Rockwell Automation 1746-QV, D17466.18 User Manual

Allen-Bradley
Open-loop Velocity
User
Control Module
(Cat. No. 1746-QV)
Manual

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation, and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or in part, without written permission of Allen-Bradley Company, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death,
!
Attention statements help you to:
property damage or economic loss.
identify a hazard
avoid the hazard
recognize the consequences
Important: Identifies information that is critical for successful
application and understanding of the product.
SLC is a trademark of Allen-Bradley Company, Inc. PKZIP and PKUNZIP are registered trademarks of PKWARE Inc.


Manual Changes (Series A/D)

Changes to this revision of the manual include these additions:
Considerations for Selecting the "15V dc Power Supply (chapter 4)
Other Design Considerations (chapter 4)
Testing for Proper System Operation (chapter 5)
Power Supply Loading Specifications (appendix A)
Publication
1746-6.18 – April 1998
Notes:
Summary of Changestoc–ii
Publication
1746-6.18 – April 1998

Table of Contents

System Overview
Chapter Objectives
Is the 1746-QV Module?
What What Is an SLC-500 System? Why Use This System? How Does It Work? What
Are Typical Applications?
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
Quick Start
Procedure
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting Up the Software
Chapter Objectives Obtaining
Configuring Your SLC Processor, Off-line Modify
General Profile
the Ladder Program Electronically from
BBS or the Internet About the Rockwell Bulletin Board System (BBS) To Access BBS: To Access the Internet:
N Files in Y
Output
Image T
Conventions for Profiles
Operation
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
our SLC Processor, Off-line
able with Profile Data
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . .
. . . . . . . . . . . . . .
1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1–1 1–1 1–1 1–2 1–2 1–2
2–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2–1
3–1. . . . . . . . . . . . . . . . . . . . . . . . . . .
3–1 3–1
3–1 3–1 3–2 3–2 3–4 3–4 3–5 3–5
Setting Up the Hardware
Chapter Objectives Connect Connect Minimizing Considerations
Other
the LDT to Module Inputs Module Outputs to Output Devices
Interference from Radiated Electrical Noise
Selection Application
of the "15V dc Power Supply
Design Considerations
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
for the "15V dc Supply
of the "15V dc Power Supply
. . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
4–1. . . . . . . . . . . . . . . . . . . . . . . . . .
4–1 4–1 4–2 4–2 4–3 4–3 4–4 4–4
Table of Contentsii
Operating the Module for the First Time
Chapter Objectives Power Up the System
Check
Wiring and Grounding Get Ready to Move the Ram Move the Ram Jog
the Ram to the Reference Position
Test
for Proper System Operation
Troubleshoot Possible Problems
Using
Status Bits for Errors Detected by the Module Troubleshooting Conditions
That Control Module Outputs
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . .
T
able
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Specifications
Electrical Physical Environmental
Specifications
Specifications
Specifications
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Ladder Program
. . . . . . . . . .
. . . . . . . . . . . . . . . . . .
5–1. . . . . . . . . . . . . . .
5–1 5–1 5–1 5–2 5–2 5–3 5–4 5–4 5–4 5–5 5–5
A–1. . . . . . . . . . . . . . . . . . . . . . . . . . . .
A–1 A–1 A–1
B–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SLC Processor Files
Input G
File
Output
Image T
able
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Image T
able
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C–1 C–2 C–2



Chapter Objectives

What Is the 1746-QV Module?

What Is an SLC-500 System?

This chapter presents a conceptual overview of how you use the 1746-QV module in an application.
The 1746-QV module is part of an SLC-based open-loop control system for controlling the speed and placement of an hydraulic ram. The module accepts an input from a linear displacement transducer (LDT) and motion profiles that you program into the SLC processor, and varies its output in the range of "10V dc. The SLC processor sends to the module a pair of extend and retract profiles that define when to accelerate or decelerate hydraulic motion.
The Allen-Bradley Small Logic Controller (SLC) system is a programmable control system with an SLC processor, I/O chassis containing analog, digital, and/or special-purpose modules, and a power supply. The 1746-QV module interfaces your hydraulic ram and position-monitoring device (LDT) to the ladder sequence in your SLC processor. The system can be illustrated as follows:
Power Supply
SLC-500 Processor
Position Input from LDT
HYDRAULIC
RUN
FAULT LDT/"10V DC
1746-QV module
Analog Output
"10v dc
Piston-type Hydraulic Cylinder and Linear Displacement Transducer (LDT)
Axis Motion
Proportional Amplifier
Publication
Proportional Valve
1746-6.18 April 1998
1–2
Position
Position
Head
Head
System Overview

Why Use This System?

How Does It Work?

Extend Direction
3
Voltage
2
1
4
Segments
Because you can change the speed of the hydraulic ram with extend and retract profiles and store additional profiles (recipes) in data table iNteger (N) files, this control system has these benefits:
reduced cycle time – you can increase ram speed for faster operation
reduced or eliminated pressure spikes and water-hammering for
smoother operation and less wear and tear on the machine – you can profile accelerations and decelerations of the hydraulic ram
energy savings – you can match the speed of the hydraulic pump
to the force that you need
faster new-part change-over – you can store your setups and
minimize mechanical re-adjustments between parts
The 1746-QV module executes the extend and retract profiles that you load to control the motion of the hydraulic ram. You can program up to seven different voltages over the length of travel in both the extend and retract directions to control how the ram accelerates or decelerates.
Retract Direction
4
5
6
7
Voltage
1
3
2
Segments
5
6
7
LDT

What Are Typical Applications?

LDT
Each position setpoint triggers a corresponding voltage output in the range of –10V to +10V dc that translates into speed. The LDT provides high-speed position updates to the module for consistent and repeatable motion.
Use the 1746-QV module in an SLC-based system for low-cost control of:
hydraulic machinery
simple (non-CNC) hydraulic presses
diecasting machinery
welder placement
pneumatic actuators for clamping or placement
In addition, the module is designed to support standard proportional amplifiers and retrofit into most existing hydraulic systems.
Publication
1746-6.18 April 1998

Procedure



Use this chapter as an abbreviated procedure for getting the 1746-QV module into operation or as an overview if you need more information.
1746-QV Module Input Terminal Block
(+) Gate Out
8
(–) Gate Out
7
(–) Interrogate
6
(+) Interrogate
5
Shield/Frame
4
–15V dc PS
3
PS Common
2
+15v dc PS
1
1.
Load Ladder Logic into Your Computer Chapter 3
Obtain the ladder program (appendix B) from Rockwell Software Bulletin Board (BBS) or the Internet.
From
BBS:
in the Allen-Bradley Products Library directory
and decompress it with PKUNZIP available on BBS. The ladder program, VELMOD, is SLC500
code (65 Kbyte).
Download it into a hard drive subdirectory where your programming software looks for files.
.
The
(216) 646-ROCK (-7625). If a new user
, follow prompts to register
manual is in W
ord format. Download it
. Log in. Look for 1746QV
into a hard drive sub-
From Internet: webpage http://www.ab.com If a new user, click Join Now and follow prompts to
register. Log in. Search for QV: on homepage, click Search Our Site, insert QV in window, and click
button. The manual is PDF format and requires Adobe Acrobat viewer
search
. The ladder program is PDF
format and must be entered manually.
2.
Set Up Your Software Chapter 3
Configure the SLC Processor and I/O with your programming software. Enter the following:
a) processor type, b) module I/O-chassis slot, c) module ID (13115), d) G-file size (7 words), and e) G-file configuration values from the ladder program (appendix B).
Modify N files for the profile found in the ladder program (appendix B) to suite your application.
3.
Connect the LDT to the Module’s Input Terminal Block Chapter 4
The following are connections between the 1746-QV module and typical LDTs such as Temposonics, Balluff, Santest, and Gemco.
Inter­rogate
Temposonics II, RPM or DPM
(+)
(+)
10
(–)
(–)
(–)
"15V
PS Common
1
Frame
23456789
GND
(+)
Gate
Out
dc PS
The
views are looking at the connector on the LDT head.
Balluff BTL-2-L2 & -2-M2
Interro­gate (–)
3
"15V dc PS
Gate
7 (+)
Out (–)
Gate
2
45
(–)
8
6
PS Common
Out (+)
1
Interro­gate (+)
Santest GYRP & GYRG
+15V dc PS
Gate Out (+)
NC
1
5
Interrogate
2
4
6
PS Common
3
(+)
7
(–)
Gate Out (–)
Gemco Quick-Stick II 951VP
w/PWM
Output
B–BLK PS Common C–RED +15V dc PS K–GRY + Interrogate E–BRN –Sq Wave Out* F–BLU +Sq Wave Out* A–WHT –Interrogate G, D, H RS232RXD J–PUR 2nd PS COM
*951RS has pulse trigger
1746-QV Input Pin #
(+) and (–) wires of same function should be a twisted pair within the cable. Note 1: In the table, we use the term “gate out” for pulse trigger or square wave (Gemco) and start/stop (Balluf
Function Temposonics II
8
(+) Gate Out
7
(–) Gate Out
6
(–) Interrogate
5
(+) Interrogate 4 Shield/Frame n/a 3
–15V dc PS 2 PS 1 +15V dc PS
Common
RPM or DPM
4 – Pink 3 – Gray 10 – Green 9 – Y
6 – Blue 1 – White 5 – Red
ellow
Balluff BTL-2-L2 & -M2
2 – Gray (note 1) 5 – Green (note 1) 3 – Pink 1 – Yellow n/a 8 – White 6 – Blue 7 – Brown
Santest GYRP/GYRG
pin
5
pin
7
pin
6
pin
4 n/a n/a n/a n/a pin
3 pin
1
f -M2) LDT signals.
Publication
Gemco
Quick-
Stick 951VP/RS
F – Blue (note 1) E – Brown (note 1) A – White K – Gray
B – Black C – Red
1746-6.18 April 1998
2–2
Quick Start
4.
Important:
output cable to a 0V connection in the amplifier
1746-QV Terminal Block
5.
Connect Module Output Terminals to Output Devices With Correct Bonding Chapter 4
Connect the shield of the amplifier
Analog Output ("
Output
2 1
10v dc)
.
Servo Amplifier (Proportional)
(+)
Dif
f.
Input
(–)
Outputs to valves
0V
A B
Minimize Interference from Electrical Noise with Correct Shielding and Grounding Chapter 4
Important: Connect PS output commons togerther.
Connect the following to earth ground: a) cable shields (except for amplifier outputs) at one end only b) input terminal 4, c) case grounds of PS and amplifier, e) LDT flange.
Case GND
Important:
connect PS output commons together and isolate from earth ground.
Belden 8761
For correct bonding,
ransducer (LDT)
LDT Power
LDT Signals
1746-QV Module
Input
1 2 3
5-8
4
2
Output
1
earth ground
"
15V PS
(+) (C) (–)
Belden 8770
Analog Output
Piston-type Hydraulic Cylinder and Linear Displacement T
+24V dc PS 0V dc PS
Do NOT connect output shields to earth ground
T
o solenoid A
T
o solenoid B
,
24V PS
(–) (+)
Servo Proportional Amplifier
0V
Valves
Case GND
Belden 8761
Case GND
Cable Note
Cable Note: Use cable recommended by the LDT and amplifier manufacturer
Publication
1746-6.18 April 1998
LDT
Cable
.
Note
6.
After
loading profiles with the ladder program (step 1), alternately
Operate the Module for the First time Chapter 5
and Hydraulic Ram
run the extend profile (O:e.0/0 = 0-to-1),
then the retract profile (O:e.0/1 = 0-to-1). Modify the profile to reach the preset reference, and set it.
Important:
If motion is reversed: for a "10V dc output, change the sign (") of all extend/retract voltage
values; or for a +10V output, energize the other solenoid on the directional valve (with ladder logic).
To do this:
load all profiles 1 N7:40 set preset reference to zero clear errors read current position run an extend profile run a retract profile
Enter decimal:
8 N7:50
16 N7:50
read, only
1 N7:50 2 N7:50
at address:
N7:61

Setting Up the Software

Chapter Objectives

Obtaining the Ladder Program Electronically from BBS or the Internet

This chapter helps you do the following:
Obtain the ladder program electronically
Configure your SLC processor off-line
Modify N files in your SLC processor, off-line
General conventions for profiles
Profile operation
You can obtain ladder logic electronically and download it to your SLC processor conveniently without the worry of data-entry errors.
About the Rockwell Bulletin Board System (BBS)
You can access the Rockwell Software Bulletin Board System (BBS) by modem. Anyone is welcome. The BBS provides utilities, examples, and technical information on Rockwell Software products and on selected Allen-Bradley products.
new users may:
– send and receive messages – download General Access files – upload files for review by technical support specialists
verified customers may:
– search for new and existing files – download files such as utilities, example programs, tech info – access software bulletins
subscribers to tech bulletins, DataDisc CD-ROM may:
– download tech bulletins of the Tech Bulletin Subscription series
User accounts are automatically generated online. We use our product data base to verify BBS accounts at your initial log-in, and we adjust your security level according to your support status. Should your registration information change, you can update your account from the “Configure System Defaults” menu.
To Access BBS:
1. Set your modem to no parity, 8 data bits, and 1 stop bit.
2. Dial (216) 646-ROCK (-7625).
3. Follow prompts to log in. New users must create a new account.
4. Look for 1746QV in the Allen-Bradley Products Library. The manual
is formatted in Microsoft Word and compressed with PKZIP. The ladder program, VELMOD, is SLC code.
Publication
1746-6.18 April 1998
3–2
Setting Up the Software
5. Download ladder program VELMOD (65 Kbyte SLC code) into the
subdirectory on your hard drive where your programming software looks for files. With RSLogix: C:\ . . . RSLogix 500 English\Project.
6. Download the ladder program to your SLC processor.
7. Download the manual into a hard drive subdirectory. You must
decompress the Word version with PKUNZIP available on BBS.
To Access the Internet:
1. Access the Allen-Bradley webpage at: 
2. To access the member area, you must log in. If you do NOT have
an account, click Join Now and follow the prompts to register.
3. Search for QV: on homepage, click Search Our Site, insert QV into
the window, and click Search button. The manual is PDF format and requires Adobe Acrobat viewer. The ladder program is PDF format and must be entered manually.

Configuring Your SLC Processor, Off-line

This procedure assumes you are using RSLogix500 Programming Soft­ware, version 2.10 or later. For other software, the procedure may vary.
1. Open your 1746-QV project,
VELMOD.
2. Configure the type of SLC processor. To do this: A. Open the file, Controller Properties.
B. Select the SLC processor type and click OK.
3. Configure the rack size, module slot, and module ID: A. Open the file, I/O Configuration.
B. Select the rack size. C. Highlight the slot number for the module. D. From the list of modules, scroll to 1746-QV and double–click.
If the module is not listed: – Scroll to Other and double-click. – Enter the module’s ID (13115) and double-click.
4. Size the “G” file: A.Highlight 1746-QV (or 13115 if module was not listed).
B. Click [A
dv Config].
Publication
1746-6.18 April 1998
C. In the dialog box, enter a G-file length of 7. D. Press [E
dit G Data].
Setting Up the Software
For e a ple o enter an calibration of 8.9373
Configuration Bit
1 1 0
–16,384
–32,768
1 1 0
–16,384
towards
3–3
5. Enter values in the G file:
If the module was listed: If the module was not listed (you entered the ID):
You get the G–file Setup screen. Enter data from the table, below.
You get the following display, shown in decimal radix. Enter a value in each word as shown, next.
G–file display for unlisted module (shown in decimal radix):
Ge:0 2056 0 0 0 0 0 0
Enter a value at each G-file word address and press [ENTER]. Then cursor to the next word address and repeat. For example:
Ge:0 2056 893 730 12 1200 –32768 0
We used values from the ladder logic example (appendix B). You will want to use G-file values that suit your application:
Word: Function of G-file Word: Range: Description of G-file Word or Bit: Example:
0 Reserved. Do NOT use. n/a The processor stores a code for the 1746-QV module. 2056
words 1 & 2 refer to the gradient or transducer calibration value stamped on the name plate on the transducer housing.
1 LDT calibration: upper 3 digits 2 LDT calibration: lower 3 digits 3 Full-scale length (L) of LDT 2vLv160 inch Enter the length of the LDT (160 inches max). 12 4 Full-scale count (C) 2vCvLx100 Typically C = L x 100.
5 Configuration Bits
15 14 13 12-0 Equivalent V 0 1 0 0 1 0 0 0
0 1 1 0
6 Preset Reference –32,768 to +32,767 Typically zero or home reference value. 32,767 = 327.67 inches. 0
+16,384 –32,768
0
0
+24,576
800-999 ms/inch 000-999 ms/inch
bits 0-12 Set to zero.
alue
bit 13 0 = output maintained during LDT fault while running profiles and
bit 14 Type of LDT: 0 for RPM, 1 for DPM bit 15 0 = position data increases when moving away from LDT head
For example: To enter an LDT calibration of 8.9373, use decimal radix and enter 893 in word 1 and 730 in word 2.
Position Data (I:e.1) = C/(L x 100)
LDT Calibration
during SLC mode change
1 = output resets for LDT fault and SLC mode change
1 = position increases when moving toward LDT head
893 730
1200
–32,768
(bit
15 = 1 for position increases towards LDT head)
Examples of Full-scale Count Values
LDT Physical Length
from 160” to 2” 1 0.01 L (160” to 2”) L x 100 16” 2 0.01 160 8000 16” 4 0.01 160 4000 16” 10 0.001 160 16000
No. of Recirculations
Resolution
Full-scale Length (L)
Full-scale Counts (C)
Important: The module checks for invalid data such as out of range values or the setting of reserved bits 0-12. You can clear a data-entry configuration error only by re-entering a corrected value.
6. Save when done
.
Click OK. Click OK. Close window.
Publication
1746-6.18 April 1998
3–4
Co and Bit Enable these bits
/bit #)
with your ladder logic, where e
Setting Up the Software

Modify N Files in Your SLC Processor, Off-line

A set of profile data for initial configuration
One N file may contain the initial commands, setpoints, and values for configuring the extend and retract profiles.
Retract Voltages
Retract Positions
Extend V
oltages
Extend Positions
Command and Setpoints
>>> >>> >>>
>>>
Output
Command and Setpoints
Image T
able
>>> >>> >>>
>>>
1746-QV
Extend and Retract Profiles
Module
The file contains commands and data starting at the these addresses:
command and position setpoints for extend #N7:0
command and voltage (velocity) values for extend #N7:10
command and position setpoints for retract #N7:20
command and voltage (velocity) values for retract #N7:30
The sample ladder program (appendix B) copies profile data into the output image table from the above locations.
Output Image Table with Profile Data
Word: Function of Output Image Word: Bit #: Description: (For command bits, a 0-to-1 transition enables the command)
0 Command Bits
(O:e.0
represents the I/O slot number.
1-7 Position Setpoint or Voltage Value n/a Important: Position setpoints are in units of 0.01” (200 = 2.00”)
0 Set to run an extend profile. 1 Set to run a retract profile. 2 Set to disable the profile. This bit over-rides bit 0 or 1. 3 Set to change the current position data to the value of the preset reference
stored in Ge:6. 4 Set to clear any data-entry errors. 5 Set to define words 1-7 as programmed position setpoints for extend. 6 Set to define words 1-7 as programmed voltage values for extend. 7 Set to define words 1-7 as programmed position setpoints for retract. 8 Set to define words 1-7 as programmed voltage values for retract.
9-15 Reserved. Do NOT use.
within the range of –327.68” to +327.67”, and voltage values in
5mV units (3005 = 3.005V) within the range of "10,000mV.
The data monitor mode of your programming software displays the data files shown below (with values from the ladder program).
Important: Modify these values to suit the preset reference chosen for the G file and/or to match the LDT length.
Extend Positions: N7:0 32 –45 50 200 300 400 425 500 0 0 Extend V Retract Positions: Retract V
Publication
elocities: N7:10 64 3000 3750 4000 4000 4000 4000 4000 0 0
N7:20 128 –45 50 200 300 400 425 500 0 0
elocities: N7:30 256 5000 6000 6000 3000 1000 50 25 0 0
1746-6.18 April 1998
Setting Up the Software
3–5

General Conventions for Profiles

Consider the following when you set up your profiles:
Extend and retract define the profile with respect to the LDT head:
extend is always away from the head, retract is always towards it
Position data changes direction depending on how you set
configuration bit Ge:0/15 for LDT motion: 0 = position data increases when moving away from LDT head 1 = position data increases when moving towards LDT head
Each position setpoint triggers from the absolute position data
(I:e.1) as modified by the preset reference.
Position setpoints are in units of 0.01”.
For example, enter 2” as 200.
If you enter position setpoints in random order, the module places
them in ascending order (P1 = lowest and P7 = highest) with their associated voltage value.
Speed segments are defined increasing from the LDT head,
regardless of position data direction.
Speeds are reported in the input image table words 2-7 (I:e.2-I:e.7)
for the previous profile (extend speeds reported during the next retract profile and vice versa)
Voltage values (for speed) are in the range of "10,000mV in
multiples of 5mV. For example, enter –5.005V as –5005.
Important: Enter voltage values in multiples of 5mV or the module will fault, causing you to correct and re-download the profile.

Profile Operation

Voltage values are cleared when you re-program position
setpoints. The profile is cleared when the module loses power or when you change the value of any G-file configuration word.
Important: Your application may require different position setpoints and voltage values. Your profiles must be consistent with the physical parameters of the LDT and G file to guard against damaging hardware.
In general:
For relatively faster and smoother motion, use two speed segments
for acceleration and five speed segments for deceleration.
Adjust the ramp rate on the proportional amplifier for the smoothest
operation. Initially, start with the ramp disabled (fastest ramp rate).
You may compensate for deadband or valve overlap by specifying a
voltage value greater than or equal to the valve’s bias current.
Profile operation depends on how the module reports position data. With the data-direction bit (Ge:0/15), you select whether: – position data increasing towards the LDT head (Ge:0/15 = 1) – position data increasing away from the LDT head (Ge:0/15 = 0)
Publication
1746-6.18 April 1998
3–6
Setting Up the Software
For
Position Data Increasing Towards LDT Head (Ge:0/15 = 1)
Voltage
Output = 0 past position 1
Position
Position
Voltage
Output = 0 past position 7
Position
V1
Speed Segment 6
V2 V3 V4
Speed Segment 5
Speed Segment 4
Speed Segment 3
V5 V6 V7
Speed Segment 2
Speed Segment 1
P7P6P5P4P3P2P1
Starting with the ram between P7 and the LDT head (open position),
running the extend profile results in V7 applied to the output. As the ram passes below P7, V6 is applied to the output, etc.
If the ram passes below P1, the output is forced to 0V dc, and the
profile is disabled. You must load new data to operate the profile.
Placement operations require two segments.
For example, if P2 = 6.07”, V2 = 1.500V, P1 = 0.00” (or a value less than P2), and V1 = –1.500V, then the module will place the ram in the vicinity of P2 (between 6.02 and 6.12). The negative voltage V1 causes motion to reverse or stop. To see this, enter the example values for P2, V2, P1, and V1 in the previous diagram.
Data Increases from LDT Head (Ge:0/15 = 0)
V7
Speed Segment 6
V6 V5 V4
Speed Segment 5
Speed Segment 4
Speed Segment 3
P4P5P7
V3 V2 V1
Speed Segment 2
Speed Segment 1
P1P2P3P6
LDT
head
LDT
head
Starting with the ram between P1 and the LDT head (open position),
running the extend profile results in V1 applied to the output. As the ram passes P1 towards P2, V2 is applied to the output, etc.
If the ram passes P7, the output is forced to 0V dc, and the extend
profile is disabled. You must load new data to operate the profile.
Publication
1746-6.18 April 1998

Setting Up the Hardware

Chapter Objectives

Connect the LDT to Module Inputs

1746-QV Module Input Terminal Block
(+) Gate Out
8
(–) Gate Out
7
(–) Interrogate
6
(+) Interrogate
5
Shield/Frame
4
–15V dc PS
3
PS Common
2
+15v dc PS
1
Interro­gate
Temposonics II, RPM or DPM
(+)
(–)
(+)
10
(–)
(–)
This chapter helps you install the hardware with these tasks:
connect the LDT to module input terminals
connect module output terminals to output devices
minimize interference from radiated electrical noise
considerations for the "15V dc power supply
other design considerations
We assume that you will use one of the following types of LDT:
Temposonics II: RPM TTSRxxxxxxR, or
DPM TTSRxxxxxxDExxx
Balluff: BTL-2-L2, or BTL-2-M2
Santest: GYRP, or GYRG
Gemco Quick-Stick II: 951VP, or 951 RS
We illustrate typical connections between the 1746-QV module and these types of LDTs. (There are other suppliers with compatible LDTs.)
Balluff BTL-2-L2 & -2-M2
Gate
Out (–)
Gate
Out (+)
2
45
(–)
8
3
7 (+)
6
PS Common
1
Interro­gate (+)
+15V dc PS
Gate Out (+)
Frame GND
Out
Interro­gate (–)
"15V dc PS
"15V
PS Common
1
23456789
(+)
Gate
dc PS
The views are looking at the connector on the LDT head.
Santest GYRP & GYRG
NC
PS Common
2
1
5
Interrogate
3
(+)
4
7
(–)
6
Gate Out (–)
Gemco Quick-Stick II 951VP
w/PWM
Output
B–BLK PS Common C–RED +15V dc PS K–GRY + Interrogate E–BRN –Sq Wave Out* F–BLU +Sq Wave Out* A–WHT –Interrogate G, D, H RS232RXD J–PUR 2nd PS COM
*951RS has pulse trigger
Connect each 1746-QV input pin # to the corresponding LDT pin #.
1746-QV Input Pin #
(+) and (–) wires of the same function should be a twisted pair within the cable. Note 1: In the table, we use the term “gate out” for pulse trigger or square wave (Gemco) and start/stop (Balluff -M2) LDT signals.
Function Temposonics II
RPM or DPM
Balluff BTL-2-L2 & -M2
Santest GYRP/GYRG
Gemco Quick­Stick 951VP/RS
8 (+) Gate Out 4 – Pink 2 – Gray (note 1) pin 5 F – Blue (note 1) 7 (–) Gate Out 3 – Gray 5 – Green (note 1) pin 7 E – Brown (note 1) 6 (–) Interrogate 10 – Green 3 – Pink pin 6 A – White 5 (+) Interrogate 9 – Yellow 1 – Yellow pin 4 K – Gray 4 Shield/Frame n/a n/a n/a n/a 3 –15V dc PS 6 – Blue 8 – White n/a n/a 2 PS Common 1 – White 6 – Blue pin 3 B – Black 1 +15V dc PS 5 – Red 7 – Brown pin 1 C – Red
Publication
1746-6.18 April 1998
4–2
Setting Up the Hardware

Connect Module Outputs to Output Devices

1746-QV
Output
Terminal Block
Module outputs connect to a separate 2-conductor output terminal block located beneath the input terminal block.
+24V dc PS 0V dc PS
Analog Output ("
2 1
10v dc)
Servo Amplifier (Proportional)
(+)
Dif
f.
Input
(–)
Outputs to valves
Important:
output cable to a 0V connection in the amplifier Do not connect the shield to earth ground.
0V
A B
Ground the shield of the amplifier
T
o solenoid A
T
o solenoid B
.
Note: Follow manufacturer recommendations for shielding the output cables of the proportional amplifier. Typically, pulse-width modulated outputs radiate electrical noise originating from the +24V dc power supply, so isolate the shields of the amplifier output cable to a 0V dc connection inside the proportional amplifier.
You have a choice of three configurations to match your hydraulics:
proportional amplifier with ramp and proportional valve
servo amplifier with ramp and variable-volume pump
Allen-Bradley 1305 Drive and hydraulic pump

Minimizing Interference from Radiated Electrical Noise

You may use either of the following output voltage ranges:
0-10V dc for the Allen-Bradley 1305 Drive or variable-volume pump
–10 to +10V dc for the proportional amplifier and proportional valve
Important: Signals in this type of control system are very susceptible to radiated electrical noise. The module is designed to set the loss-of­sensor bit I:e.0/8 and the LDT-error bit I:e.0/0 when it detects position values that are lost or corrupted by electrical noise.
Connect module output terminals to output devices with correct bonding:
connect power supply output commons together
electrically isolate power supply output commons from earth ground
use bond wires that are equal in size to signal wires
Minimize interference from radiated electrical noise with correct shielding and grounding:
connect all of the following to earth ground:
– LDT flange, frame, and machine – I/O chassis – protective ground – AC ground – cable shields at one end only, preferably with 3/8” braid wire (for analog output, "15V dc PS, 24V dc PS, and LDT) – terminal 4 of the input terminal block
Publication
1746-6.18 April 1998
Setting Up the Hardware
run shielded cables only in low-voltage conduit
place the SLC-500 processor, power supply, and I/O chassis
assembly in a suitable enclosure
Typical grounding and shielding for this type of control system:
4–3
LDT Power
LDT Signals
Cable Note: Use cable recommended by the LDT and amplifier manufacturer
.
Considerations for the "15V dc Supply
Cable Note
1746-QV Module
Input
1 2 3
5-8
4
Output
earth ground
"
15V Power Supply (+) (C) (–)
Analog Output
Piston-type Hydraulic Cylinder and Linear Displacement T
Case GND
Belden 8770
Belden 8761
ransducer (LDT)
LDT
Belden 8761
Servo Proportional Amplifier
0V
and Hydraulic Ram
24V Power Supply
(–) (+)
Cable Note
Valves
Case GND
Case GND
Selection of the "15V Power Supply
The positive and negative supply of some "15V dc power supplies decay at different rates when ac power is removed. The module’s output will be biased, based upon the difference in voltage level between the positive and negative supply. The duration is dependent upon the magnitude of the difference and the decay rate. For these reasons, the "15V dc power supply should have or be equipped with:
proper interlocks with machine operation and e-stop circuits
an internal voltage-sense relay that drops the "15V (without
variation in decay rates) upon loss of ac power
auxiliary relay to indicate proper operation and voltage
(such as loss of +15V but not –15 V dc)
Power
Supply Loading
The module and LDT load the power supply typically as follows:
Supply No Transducer
No Load
+15V dc 86mA 128mA 141mA 128mA –15V dc 14mA 30mA 30mA 40mA
*MTS Temposonics II, model T1SR0U0120R (Other LDTs will have different loading.)
Transducer Only *
LDT + Module: +10V dc @ 10mA
Publication
LDT + Module: –10V dc @ 10mA
1746-6.18 April 1998
4–4
Setting Up the Hardware
Application of the "15V Power Supply
The module uses the "15V dc power supply to drive the "10V dc valve output and to power the LDT. The module detects loss of "15V dc with its internal LDT diagnostic. The diagnostic concludes loss of "15V when it detects loss of LDT magnet.
Partial failure of the "15V dc power supply may cause limited machine operation when the LDT continues to operate properly. Some LDTs will operate with its supply voltage down to 12V. If you monitor the "15V dc with SLC diagnostics, you can enable a blocking valve to lock the actuator in its last position upon detection of:
e-stop
power loss
low voltage condition of the "15V dc supply
ATTENTION: If you provide a system e-stop circuit and design the system to manage power to the SLC chassis and "15V dc supply, in all cases DO NOT connect the e-stop to ac power for power supplies.

Other Design Considerations

ATTENTION: We recommend using reasonable methods to assure that unintended motion does not cause machine damage or create a safety issue with personnel who will operate the machine. (Chapter 5 covers testing for proper system operation.)
Use a proportional valve that does not respond to voltage spikes
created by power supply operation.
Shut down the hydraulic system upon loss of ac power and
automatically vent pressurized fluid back to the tank.
Provide ladder programming that interlocks the operation of the
power supply with permissives to run the hydraulic pump.
Connect a high-speed relay between the module and the valve
amplifier to drop-out the valve signal upon loss of ac power.
Publication
1746-6.18 April 1998

Operating the Module for the First Time

Chapter Objectives

Power Up the System

This chapter outlines the steps for operating the module for the first time with an operating hydraulic ram. We cover these steps:
power-up the system
test for proper system operation
troubleshoot possible problems
Starting with module and LDT power turned off, bring the system on-line for the first time as follows (refer to I/O wiring in chapter 4):
Check Wiring and Grounding
1. Disconnect the LDT connector at the head end.
2. Disconnect both of the module’s input and output terminal blocks.
3. Turn ON the power supplies for the LDT and SLC processor, and
check the LDT connector and module input terminal block for:
pin 1 +15V dc
pin 2 PS common
pin 3 –15V dc
4. Observe that the module’s fault LED (red) is ON.
5. Verify NO continuity between pin 2 (PS commons) and pin 4
(shield/frame) on the module’s input terminal block.
6. Verify NO continuity between the LDT cable shield and pin 2
(PS commons) on the module’s input terminal block.
7. Verify continuity between pin 2 (PS commons) on the module’s
input terminal block and the output common on the "15V dc PS that powers the LDT and module.
8. Verify continuity between pin 2 (PS commons) on the module’s
input terminal block and the (–) terminal on the +24V dc PS that powers the proportional amplifier.
9. Verify NO continuity between the +24V dc PS (–) connection
and earth ground.
10.Verify continuity between the shield of the amplifier output cable
and pin 2 (PS commons) on the module’s input terminal block.
11. Verify continuity between the cable shield (Belden 8761 or
equivalent) on the +24V dc PS and earth ground.
Publication
1746-6.18 April 1998
5–2
N
FA
Operating the Module
Get Ready to Move the Ram
1. Turn on the +24V dc PS that powers the amplifier.
2. Turn on the hydraulic pump and “null” the ram for no movement.
3. Turn off all power supplies.
4. Connect the LDT cable and input terminal block.
5. Turn on all power supplies.
6. Be sure that you have loaded the extend and retract profiles into
the module.
7. Observe module LEDs. The RUN LED (green) should be blinking.
If not blinking, refer to troubleshooting covered last in this chapter. Module LEDs indicate the following to assist you with the procedures:
This LED: Is: When the Module detects:
RUN (green)
FAULT (red)
For Series A Revision A: During startup, Run LED ON and Fault LED flashing indicate outputs are at 0V dc. During profiles, Fault LED is OFF.
Flashing output is at 0V dc ON OFF no internal faults Flashing ON an internal fault
profiles are loaded and output is active
an LDT fault
8. Observe that the output image table word 0 (O:e.0) is zero.
If not zero, toggle the value of N7:50 from 0 to 16 to 0. Reload the profiles by entering the value of 1 into N7:40. If profiles do not reload, refer to Troubleshooting on page 5-4.
9. With the output terminal block still disconnected, run the extend
profile by changing the value in N7:50 to 1. The RUN LED should change to ON. If not, refer to troubleshooting covered last.
Important: Reset the value in N7:50 to 0.
10.Connect the output terminal block.
Move the Ram
Important: When you set an output bit with your programming terminal, the commanded action takes place immediately.
1. Run the extend profile by momentarily changing the value in
N7:50 to 1, and observe the direction of ram movement in N7:61. If the ram moves in the wrong direction:
If using this type of valve and signal: Then reverse the:
proportional valve with "10V input sign (") of all voltage values and load them into the module hydraulic motor or ac drive with 0-10V input other solenoid on the directional valve (with ladder logic)
Publication
1746-6.18 April 1998
Operating the Module
2. After reversing the sign of voltages (if needed), run the extend
profile again by changing the value in N7:50 to 1. Observe that the direction of ram travel is correct.
Important: Reset the value in N7:50 to 0.
3. Check the position value reported in the status word, N7:61, as
you run the ram to the end of its travel. If the position data is reversed, you may need to change the data-direction bit (Ge:5/15) in the G file off-line as follows:
0 = position increases while moving away from LDT head
1 = position increases while moving toward LDT head
Important: You must reload profiles for either of these conditions:
Changing a value in the G file. (This clears the profiles).
When position data exceeds the position setpoint that is
farthest from the LDT head, the profile is disabled and you must modify position setpoints and reload the profiles.
4. Verify operation of the retract profile by changing the value in N7:50 to 2. Important: Reset the value in N7:50 to 0, afterwards.
5–3
Jog the Ram to the Reference Position
The reference position may require that you jog the ram beyond a position defined by the profile in the ladder program (appendix B). You may jog the ram as follows:
1. Observe the current position data (in I:e.1).
2. Modify profile position setpoint(s) to permit the ram to travel to the
required reference position using the current position. For example: If position data reads –100, change P1 to –1300 (length of the LDT)
3. Important: Reset the value in N7:50 to 0. Load the profiles into the module.
4. Run the extend profile by changing the value in N7:50 to 1, and jog the ram to the reference position.
5. At the reference position, the position data, I:e.1, (N7:61) will be an arbitrary value. Set the position data to the value of the preset reference by changing the value in N7:50 to 8 (N7:40 must = 0). Position data will change to preset reference (0 in this example).
6. Verify that N7:61 now reads zero at the reference position.
Important: Once you establish the reference position:
the module will maintain the preset reference’s position data in I:e.1
all profile position setpoints will be referenced to it
(until you clear Ge:6 by changing any G-file value or set another reference position. The preset reference is retained during power up.
Publication
1746-6.18 April 1998
5–4
Operating the Module

Test for Proper System Operation

Troubleshoot Possible Problems

ATTENTION: Test for proper system operation to verify that precautions to guard against unexpected motion perform as intended. (See Power Supply and Design Considerations in chapter 4)
Because of the wide variety of applications for this module, we leave the procedural details to you.
Look for proper system operation as you test for these conditions:
controlled system startup/shutdown when turning hydraulics on/off
startup/shutdown of ac to power supplies
("15V dc, SLC chassis, and 24V dc)
loss of LDT input
effect of the last-state-of-output bit (G-file, word 5, bit 13)
regarding one or more of the above
Using Status Bits for Errors Detected by the Module
The module is designed to detect and indicate status as follows (in the input image table word I:e.0 or N7:60 in the ladder program):
hardware operational faults
data entry errors when entering setpoints or setting control bits
acknowledgement of stored setpoints
Important: To clear error bits, toggle N7:50 from 0 to 16 to 0.
Bit #: Description: (for error & fault bits 0-8, status of 0 = OK, status of 1 = fault.)
0 The module sets this LDT error bit when it detects a:
– broken or mis-wired LDT cable – faulty LDT – incompatible LDT type (DPM or RPM) – missing LDT magnet
– loss of "15V dc PS 1 Module fault, such as EEPROM error. May turn outputs OFF (fault dependent) 2 The module sets this bit when it detects any of the following invalid command bits
or bit combinations in output image table word 0 (O:e.0):
– one or more of the reserved bits 9-15 were set
– bit 5 or 7 (position) was set concurrently with bit 6 or 8 (voltage)
– output enable bit 0 (extend) or 1 (retract) was set before loading valid profiles
– both output enable bits 0 (extend) and 1 (retract) were set concurrently
– started to run a profile after the module had flagged an LDT error (I:e.0/0) 3 You set one or more of the reserved bits 0-13 in G-file word 5 (Ge:5). 4 You entered an invalid length (word 3) or count (word 4) in the G file. 5 You entered an invalid LDT calibration (words 1 and/or 2) in the G file. 6 You entered position setpoint outside the range –32,768 to +32,767 in O:e.1-O:e.7. 7 You entered a voltage value outside the range of "10,000mV in O:e.1-O:e.7. 8 Loss of sensor. The module detected position data (in I:e.1) greater than the LDT
length plus the preset reference. Clear this bit by running a profile.
9-11 Reserved. Do NOT use.
Publication
1746-6.18 April 1998
Operating the Module
ha wrong ign .
Module reect pre- et reference when
Profile will not load into the odule.
Bit #: Description: (for error & fault bits 0-8, status of 0 = OK, status of 1 = fault.)
12 The module sets this bit after it stores retract position setpoints or voltage values,
or when retract profile is active. It remains set until another operation is performed.
13 The module sets this bit after it stores your position setpoints.
It resets it after you reset the “program position” bit (O:e.0/5 or O:e.0/7)
14 The module sets this bit after it stores your voltage values.
It resets it after you reset the “program voltage” bit (O:e.0/6 or O:e.0/8)
15 The module sets this bit when it detects the profile is active (output is applied).
Troubleshooting Table
If you observe this condition: Try this solution: Refer to this part of the manual:
5–5
Sensor signal (N7:61) has wrong sign ().
After download, sensor values do not match values in N7:61 before download.
Module rejects pre-set reference when N7:50 is toggled from 0 to 8 to 0.
Profiles will not load into the module.
Unable to initiate extend/retract profiles. Write ladder rung for extend profile, another for retract.
1. Change direction bit (Ge:5/15) and re–download. a) Enter values in G file, page 3-3.
2. Calibrate the sensor at opposite end of cylinder. Re-do Jog Ram to Reference, pg 5-3. After axis calibration (preset ref = set, and N7:50 = 8),
you must upload and save SLC data files in the PC.
1. Pre-set Ref in G file must be within profile range. Enter values in G file, page 3-3.
2. N7:40 must = 0 when setting N7:50 = 8.
1. Each profile setpoint must be within sensor’s range. Verify full-scale count in Ge:4, page 3-3.
2. Clear any errors by toggling N7:50 (0 to 16 to 0) Prior to step 8 in Get Ready to Move Ram.
3. N7:40 must = 0 when setting pre-set reference with N7:50 = 8.
Each must include appropriate permissives to enable a MOV instruction with Source (1 = extend, 2 = retract) and Destination = N7:50.
Conditions That Control Module Outputs
The module is designed to control its outputs as follows:
The module is designed to: When these conditions are satisfied:
apply profile voltages to the output
retain its outputs in last state
turn OFF its outputs any of the following:
all of the following: – valid extend and retract profiles are stored in the module – the “stop profile” bit (O:e.0/2) is reset. – a “run profile” bit (O:e.0/0 or O:e.0/1) is set
any of the following: – loss of backplane power ("15V dc PS remains applied) – loss of sensor (LDT)
– SLC mode change or LDT fault (G:e:0/13 = 0)
– LDT position exceeded the setpoint farthest from LDT head – loss of "15V dc PS – the “disable output” bit (O:e.0/2) is set – SLC mode change or LDT fault (G:e:0/13 = 1)
b) Move the Ram, step 3, page 5-3.
none
Re-do Jog Ram to Reference, pg 5-3.
Jog Ram to Reference, step 5, pg 5-3.
none
Publication
1746-6.18 April 1998
5–6
Notes:
Operating the Module
Publication
1746-6.18 April 1998

Electrical Specifications


Module Specifications
This appendix lists the specifications for the 1746-QV Open-loop Velocity Control Module.
215 mA at 5V dc (from backplane)
Power Requirements
I/O Chassis Location Any I/O-chassis slot except slot 0 Isolation
LDT Inputs
Compatible LDT Input Devices
Module Range and Resolution
Analog Output Accuracy of Voltage Output Within "1% of its programmed value
Module Update Time 2 ms
400 mA at +15V dc and 295 mA at –15V dc (from independent PS, typical but LDT dependent)
1500V ac optical isolation between LDT input and backplane
"Interrogate "Gate "15V dc PS
PS Common Shield/Frame
Linear Displacement Transducer such as: Balluff BTL-2-L2 or -M2 Gemco Quick-Stick II Santest GYRP or GYRG Temposonics II with DPM or RPM
160 inches "0.01 inch
0-10V dc @ 250 mA or –10 to +10V dc @ 250 mA


Physical Specifications

Environmental Specifications

Run ON Profile running, Output active (green): Flashing Output at 0V dc
LED Indicators
Module ID Code 13115 Maximum Wire Size Two 18 AWG wires per terminal on terminal block
Operating Temperature Storage Temperature Relative Humidity 5% to 95% (without condensation) Agency Certification
(when marked on product or package)
Fault OFF Module OK (red): Flashing LDT fault
ON Module fault
0°C to 60°C (32°F to 140°F) –40°C to +85°C (–40°F to +185°F)
CE marked for all applicable directives
Publication
1746-6.18 April 1998
Notes:
Module SpecificationsA–2
Publication
1746-6.18 April 1998



The following data define extend and retract profiles for the sample program:
Extend position setpoints #N7:0 Extend voltage values #N7:10 Retract position setpoints #N7:20 Retract voltage values #N7:30
This ladder program loads profiles into the module through the output image table. (The 1746-QV module is in slot 1 for this example.)
Rung 2.0 Program Profile | | S:1 N7:40 | |–––] [––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––(L)–––––––+ | 15 0 | | Rung 2:1 | | Set to |Extend |Positions |Voltages | | program |profile |stored |stored | | profile |complete Extend Position Setpts. | | | | N7:40 N7:8 I:1.0 I:1.0 +COP–––––––––––––––+ | |–––] [–––––––––]/[–––––––]/[––––––––]/[––––––––––––––––––+COPY FILE +–| | 0 0 13 14 |Source #N7:0| | | |Dest #O:1.0| | | |Length 8| | | +––––––––––––––––––+ | Rung 2:2 | Set to |Extend |Positions |Voltages | | program |profile |stored |stored | | profile |complete Extend Velocity Setpts. | | | | N7:40 N7:8 I:1.0 I:1.0 +COP–––––––––––––––+ | |–––] [–––––––––]/[–––––––] [––––––––]/[––––––––––––––––––+COPY FILE +–| | 0 0 13 14 |Source #N7:10| | | |Dest #O:1.0| | | |Length 8| | | +––––––––––––––––––+ | Rung 2:3 | Set to |Extend |Run/store |Positions |Voltages Extend | | program |profile |retract |stored |stored profile | | profile |complete complete | | | | N7:40 N7:8 I:1.0 I:1.0 I:1.0 N7:8 | |–––] [–––––––––]/[–––––––]/[––––––––]/[––––––] [––––––––––––––––+––––(L)––––+–| | 0 0 12 13 14 | 0 | | | | Program | | | | extend | | | | voltages | | | | O:1.0 | | | +––––(U)––––+ | | 6 | Rung 2:4 | Set to |Extend |Positions |Voltages | | program |profile |stored |stored | | profile |complete Retract Position Setpts.| | | | N7:40 N7:8 I:1.0 I:1.0 +COP–––––––––––––––+ | |–––] [–––––––––] [–––––––]/[––––––––]/[––––––––––––––––––+COPY FILE +–| | 0 0 13 14 |Source #N7:20| | | |Dest #O:1.0| | | |Length 8| | | +––––––––––––––––––+ |
Publication
1746-6.18 April 1998
Ladder ProgramB–2
Rung 2:5 | Set to |Extend |Run/store |Positions |Voltages | | program |profile |retract |stored |stored | | profile |complete Retract Velocity Setpts.| | | | N7:40 N7:8 I:1.0 I:1.0 I:1.0 +COP––––––––––––+ | |–––] [–––––––––] [–––––––] [––––––––] [––––––]/[––––––––––––+COPY FILE +–| | 0 0 12 13 14 |Source #N7:30| | | |Dest #O:1.0| | | |Length 8| | | +–––––––––––––––+ | Rung 2:6 | Set to |Extend |Run/store |Positions |Voltages Retract | | program |profile |retract |stored |stored profile | | profile |complete complete | | | | N7:40 N7:8 I:1.0 I:1.0 I:1.0 N7:8 | |–––] [–––––––––] [–––––––] [––––––––]/[––––––] [––––––––––––––––+––––(L)––––+–| | 0 0 12 13 14 | 1 | | | | Program | | | | retract | | | | voltages | | | | O:1.0 | | | +––––(U)––––+ | | 8 | Rung 2:7 | Set to |Extend |Retract Loading | | program |profile |profile profiles | | profile |complete |complete complete | | | | N7:40 N7:8 N7:8 N7:40 | |–––] [–––––––––] [–––––––] [––––––––––––––––––––––––––––––––––––+––––(U)––––+–| | 0 0 1 | 0 | | | | Extend | | | | Profile | | | | Complete | | | | N7:8 | | | +––––(U)––––+ | | | 0 | | | | Retract | | | | Profile | | | | Complete | | | | N7:8 | | | +––––(U)––––+ | Rung 2:8 1 | Set to | | program | | profile | | | | N7:40 +COP–––––––––––––––+ | |–––]/[–––––––––––––––––––––––––––––––––––––––––––––––+–+COPY FILE +–+–| | 0 | |Source #I:1.0| | | | | |Dest #N7:60| | | | | |Length 8| | | | | +––––––––––––––––––+ | | | | | | | | +MOV–––––––––––––––+ | | | +–+MOVE FILE +–+ | | |Source N7:50 | | | | 0 | | | |Dest O:1.0 | | | | 0 | | | +––––––––––––––––––+ | Rung 2:9 |–––––––––––––––––––––––––––––––––––+END+––––––––––––––––––––––––––––––––––––––+
Extend Positions Extend V
oltages Retract Positions Retract V
oltages
G-file for Module Configuration
Publication
1746-6.18 April 1998
Address Data
(radix = DECIMAL) #N7:0 32 –45 50 200 300 400 425 500 0 0 #N7:10 64 3000 3750 4000 4000 4000 4000 4000 0 0 #N7:20 128 –45 50 200 300 400 425 500 0 0 #N7:30 256 5000 6000 6000 3000 1000 50 25 0 0
G1:0 2056 890 640 12 1200
SLC Code for QV Module
LDT
Calibration
Length Counts
–32,768 0
Config W
ord 5 bit 15=1 (position increases toward LDT head)
Preset Reference

Input Image Table


SLC Processor Files
You use the following files when programming the SLC processor for an application with the 1746-QV module:
input image table to indicate status
G file to configure the module for its LDT
output image table for commands and loading profiles
Word 0 (I:e.0 or N7:60 in the ladder program) reports status such as hardware faults, your data-entry errors, and acknowledgement of profile data stored in the module. Word 1 reports position data. Words 2-7 report speeds of the previous profile.
Word #: Bit #: Description: (for error & fault bits 0-8, status of 0 = OK, status of 1 = fault.)
0
1 n/a Position data
2-7 n/a Speed segments 1-6, respectively
0 The module sets this LDT error bit when it detects a:
– broken or mis-wired LDT cable – faulty LDT – incompatible LDT type (DPM or RPM) – missing LDT magnet
– loss of "15V dc PS 1 Module fault, such as EEPROM error. May turn outputs OFF (fault dependent) 2 The module sets this bit when it detects any of the following invalid command bits or bit
combinations in output image table word 0 (O:e.0):
– one or more of the reserved bits 9-15 were set
– bit 5 or 7 (position) was set concurrently with bit 6 or 8 (voltage)
– output enable bit 0 (extend) or 1 (retract) was set before loading valid profiles
– both output enable bits 0 (extend) and 1 (retract) were set concurrently
– started to run a profile after the module had flagged an LDT error (I:e.0/0) 3 You set one or more of the reserved bits 0-13 in G-file word 5 (Ge:5). 4 You entered an invalid length (word 3) or count (word 4) in the G file. 5 You entered an invalid LDT calibration (words 1 and/or 2) in the G file. 6 You entered a position setpoint outside the range of –32,768 to +32,767 in O:e.1-O:e.7. 7 You entered a voltage value outside the range of "10,000mV in O:e.1-O:e.7. 8 Loss of sensor. The module detected position data (in I:e.1) greater than the LDT
length plus the preset reference. Clear this bit by running a profile.
9-11 Reserved. Do NOT use.
12 The module sets this bit after it stores the retract position setpoints or voltage values, or
when the retract profile is active. It remains set until another operation is performed.
13 The module sets this bit after it stores your position setpoints.
It resets it after you reset the “program position” bit (O:e.0/5 or O:e.0/7)
14 The module sets this bit after it stores your voltage values.
It resets it after you reset the “program voltage” bit (O:e.0/6 or O:e.0/8)
15 The module sets this bit when it detects the profile is active (output is applied).
. The module computes the speed of each segment and reports them in the subsequent profile (reports extend speeds during the next retract profile, etc.)

Publication
1746-6.18 April 1998
SLC Processor FilesC–2
For e a ple o enter an calibration of 8.9373
1 0 0 0
–32,768
0 1 1
+24,576
increa e towards
0 1 1
+24,576
head
Co and Bit Enable these bit
with your ladder logic.

G File

Use this file (Ge:0) to configure the module for use with the LDT. Example values are those from the sample ladder logic (appendix B).
Word: Function of G-file Word: Range: Description of G-file Word or Bit: Example:
0 Reserved. Do NOT use. n/a The processor stores a code for the 1746-QV module. 2056
words 1 & 2 refer to the gradient or transducer calibration value stamped on the name plate on the transducer housing.
1 LDT calibration: upper 3 digits 2 LDT calibration: lower 3 digits
800-999 ms/inch 000-999 ms/inch
For example: To enter an LDT calibration of 8.9373, use decimal radix and enter 893 in word 1 and 730 in word 2.
3 Full-scale length (L) of LDT 2vLv160 inch Enter the length of the LDT (160 inches max). 12 4 Full-scale count (C) 2vCvLx100 Typically C = L x 100.
1200
Position Data (I:e.1) = C/(L x 100)
LDT Calibration
5 Configuration Bits
15 14 13 12-0 Equivalent V 0 1 0 0 1 0 0 0 1 1 0 0
0
0
+16,384 –32,768 –16,384
bits 0-12 Set to zero.
alue
bit 13 0 = output maintained during LDT fault or SLC mode change
1 = output resets for LDT fault or SLC mode change
bit 14 Type of LDT: 0 for RPM, 1 for DPM
–32,768
(bit for position increases
LDT head)
bit 15 0 = position data increases when moving away from LDT head
1 = position increases when moving toward LDT head
6 Preset Reference –32,768 to +32,767 Typically zero or home reference value. 32,767 = 327.67 inches. 0
Examples of Full-scale Count Values
893 730
15 = 1

Output Image Table

Word: Function of Output Image Word: Bit #: Description: (For command bits, a 0-to-1 transition enables the command)
0 Command Bits
1-7 Position 1-7 Setpoint or Voltage
(i.e. word 2 = position 2, etc.)
LDT Physical Length
No. of Recirculations
Resolution
Full-scale Length (L)
Full-scale Counts (C)
from 160” to 2” 1 0.01 L (160” to 2”) L x 100 16” 2 0.01 160 8000 16” 4 0.01 160 4000 16” 10 0.001 160 16000
The ladder program loads commands and profile data into the module through the output image table, O:e.0–O:e.7.
0 Set to run an extend profile.
s
1 Set to run a retract profile. 2 Set to disable the profile. This bit over-rides bit 0 or 1. 3 Set to change current position data to the value of preset reference in Ge:6. 4 Set to clear any data-entry errors. 5 Set to define words 1-7 as programmed position setpoints for extend. 6 Set to define words 1-7 as programmed voltage values for extend. 7 Set to define words 1-7 as programmed position setpoints for retract. 8 Set to define words 1-7 as programmed voltage values for retract.
9-15 Reserved. Do NOT use.
n/a Important:
Enter position setpoints in units of 0.01” (200 = 2.00”) within the range of –327.68 to +327.67”, and voltage values in 5mV units (3005 = 3.005V) within the range of "10,000mV.
Publication
1746-6.18 April 1998

A
access
to BBS or Internet, 3-1, 3-2
applications of module, 1-2
B
BBS, Rockwell Software Bulletin Board, 3-1 benefits, of module, 1-2 bits
command, 3-4, C-2 G-file configuration, 3-3, B-2, C-2 status, 5-4, C-1
C
cables, 4-3 calibration (value) of LDT, 3-3, B-2, C-2 configure
G file, 3-3, B-2, C-2 motion profiles, 1-2, 3-4 SLC processor
connections,
inputs to module, 4-1 outputs from module, 4-2
count, full-scale, 3-3
, 3-2
I, J, K
ID
of module, 3-2, A-1 input terminal block, of module, 4-1, 5-1 input image table (status), 5-4, C-1 Internet, access to, 3-2
L,M
ladder program, B-1 LDT
calibration value, 3-3 configuration in G file, 3-3 connections to, 4-1 fault, 5-2, 5-4 length of, 3-3 movement of, 3-5 types of, 4-1
LEDs, 5-2, A-1
N
N file, 3-4, 5-2, B-1 noise, electrical, 4-2
O
D
data direction (bit), 3-3, 3-5, 5-3, C-2 data, profile, 3-4, 3-5, B-2, C-2 download, from BBS, 3-1
E
error
, see fault
extend profile, 1-2, 3-4, 5-2, C-2
F
fault, module and LDT
, 5-2, 5-4, C-1
G,H
G file, 3-2, 3-3, 3-5, 3-6, 5-3, B-2, C-2 grounding, 4-2, 4-3, 5-1
output
conditions, 5-5 connections, of module, 4-2, 5-1 image table, 3-4, C-2 terminal block, 4-2 status, 5-4
overview of module and system, 1-1
P
position data, 3-4, 3-5, 5-3, C-1 position setpoints, 3-4, 3-5, 5-2, 5-3, C-2 power supply, considerations, 4-3 preset reference, 3-3, 5-3 profile, 1-2, 3-3, B-1, C-2
conventions, 3-5 operation of, 3-5
I–2
Q
quick
start, 2-1
R
ram, hydraulic, 1-1, 1-2
procedure to move, 5-2, 5-3
set reference position of, 5-3 reference, preset, 3-3, 5-3 retract profile, 1-2, 3-4, 5-3 reverse motion, 5-2
S
segments, speed, 1-2, 3-4, 3-5
(also see voltage values) shielding, of cables, 4-2, 4-3, 5-1 specifications, of module, A-1 status (input image table) 5-4, C-1
of outputs, 5-4 system, power up, 5-1
T, U, V
testing,
for proper system operation, 5-4 travel, length of LDT troubleshooting, with
LEDs, 5-2 module status bits, 5-4 output conditions, 5-5 troubleshooting table, 5-5
voltage values, 3-4, 3-5, 5-2, C-2
W, X, Y
wiring,
system, 4-1, 4-2, 5-1
, 1-2, 3-3
, Z
Publication
1746-6.18 April 1998
Worldwide representation.
Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve
productivity and quality for more than 90 years. We design, manufacture and support a broad
range of automation products worldwide. They include logic processors, power and motion
control devices, operator interfaces, sensors and a variety of software. Rockwell is one of the
world’s leading technology companies.
Argentina • Denmark • Ecuador • Egypt • El Salvador Ireland Philippines Sweden
Australia • Austria • Bahrain • Belgium
Israel Italy Jamaica Poland • Portugal • Puerto Rico • Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore
Switzerland T
Japan • Jordan • Korea • Kuwait • Lebanon
aiwan
Thailand T
Brazil
Finland
urkey • United Arab Emirates • United Kingdom • United States • Uruguay • V
Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic
France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia •
Malaysia Mexico
Netherlands
New
Slovakia Slovenia
Zealand • Norway
South Africa, Republic • Spain
enezuela • Y
ugoslavia
Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444
Publication
Supercedes
1746-6.18 April 1998
Publication 1746-6.18 – February 1998
Copyright 1998 Allen-Bradley Company
Pakistan
Peru
PN955132-83
, Inc. Printed in USA
Loading...