Because of the variety of uses for the products described in this
publication, those responsible for the application and use of this
control equipment must satisfy themselves that all necessary steps
have been taken to assure that each application and use meets all
performance and safety requirements, including any applicable laws,
regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown
in this guide are intended solely for purposes of example. Since there
are many variables and requirements associated with any particular
installation, Allen-Bradley does not assume responsibility or liability
(to include intellectual property liability) for actual use based upon
the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some
important differences between solid-state equipment and
electromechanical devices that should be taken into consideration
when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole
or part, without written permission of Rockwell Automation, is
prohibited.
Throughout this manual we use notes to make you aware of safety
considerations:
ATTENTION
Identifies information about practices or
circumstances that can lead to personal injury or
death, property damage or economic loss
!
Attention statements help you to:
identify a hazard
•
avoid a hazard
•
recognize the consequences
•
IMPORTANT
ControlNet is a trademark of Rockwell Automation
SLC 500 is a trademark of Rockwell Automation.
RSLogix 500 is a trademark of Rockwell Automation.
Belden is a trademark of Belden, Inc.
Identifies information that is critical for successful
application and understanding of the product.
Overview
Table of Contents
Preface
Who Should Use this Manual. . . . . . . . . . . . . . . . . . . . . . . P-1
Read this preface to familiarize yourself with the rest of the manual.
This preface covers the following topics:
who should use this manual
•
the purpose of this manual
•
contents of this manual
•
related documentation
•
common techniques used in this manual
•
Allen-Bradley support
•
Who Should Use this
Manual
Purpose of this Manual
Use this manual if you are responsible for the design, installation,
programming, or maintenance of an automation control system that
uses Allen-Bradley small logic controllers.
You should have a basic understanding of SLC 500™ products. You
should understand electronic process control and be able to interpret
the ladder logic instructions required to generate the electronic signals
that control your application.
If you do not, contact your local Allen-Bradley representative for the
proper training before using this product.
This manual is a learning and reference guide for the 1746-NI16
Analog Input Module. It contains the information you need to install,
wire, and configure the module. It also provides diagnostic and
troubleshooting information and application examples.
1Publication 1746-UM001A-US-P
Preface 2
Contents of this Manual
ChapterTitleContent
PrefaceDescribes the purpose, background, and scope
of this manual. Also specifies the audience for
whom this manual is intended and gives
directions to using Allen-Bradley support
services. Provides listing of related
documentation.
1OverviewProvides a hardware and system overview.
Explains and illustrates the theory behind the
input module.
2Quick Start for
Experienced Users
3Installation and
Wiring
4Preliminary Operating
Considerations
5Channel
Configuration
Data and Status
6Module Diagnostics
and Troubleshooting
7Application ExamplesExamines both basic and supplementary
Appendix ASpecificationsProvides physical, electrical, environmental, and
Appendix BConfiguration
Worksheet
Appendix CTwo’s Complement
Binary Numbers
Serves as a Quick Start Guide for the
experienced user.
Provides installation information and wiring
guidelines.
Gives you the background information you need
to understand how to address and configure the
module for optimum operation as well as how to
make changes once the module is in a run state.
Examines the channel configuration word and
the channel status word, bit by bit, and explains
how the module uses configuration data and
generates status during operation.
Explains how to interpret and correct problems
that may occur while using the module.
applications and gives examples of the ladder
logic necessary to achieve the desired result.
functional specifications for the module.
Provides a worksheet to help configure the
module for operation.
Describes the two’s compliment binary number
system.
Publication 1746-UM001A-US-P
Appendix DCalibrationDescribes how to calibrate the 1746-NI16
module.
GlossaryLists key terms and abbreviations.
Preface 3
Related Documentation
The following documents contain information that may be helpful to
you as you use Allen-Bradley SLC products. If you would like a
manual, you can:
download a free electronic version from the internet:
•
www.theautomationbookstore.com
purchase a printed manual by:
•
– contacting your local distributor or Rockwell Automation
representative
– visiting www.theautomationbookstore.com and placing
your order
– calling 1.800.963.9548 (USA/Canada)
or 001.330.725.1574 (Outside USA/Canada)
ForRead This DocumentDocument
Number
An overview of the SLC 500 family of productsSLC 500™ System Overview1747-2.30
A description on how to install and use your Modular SLC
500 programmable controller
A description on how to install and use your Fixed SLC 500
programmable controller
A procedural and reference manual for technical personnel
who use an HHT to develop control applications
An introduction to HHT for first-time users, containing basic
concepts but focusing on simple tasks and exercises, and
allowing the reader to quickly begin programming
A reference manual that contains status file data and
instruction set information for the SLC 500 processors and
MicroLogix 1000 controllers.
In-depth information on grounding and wiring Allen-Bradley
programmable controllers
A description on how to install a PLC-5R systemPLC-5™ Family Programmable Controllers
A description of important differences between solid-state
programmable controller products and hard-wired
electromechanical devices
An article on wire sizes and types for grounding electrical
equipment
Installation & Operation Manual for Modular
Hardware Style Programmable Controllers
Installation & Operation Manual for Fixed
Hardware Style Programmable Controllers
Allen-Bradley Hand-Held Terminal User Manual1747-NP002
Getting Started Guide for HHT1747-NM009
SLC 500™/ MicroLogix 1000™ Instruction Set
Reference Manual
Allen-Bradley Programmable Controller Grounding
and Wiring Guidelines
Hardware Installation Manual
Application Considerations for Solid-State ControlsSGI-1.1
National Electrical CodePublished by the
1747-6.2
1747-6.21
1747-6.15
1770-4.1
1785-6.6.1
National Fire
Protection
Association of
Boston, MA.
A complete listing of current Allen-Bradley documentation,
including ordering instructions. Also indicates whether the
documents are available on CD-ROM or in multi-languages.
A glossary of industrial automation terms and abbreviationsAllen-Bradley Industrial Automation GlossaryAG-7.1
Allen-Bradley Publication IndexSD499
Publication 1746-UM001A-US-P
Preface 4
Common Techniques Used
in this Manual
Allen-Bradley Support
The following conventions are used throughout this manual:
Bulleted lists such as this one provide information, not
•
procedural steps.
Numbered lists provide sequential steps or hierarchical
•
information.
Text in
•
Key names appear in bold, capital letters within brackets (for
•
example,
Allen-Bradley offers support services worldwide, with over 75 Sales/
Support Offices, 512 authorized Distributors and 260 authorized
Systems Integrators located throughout the United States alone, plus
Allen-Bradley representatives in every major country in the world.
this f o nt
[ENTER]
indicates words or phrases you should type.
).
Local Product Support
Contact your local Allen-Bradley representative for:
sales and order support
•
product technical training
•
warranty support
•
support service agreements
•
Technical Product Assistance
If you need to contact Allen-Bradley for technical assistance, please
review the information in the Troubleshooting chapter first. Then call
your local Allen-Bradley representative.
Your Questions or Comments on this Manual
If you find a problem with this manual, please notify us of it on the
enclosed Publication Problem Report.
If you have any suggestions for how this manual could be made more
useful to you, please contact us at the address below:
Allen-Bradley
Control and Information Group
Technical Communication, Dept. A602V, T122
P.O. Box 2086
Milwaukee, WI 53201-2086
Publication 1746-UM001A-US-P
Chapter
1
Overview
This chapter describes the 1746-NI16 analog input module and
explains how the SLC 500 processor gathers analog input data from the
module. Included is information about:
the module’s hardware and diagnostic features
•
an overview of system operation
•
General Description
The module receives and stores digitally converted analog data into its
image table for retrieval by all fixed and modular SLC 500 processors.
The modules, 1746-NI16V and 1746-NI16I, support connections for up
to 16 voltage or current analog sensors.
The 1746-NI16 is a multi-class (Class 1 or Class 3) single-slot module.
(1)
Class 1
Class 3 configuration utilizes 32 input words and 32 output words.
Fixed and SLC 5/01 processors can only operate as Class 1. When the
module is used in a remote I/O chassis with a 1747-ASB, it can only
operate in Class 1 mode. The SLC 5/02, SLC 5/03, SLC 5/04 and
SLC 5/05 processors can be configured for either Class 1 or Class 3.
When the module is used in a remote ControlNet™ chassis with a
1747-ACN(R), it can also operate in either Class 1 or Class 3 mode.
Operate the module in Class 3 mode whenever possible.
The 16 high-impedance input channels can be wired as single-ended
inputs. The module provides a direct interface to the following input
types:
configuration utilizes 8 input words and 8 output words.
±10V dc
•
1 to 5V dc
•
0 to 5V dc
•
0 to 10V dc
•
0 to 20 mA
•
4 to 20 mA
•
±
20 mA
•
0 to 1 mA
•
(1)
Requires use of block transfer in a remote configuration.
1Publication 1746-UM001A-US-P
1-2 Overview
The data presented to the processor can be configured as:
Engineering Units
•
Scaled-for-PID
•
Proportional Counts (-32,768 to +32,767 range)
•
Proportional Counts with User Defined Range (Class 3 Only)
•
1746-NI4 Data Format
•
Each input channel also provides open-circuit, out-of-range, and
invalid configuration indication via the LED’s. These conditions are
also displayed in the channel status word.
Hardware Features
The module fits into any slot, except the processor slot (0), in either
an SLC 500 modular system or an SLC 500 fixed system expansion
chassis (1746-A2).
Channel Status
LEDs (Green)
Module Status LED
(Green)
Removable Terminal Block
The module contains a removable terminal block, providing
connection for 16 analog input channels, which are specifically
designed to interface with analog current and voltage input signals.
The channels can only be wired as single-ended inputs. There are no
output channels on the module. The module is configured via the
user program. The following graphic displays the main hardware
features.
Label
Cable Tie Slots
Publication 1746-UM001A-US-P
Self-locking Tabs
Hardware FeatureFunction
Overview 1-3
Channel Status LED
Indicators
Module Status LEDDisplays module operating and fault status.
Side Label (Nameplate)Provides module information.
Removable Terminal
Block
Door LabelPermits easy terminal identification.
Cable Tie SlotsSecures and routes wiring from the module.
Self-Locking TabsSecures module in the chassis slot.
Displays channel operating and fault status.
Provides physical connection to input
devices.
General Diagnostic Features
The 1746-NI16 module contains diagnostic features to help identify
the source of problems that may occur during power-up or during
normal channel operation. These power-up and channel diagnostics
are explained in Chapter 6, Module Diagnostics and Troubleshooting.
The module communicates to the SLC 500 processor through the
parallel backplane interface and receives power from the SLC 500
power supply through the backplane. The +5V dc backplane supply
powers the SLC circuitry and the +24V dc backplane supply powers
the module analog circuitry. No external power supply is required.
You may install as many 1746-NI16 analog modules in a 1746 chassis
as the chassis power supply can support.
System Overview
The NI16I can only receive current inputs. The NI16V can only receive
voltage inputs.
System Operation
At power-up, the module performs a check of its internal circuits,
memory, and basic functions. During this time, the module status LED
remains off. If no faults are found during the power-up diagnostics,
the module status LED is turned ON.
After power-up checks are complete, the module waits for valid
channel configuration data from the SLC ladder logic program
(channel status LEDs off). After configuration data is written to one or
more channel configuration words and the channel enable status bits
are set, the channel status LEDs are turned ON and the module
continuously converts the analog input to a value within the range
selected in the configuration word.
Publication 1746-UM001A-US-P
1-4 Overview
Each time a channel is read by the module, that data value is tested by
the module for a fault condition (i.e., open-circuit, over-range, and
under-range). If a fault condition is detected, a unique bit is set in the
channel status word and the channel status LED blinks.
The SLC processor reads the converted analog data from the module
at the end of the program scan or when commanded by the ladder
program. If the processor and module determine that the backplane
data transfer was made without error, the data is used in your ladder
program. A graphic representation of this is shown below.
Data Transfer Between the Module and Processor (shown for one channel)
Voltage or Current
Analog Channel Input
1746-NI16
Analog
Input
Module
Channel Data Word
Channel Status Word
Channel Configuration Word
from Ladder Program
SLC 500
Processor
Module Operation
The 1746-NI16 module’s input circuitry consists of four
analog-to-digital (A/D) converters. Each of the 4 A/D converters
multiplex 4 inputs for a total of 16 single-ended inputs.
The A/D converters read the selected input signal and convert it to a
digital value. The multiplexer sequentially switches each input
channel to the module’s A/D converter. Multiplexing provides an
economical means for a single A/D converter to convert multiple
analog signals. However, multiplexing also affects the speed at which
an input signal can change and still be detected by the converter.
Publication 1746-UM001A-US-P
Module Calibration
The 1746-NI16 module is already factory calibrated and ready for use.
Although factory calibration is suitable for most applications, the
module can be calibrated by the user. See Appendix D for more
information on calibration.
Chapter
2
Quick Start for Experienced Users
This chapter can help you to get started using the 1746-NI16 analog
input module. The procedures here are based on the assumption that
the user has an understanding of SLC 500™ products. The user should
understand electronic process control and be able to interpret the
ladder logic instructions required to generate the electronic signals
that control the application.
Because this chapter is a start-up guide for experienced users, this
chapter does not contain detailed explanations about the procedures
listed. It does, however, reference other chapters in this book where
you can get more information about applying the procedures
described in each step. It also references other documentation that
may be helpful if you are unfamiliar with programming techniques or
system installation requirements.
Required Tools and
Equipment
If you have any questions or are unfamiliar with the terms used or
concepts presented in the procedural steps, always read the referenced chapters and other recommended documentation before
trying to apply the information.
This chapter will:
tell you what equipment you need
•
explain how to install and wire the module
•
show you how to set up one channel for analog input
•
examine the state of the LEDs at normal startup
•
examine the channel status word
•
Have the following tools and equipment ready:
medium blade screwdriver
•
medium cross-head screwdriver
•
analog input device
•
cable for wiring inputs to module
•
SLC processor and power supply installed in chassis
•
analog input module (1746-NI16)
•
programming device and software
•
1Publication 1746-UM001A-US-P
2-2 Quick Start for Experienced Users
Procedures
1.Check the contents of shipping box.Reference
Unpack the shipping box making sure that the contents include:
analog input module (Catalog Number 1746-NI16)
•
removable terminal block (factory-installed)
•
Installation Instructions
•
If the contents are incomplete, call your local Allen-Bradley representative for assistance.
2.Ensure that your chassis and power supply support the 1746-NI16 module.Reference
If you are installing the module in a hazardous location, read “Hazardous Location Considerations” on page 3-1.
Review the power requirements of your system to ensure that your chassis supports the module:
If you are combining a 1746-NI16 module with another I/O module in a fixed controller, refer to the I/O
•
module compatibility table found in Chapter 3.
For modular style systems, calculate the total load on the system power supply using the procedure
•
described in the
the
SLC 500 Family System Overview
The 1746-NI16 backplane current consumption is 125 mA at 5V dc and 75 mA at 24V dc.
•
SLC Installation & Operation Manual for Modular Style Controllers
(publication 1747-2.30).
(publication 1747-6.2) or
Chapter 3
(Installation and
Wiring)
Appendix A
(Specifications)
Publication 1746-UM001A-US-P
Quick Start for Experienced Users 2-3
3.Insert the 1746-NI16 module into the chassis.Reference
ATTENTION
Never install, remove, or wire modules with power applied to the chassis or devices
wired to the module.
!
Make sure system power is off; then insert the module into your 1746 chassis.
In this example procedure, local slot 1 is selected. Any slot may be used except 0.
Chapter 3
(Installation and
Wiring)
Top and Bottom
Module Releases
Card
Guide
4.Connect sensor cable.Reference
Connect sensor cable to the module’s terminal block.
Important:
Follow these guidelines when wiring the module:
Use shielded communication cable (Belden™ 8761) and keep length as short as possible.
•
Connect only one end of the cable shield to earth ground.
•
Connect all the shields to the earth ground at the SLC 500™ chassis mounting tab.
•
Single-ended source commons may be jumpered together at the terminal block.
•
Channels are not isolated from each other. All analog commons are connected together internally.
•
Common mode voltage range is ±10.25 volts. The voltage between any two terminals must be less than
•
20.5 volts.
The module does not provide power for the analog input transmitters or sensors.
•
Use a power supply that matches the transmitter (sensor) specifications.
•
Terminal Bl ock
IN 0
IN 2
IN 4
IN 6
Analog Com
IN 1
IN 3
IN 5
IN 7
Analog Com
Sensor Cable
Chapter 3
(Installation and
Wiring)
Publication 1746-UM001A-US-P
2-4 Quick Start for Experienced Users
5.Configure the system.Reference
Configure your system I/O for the particular slot the 1746-NI16 is in (slot 1 in this example). Enter the module ID
code. The ID code is for Class 1 interface or Class 3 interface. See Chapter 4 for more information on Class 1 and
Class 3 interfaces.
Chapter 4
(Preliminary
Operating
Considerations)
Important:
Not all programming software supports configuration for Class 3 operation.
Advanced Programming Software (APS) supports Class 3 configuration, after entering the ID code.
•
SLC 500 A.I. Series Programming Software supports Class 3 configuration, after entering the ID code.
•
RSLogix 500, version 1.30 or later, supports Class 3 configuration, after entering the ID code.
•
Earlier versions of RSLogix 500 only supports configuration for Class 1 operation. Contact Rockwell
•
Software for information on upgrading your software.
Appendix C
(Converting from
1746-NI4 or
1746-NI8 to
1746-NI16)
Device’s user
manual.
6.Determine the operating parameters.Reference
Determine the operating parameters for channel 0. This example shows the channel 0 configuration word. The
module is in slot 1. The default configuration word is all zeros.
On powerup, the first pass bit (S:1/15)
is set for one scan, enabling the MOV
instruction that transfers the channel
configuration word 0. This configures
and enables channel 0.
Chapter 7
(Application Examples)
Publication 1746-UM001A-US-P
Quick Start for Experienced Users 2-7
8.Write the ladder program.Reference
Write the remainder of the ladder logic program that specifies how your analog input
data is processed for your application. In this procedure the module is located in slot 1.
1112131415910867450123
0000000000000000
Bit Number
Channel 0 data Word
(Variable input data)
1746-NI16 Module Input Image - Data Word
I:1.0Channel 0 data word
I:1.1Channel 1 data word
I:1.2Channel 2 data word
I:1.3Channel 3 data word
I:1.4Channel 4 data word
I:1.5Channel 5 data word
I:1.6Channel 6 data word
(Channel Configuration,
(Application Examples)
Your programming device’s
(1)
Class 1
14-bit integer (bits 1 and 0 = 00)
14-bit integer (bits 1 and 0 = 00)
14-bit integer (bits 1 and 0 = 00)
14-bit integer (bits 1 and 0 = 00)
14-bit integer (bits 1 and 0 = 00)
14-bit integer (bits 1 and 0 = 00)
14-bit integer (bits 1 and 0 = 00)
Chapter 5
Data and Status)
Chapter 7
user manual.
Class 3
(2)
16-bit integer
(2)
16-bit integer
(2)
16-bit integer
(2)
16-bit integer
(2)
16-bit integer
(2)
16-bit integer
(2)
16-bit integer
I:1.7Channel 7 data word
I:1.8Channel 8 data word
I:1.9Channel 9 data word
I:1.10Channel 10 data word
I:1.11Channel 11 data word
I:1.12Channel 12 data word
I:1.13Channel 13 data word
I:1.14Channel 14 data word
I:1.15Channel 15 data word
(1) In Class 1, the error is ± 3 LSB of the Class 3 resolution.
(2) Bits 1 and 0 of the data word are overwritten in Class 1 to indicate data from Channels 0 to 7
(3) Bits 1 and 0 of the data word are overwritten in Class 1 to indicate data from Channels 8 to 15
14-bit integer (bits 1 and 0 = 00)
14-bit integer (bits 1 and 0 = 01)
14-bit integer (bits 1 and 0 = 01)
14-bit integer (bits 1 and 0 = 01)
14-bit integer (bits 1 and 0 = 01)
14-bit integer (bits 1 and 0 = 01)
14-bit integer (bits 1 and 0 = 01)
14-bit integer (bits 1 and 0 = 01)
14-bit integer (bits 1 and 0 = 01)
(2)
16-bit integer
(3)
16-bit integer
(3)
16-bit integer
(3)
16-bit integer
(3)
16-bit integer
(3)
16-bit integer
(3)
16-bit integer
(3)
16-bit integer
(3)
16-bit integer
Publication 1746-UM001A-US-P
2-8 Quick Start for Experienced Users
9.Go through the system start-up procedure.Reference
Apply power. Download your program to the SLC 500 processor and put the controller into Run mode. During
a normal start up, the module status LED and any enabled channel status LED turn on.
Chapter 6
(Module Diagnostics and
Troubleshooting)
INPUT
0-34-7
Channel
Status LEDs
Module Status LED
ANALOG MODULE
8-1112-15
10.Check that the module is operating correctly.Reference
(Optional) If the Module Status LED is off, or if the Channel 0 LED is off or blinking, refer to Chapter 6.
Class 3 Interface - Monitor the status of input channel 0 to determine its configuration setting and
operational status. This is useful for troubleshooting when the blinking channel LED indicates that an error
Chapter 5
(Channel Configuration,
Data and Status)
has occurred. The example below shows the Class 3 status word for channel 0 with no errors.
Chapter 6
(Module Diagnostics and
Troubleshooting)
12415 14 1311 10987 6532
0011110 000 00 00
Publication 1746-UM001A-US-P
10
00
Bit Number
Channel 0 Status Word (I:1.8)
• Class 1 Data or Status Configuration
• Input Type
• Data Format
• Calibrate Channel Status
• Filter Frequency
• Error Conditions
Chapter 7
(Application Examples)
Installation and Wiring
This chapter tells you how to:
avoid electrostatic damage
•
determine the chassis power requirement for the module
•
choose a location for the module in the SLC chassis
•
install the module
•
wire the module’s terminal block
•
wire input devices
•
Chapter
3
Hazardous Location
Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, D or non-hazardous locations only. The following ATTENTION
statement applies to use in hazardous locations.
ATTENTION
!
EXPLOSION HAZARD
Substitution of components may impair suitability
•
for Class I, Division 2.
Do not replace components or disconnect
•
equipment unless power has been switched off.
Do not connect or disconnect components unless
•
power has been switched off.
This product must be installed in an enclosure.
•
1Publication 1746-UM001A-US-P
3-2 Installation and Wiring
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements
de Classe 1, Division 2, Groupes A, B, C, D ou non dangereux. La
mise en garde suivante s’applique à une utilisation dans des
environnements dangereux.
MISE EN GARDE
!
DANGER D’EXPLOSION
La substitution de composants peut rendre
•
cet équipement impropre à une utilisation en
environnement de Classe 1, Division 2.
Ne pas remplacer de composants ou
•
déconnecter l'équipement sans s'être assuré
que l'alimentation est coupée.
Ne pas connecter ou déconnecter des
•
composants sans s'être assuré que
l'alimentation est coupée.
Ce produit doit être installé dans une
•
armoire.
Electrostatic Damage
Electrostatic discharge can damage semiconductor devices inside this
module if you touch backplane connector pins. Guard against
electrostatic damage by observing the following precautions.
ATTENTION
Electrostatic discharge can degrade performance or
cause permanent damage. Handle the module as
stated below.
!
Wear an approved wrist strap grounding device when handling
•
the module.
Touch a grounded object to rid yourself of electrostatic charge
•
before handling the module.
Handle the module from the front, away from the backplane
•
connector. Do not touch backplane connector pins.
Keep the module in its static-shield bag when not in use, or
•
during shipment.
Publication 1746-UM001A-US-P
Installation and Wiring 3-3
1746-NI16 Power
Requirements
Module Location in Chassis
The 1746-NI16 module receives its power through the SLC 500™
chassis backplane from the fixed or modular +5V dc/+24V dc chassis
power supply. The +5V dc backplane supply powers the SLC circuitry,
and the +24V dc backplane supply powers the module analog
circuitry. The maximum current drawn by the module is shown in the
table below.
5V dc Amps24V dc Amps
0.1250.075
When you are using a modular system configuration, add the values
shown in the table above to the requirements of all other modules in
the SLC chassis to prevent overloading the chassis power supply.
When using a fixed system controller, see “Fixed Expansion Chassis
Considerations” on page 3-3.
Modular Chassis Considerations
Place your 1746-NI16 module in any slot of an SLC 500 modular, or
modular expansion chassis, except for the extreme left slot (slot 0) in
the first chassis. This slot is reserved for the processor or adapter
modules.
ATTENTION
For applications using the upper limit of the
operating temperature range, the 1746-NI16 module
(or multiple 1746-NI16 modules) should be placed in
the right most slot(s) of the chassis. The specification
for operating temperature is:
!
Operating Temperature Range
0°C to 60°C (32°F to 140°F) in any slot except slot 0
Fixed Expansion Chassis Considerations
The chart on page 3-4 depicts the range of current combinations
supported by the fixed I/O expansion chassis. To use it, first find the
backplane current draw and operating voltage for both of the modules
you plan to use in the chassis. The table on page 3-4 shows these
specifications.
Publication 1746-UM001A-US-P
3-4 Installation and Wiring
OA16 and IA16 (0, 455)
OW16 and IA16 (180, 255)
Plotted from example
shown on page 3-5.
Current (mA) at 5V dc
Current (mA) at 24V dc
Next, plot each of the currents on the chart. If the point of intersection
falls within the operating region, your combination is valid. If not,
your combination cannot be used in a 2-slot, fixed I/O chassis. See
the example on page 3-5.
BAS15040IN16850NT46040
BASn150125INT41100OA81850
BLM10000 IO43025OA163700
BTM11085IO86045OAP123700
DCM3600IO129070OB6EI460
FIO4I55150IO12DC8060OB81350
FIO4V55120ITB16850 OB162800
HS3000ITV16850OB16E1350
HSTP12000IV8500OB32, series D 1900
IA4350IV16850OB32E1900
IA8500IV32, series D 500OBP81350
IA16850KE15040OBP162500
IB8500KEn150125OG161800
IB16850NI42585OV81350
IB32, series D 500NI8200100OV162700
IC16850NI1612575OV32, series D 1900
IG161400NIO4I55145OVP162500
IH16850NIO4V55115OW16170180
IM4350NO4I55195OW44545
IM8500NO4V55145OW88590
IM16850NR45050OX88590
Publication 1746-UM001A-US-P
Installation and Wiring 3-5
Fixed Chassis Example
The following example shows how to use the chart and table on
page 3-4 to determine if the module combination of an 1746-IN16 and
1746-NI16 is supported by the fixed I/O chassis.
1. Find the current draws of both modules in the table.
IN16 = 85 mA at 5V dc and 0 mA at 24V dc
NI16 = 125 mA at 5V dc and 75 mA at 24V dc
2. Add the current draws of both modules at 5V dc.
85 mA + 125 mA = 210 mA
3. Plot this point on the chart above (210 mA at 5V dc).
4. Add the current draws of both modules at 24V dc.
0 mA + 75 mA = 75 mA
5. Plot this point on the chart above (75 mA at 24V dc).
The resulting point of intersection is marked with an “x” on the chart
above, showing that this combination falls within the operating region
of the fixed I/O chassis.
IMPORTANT
When using the table, be aware that there are certain
conditions that affect the compatibility characteristics of
the BASIC module (BAS) and the DH-485/RS-232C
module (KE).
When you use the BAS module or the KE module to
supply power to a 1747-AIC Link Coupler, the Link
Coupler draws its power through the module. The
higher current drawn by the AIC at 24V dc is
calculated and recorded in the table for the modules
identified as BASn (BAS networked) or KEn (KE
networked). Make sure to refer to these modules if
your application uses the BAS or KE module in this
way.
Publication 1746-UM001A-US-P
3-6 Installation and Wiring
General Considerations
Most applications require installation in an industrial enclosure to
reduce the effects of electrical interference. Analog inputs are highly
susceptible to electrical noise. Electrical noise coupled to the analog
inputs reduces the performance (accuracy) of the module.
Group your modules to minimize adverse effects from radiated
electrical noise and heat. Consider the following conditions when
selecting a slot for the analog input module. Position the module:
in a slot away from sources of electrical noise such as
•
hard-contact switches, relays, and AC motor drives
away from modules which generate significant radiated heat,
•
such as the 32-point I/O modules (series C or earlier)
In addition, route shielded analog input wiring away from any
high-voltage I/O wiring.
Compliance to European
Union Directives
This product is approved for installation within the European Union
and EEA regions. It has been designed and tested to meet the
following directives.
EMC Directive
The 1746-NI16 analog input module is tested to meet Council
Directive 89/336/EEC Electromagnetic Compatibility (EMC) and the
following standards, in whole or in part, documented in a technical
construction file:
EN 50081-2
•
EMC - Generic Emission Standard, Part 2 - Industrial
Environment
EN 50082-2
•
EMC - Generic Immunity Standard, Part 2 - Industrial
Environment
This product is intended for use in an industrial environment.
Publication 1746-UM001A-US-P
Installation and Wiring 3-7
Module Installation and
Removal
When installing the module in a chassis, it is not necessary to remove
the terminal block from the module. However, if the terminal block is
removed, use the write-on label located on the side of the terminal
block to identify the module location and type.
SLOT
MODULE
•
RACK
Terminal Block Removal
ATTENTION
Remove power before removing or inserting this
module. When you remove or insert a module with
power applied, an electrical arc may occur. An
electrical arc can cause personal injury or property
damage by:
!
sending an erroneous signal to your system’s field
•
devices, causing unintended machine motion.
causing an explosion in a hazardous environment
•
Electrical arcing causes excessive wear to contacts on
both the module and its mating connector. Worn
contacts may create electrical resistance.
To remove the terminal block:
1. Loosen the two terminal block release screws.
2. Grasp the terminal block at the top and bottom and pull
outward and down.
Terminal Block Release
Screws
Publication 1746-UM001A-US-P
3-8 Installation and Wiring
Module Installation Procedure
1. Read the “Module Location in Chassis” section beginning on
page 3-3.
2. Align the circuit board of the analog input module with the card
guides located at the top and bottom of the chassis.
3. Slide the module into the chassis until both top and bottom
retaining clips are secured. Apply firm, even pressure on the
module to attach it to its backplane connector. Never force the
module into the slot.
4. Cover all unused slots with the Card Slot Filler, catalog number
1746-N2.
Top and Bottom
Module Release(s)
Card
Guide
Module Removal Procedure
1. Press the releases at the top and bottom of the module and slide
the module out of the chassis slot.
2. Cover all unused slots with the Card Slot Filler, catalog number
1746-N2.
Publication 1746-UM001A-US-P
Loading...
+ 90 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.