary errors None; unit will self-correct
Listen only Cycle power
missing terminators, etc.
No other nodes present on network
Incorrect network configuration
Add other nodes to the network
Cycle power or reset unit If fault persists, contact Allen-Bradley representative or distributor.
Publication 1747-UM003 A-EN-P
5-4 Troubleshooting
Publication 1747-UM003A-EN-P
Specifications
Description Specification
Module Location 1746 I/O chassis, leftmost slot
Appendix
A
Interconnect Cable Quad shield RG-6 coaxial cable - Refer to the
System Manual,
Power Dissipation 5 Watts
Thermal Dissipation 17.06 BTU/hr
Backplane Current 0.9A at 5V dc
Environmental Conditions:
Operational Temperature
Storage Temperature
Relative Humidity
Agency Certification (when product or packaging is marked)
+0°C to +60°C (+32F° to +140°F)
-40C° to +85°C (-40F° to +185°F)
5% to 95% (without condensation)
CSA certified
CSA Class I, Division 2
Groups A, B, C, D certified
UL listed
CE compliant for all applicable directives
publication 1786-6.2 for more information.
ControlNet Cable
1 Publication 1747-UM003 A-EN-P
A-2 Specifications
Publication 1747-UM003A-EN-P
Appendix
B
Understanding Your SLC 500/1746 Control System
This appendix provides information on using SLC 500/1746 control systems. Topics include:
selecting your SLC 500/1746 control power supply
system installation recommendations
mounting your control system
installing your I/O modules
wiring the I/O modules
calculating heat dissipation for your control system
When configuring a modular system, you must have an individual power supply for each chassis. Careful system configuration results in the best performance. Excessive loading of the power supply outputs can cause a power supply shutdown or premature failure.

Selecting Your SLC 500/1746 Control Power Supply

There are three different ac power supplies and four dc power supplies. For ac power supplies, the 120/240V selection is made by a jumper. Place the jumper to match the input voltage. The power supply has an LED that illuminates when the power supply is functioning properly. On the following page are the general specifications for the power supplies.
1747-UM003A-US-P
B-2 Understanding Your SLC 500/1746 Control System

Power Supply Specifications

Description: Specification: 1746-
P1 P2 P3 P4 P5 P6 P7
Line Voltage 85 to 132/170 to 265V ac 47
to 63 Hz
Typical Line
135 VA 180 VA 90 VA 240 VA 85 VA 100 VA 12V dc input:
Power Reqmnt.
Maximum
20A 45A 20A 20A (required for turn-on)
Inrush Current
Internal Current Capacity
Fuse Protection
24V dc User
(2)
2A at 5V dc
0.46A at 24V dc
1746-F1 or equivalent
5A at 5V dc
0.96A at 24V dc
1746-F2 or
(3)
equivalent
200 mA Not Power Current Capacity
24V dc User
18 to 30V dc 20.4 to 27.6V dc18 to 30V dc Power Volt. Range
Ambient Operating
°C to +60°C (+32°F to +140°F)
0
Current capacity is derated 5% above +55 Temperature
Isolation
(6)
1800V ac RMS for 1s
19.2 to 28.8V dc85 to 130/170
3.6A at 5V dc
0.87A at 24V dc
1746-F3 or
(4)
equivalent
Applicable
None
to 265V ac 47
90 to 146V dc 30 to 60V dc10 to 30V dc
to 63 Hz
24V dc input:
10.0A at 5V dc
2.88A at 24V
(1)
dc
5A at 5V dc
0.96A at 24V dc
50 VA
12V dc input:
2.0A at 5V dc
0.46A at 24V dc
75 VA
24V dc input:
3.6A at 5V dc
0.87A at 24V dc
Fuse is soldered in place.
(5)
°C.
(1)
1A
°C to +60°C
0 (+32
°F to
+140
°F) no
200mA Not Applicable
°C to +60°C (+32°F to +140°F)
0 Current capacity is derated 5% above +55
°C.
derating
(7)
2600V dc for 1s1800V ac RMS for 1s 600V ac RMS for 1s
CPU Hold-up
(8)
Time
20 ms (full load) 3000 ms (no
load)
5 ms (full load) 1000 ms (no load)
20 ms (full load) 3000 ms (no load)
20 ms (full load) 3000 ms (no load)
5 ms (full load) 1500 ms (no load)
12V dc input:
1.37 ms at 0V dc (full load) 895 ms at 0V dc (no load) 10 ms at 9V dc (full load) continuous at 9V dc (no load)
24V dc input: 40 ms at 0V dc (full load) 1860 ms at 0V dc (no load) 790 ms at 11V dc (full load) continuous at 11V dc (no load)
Certification UL listed
C-UL or CSA certified (as indicated by product or packaging markings)
CE compliant for all applicable directives
Hazardous
Class I, Division 2 Environment Certification
(1) The combination of all output power (5 volt backplane, 24 volt backplane, and 24 volt user source) cannot exceed 70 watts. (2) Power supply fuse is intended to guard against fire hazard due to short-circuit conditions. This fuse may not protect the supply from miswiring or excessive transient in the
power line. (3) Equivalent fuses: 250V-3A fuse, Nagasawa ULCS-61ML-3, or BUSSMAN AGC 3. (4) Equivalent fuse: 250V-3A fuse, SANO SOC SD4, or BUSSMAN AGC 3. (5) Equivalent fuse: 125V-3A fuse, Nagasawa ULCS-61ML-5, or BUSSMAN AGC 5. (6) Isolation is between input terminals and backplane. (7) No isolation between input terminals and backplane. However, dielectric withstand between input terminals and chassis ground terminal is 600V ac RMS for 1s. (8) CPU hold-up time is for 0V unless specified. Hold-up time is dependent on power supply loading.
Publication 1747-UM003A-EN-P
Understanding Your SLC 500/1746 Control System B-3
Example for Selecting a 1746 Power Supply
Select a power supply for chassis 1 and chassis 2 for the control system below. (The worksheets for this example start on Page B-4.)
Table B.1 Chassis 1
Chassis 1
PC
Chassis 2
? ?
1747-AIC
DH-485 Network
Chassis 1 Contains:
Slot Number
0 Processor Unit 1747-L524 0.35 0.105
1 ControlNet Scanner 1747-SCNR 0.90 Not Applicable
2 Transistor Output
3 Triac Output Module 1746-OA16 0.37 Not Applicable
Peripheral device
Description Catalog Number Power
Module
Isolated Link Coupler 1747-AIC Not
Total Current: 1.755
Slot Slot 012 3 012345 6
Power Supply at
Supply at 5V
24V dc (Amps)
dc (Amps)
1746-OB8 0.135 Not Applicable
0.085
Applicable
0.190
(1)
Table B.2 Chassis 2
(1) Power Supply 1746-P1 is sufficient for Chassis #1. The “Internal Current Capacity” for this power supply is 2 Amps at 5V
dc, 0.46 Amps at 24V dc.
Chassis 2 Contains:
Slot Number
Description Catalog Number Power
Supply at 5V dc (Amps)
0 ControlNet Adapter 1747-ACNR15 0.900 Not Applicable
1 Input Module 1746-IA16 0.085 Not Applicable
2 Input Module 1746-IA16 0.085 Not Applicable
3 Relay Output Modules 1746-OB32 0.452 Not Applicable
4 Relay Output Modules 1746-OB32 0.452 Not Applicable
5 Relay Output Modules 1746-OB32 0.452 Not Applicable
6 Combination Module 1746-IO12 0.09 0.07
Total Current: 2.616
(1) Power Supply 1746-P2 is sufficient for Chassis #2. The “Internal Current Capacity” for this power supply is 5 Amps at 5V dc,
0.96 Amps at 24V dc.
Publication 1747-UM003 A-EN-P
Power Supply at 24V dc (Amps)
(1)
0.07
B-4 Understanding Your SLC 500/1746 Control System
Example - Worksheet for Selecting a 1746 Power Supply
Procedure
1. For each slot of the chassis that contains a module, list the slot number, the catalog number of the module, and its 5V and 24V maximum currents.
Chassis Number: _______ Chassis Number: _______
slot _______
0
slot _______
1
slot _______
2
slot _______
3
slot _______ slot _______ slot _______ slot _______
Catalog Number
_________
L524
_________
SCNR
_________
OB8
_________
OA16
_________ _________ _________ _________
Maximum Currents 5V 24V
______________ ______________ ______________ ______________
0.350
0.900
0.135
0.370
0.105 NA NA NA
______________ ______________ ______________ ______________
slot _______
0
slot _______
1
slot _______
2
slot _______
3
slot _______
4
slot _______
5
slot _______
6
slot _______
Catalog Number
_ACNR15_ _________
IA16
_________
IA16
_________
OB32
_________
OB32
_________
OB32
_________
IO12
_________
Maximum Currents 5V 24V
______________
0.900
______________
0.085
______________
0.085
______________
0.452
______________
0.452
______________
0.452
______________
0.090
______________
NA NA NA NA NA NA
0.070
Peripheral Device
_________
AIC
______________
NA
0.190
Peripheral Device
_________
______________
2. Add the power supply loading currents of
all the system devices ( at 5V and 24V).
Total Current:
When using the 1746-P4 power supply, use the formula below to calculate total power consumption of all the system devices (at 5V and 24V). Note that the 1746-P4 total power supply loading currents cannot exceed 70 W you are not using a 1746-P4 power supply, proceed to step 3.
The user current @ 24V listed below is for example only. The current required depends on the application.
Total current @ 5V
x5V) + x24V)
Total current @ 24V
+x
___________
User Current @ 24V
24V)
0.1901.755
atts. If
Total Power
= W
Total current @ 5V
+(
Total current @ 24V
Total Current:
24V)
+
x5V)x
___________
User Current @ 24V
x24V) = W
0.0702.516
Total Power
3. Compare the Total Current required for the chassis with the Internal Current Capacity of the power supplies.
To select the proper power supply for your chassis, make sure that the power supply loading current for the chassis is
less than
the
internal current capacity for the power supply, for both 5V and 24V loads.
Internal Current Capacity
5V 24V Catalog Number 1746-P1 Catalog Number 1746-P2 Catalog Number 1746-P3 Catalog Number 1746-P4
Catalog Number 1746-P5 Catalog Number 1746-P6 Catalog Number 1746-P7
2.0A
5.0A
3.6A
10.0A
5.0A
5.0A
2.0A (12V dc input)
3.6A (24V dc input)
|
0.46A
| 0.96A | 0.87A | 2.88A
(70W maximum)
0.96A
|
0.96A
|
0.46A (12V dc input)
| |
0.87A (24V dc input)
|
Required Power Supply for this Chassis: 1746-
Publication 1747-UM003A-EN-P
P1
Required Power Supply for this Chassis: 1746-
P2
Understanding Your SLC 500/1746 Control System B-5
Worksheet for Selecting a 1746 Power Supply
Make copies of this worksheet as needed. For a detailed list of device load currents, refer to the SLC 500 price sheet, product instruction sheet, or appropriate product data.
Consider future system expansion when selecting a power supply.
Procedure
1. For each slot of the chassis that contains a module, list the slot number, the catalog number of the module, and its 5V and 24V maximum currents.
Chassis Number: _______ Chassis Number: _______
slot _______ slot _______ slot _______ slot _______ slot _______ slot _______ slot _______ slot _______
Catalog Number
_________ _________ _________ _________ _________ _________ _________ _________
Maximum Currents 5V 24V
______________ ______________ ______________ ______________ ______________ ______________ ______________ ______________
slot _______ slot _______ slot _______ slot _______ slot _______ slot _______ slot _______ slot _______
Catalog Number
_________ _________ _________ _________ _________ _________ _________ _________
Maximum Currents 5V 24V
______________ ______________ ______________ ______________ ______________ ______________ ______________ ______________
Peripheral Device
_________
______________
Peripheral Device
_________
______________
2. Add the power supply loading currents of
all the system devices ( at 5V and 24V).
Total Current:
When using the 1746-P4 power supply, use the formula below to calculate total power consumption of all the system devices (at 5V and 24V). Note that the 1746-P4 total power supply loading currents cannot exceed 70 W you are not using a 1746-P4 power supply, proceed to step 3.
The user current at 24V listed below is for example only. The current required depends on the application.
Total current at 5V
x5V) + x24V)
Total current at 24V
+x
___________
User Current at 24V
atts. If
Total Power
24V)
= W
Total current at 5V
+(
Total current at 24V
Total Current:
24V)
+
x5V)x
___________
User Current at 24V
x24V) = W
Total Power
3. Compare the Total Current required for the chassis with the Internal Current Capacity of the power supplies.
To select the proper power supply for your chassis, make sure that the power supply loading current for the chassis is
less than
the
internal current capacity for the power supply, for both 5V and 24V loads.
Internal Current Capacity
5V 24V Catalog Number 1746-P1 Catalog Number 1746-P2 Catalog Number 1746-P3 Catalog Number 1746-P4
2.0A
5.0A
3.6A
| | 0.96A | 0.87A
10.0A | 2.88A
0.46A
(70W maximum)
Required Power Supply for this Chassis: 1746-
Required Power Supply for this Chassis: 1746-
Publication 1747-UM003 A-EN-P
B-6 Understanding Your SLC 500/1746 Control System
This section provides specific recommendations to help you install your SLC 500/1746 components. For general installation guidelines, also refer to the requirements specific to your region.

SLC 500 System Installation Recommendations

Europe: Reference the standards found in EN 60204 and your national
United States: Refer to article 70E of the National Fire Protection

Typical Installation

The figure below consists of some components that make up a typical installation.
(1) An IEC- or NEMA-rated enclosure suitable for your
application and environment that shields your adapter from electrical noise and airborne contaminants.
(2) Disconnect device that allows you to remove power from
system.
(3) Fused isolation transformer or a constant voltage
transformer, as your application requires. (4) Master control relay/emergency-stop circuit. (5) Terminal blocks or wiring ducts. (6) Suppression devices for limiting electromagnetic
interference (EMI) generation.
regulations.
Association (NFPA). It describes electrical safety requirements for employee workplaces.
(1)
(2) Disconnect Device
(4)
(6)
(3) Isolation Transformer
(5)
Publication 1747-UM003A-EN-P
SLC 500 Chassis

Selecting an Enclosure

The enclosure protects the equipment from atmospheric contamination. Standards established by the International Electrotechnical Commission (IEC) and National Electrical Manufacturer’s Association (NEMA) define enclosure types based on the degree of protection an enclosure provides. Select an IEC­or NEMA-rated enclosure that suits your application and environment.
Understanding Your SLC 500/1746 Control System B-7
The enclosure should be equipped with a disconnect device. To calculate the heat dissipation of your controller, Refer to Calculating Heat Dissipation for Your Control System on page B-34.

Spacing Considerations

Up to three chassis can be connected (for a maximum of 30 I/O slots). Follow the recommended minimum spacing shown below to allow for convection cooling
within the enclosure.
(2)
(1)
(3)
(3)
1746-C7 Cable
(4)
IMPORTANT
1746-C9 Cable
Be careful of metal chips when drilling mounting holes for the chassis. Do not drill holes above a mounted control system.
(3)
(1)
(2)
(1)
1746-C9 Cable
(2)(2)
1746-C9 Cable
Recommended Spacing:
1. 15.3 to 20 cm (6 to 8 in.) when using the 1746-C9 cable.
IMPORTANT
2. Greater than 10.2 cm (4 in.).
3. Greater than 15.3 cm (6 in.).
4. 7.7 to 10.2 cm (3 to 4 in.) when using the 1746-C7 cable.
When making a vertical connection between two A13 chassis with a 1746-C9 cable, you must limit the space to 15.3 cm (6 in.) for the C-9 cable to reach from chassis to chassis.
(3)
Publication 1747-UM003 A-EN-P
B-8 Understanding Your SLC 500/1746 Control System

Preventing Excessive Heat

For most applications, normal convection cooling keeps the adapter components within the specified operating range of 0° to +60° C (+32° to +140° F). Proper spacing of components within the enclosure is usually sufficient for heat dissipation.
In some applications, a substantial amount of heat is produced by other equipment inside or outside the enclosure. In this case, place blower fans inside the enclosure to assist in air circulation and to reduce “hot spots” near the adapter.
Additional cooling provisions might be necessary when high ambient temperatures are encountered.
IMPORTANT
Do not bring in unfiltered outside air. It may introduce harmful contaminants of dirt that could cause improper operation or damage to components. In extreme cases, you may need to use air conditioning to protect against heat build-up within the enclosure.

Wiring Layout

Careful wire routing within the enclosure helps to cut down electrical noise between I/O lines. Follow these rules for routing your wires:
Route incoming power to the power supply by a separate path from wiring
to I/O devices. Where paths must cross, their intersection should be perpendicular.
IMPORTANT
If wiring ducts are used, allow for at least 5 cm (2 in.) between I/O wiring
ducts and the adapter. If the terminal strips are used for I/O wiring, allow for at least 5 cm (2 in.) between the terminal strips and the adapter.
Limit the cable length for the TTL input module to 15 m (50 ft.) per point
and 3 m (10 ft.) per point for the TTL output module. Use low power dc I/O wiring even though it is less tolerant to electrical noise.
Do not run signal or communications wiring and power wiring in the same conduit.
Publication 1747-UM003A-EN-P
Loading...