Regency U21 User Manual

4 (1)

E21 Gas Insert

Owners &

Installation Manual

www.regency-fire.com

MODELS: E21-NG3 Natural Gas E21-LP3 Propane

WARNING:

If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.

FOR YOUR SAFETY

Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.

Installation and service must be performed by a qualified installer, service agency or the gas supplier.

FOR YOUR SAFETY

What to do if you smell gas:

Do not try to light any appliance

Do not touch any electrical switch: do not use any phone in your building.

Immediately call your gas supplier from a neighbour's phone. Follow the gas supplier's instructions.

If you cannot reach your gas supplier, call the fire department.

Tested by:

Installer: Please complete the details on the back cover and leave this manual with the homeowner.

Homeowner: Please keep these instructions for future reference.

918-671c

FPI FIREPLACE PRODUCTS INTERNATIONAL LTD. 6988 Venture St., Delta, BC Canada, V4G 1H4

01/17/12

CONGRATULATIONS!

You are the owner of a state-of-the-art Gas Insert by:

FPI FIREPLACE PRODUCTS INTERNATIONAL LTD.

The Regency® Gas Fireplace Series has been designed to provide you with all the warmth and charm of a fireplace, at the flick of a switch. The models E21-NG3 and E21-LP3 of this series have been approved by Warnock Hersey for safety. As it also bears our own mark, it promises to provide you with economy, comfort and security for many trouble free years to follow. Please take a moment now to acquaint yourself with these instructions and the many features of your Regency® Fireplace.

2

Regency® E21-3 Gas Fireplace Insert

 

Regency U21 User Manual

INSTALLATION

40-1/8"

22-11/16"

9-7/8”

51

Low Profile Faceplate Dimensions

* Standard size shown, custom size also available.

3

Regency® E21-3 Gas Fireplace Insert

TABLE OF CONTENTS

 

SAFETY LABEL

 

Serial No. Decal ...........................................................

4

REQUIREMENTS

 

MA Code - CO Detector ................................................

5

INSTALLATION

 

Before You Start ............................................................

7

Important Message ......................................................

8

General Safety Information............................................

8

Policy for Solid Fuel Burning & Factory Built Fireplaces9

Installation Checklist......................................................

9

Minimum Fireplace Clearances.....................................

9

Clearances to Combustibles........................................

10

Gas Connection...........................................................

11

High Elevation .............................................................

11

Wiring Diagrams..........................................................

12

Flue Connector Installation .........................................

13

Gas Pipe Pressure Testing ..........................................

14

Offset Flue Adaptor......................................................

14

Venting.........................................................................

14

Combustion and Ventilation Air....................................

14

Valve Description.........................................................

15

Test for Flue Spillage...................................................

15

Optional Brick Panel....................................................

15

Gas Insert Aeration system ........................................

15

Log Set Installation......................................................

16

Faceplate & Trim Installation .......................................

20

Flush Glass.................................................................

21

Flush Louvers..............................................................

21

Optional Bay Front.......................................................

22

Bay Louvers.................................................................

22

Conversion from NG to LP ..........................................

23

Full Screen doors ........................................................

26

Low profile faceplate installation..................................

28

Low profile hearth trim installation...............................

30

Remote Control ...........................................................

31

Wall Switch ..................................................................

31

Wall Thermostat ..........................................................

31

Final Check..................................................................

32

OPERATING INSTRUCTIONS

 

Operating Instructions ................................................

32

Lighting Procedure ......................................................

32

Shutdown Procedure...................................................

32

First Fire ......................................................................

32

Copy of Lighting Plate Instructions .............................

33

Automatic Convection Fan Operation..........................

34

Normal Operating Sounds of Gas Appliances.............

34

MAINTENANCE

 

Maintenance Instructions.............................................

34

Log Replacement ........................................................

34

Glass Gasket...............................................................

34

Gold-plated Accessories..............................................

34

Door Glass Replacement ............................................

35

Removing Valve Assembly ..........................................

35

Removing the Fan .......................................................

35

PARTS LIST

 

Main Assembly ............................................................

36

Burner Assembly & Log Set.........................................

37

Bay & Flush Front Assembly .......................................

38

Low profile faceplate ...................................................

39

Faceplate Assembly ....................................................

39

WARRANTY

 

Warranty ....................................................................

44

4

Regency® E21-3 Gas Fireplace Insert

 

This is a copy of the label that accompanies each Regency® Gas Insert. We have printed a copy of the contents here for your review.

The safety label is located on the front inside base of the unit visible when the bottom louver is open.

Note: Regency® units are constantly being improved. Check the label on the unit and if there is a difference, the label on the unit is the correct one.

Please note that with the addition of thermostat control and outside combustion air supply, this unit is approved for bedroom installations.

For the State of Massachusetts, installation and repair must be done by a plumber or gasfitter licensed in the Commonwealth of Massachusetts.

For the State of Massachusetts, flexible connectors shall not exceed 36 inches in length.

For the State of Massachusetts, the appliances individual manual shut-off must be a t-handle type valve.

The State of Massachusetts requires the installation of a carbon monoxide alarm in accordance with NFPA 720 and a CO alarm with battery back up in the same room where the gas appliance is installed.

SAFETY LABEL

 

THISREMOVENOTDO LABEL/ NE PAS ENLEVER CETTE ÉTIQUETTE

 

Serial No./

No de Serie

Clearances to Combustibles/

Materiaux

undansqueinstalleetrepeutNefoyer non Combustibles:

évacuation.àgazaufoyerceavecairàltrefi

convertedbeenhasreplacefiThisWARNING:for use

cannotandonlyinsertreplacefigasawithbe used for

 

approved-rereplacefitheandreplaced,beenhave by Top of unit to

jurisdiction.havingauthoritythe

NEMILA/LYPPUSLACIRTCELE TAT I O N B 14"/355mm

than/MoinslessELECTRIQUE:115V60HZde 2 AMP.

918-672b

327

 

Thisreplace.fibuiltfactorylistedreplace,fi vented

 

B.C.,Delta,Ltd.,InternationalProductsCanada

DuplicateSerialNo.

 

 

327

NG3-E21INSERT:FIREPLACEE21-LP3 APPAREIL FONCTIONNANT CONCU POUR For installation into a ventedcombustibleMinimumnon-

Des Minimum Degagement

 

/ wall to unit of Side

 

Cote:

9"/229mm A

1372m)-(610610m)-(0(0-1372m) burning wood or solid fuels unlessoriginalpartsall

 

dessus: Au / mantle

Btu/h22,000Btu/h23,500inputMaximum22,500 Btu/h Debit calorifique maximum

Btu/h11,000Btu/h11,750inputMinimum11,250 Btu/h Debit calorifique minimum

COMBUSTIBLEDUAVECUTILISERPASNEFUEL.SOLIDWITHUSEFORNOT SOLIDE. MADE IN CANADA / FABRIQUE AU CANADA

HEATERFIREPLACEGASVENTEDListed:

CGA2007,-2.33a-2007/CSA-Z21.88aANSIto:Tested2.17-M91

altitude.highatuseforapplianceredfiGas

U.S.A.andCANADApour:for/CertifeeedCertifi 4001172

12.0"kPa)(1.25WC/C.E.5.0"pressuresupplyMinimumGaz)(NaturelGasNaturalWC/C.E.Propane(2.99 kPa) ETREPressionINSEREd’alimentationDANS UNminimumFOYER gas fireplace heater is not for uselters.withairfi

11.0"kPa)(0.95WC/C.E.3.8"highpressureManifoldWC/C.E. (2.74 kPa) Pression tublure d'échappement élevée combustible muni d'un event. Neutiliserpasde

2.9"kPa)(0.27WC/C.E.1.1"lowpressureManifoldWC/C.E. (0.72 kPa) Pression tublure d'échappement basse

ft.4500-2000ft.2000-0Altitude0-4500 ft. L'altitude

DMS44DMS43sizeceOrifi54 DMS Grandeur de l’injecteur

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FireplaceFPI

Model/

E21-NG3

E21-LP3

Modele:

5

Regency® E21-3 Gas Fireplace Insert

REQUIREMENTS

MA Code - CO Detector

(for the State of Massachusetts only)

5.08: Modifications to NFPA-54, Chapter 10

(2) Revise 10.8.3 by adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors

a.In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent floor level.

b.In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

2.APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.

3.SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight

(8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, "GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL

OBSTRUCTIONS".

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1.The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented" in the most current edition of NFPA 54 as adopted by the Board; and

2.Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

1. Detailed instructions for the installation of the venting system design or the venting system components; and

2. A complete parts list for the venting system design or venting system.

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies "special venting systems", the following requirements shall be satisfied by the manufacturer:

1. The referenced "special venting system" instructions shall be included with the appliance or equipment installation instructions; and

2. The "special venting systems" shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

6

Regency® E21-3 Gas Fireplace Insert

 

BEFORE YOU START

Safe installation and operation of this appliance requires common sense, however, we are required by the Canadian Safety Standards and ANSI

Standards to make you aware of the following:

INSTALLATION AND REPAIR SHOULD BE DONE BY AN AUTHORIZED SERVICE PERSON. THE APPLIANCE SHOULD BE INSPECTED BEFORE USE AND AT LEAST ANNUALLY BY A PROFESSIONAL SERVICE PERSON. MORE FREQUENT CLEANING MAY BE REQUIRED DUE TO EXCESSIVE LINT FROM CARPETING, BEDDING MATERIAL,ETC.IT IS IMPERATIVETHAT CONTROLCOMPARTMENTS,BURNERS ANDCIRCULATINGAIRPASSAGEWAYS OF THE APPLIANCE BE KEPT CLEAN.

DUE TO HIGH TEMPERATURES, THE APPLIANCE SHOULD BE LOCATED OUT OF TRAFFIC AND AWAY FROM FURNITURE AND DRAPERIES.

WARNING: FAILURE TO INSTALL THIS APPLIANCE CORRECTLY WILL VOID YOUR WARRANTY AND MAY CAUSE A SERIOUS HOUSE FIRE.

CHILDREN AND ADULTS SHOULD BE ALERTED TO THE HAZARDS OF HIGH SURFACE TEMPERATURES, ESPECIALLY THE FIREPLACE GLASS, AND SHOULD STAY AWAYTO AVOID BURNS OR CLOTHING IGNITION.

INSTALLATION

YOUNG CHILDREN SHOULD BE CARE-

FULLY SUPERVISED WHEN THEY ARE

IN THE SAME AREA AS THE APPLI-

ANCE. TODDLERS,YOUNG CHILDREN

AND OTHERS MAY BE SUSCEPTIBLE

TO ACCIDENTAL CONTACT BURNS. A

PHYSICALBARRIERSISRECOMMEND-

ED IFTHERE ARE AT RISK INDIVIDUAL

INTHE HOUSE. TO RESTRICT ACCESS

TO A FIREPLACE OR STOVE, INSTALL

AN ADJUSTABLE SAFETY GATE TO

KEEP TODDLERS, YOUNG CHILDREN

AND OTHER AT RISK INDIVIDUALS OUT

OF THE ROOM AND AWAY FROM HOT

SURFACES.

CLOTHING OR OTHER FLAMMABLE

MATERIAL SHOULD NOT BE PLACED

ON OR NEAR THE APPLIANCE.

7

Regency® E21-3 Gas Fireplace Insert

INSTALLATION

IMPORTANT MESSAGE

SAVE THESE

INSTRUCTIONS

The Regency® Gas Fireplace must be installed in accordance with these instructions. Carefully read all the instructions in this manual first. Consult the "authority having jurisdiction" to determine the need for a permit prior to starting the installation. It is the responsibility of the installer to ensure this fireplace is installed in compliance with the manufacturer's instructions and all applicable codes.

GENERAL SAFETY

INFORMATION

1)The appliance installation must conform with local codes or, in the absence of local codes, with the current Canadian or National Gas Codes, CAN1-B149 orANSI Z223.1 Installation

Codes.

2)The appliance when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes with the current

National Electrical Code,ANSI/NFPA70 or CSA

C22.1 Canadian Electrical Code.

3)See general construction and assembly instructions. The appliance and vent should be enclosed.

4)This appliance must be connected to the specified vent and termination cap to the outside of the building envelope. Never vent to another room or inside a building. Make sure that the vent is installed as per Venting instructions.

5)This appliance may only be installed in a vented, solid fuel burning masonry, listed factory built

fireplace, or zero clearance kit part # 530-936.

6)ThisapplianceisListedforbedroom installations when used with a Listed Millivolt Thermostat.

Some areas may have further requirements, check local codes before installation.

7)This appliance is Listed forAlcove installations, maintain minimum Alcove clearances as follows, minimum ceiling height of 53-1/2", minimum width of 48" and a maximum depth of 36".

8)This unit is not approved for installation into a mobile home.

9)Inspect the venting system annually for blockage and any signs of deterioration.

10)Any safety glass removed for servicing must be replaced prior to operating the appliance.

11)To prevent injury, do not allow anyone who is unfamiliar with the operation to use the fireplace insert.

12)Wear gloves and safety glasses for protection while doing required maintenance.

13)Ensure adequate combustion and ventilation air.

14)Under no circumstances should this appliance be modified. Parts that have to be removed for servicing should be replaced prior to operating this appliance.

15)Installation and any repairs to this appliance should be done by a qualified service person.

A professional service person should be called to inspect this appliance annually. Make it a practice to have all of your gas appliances checked annually.

16)Do not slam shut or strike the glass door.

17)Under no circumstances should any solid fuels (wood, paper, cardboard, coal, etc.) be used in this appliance.

18)The appliance area must be kept clear and free of combustible materials, (gases and other flammable vapours and liquids).

19)Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the electrical control system and any gas control which has been under water.

20)WARNING: Failure to position the parts in accordance with the diagrams in this manual or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.

21)WARNING: Operation of this appliance when not connected to a properly installed and maintained venting system or tampering with the blocked vent shut-off system can result in carbon monoxide (CO) poisoning and possible death.

Emissions from burning wood or gas could contain chemicals known to the State of California to cause cancer, birth defects or other reproductive harm.

8

Regency® E21-3 Gas Fireplace Insert

 

POLICY FOR SOLID FUEL BURNING & FACTORY BUILT FIREPLACES

The Regency® E21 may be installed and vented into any solid fuel fireplace that has been installed in accordance with the National, Provincial and local building codes and is constructed of noncombustible materials.

1)Installer must mechanically attach the supplied label to the inside of the firebox of the fireplace into which the gas fireplace insert is installed.

"WARNING: This fireplace has been converted for use with a gas fireplace insert only and cannot be used for burning wood or solid fuels unless all original parts have been replaced, and the fireplace re-approved by the authority having jurisdiction."

2)Do not cut any sheet-metal parts of the

fireplace, in which the gas fireplace insert is to be installed.

3)Ifthefactory-builtfireplacehasnogasaccess hole(s) provided, an access hole of 1-1/2"

(37.5mm) or less may be drilled though the lowersidesorbottomofthefireboxinaproper workmanship like manner. This access hole must be plugged with a non-combustible insulation after the gas supply line has been installed.

4)Thefireplacefluedampercanbefullyblocked open or removed for installation of the gas

fireplace insert.

5)The fireplace and fireplace chimney must be clean and in good working order and constructed of non-combustible materials.

6)The chimney cleanouts must fit properly.

7)Refractory (firebricks), glass doors, screen rails, screen mesh and log grates can be removed from the fireplace before installing the gas fireplace insert.

8)Smoke shelves, shields and baffles may be removedifattachedbymechanicalfasteners.

If any part is removed it must not weaken the structural integrity of the factory built.

9)Trim panels or surrounds shall not seal ventilation openings in the fireplace.

INSTALLATION

CHECKLIST

1)Locate your appliance. Refer to the "Clearances to Combustibles" and "Minimum

Fireplace Clearances" sections.

2)Make gas and electrical connections. Refer to the "Gas Connection" section.

Test the pilot. Must be as per diagram in the

"Valve Description" section.

3)Install Flue Connector. Refer to the "Flue Connector Installation" section.

4)Install vent. Refer to the "Venting" section.

5)Test Gas pressure. Refer to the "Gas Pipe Pressure Testing" section.

Check aeration. Refer to the "Gas Insert Aeration System" section.

6)Test for flue spillage. Refer to the "Test for

Flue Spillage" section.

7)Install standard and optional features. Refer to the following sections where applicable:

a.Brick Panel

b.Faceplate & Trim

c.Flush Glass

d.Flush Louver

e.Full Screen Doors

f.Remote Control

g.Wall Switch

h.Wall Thermostat

8)Final check. Refer to the "Final Check" section.

Before leaving this unit with the customer, the installer must ensure that the appliance is firing correctly and operation fully explained to customer.

This includes:

1)Clocking the appliance to ensure the correct

firing rate (rate noted on label) after burning appliance for 15 minutes.

2)Ifrequired,adjustingtheprimaryairtoensure that the flame does not carbon. First allow the unit to burn for 15-20 min. to stabilize.

3)Ensurethattheapplianceisventingcorrectly.

CAUTION: Any alteration to the product that causes sooting or carboning that results in damage is not the responsibility of the manufacturer.

INSTALLATION

MINIMUM FIREPLACE

CLEARANCES

Diagram shows the minimum fireplace opening required to be able to install the Regency® gas

fireplace insert.

13-1/8” (333mm)

Low profile faceplate

Note: If you are installing the 3" offset flue adaptor

(532-920) , the minimum fireplace dimensions are as follows:

Width (at front):

29-1/8" (740mm)

Depth:

17" (381mm)

Height:

18-5/8" (473mm)

9

Regency® E21-3 Gas Fireplace Insert

INSTALLATION

CLEARANCES TO COMBUSTIBLES

The minimum clearance from the side of the appliance to a combustible

Note: A non-combustible mantel may be installed at a lower height

side wall is 9 inches (229mm). The minimum clearance from the top of

 

if the framing is made of metal studs covered with a non-

the louver to a combustible mantel is 14 inches (356mm). The minimum

 

combustible board.

height from the top of the louver to the ceiling is 36 inches (914mm).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Regency® E21-3 Gas Fireplace Insert

 

GAS CONNECTION

Only persons licensed to work with gas piping may make the necessary gas connections to this appliance.

The gas connection is a 3/8" NPT accessible on the left side of the unit. The gas line connection may be made of rigid pipe, copper pipe or an approved flex connector. (If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA

B149 installation code.

For USA installations follow local codes and/or the current National Fuel Gas Code, ANSI

Z223.1.

When using copper or flex connectors use only approved fittings.Always provide a union so that gas lines can be easily disconnected for burner or fan servicing. Flare nuts for copper lines and

flex connectors are usually considered to meet this requirement.

Important: Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.

For minimum and maximum supply pressure see the System Data table.

1)If the appliance is to be installed into an existing chimney system, thoroughly clean the masonry fireplace that has been chosen for the Regency® Gas Fireplace.

2)The appliance is provided with an opening on the left hand side of the control compartment for the gas line.

Note: During any pressure testing of the gas supplypipingsystemthatexceedstestpressures of 1/2 psig, this appliance and its individual shut-off valve must be disconnected from the piping system. If test pressures equal to or less than 1/2 psig are used then this appliance must be isolated from the piping system by closing its individual manual shut-off valve during the testing.

CAUTION: If the glass is removed for servicing, it must be replaced prior to operating the appliance. The glass must be fixed in the closed position when operating.

INSTALLATION

System Data

 

For altitude:

Natural Gas

0-2000 ft.

 

 

Propane:

0-4500 ft.

 

 

 

 

 

Burner Inlet Orifice Sizes:

 

 

 

 

Natural Gas

Propane

 

Burner

 

#43

#54

 

 

 

 

 

 

 

Max. Input Rating

 

 

 

 

- Natural Gas

23,500 Btu/h

 

- Propane

 

22,500 Btu/h

 

 

 

 

 

 

Min. Input Rating

 

 

 

 

- Natural Gas +/-5%

11,750 Btu/h

 

-Propane +/-5%

11,250 Btu/h

 

 

 

 

 

 

Supply Pressure

 

 

 

 

Natural Gas

 

min.

5.0" w.c.

 

Propane

 

min.

12.0" w.c.

 

 

 

 

 

Manifold Pressure (High)

 

 

 

Natural Gas

 

3.8"

+/- 0.2" w.c.

 

Propane

 

11"

+/- 0.2" w.c.

 

Circulation Fan: 120 VAC, 60 Hz

 

Variable Speed: 127 CFM, thermally

 

activated

 

 

 

 

 

 

 

 

NATURAL GAS E21-NG3

 

For altitude:

2000 ft - 4500 ft.

 

Burner Inlet Orifice Size:

44 DMS

 

Max. Input Rating

22,000 Btu/h

 

Min. Input Rating

+/-5%

11,000 Btu/h

HIGH ELEVATION

This unit is approved in Canada for altitude

0 to 4500 ft. (CAN/CGA 2.17-M91) with the orifice supplied.

11

Regency® E21-3 Gas Fireplace Insert

INSTALLATION

WIRING DIAGRAMS

This heater does not require a 120VA.C. supply for operation. In case of a power failure, the burner switch and the optional remote control/ thermostat will continue to operate. However, a 120V A.C. power supply is needed for the fan/blower operation.

Caution: Ensure that the wires do not touch any hot surfaces and are away from sharp edges.

When connected with 120 volts, the appliance must be electrically grounded in accordance with local codes or, in the absence of local

codes the current CSA C22.1 (in Canada) or with the National Electrical Code ANSI/NFPA

70-1987 (in USA).

NOTE: This unit is equipped with a heat sensor thermodisc which will prevent the blower from operating until the unit reaches the correct temperature.

For NATURAL GAS Units and Units NOT Equipped with DC Spark Boxes

#8 Ground Lug

 

 

 

Grounding

 

 

 

 

 

Green

 

 

 

 

 

 

 

 

 

 

 

Ground

 

 

 

Nut

 

 

 

Lug Detail

 

 

 

 

 

 

Fan

 

 

 

 

 

 

 

 

 

 

 

 

 

Lockwasher

Fan ground

Thermopile

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Star washer

 

 

 

 

GasPilot

 

 

Neutral

 

 

 

 

 

Nut

 

 

 

 

Electrode

 

 

 

 

 

 

 

 

Power cord

 

 

 

 

 

 

 

 

 

 

 

 

Ground

 

 

 

 

 

 

 

ground wire

120V AC Live

 

 

 

Black

 

 

 

 

 

 

 

 

 

Star washer

 

 

 

 

60 Hz

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Red

Black

 

Black

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pilot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Assembly

 

 

 

 

Fan

 

Rotary Speed

 

 

 

 

 

 

 

 

 

 

 

 

 

Control

 

 

 

 

 

 

 

 

 

 

 

Thermodisc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Thermocouple In

 

Piezo

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ignitor

 

 

 

 

 

 

Gas

ILO T

 

ON

I

 

 

 

 

 

 

Black

ON

 

In

P

 

 

H

White

 

 

 

 

 

 

Burner

 

 

FF

O

OL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brown

 

 

 

 

 

Red

OFF

 

 

 

 

 

 

Red

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

"S.I.T" Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF ON

Thermostat

 

 

 

 

 

 

 

 

 

 

 

Vent Spill

 

 

Remote Transmitter

 

 

 

 

 

 

 

 

Switch

 

Remote

(Millivolt)

 

 

(Optional)

 

 

 

 

 

 

 

 

(Auto Reset)

 

Receiver

(Optional)

 

 

Regency

 

 

 

 

 

 

 

 

 

 

(Optional)

 

 

 

 

 

 

 

 

 

 

 

 

 

(Millivolt)

 

 

 

 

 

CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.

WARNING: Electrical Grounding

Instructions

This appliance is equipped with a three pronged (grounding) plug for yourprotectionagainstshockhazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the grounding prong from this plug.

12

Regency® E21-3 Gas Fireplace Insert

 