Regency P40-LP1, P40-NG1 User Manual

0 (0)
Regency P40-LP1, P40-NG1 User Manual

Gas Fireplaces

P40 Gas Fireplace

P40 Direct Vent Gas Fireplace

Model

P40-NG1

P40-LP1

Fuel Type

Natural Gas

Propane

 

 

 

Minimum Supply Pressure

5” W.C. (1.25 kPa)

12” W.C. (3.00 kPa)

 

 

 

Manifold Pressure - High

3.5” W.C. (0.87 kPa)

10” W.C. (2.49 kPa)

 

 

 

Manifold Pressure - Low

1.6” W.C. (0.39 kPa)

3.6” W.C. (0.89 kPa)

 

 

 

Orifi ce Size - Front Burner

#44 DMS

#55 DMS

 

 

 

Orifi ce Size - Rear Burner

#35 DMS

#53 DMS

 

 

 

Minimum Input

13,000 BTU/h (3.81 kW)

12,000 BTU/h (3.51 kW)

 

 

 

Maximum Input

45,000 BTU/h (13.19 kW)

43,000 BTU/h (12.60 kW)

 

 

 

Vent Sizing

5” Inner / 8” Outer

5” Inner / 8” Outer

 

 

 

Approved Venting Systems

Flex Vent Systems:

FPI AstroCap™ Flex Vent

Rigid Pipe Vent Systems:

Simpson Dura-Vent® Direct Vent GS

 

Selkirk Direct-Temp

B

A

C

D

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit Dimensions

Description

 

 

 

 

P40

 

 

 

 

 

 

 

 

 

 

A

Front Face Width

 

 

 

 

40” (1016mm)

B

Rear Firebox Width

 

 

 

 

33-7/16” (889mm)

C

Front Face Height

 

 

 

 

34” (864mm)

D

Height w/ Standoff

 

 

 

 

42-1/2” (1080mm)

E

Unit Depth

 

 

 

 

20-1/16” (508mm)

F

Height to Vent

 

 

 

 

35-1/4” (826mm)

 

 

 

 

 

 

 

 

 

 

Framing Dimensions

Description

 

 

 

 

P40

 

 

 

 

 

 

 

 

 

 

G

Framing Width

 

 

 

 

40-1/2” (1029mm)

H***

Framing Height***

 

 

 

42-1/2” (1080mm)*** + Hearth

I

Framing Depth

 

 

 

 

20-1/16” (508mm)

J

Corner Wall Length

 

 

 

 

50-5/8” (1286mm)

K

Corner Facing Wall Width

 

 

 

 

71-5/8” (1524mm)

L

Minimum Height to Combustibles

 

 

 

 

51-7/8” (1318mm)

M

Vent Centerline Height

 

 

 

 

45-3/8” (1153mm)

N

Non-Combustible Facing Height

 

 

 

 

10-1/4” (260mm)

O

Gas Connection Height

 

 

 

 

1-1/2” (38mm)

P

Gas Connection Inset

 

 

 

 

4-3/4” (121mm)

Q

Gas Connection Width

 

 

 

 

3-1/4” (102mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit requires 120V to operate. See

“Wiring Diagram,” on page 17, for more details. Receptacle is included with manual.

L

 

Drywall

 

 

(or other

Top Header

 

facing)

 

 

(non-combustible)

Top Header

N

 

(non-combustible)

Non-Combustible Facing

H

11" (279mm) dia. Hole through wall Vent.

G

I

M

J

O

P Q

K

Opening for gas connection

Please refer to Page 11 (Exterior Vent Terminations) for additional guidelines on vent locations.

***Important: Framing height requires consideration of the hearth depth. Dimension H = H + the thickness of installed hearth.

June 2007 Regency Product Specifications Book

45

Fireplaces Gas

Gas Fireplaces

P40 Gas Fireplace

Framing and Finishing

1)Frame the enclosure for the unit with framing material. Use the determined total thickness of facing material (e.g. drywall plus ceramic tiles) to adjust the framing depth to allow the fi nished surface to be fl ush with the front of the unit. Total facing thickness can vary from 1/2” (13mm) to 1-1/4” (32mm) thick.

Note: Header for the P40 must be non combustible.

2)For exterior walls, insulate the enclosure to the same degree as the rest of the house, apply vapor barrier and drywall, as per local installation codes. (Do not insulate the fireplace itself.)

3)Ensure that all of the clearances listed below are met. Combustible material may be brought up to the sides of the unit and be covered with ceramic tiles, bricks, rock or other suitable combustible

fi nishing materials. Non-combustible facing is required above the unit. (See Dimension “N” on page 41)

Note: You must maintain proper clearances from the vent to combustible materials (See Below).

4)Use metal studs for framing where the minimum clearance from the vent to combustible material cannot be maintained.

Clearance Requirements

Required hearth must be non-combustible. (Page 43)

Required non-combustible facing above unit. (See Dimension “N” on page 41)

D

C

A

F

B

B

 

 

 

H

 

 

 

 

 

 

 

 

 

I

 

 

 

 

 

 

G

 

 

E

 

 

 

 

 

 

 

 

 

 

 

 

 

Clearance:

 

Dimension

 

 

 

Measured From:

A: Mantel Height

 

12” (305mm)

 

Minimum (Additional on this page)

B: Sidewall

 

8” (203mm)

 

 

 

Side of installed front

C: Ceiling

 

39” (991mm)

 

 

 

Top of installed unit

D: Mantel Depth

 

13” (330mm)

 

Maximum (Additional on this page)

E: Alcove Width

 

56” (1422mm)

 

Sidewall to Sidewall (Minimum)

F: Alcove Depth

 

36” (914mm)

 

Front to back wall (Maximum)

G: Hearth Height

 

1-1/2” (39mm)

 

Floor to top of Hearth. (Hearth must

 

 

 

 

not be higher than base of fi rebox.)

H: Hearth Width

 

40” (1016mm)

 

 

Edge to Edge of Hearth

I: Hearth Depth

 

16” (406mm)

 

 

 

Front of Hearth to Wall

46

 

 

 

 

 

 

Gas Fireplaces

Vent Clearances

Clearance Dimension

Horizontal - Top

2-1/2” (64mm)

Horizontal - Side

1-1/2” (38mm)

Horizontal - Bottom

1-1/2” (38mm)

Vertical (Flex or Rigid)

1-1/4” (32mm)

WARNING

Failure to maintain required clearances is a major cause of chimney related fires. Installation of this fireplace must comply with these clearances.

Hearth Requirements

A 40" (1016mm) wide x 16" (406mm) deep x 1-1/2" (38mm) thick hearth is required, unless the unit is raised 4" (102mm).

All measurements are from the bottom of the unit. Therefor the bottom of the unit would be fl ush with the top of a non-combustible hearth or 4” above the surface of a combustible fl oor.

Floor Mounted Fireplace

Raised Fireplace

Full Screen Door Facing Requirements

10-1/4” Above Fireplace

6”

6”

WARNING: When installing the Full Screen Doors

The Full Screen Front requires additionalnoncombustiblefacing and non-combustible framing. Ensure the 10-1/4" above the fireplace, 6" on both sides and both the header and side studs are non-combustible materials. All other clearances, including mantel, remain the same.

June 2007 Regency Product Specifications Book

Gas Fireplaces

Combustible Mantels

Because of the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of the louvers are shown in the diagram below. Mantel may be installed anywhere in the shaded area or higher.

Mantel Clearances

14

12

10

8

6

4

2

0

 

 

 

 

13" (330mm)

 

 

 

 

 

 

 

 

 

 

 

Drywall

 

 

 

 

8”(203mm)

 

 

 

 

 

 

 

1" (25mm)

Non-Combustible

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Header

 

 

B

 

C

 

 

 

Non-Combustible

 

 

 

 

 

D

 

Facing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standoff

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

Top of

A Louvers

To Floor

Side View

 

Mantel Clearances

A

B

C

D

Front

33” (838mm)

21” (356mm)

17” (254mm)

12” (178mm)

 

 

 

 

 

Note: If desired a non-combustible mantel may be installed at a lower height.

Note: Ensure the paint that is used on the mantel and the facing is “heat resistant” or the paint may discolour.

Mantel Leg Clearances

Combustible mantel leg clearances as per diagram below: Clearances are from the fi nished edge of the unit or installed front.

P40

Maximum

1-1/2” projection at 2” minimum clearance.

8” Side Wall

Mantelleg

1-1/2"

Mantelleg

2"

 

 

 

 

6”

 

7¼”

 

Allowable mantel leg

 

 

projection.

 

Regency Direct Vent System (Flex)

Horizontal Terminations Only

These venting systems, in combination with the P40 Direct Vent Gas

Fireplace, have been tested and listed as a direct vent heater system by Warnock Hersey. The location of the termination cap must conform to the requirements in the Vent Terminal Locations diagram.

FPI Direct Vent (Flex) System Termination Kits include all the parts needed to install the P40 using a flexible vent.

June 2007 Regency Product Specifications Book

 

 

 

P40 Gas Fireplace

FPI Kit #

Length

Contains:

#946-618

6 Feet

1)

8” fl exible outer liner (Kit length)

 

 

2)

5” fl exible inner liner (Kit length)

 

 

3)

spring spacers (3)

 

 

4)

thimble (2)

 

 

5)

AstroCap termination cap (1)

 

 

6)

screws (12)

#946-616

10 Feet

 

 

7)

tube of Mill Pac (1)

 

 

8)

plated screws (8)

 

 

9)

S.S. screws #8 x 1-1/2” drill point, (4)

 

 

10)

vinyl siding standoff

 

 

 

 

Notes:

1)Liner sections should be continuous without any joints or seams.

2)Only Flex pipe purchased from Regency may be used for Flex installations.

3)Horizontal sections must be supported every 3 feet.

AstroCap XL

(Part# 946-623/P)

Wall Thimble (required in Canada only)

 

Vinyl Siding

 

Standoff

5” dia. flue pipe

 

8" dia.

spring spacer

Flue pipe

 

Snorkel Terminations

Snorkel Terminations:

For installations requiring a vertical rise on the exterior of the building, 14inch and 36-inch tall Snorkel Terminations are available. Follow the same installation procedures as used for standard Horizontal Termination. NEVER install the snorkel upside down.

Below Grade Snorkel Installation (Dura-Vent Only)

If the Snorkel Termination must be installed below grade, i.e. basement application, proper drainage must be provided to prevent water from entering the Snorkel Termination. Refer to Rigid Pipe Installation instructions for details. Do not attempt to enclose the Snorkel within the wall, or any other type of enclosure.

47

Fireplaces Gas